SSL-SMOKE User’s Manual
IMPORTANT: Read all of the instructions before
attempting to install the SSL-SMOKE detector.
DESCRIPTIONS
The SSL-SMOKE detector is a device, which connects with
SSL-EMD. When smoke is detected an alarm will sound
alerting the users. Through the SNMP-SSL card, the user can
monitor it and receive notifications of the alarms.
C/DC smoke detector can be powered by 120VAC utility
power or
protection in the event of a power failure or a dead battery.
a 9-volt battery. AC/DC smoke detectors offer added
INSTALLATION
1. Detach the cover by twisting it until it unlatches from the
smoke detector base.
2. Using the smoke detector base as pattern, trace outlines o
the two keyhole slots onto the mounting surface.
3. Drill a pilot hole in the center of the small end of each of the
keyhole slots in the mounting surface.
4. Insert and tighten the mounting screws in the pilot holes
leaving approximately 1/8” of the screws sticking out.
5. Mount the smoke detector base making sure that screws
are positioned in the small ends of the keyholes and tighten
the screws.
6. Snap on the battery wire clip and insert the battery into
battery holder.
7. Replace the cover by twisting it until it latches. The smoke
detector is now operating.
8. Test the smoke detector by pushing test button on cove
and holding the button down for about 2-seconds.
Use the following steps to set-up and connect the
SSL-SMOKE detector to the SSL-EMD:
1. Loosen the screws on SSL-EMD.
This type o
2. Connect the wires from the SSL-SMOKE detector to the
SSL-EMD Alarm-1 and/or Alarm-2, and then tighten the screws.
3. Connect the straight-through CAT5 network cable from the
SNMP-SSL card’s RJ45 connector labeled “COM” to the
connector labeled “010101” on the SSL-EMD.
4. Verify that the SNMP-SSL card has a network connection and
is powered on.
5. Check the LED (Power/Status) of SSL-EMD, it will flash ever
5-seconds.
6. Open a Web browser and connect to the SNMP-SSL card.
7. Change the setting of “SSL-EMD Status” from “Disable” to
“Auto” on the EMD Configuration page.
8. Set the status of Alarm-1 and/or Alarm-2 to “Normal Open”.
9. The installation of the SSL-SMOKE detector is complete. See
the SNMP-SSL User’s Manual.
Note: The SSL-SMOKE detector operates with 120VAC or a
9-volt battery. Connecting to the 120VAC utility power is not
required to operate the detector. However, operating with both
the utility power and the battery offers added protection in the
event of a power failure or a dead battery.
LIMITED PRODUCT WARRANTY
Para Systems Inc. (Para Systems) warrants this equipment, when
properly applied and operated within specified conditions, against
faulty materials or workmanship for a period of three years from the
date of original purchase by the end user. For equipment sites within
the United States and Canada, this warranty covers repair o
replacement of defective equipment at the discretion of Para Systems.
Repair will be from the nearest authorized service center.
Replacement parts and warranty labor will be borne by Para Systems.
For equipment located outside of the United States and Canada, Para
Systems only covers faulty parts. Para Systems products repaired o
replaced pursuant to this warranty shall be warranted for the remaining
portion of the warranty that applies to the original product. This
warranty applies only to the original purchaser who must have properl
registered the product within 10 days of purchase.
The warranty shall be void if (a) the equipment is damaged by the
customer, is improperly used, is subjected to an adverse operating
environment, or is operated outside the limits of its electrical
specifications; (b) the equipment is repaired or modified by anyone
other than Para Systems or Para Systems-approved personnel; or (c)
has been used in a manner contrary to the product's operating manual
or other written instructions.
ny technical advice furnished before or after delivery in regard to use
or application of Para Systems’s equipment is furnished without charge
and on the basis that it represents Para Systems’s best judgment
under the circumstances, but it is used at the recipient's sole risk.
EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO
WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
PARTICULAR PURPOSE. Some states do not permit limitation o
implied warranties; therefore, the aforesaid limitation(s) may not apply
to the purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL PAR
SYSTEMS BE LIABLE FOR DIRECT, INDIRECT, SPECIAL,
INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF
THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE
POSSIBILITY OF SUCH DAMAGE. Specifically, Para Systems is not
liable for any costs, such as lost profits or revenue, loss of equipment,
loss of use of equipment, loss of software, loss of data, cost o
substitutes, claims by third parties, or otherwise. The sole and
exclusive remedy for breach of any warranty, expressed or implied,
concerning Para Systems’s products and the only obligation of Para
Systems hereunder, shall be the repair or replacement of defective
equipment, components, or parts; or, at Para Systems’s option, refund
of the purchase price or substitution with an equivalent replacement
product. This warranty gives you specific legal rights and you may
also have other rights, which vary from state to state.
OBTAINING TECHNICAL ASSISTANCE
Para Systems (Minuteman UPS) Technical Support:
Phone: 1-972-446-7363
Fax: 1-972-446-9011
Web: www.minutemanups.com/support/con_tech2.php
www.minutemanups.com © Copyright 2008 34000363 R1
SSL-SMOKE User’s Manual
IMPORTANT: Read all of the instructions before
attempting to install the SSL-SMOKE detector.
