Mira Advance Low Pressure, Advance Low Pressure Flex Installation Manual

1
Installation Guide
MIRA ADVANCE ATLP LOW PRESSURE
9.0
k
W
ADJUSTABLE TEMPERATURE LIMIT THERMOSTATIC
This product is suitable for gravity cold water only.
Please leave these instructions at the installation address.
2
If you experience any difculty with the installation or operation of your new Pumped Electric Shower, then please refer to 'Fault Diagnosis', before contacting Mira Showers. Our contact details can be found on the back cover of this guide.
CONTENTS
Shower Models ........................................................................................ 3
Guarantee ............................................................................................3
Patents and Design Registration ..........................................................3
Important Safety Information .................................................................4
Pack Contents .........................................................................................6
Specications .......................................................................................... 7
Standards and Approvals ..................................................................... 7
Dimensions ...........................................................................................8
Installation Requirements ......................................................................9
General .................................................................................................9
1. Plumbing ..........................................................................................9
Pipework .................................................................................... 11
Plumbing Schematic Diagram .................................................... 11
2. Electrical ......................................................................................... 12
Electrical Schematic Diagram ....................................................12
Installation .............................................................................................14
Commissioning .....................................................................................18
Set Maximum Temperature and Commissioning Cycle ...................... 18
BEAB Care ......................................................................................... 19
Maintenance ...........................................................................................20
Fault Diagnosis ......................................................................................20
1. Installer Troubleshooting Guide...................................................... 20
2. Diagnostic Procedure ..................................................................... 21
Error Code Table ................................................................................22
BEAB Care In-Service Tests ................................................................. 25
Spare Parts ............................................................................................28
Wiring Diagram ...................................................................................... 30
Accessories ...........................................................................................31
Customer Service .................................................................................. 32
3
SHOWER MODELS
Mira Advance Low Pressure models covered by this guide
Product
Variant
Adjustable
Temperature
Limit
Extended
Lever
Control
Model
No.
Standard
9.0 kW
J97I
Flex
9.0 kW
J97K
Guarantee
For domestic installations, Mira Showers guarantee the Mira Advance ATLP against any defect in materials or workmanship for a period of two years from the date of purchase (shower ttings for one year).
For non-domestic installations, Mira Showers guarantee the Mira Advance ATLP against any defect in materials or workmanship for a period of one year from the date of purchase.
For Terms and Conditions refer to the back cover of this guide.
Recommended Usage
Domestic
Light Commercial
Heavy Commercial
Healthcare
Patents and Design Registration
Design Registration: 000738141: 0003, 0006, 0007, 0009
Patents: GB: 2269466, 2270370, 2298478, 2298479, 2298481,
2289323, 2359339. Ireland: 80655, 83692.
4
Installation must be carried out in accordance with these instructions, and must be conducted by designated, qualied and competent personnel.
WARNING!
Follow all warnings, cautions and instructions contained in this guide, and on or inside the shower.
1. This shower can deliver scalding temperatures if not operated, installed or maintained in accordance with the instructions, warnings and cautions contained in this guide and on or inside the appliance.
2. Products manufactured by us are safe and risk-free, provided that they are
installed, used and maintained in good working order, in accordance with our instructions and recommendations.
3. This product is suitable for installation within Zone 1 and is rated IPX4.
4. Isolate the electrical and water supplies before commencing installation. The
electricity must be turned off at the mains and the appropriate circuit fuse removed, if applicable.
5. Mains connections are exposed when the cover is removed.
6. Refer to the wiring diagram before making any electrical connections.
7. Make sure all electrical connections are tight, to prevent overheating.
8. Make sure that any pipework that could become frozen is properly insulated. The
shower unit must not be tted where it may be exposed to freezing conditions.
9. The water supplies to this product must be isolated if the product is not to be used for a long period of time. If the product or pipework is at risk of freezing during this period they should also be drained of water.
10. DO NOT operate this appliance if it is frozen. Isolate the electrical supply and allow to thaw. Check for leaks before reconnecting the electrical supply.
