Minuteman Smart Up, MSU 700, MSU 1000, MSU 1400 User Manual

Page 1
Smart Up Series
Uninterruptible Power Supply
User’s Manual
Page 2
Page 3
Smart Up Series User’s Manual
1. Introduction 2
2. Controls and Indicators 4
4. Operation 7
5. Troubleshooting 1 1
6. Replacing the Battery 12
7. Obtaining Service 15
8. Specifications 16
9. Limited Warranty 17
ã Copyright Para Systems, Inc., 1999
1
Page 4
Thank you for purchasing a Minuteman power protection product. It has been designed and manufactured to provide many years of trouble free service.
Please read the manual before installing your Smart Up Series UPS as it provides the information that should be followed during installation and main­tenance of the UPS and batteries allowing you to correctly set up your sys­tem for the maximum safety and performance.
Included is information on customer support and factory service if it is required. If you experience a problem with the UPS, please refer to the Troubleshooting guide in this manual to correct the problem or collect enough information so that the Minuteman technical support department can rapidly assist you.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
NOTICE: This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense.
This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference regula­tions of the Canadian Department of Communications.
Le présent appareil numérique n’emit pas de bruits radioélectriques dépassant les limites applicables aux appareils numérique de la Class A presc rites dans le Règlement sur le brouillage radioélectrique édicte
CAUTION: WHEN DISCONNECTING THE INTERNAL BATTERIES, THE UPS
CANNOT BE RUNNING IN THE BA TTERY MODE. THE UPS MUST BE OFF OR SUPPLYING POWER T O THE LOAD FROM THE UTILITY MAINS.
W ARNING: CHANGES OR MODIFICATIONS TO THIS UNIT NOT EXPRESSL Y
APPROVED BY THE P ARTY RESPONSIBLE FOR COMPLIANCE COULD VOID THE USER’S AUTHORITY TO OPERA TE THE EQUIPMENT .
2
Page 5
Receiving Inspection
After removing your Minuteman UPS from its carton, it should be inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored. The packing materials that your UPS was shipped in are carefully designed to minimize any shipping damage. In the unlikely case that the UPS needs to be returned to Minute­man, please use the original packing material. Since Minuteman is not responsible for shipping damage incurred when the system is returned, the original packing material is inexpensive insurance.
PLEASE SA VE THE P ACKING MA TERIALS!
W ARNING: RISK OF ELECTRICAL SHOCK. HAZARDOUS LIVE PARTS
INSIDE THIS POWER SUPPL Y ARE ENERGIZED FROM THE BA TTERY EVEN WHEN THE AC INPUT POWER IS DISCONNECTED.
TO DE-ENERGIZE THE OUTPUTS OF THE UPS:
1. IF THE UPS IS ON PRESS THE ON/OFF BUTTON FOR 1 SECOND.
2. DISCONNECT THE UPS FROM THE AC POWER OUTLET .
3. TO DE-ENERGIZE THE UPS COMPLETEL Y , DISCONNECT THE BA TTERY .
(SEE SECTION 6 FOR INSTRUCTIONS)
CAUTION! TO REDUCE THE RISK OF ELECTRICAL SHOCK IN CONDI-
TIONS WHERE LOAD EQUIPMENT GROUNDING CANNOT BE VERIFIED, DISCONNECT THE UPS FROM THE AC POWER OUTLET BEFORE INST ALLING A COMPUTER INTERFACE CABLE. RECONNECT THE POWER CORD ONL Y AFTER ALL SIGNALING CONNECTIONS ARE MADE.
CAUTION! CONNECT THE UPS TO A TWO POLE, THREE WIRE GROUND-
ING AC POWER OUTLET . THE RECEPT ACLE MUST BE CONNECTED TO APPROPRIA TE BRANCH PROTECTION (CIRCUIT BREAKER OR FUSE). CONNECTION TO ANY OTHER TYPE OF RECEPT ACLE MA Y RESUL T IN A SHOCK HAZARD AND VIOLA TE LOCAL ELECTRICAL CODES.
Para Systems Life Support Policy
As a general policy, Para Systems, Inc. (Para Systems) does not recommend the use of any of its products in life support applications where failure or malfunction of the Para Systems product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness. Para Systems does not recommend its products for use in direct patient care. Para Systems will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to Para Systems that (a) the risks of injury or damage have been minimized, (b) the customer assumes all such risks, and (c) the liability of Para Systems, Inc. is adequately protected under the circumstances.