OPERATION, TESTING AND MAINTENANCE
Operation: The smoke detector is operating once the
battery is connected. When products of combustion are
sensed, the unit sounds a loud pulsating alarm until you
push the reset button once. Note: When the battery is
replaced or tested or the alarm is reset the smoke detecto
will operate normally after two minutes.
Testing: Test by pushing test button on cover and holding
the button down for about 2-seconds. This will sound an
alarm if all electronic circuitry is working properly. If no
alarm sounds, the unit has a defective battery or othe
failure. You can also test the smoke detector by blowing
smoke into it. Test the smoke detector monthly to assure
proper operation. Erratic noise or low sound from the
smoke detector may indicate a defective smoke detector.
Return it for service.
Warning: Test the smoke detector operation if an RV or a
mobile home vehicle has been in storage, and before each
trip, and at least once per week during use.
Maintenance: The smoke detector is virtually
maintenance free. However, under dusty conditions, a
vacuum may be used to clear the sensing chamber o
dust. Do not remove smoke detector cover when
vacuuming.
electronic chamber. Do not try to repair the smoke detector.
BATTERY REPLACEMENT
The smoke alarm is powered by one 9V carbon-zinc
battery (alkaline batteries may also be used). The battery
should provide operation for at least one year unde
normal operating conditions. The smoke alarm has a low
battery indicator, which will “chirp” at approximately
20-second intervals for a minimum of 7-days. Replace the
battery when chirping occurs. Use only 9-volt batteries.
These smoke detectors use a high technolog
THE LIMITATIONS OF SMOKE DETECTORS
Smoke detectors are devices that can provide early warnings
of possible developing fires at a reasonable cost. However,
smoke detectors have certain limitations. For battery
powered smoke detectors, the battery must be in good
condition and installed properly.
Smoke detectors cannot sound an alarm if smoke does not
reach the detector. Therefore smoke detector may not sense
fires starting in chimneys, walls, on roofs, on the other side o
a closed door, or on a different floor. For maximum
protection, a smoke detector should be installed in each
separate sleeping area and on every level of a home.
lthough smoke detector can help save lives by providing
early warnings of a fire, they are not a substitute for an
insurance policy. Homeowners and renters should have
adequate insurance to protect their lives and property.
WHAT TO DO WHEN THE ALARM SOUNDS
• Leave immediately. Every second counts, so don’t waste
time getting dressed or picking up valuables.
• In leaving, do not open any inside door without first
feeling its surface. If hot, or if you see smoke seeping
through the cracks, do not open that door! Instead, use
your alternate exit. If the inside door is cool, place you
shoulder against it and open it slightly, but be ready to
slam it shut if fire and/or smoke come in.
• Stay close to the floor if air is smoky. Breathe shallowly
through a cloth if possible wet it.
• Once outside, go to your selected meeting place and
make sure everyone is there.
• Call the fire department from your neighbor’s home - not
from yours!
• Do not return to your home until fire officials say that it’s
all right to do so.
Further information on fire safety can be obtained in a
pamphlet titled “In A Fire Seconds Count” published by the
NFPA, Batterymarch Park, Quincy, Mass 02269.
FALSE ALARMS
The smoke alarm is designed to minimize false alarms.
Smoking will not normally set off the alarm unless smoke is
blown directly into the detector. Combustion particles from
cooking may set off the alarm if the detector is located close
to the kitchen. Large quantities of combustion particles are
generated from spills or broiling.
If the detector does alarm, check for fires first. If a fire is
discovered, get out and call the fire department. If no fire is
present, check to see if one of the reasons listed above
may have caused the alarm.
NATIONAL FIRE PROTECTION ASSOCIATION
REQUIRED PROTECTION
For your information, the National Fire Protection
ssociation’s Standard 74, Section 2-1 provides information
regarding the smoke detection equipment required within
the family living unit. Section 2-1, 1.1 reads as follows:
“Smoke detectors shall be installed outside of each
separate sleeping area in the immediate vicinity of the
bedrooms and on each additional story of the family living
unit including basements and excluding crawl spaces and
unfinished attics.
The provisions of 2-1, 1.1 represent the minimum numbe
of detectors required by this standard. It is recommended
that the householder consider the use of additional smoke
or heat detectors for increased protection for those areas
separated by a door from the areas protected by the
required smoke detectors under 2-1, 1.1 above. The
recommended additional areas are living room, dining
room, bedroom(s), kitchen, attic (finished or unfinished),
furnace room, utility room, basement, integral or attached
garage, and hallways not included in 2-1, 1.1 above.
However, the use of additional detectors remains the opting
of the householder.”
The equipment should be installed in accordance with the
National Fire Protection Association’s Standard 74 (NFPA,
Batterymarch Park, Quincy, Mass 02269)
NOTIFY YOUR LOCAL FIRE DEPARTMENT AND
INSURANCE COMPANY THAT A SMOKE DETECTO
HAS BEEN INSTALLED