11. DO NOT install the product in a position in which service access is restricted.
12 If the shower is dismantled during installation or servicing then upon completion
the product must be inspected to ensure there are no leaks.
13. DO NOT t any form of outlet ow control (e.g. trigger handsets) as the outlet acts as a vent for the tank body. Only Mira recommended outlet ttings should be used.
14. This product is not suitable for areas with high humidity (i.e. steam rooms).
15. THIS APPLIANCE MUST BE EARTHED. MAKE SURE SUPPLEMENTARY BONDING COMPLIES WITH THE ‘REQUIREMENTS FOR ELECTRICAL INSTALLATIONS’ BS7671. This pumped electric shower is intended to be
permanently connected to the xed electrical wiring of the mains system.
16. This appliance must be provided with means for disconnection that is incorporated into the xed wiring in accordance with the relevant local wiring regulations.
17. This appliance is suitable for installation within the shower area. It must be
IMPORTANT SAFETY INFORMATION
5
positioned over a water catchment area with the controls at a convenient height for the user. The shower tting should be positioned so that it discharges down the centre line of the bath, or across the opening of a shower cubicle, and must
be directed away from the appliance.
CAUTION!
1. Read all of these instructions and retain this guide for later use.
2. The electrical installation must comply to 'BS 7671 (commonly referred to as the
IEE Wiring Regulations) and all relevant building regulations, or any particular regulation or practice specied by the local electricity supply company.
3. The plumbing installation must comply with all national or local water regulations and all relevant building regulations, or any particular regulation or practice specied by the local water company or water undertakers.
4. Switch off the appliance at the electrical isolating switch when not in use. This is for safety and is recommended with all electrical appliances.
5. This appliance is not suitable for use with any form of electronic timer. The shower must be shut down in accordance with the instructions contained in this installation guide, or the separate user guide.
6. Having completed the installation, make sure that the user is familiar with the operation of the appliance.
7. When this appliance has reached the end of its serviceable life, it should be disposed of in a safe manner, in accordance with current local authority recycling, or waste disposal policy.
8. Please pass this guide on in the event of a change of ownership of the installation
site.
6
PACK CONTENTS
Tick the appropriate boxes to familiarise yourself with the part names and to conrm that the parts are included.
Documentation
1 x User Guide
1 x Installation Template
1 x Guarantee Registration Document
1 x BEAB Care In-Service Test Record
1 x Mira Advance Low
Pressure Standard
1 x Compression Nut 4 x Wall Screws
1 x Cover Insert (blank)
4 x Wall Plugs
1 x Cover Insert (pipe)
4 x Rubber Feet
1 x Olive
Or
1 x Mira Advance Low
Pressure Flex
   
7
SPECIFICATIONS
Plumbing Supply
Supply Source Gravity fed or pumped cold water only.
Maximum Static Pressure 100 kPa (1 bar)
Minimum Static Pressure
0.8 kPa (0.008 bar) (10 kPa BEAB Care)
Maximum Inlet Temperature 30°C (20°C BEAB Care)
Minimum Inlet Temperature 2°C (5°C BEAB Care)
Inlet Connection ½" BSP male & 15 mm compression
tting.
Outlet Connection ½" BSP male fitting
Electrical Supply
Nominal Rating at 230 V 8.3 kW
Nominal Rating at 240 V 9.0 kW
Supply Fuse/Circuit Breaker 40 Amps
Residual Current Device RCD 30 mA
Supply Cable
No larger than 16 mm² Note: Refer to current IEE regulations and BS 7671 to determine minimum cable size.
Isolation Switch
45 Amp Double pole, with 3 mm contact
separation.
Maximum Ambient Temperature 30°C
Minimum Ambient Temperature 2°C
Duty Cycle 30 minutes on / 30 minutes off.
Standards and Approvals
The Mira Advance ATLP complies with the requirements of the BEAB Care Mark Standard and the relevant directives for CE marking.
The BEAB Care mark is invalid if the product is not installed and used in accordance with the manufacturer's specications and instructions.