Examples of devices considered to be life support devices are neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief or other purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators for both adults and infants, anesthesia ventilators, and infusion pumps as well as any other devices designated as “critical” by the United States FDA.
Hospital grade wiring devices and leakage current may be ordered as options on many PARA SYSTEMS UPS systems. PARA SYSTEMS does not claim that units with this modification are certified or listed as Hospital Grade by PARA SYSTEMS or any other organization. Therefore, these units do not meet the requirements for use in direct patient care.
3
Page 6
FRONT PANEL
Press and release the On/Test/Alarm Silence button to turn on, test or silence the alarm.
Press and release the OFF button to turn the UPS OFF.
The Buck LED illuminates when the UPS is correcting for a high utility line voltage.
The On Battery LED illuminates when the UPS is supplying power from the battery.
The AC Normal LED illuminates when the utility voltage is normal.
The Boost LED illuminates when the UPS is correcting for a low utility line voltage. The Overload LED illuminates when the loads connected to the UPS exceeds the
UPS power rating (see Section 4). The Replace battery LED illuminates when the UPS has detected that battery
replacement is required (see Section 6). The Load Level LEDs illuminate to show the percentage of load connected to the
UPS: 20%, 40%, 60% or 80%.
The Battery Level LEDs illuminate to show the percentage of battery capacity remaining: 25%, 50%, 75% or 100%.
4
On/T est/Alarm Silence Off On Battery
Buck Normal Boost Overload Replace Battery Load Battery
Page 7
Minuteman Smart Up
Rear Panel
Site Wiring Fault
DB9
Connector
Accessory Slot
Option Slot
Output Receptacles
Input Circuit
Breaker
Surge Only Receptacle
Input Power
Site Wiring Fault
DB9 Connector
Accessory Slot
Option Slots
Output Receptacles
Input Circuit
Breaker
Surge Only Receptacle
Input Power
DB9
Connector
Accessory Slot
Option Slot
Output Receptacles
Input Circuit
Breaker
Surge Only Receptacle
Input Power
MSU 1000i &1400i
DB9 Connector
Accessory Slot
Option Slots
Output Receptacles
Input Circuit
Breaker
Surge Only Receptacle
Input Power
5
MSU 1000 &1400
MSU 700
MSU 700i
Page 8
REAR PANEL
The Accessory Slot is used for SNMP UPS monitoring. Available from Minuteman. The DB9 connector is used for UPS monitoring and control through a computer’s serial port
(see Section 3). The Option Slots are for adding RJ-45/RJ-11 surge protection cards. Available from Min-
uteman. The Site Wiring Fault LED illuminates when the UPS detects an improperly wired AC power
outlet (see Section 3). The Output Power receptacles are NEMA 5-15R type for 120V units and IEC 320 for 230V
units. The Input Power receptacle is a IEC 320. The Input Circuit Breaker will trip in the event the load exceeds the UPS’s power rating.
INSTALLATION PLACEMENT
Please observe the following items: n Install the UPS in a temperature-controlled, indoor environment that is free of conduc-
tive contaminants. Select a location which will provide good air circulation for the UPS at all times. Avoid locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct sunlight.
n Plug the UPS into a two pole, three wire, grounded receptacle only. Do not use exten-
sion cords or adapter plugs.
DB9 CONNECTOR
Minuteman Power Management software and interface cable kits are used with this port (software and cables are optional and available from Minuteman). Use only Minuteman or Minuteman approved interface cables with these UPS’s. Connect the interface cable to the DB9 connector on the rear of the UPS. Secure the connector to the UPS via the screws on the connector housing. Connect the other end of the cable to the device that will be monitor­ing/controlling the UPS.
NOTE: CONNECTING TO THE DB9 IS OPTIONAL. THE UPS WORKS PROPERL Y
WITHOUT A CONNECTION.
6
Page 9
SITE WIRING F AULT
After plugging in the UPS, check the site wiring fault (SWF) LED on the rear of the unit. If the LED is illuminated, the UPS is plugged into an improperly wired AC outlet.
CHARGING THE BA TTERIES
The Smart Up Series UPS’s will charge the batteries whenever the unit is connected to an AC source. It is recommended that the UPS batteries be charged for a minimum of 4 hours before use. The UPS may be used immediately. However, the “on battery” run time may be less than normally expected.