8
Dimensions
Advance Low Pressure
Standard
Advance
Low Pressure Flex
402 mm
243 mm
100 mm 115 mm
84 mm 84 mm
9
General
We recommend that the product be brought into the room where it is to be installed and left to acclimatise to room temperature, this will reduce the possiblilty of condensation on electronic components. This product works best when supply temperatures and pressures remain stable and within the product specications, refer to section 'Specications'. If the supply conditions fall outside the specications, the shower may go into a safe shut down condition.
If pipework and/or electrical cables enter the shower from the rear through a hole in the wall, provision must be made to prevent water ingress back into the wall structure.
1. Plumbing
Refer to section: 'Important Safety Information' rst.
1.1 The shower is designed to operate with gravity fed water supplies providing
pressures from 0.8 kPa * (0.008 bar / 80 millimetres head) to 100 kPa (1 bar / 10 metres head) (i.e. the vertical distance from the base of the cold cistern to the top of the main unit of the shower). The unit should be never be tted to a mains supply or where the above maximum pressure may be exceeded. Failure to comply with this may result in product damage leading to signicant uncontrolled leakage from the unit.
* Note: In practice the minimum head required will increase with pipe length and the guide given in the section 'Pipework' should be used to make sure that adequate head is available for any given installation.
The shower MUST have its own separate supply from the cistern.
INSTALLATION REQUIREMENTS
Incorrect Cistern Take Off
Debris from the bottom of the cistern and air generated when the cistern rells will enter the shower supply.
Correct Cistern Take Off
Positioned away from the ball valve, with a 25 mm distance up from the base of the cistern. This connection will prevent air and debris entering the shower
supply.
25 mm
25 Gallon/113 Litre Cistern
10
1.2 Do not use sealing compounds on any pipe ttings or joints.
1.3 To avoid damage to the case when soldered ttings are used, pre-solder the
pipework and ttings before connecting them to the inlet connector assembly.
1.4 Avoid layouts where the shower hose will be sharply kinked. This may reduce the life of the hose.
1.5 Supply pipework MUST be ushed to clear debris BEFORE connecting the appliance. Debris will reduce the performance of the shower.
Avoid running the pipework through excessively hot or cold areas such as hot
loft spaces, airing cupboards, or in close proximity to hot water pipes. If this cannot be avoided, we would recommend insulating the pipes.
1.6 The shower must be tted onto a tiled or sealed nished surface, i.e. on top of the tiles. DO NOT tile up to the sides of the shower or use a sealant around the case. Failure to do this may cause appliance failure. To ensure the case and other components are not put under strain during installation always provide mechanical support when making plumbing connections. Upon completion of the installation ensure connections and back case are not under any stress due to misaligned pipework or electrical cables.
1.7 We recommend that a non-restrictive (free owing) isolating valve is tted in the cold water supply pipe from the cistern to the shower, to allow maintenance of the shower.
1.8 When installed in very hard water areas (above 200 ppm temporary hardness) your installer may advise the installation of a water treatment device, to reduce the effects of limescale formation. Any malfunction due to limescale is not covered by the manufacturer's guarantee. Your local water company will be able to advise the hardness of water in your area.
1.9 To prevent the possibility of backsiphonage, the handset must be prevented from reaching within 25 mm of the spillover level of any bath, shower tray or washbasin. The supplied hose retaining ring should enable this to be achieved for the majority of shower installations. However, there will be occasions when the hose retaining ring will not provide a suitable solution. In these instances, a double checkvalve must be tted to the outlet. Double checkvalves tted in the shower's inlet supply can cause a pressure build-up, which could exceed the maximum static inlet pressure for the appliance. The handset must be prevented from reaching within 30 mm of the spillover level of any WC, bidet or other basin that is classied higher than uid category 3.
1.10 Rear entry plumbing is accommodated without the need to recess the 15 mm inlet compression connector. If pipework and/or electrical cables enter the
shower from the rear through a hole in the wall provision must be made to prevent water ingress back into the wall structure.
1.11 The shower is tted with a pump motor, and some mechanical noise can be expected in addition to the noise generated by the spray from the handset. The type of wall surface will affect the perceived sound levels. Stud partition and panel walls have a tendency to resonate, whilst solid walls provide the quietest
Loading...
+ 22 hidden pages