CONNECTING YOUR EQUIPMENT
Plug the equipment into the receptacles on the rear of the unit. Insure that you do not exceed the maximum output rating of the UPS (refer to the back panel of the UPS or the electrical specifications in this manual). For non-critical loads, such as printers, it is recommended that the equipment be connected to the Surge Only outlet.
CAUTION! BE SURE ALL CRITICAL LOADS ARE CONNECTED TO THE
BA TTERY SUPPLIED OUTLETS. THE SURGE ONL Y OUTLET IS NOT A BA T­TERY SUPPLIED OUTLET.
CAUTION! DO NOT CONNECT A LASER PRINTER TO THE BA TTER Y
SUPPLIED RECEPT ACLES ON THE UPS. LASER PRINTERS MA Y BE CONNECTED TO THE SURGE ONL Y OUTLET .
CAUTION!: IF THE UPS INDICA TES A SITE WIRING F AUL T , HA VE A
QUALIFIED ELECTRICIAN CORRECT THE PROBLEM.
ON/TEST/SLIENCE SWITCH
Press and release this switch to turn the UPS on. After the UPS is ON, pressing this switch will implement a self test. When the UPS is in battery mode, pressing this switch will silence the alarm. If utility line is not present, press and hold this switch for 2 seconds and the UPS will turn on.
7
Page 10
OFF SWITCH
Press and release this switch to turn the UPS OFF. The UPS will continue to charge the batteries whenever it is plugged in and the utility line is present.
LED STATUS & ALARMS
LOAD LEVEL DISPLA Y
The 4-LED load percentage display shows the power level (20%, 40%, 60%, 80%) drawn by the loads which are connected to THE BA TTERY-SUPPLIED OUTLETS on the UPS. If UPS is overloaded, the OVERLOAD LED will light.
BATTER Y LEVEL DISPLA Y
This display shows the battery capacity left in the battery. The level is represented by percentage of 25, 50, 75 and 100, and these LED’s will extinguish gradually when using battery power. When battery capacity reaches the minimal level of 25%, the lowest LED(25%) blinks.
When UPS is in battery mode, the ON BATTERY LED will light, proceed by a “beep” sound for every 2 seconds, and then the UPS will start supplying power to load through battery.
ON BA TTERY MODE
8
Page 11
If an overload occurs, the OVERLOAD LED will light and an uninterrupted alarm will be heard. Under this condition, check the load connected to the UPS.
OVERLOAD
BUCK/BOOST
If the UPS detects a high utility voltage, the function of the buck is to automatically reduce the output voltage to its nominal level. If the UPS should detect a low utility voltage, the boost function will raise the output voltage to its nominal level. These two functions are repre­sented by their respective LED on the front panel.
BATTERY REPLACE
This function is to alert users of the need to replace the batteries. When the microproces­sor in the UPS detects a battery fault, the UPS alarm will give out three beeps. Each beep lasts for 0.5 seconds and interrupted by an interval of 0.5 seconds. After the initial 3 beeps, the alarm will continue to sound every hour.
9
Page 12
OVER TEMPERA TURE
When temperature inside the UPS is too high, the LED of Buck, Boost, Normal and On Battery will light, the alarm will sound continuously, and after a minute the UPS will stop supplying power to load.
BATTERY LOW
This function is to inform user of the remaining power capacity of the batteries. When the batteries reach a low capacity condition, the UPS alarm will beep once every second, and the LED on the 25% level will flash.
UPS Fault
When there is a breakdown on the UPS, all LEDs will light and the alarm will sound continuously. If this happens, turn off the UPS and unplug the power cord from the wall outlet. (see Section 7 for obtaining service)
10
Page 13
TROUBLESHOOTING CHART
Problem
No alarm, No LED indication (UPS is not turned on).
UPS does not provide expected back-up time
All LEDs are on. ‘REPLACE BA TTERY’ LED lights
UPS operates on battery even though good line voltage may be present.
Site wiring fault LED on rear panel lights.
UPS over temperature (BUCK, BOOST , NORMAL,ON BA TTERY LEDs are on)
Possible Cause
ON/TEST button is not pushed.
The rear panel circuit breaker is tripped (Button is out).
UPS fault. Batteries inside the UPS
are not fully charged. UPS is overloaded.
Batteries are weak.
Charger fault or other reason. Internal UPS fault. Weak batteries.
The rear panel circuit breaker is tripped (Button is out). Very high, low, or distorted utility voltage. Wiring error such as reversed hot/neutral or no earth ground. The exhaust fan and ventilation grill may be obstructed. The environment tempera­ture is too high.
Solution
Press the ON/TEST button to turn on the UPS. (Refer to Section 4 to turn on the UPS). Reduce some loads connected to the UPS. Reset the circuit breaker (Push button in). Call for qualified service person­nel if above actions do not solve the problem Recharge the batteries for at least 4 hours. Remove some unnecessary loads. Batteries wear faster when used often or operating at higher temperatures. If the battery is near the end of its life, replace the battery even if the REPLACE BA TTERY LED does not light (Refer to Section 6 for replacing batteries). Call for service.
Turn off UPS. Call for service. Recharge the batteries for at least 4 hours. If problem remains, replace the batteries. Reduce some loads connected to the UPS. Reset the circuit breaker (Push button in). Have qualified electrician check the input voltage. Get wiring checked by electrician.
Choose a well-ventilated area to position your UPS to allow adequate dissipation of heat. Position your UPS in cooler area.
11
Page 14
REPLACING THE BATTERY
The Smart Up Series UPS has easy-to-replace hot-swappable batteries. Please read the following warning statements before attempting to service the batteries.
WARNING! THIS UNINTERRUPTIBLE POWER SOURCE CONTAINS
POTENTIALL Y HAZARDOUS VOLT AGES. DO NOT A TTEMPT TO DISAS­SEMBLE THE UNIT BEYOND BA TTERY REPLACEMENT PROCEDURES BELOW. EXCEPT FOR THE BA TTERY, THIS UPS CONT AINS NO USER SERVICABLE P ARTS. REP AIRS CAN BE PERFORMED BY MINUTEMAN SERVICE PERSONNEL ONL Y .
CAUTION: DO NOT OPEN OR MUTILA TE BATTERIES. RELEASED
ELECTROL YTE IS HARMFUL TO THE SKIN AND EYES AND MA Y BE TOXIC.
CAUTION: DO NOT DISPOSE OF BA TTERIES IN A FIRE. THE BA TTER-
IES MA Y EXPLODE.
THE BATTERIES IN THIS UPS ARE RECYCLABLE. DISPOSE OF THE BA TTER­IES PROPERL Y . THE BA TTERIES CONT AIN LEAD AND POSE A HAZARD TO THE ENVIRONMENT AND HUMAN HEAL TH IF NOT DISPOSED OF PROPERLY. REFER TO LOCAL CODES FOR PROPER DISPOSAL EQUIREMENTS, OR RETURN THE BA TTERY TO MINUTEMAN.
CAUTION: AL THOUGH BA TTERY SYSTEM VOL T AGES ARE ONL Y 24
VDC, THE BA TTERY SYSTEM CAN STILL PRESENT A RISK. THE CURRENT CAP ABILITY OF A BATTER Y IS SUFFICIENT TO BURN WIRE OR TOOLS VERY RAPIDL Y , PRODUCING MOL TEN MET AL. OBSERVE THESE PRECAU­TIONS WHEN REPLACING THE BA TTERIES:
1. REMOVE WA TCHES, RINGS OR OTHER MET AL OBJECTS.
2. USE HAND TOOLS WITH INSULA TED HANDLES.
3. DO NOT LA Y TOOLS OR OTHER MET AL P ARTS ON TOP OF BA TTERIES
CAUTION: WHEN DISCONNECTING THE INTERNAL BA TTERIES OR
THE EXTERNAL BA TTERY P ACK, THE UPS CANNOT BE RUNNING IN THE BA TTERY MODE. THE UPS MUST BE OFF OR SUPPL YING POWER TO THE LOAD FROM THE UTILITY MAINS.
CAUTION: REPLACE BA TTERIES WITH THE SAME NUMBER AND
TYPE AS ORIGINALL Y INSTALLED IN THE UPS. THESE BA TTERIES HA VE PRESSURE OPERA TED VENTS.
12
Page 15
BATTERY REPLACEMENT PROCEDURE
PLEASE READ THE PREVIOUS “CAUTIONS” SECTION BEFORE A TTEMPTING TO REPLACE THE BA TTERIES
Battery replacement is a safe procedure when cautions and instructions are carefully followed. You may leave the UPS and the loads on for the following procedure.
1. Hold the top of the front panel, tilt it out and pull it carefully away from the chassis.
2. Loosen the bottom of the front panel from the chassis and place it on the top of the UPS. Be cautious so as not to pull the ribbon cable and touch the LED printed circuit board.
3. Use a spanner to unlock, remove and open the battery door.
4. Carefully and smoothly pull the battery out of the UPS.
Grasp and tilt out and down
Step 1:
Step 2: Place the f ront panel
Step 4: Pull ba tter y ou t
Step 3: Use a spanner to let the batt ery door d own
13
Page 16
5. Disconnect the battery: For 700VA and 1000VA models, disconnect the batteries and UPS by loosening the connectors. For 1400VA model, disconnect the batteries and UPS by pulling apart the two couplers that are connected together.
6. Connect the new battery: For 700VA and 1000VA models, connect positive (+) connectors (RED­RED) and negative (-) connectors (BLACK-BLACK) together. For 1400VA model, connect the two connected couplers on battery and UPS together.
Black(-)
Red(+)
1000VA
Push b ac k to U PSPush b a c k t o UP S
Black(-)
Red(+)
450VA and 700VA
Pu sh back to U P S
1400VA
Black(-)
Red(+)
7. Re-assemble the UPS as shown above.
14
Page 17
IF THE UPS REQUIRES SERVICE
1. Use the TROUBLESHOOTING Section 5 to eliminate obvious causes.
2. Verify that no circuit breakers are tripped. A tripped circuit breaker is the most common problem.
3. Call your dealer for assistance. If you cannot reach your dealer or if he cannot resolve the problem, call or FAX Minuteman Technical Support at the following numbers: Voice phone (972) 446-7363, FAX line (972) 446-9011, e-mail: support@minuteman-ups.com. Please have the following information available BEFORE calling technical support.
A . Your name and address. B. Where and when the unit was purchased. C. All of the model information on the rear of your UPS. D. Any information on the failure, including LEDs that may be illuminated. E. A description of the protected equipment, including model numbers if
possible.
F. A technician will ask you for the above information and, if possible, help
solve your problem over the phone. In the event that the unit requires factory service, the technician will issue you a Return Material Authorization Number (RMA #).
G. If the UPS is under warranty, the repairs will be done at no charge. If not,
there will be a charge for repair.
4. Pack the UPS in its original packaging. If the original packaging is no longer available, ask the technical support technician about obtaining a new set. It is important to pack the UPS properly in order to avoid damage in transit. Never use Styrofoam beads for a packing material. Include a letter with your name, address, day-time phone number, RMA number, a copy of your original sales receipt and a brief description of the trouble.
5. Mark the RMA # on the outside of all packages. The factory cannot accept any package without the RMA # marked on the outside.
6. Return the UPS by insured, prepaid carrier to:
Minuteman, Para Systems, Inc.
1455 LeMay Drive
Carrollton, TX 75007
15
Page 18
NOTE: 230VAC Specs Shown In ( )
Acceptable input Voltage Input Voltage (on-line operation) Output Voltage (on-line operation) Nominal input frequency Input protection Frequency limits (on-battery operation) Transfer Time Maximum Load Battery Power Supplied Output Receptacles Surge Protected Only Output Receptacles On-battery Output Voltage On-battery frequency On-battery wave shape Protection
Surge energy rating (one time 10/1000 ms waveform) Surge current capability (one time, 8/20 ms waveform) Surge response time Surge voltage let through (percentage of applied ANSI C62.41 cat A +6 v test wave form) Noise filter
Battery type: Spill proof, mainte­nance free, user replaceable, sealed lead acid Typical battery life
Typical recharge time Operating temperature Storage temperature Operating and storage relative humidity Operating elevation Storage elevation Electromagnetic immunity Audible noise at 1 m (3 ft.) Size ( H x W x D)
Weight-net (shipping) Safety and approval
EMC Verification
MSU 700
0-145 (0-288) VAC
91-145 (174-288) VAC
103-131 (200-253) VAC
50 or 60 Hz auto-sensing
Manual reset circuit breaker
50 or 60 Hz
+ 0.1%
2-4 ms. Typical 700VA 450W 3 (4)
1 (1)
115 VAC (230 VAC)
50 or 60 Hz +.1 Hz unless synchronized to utility during brownout
True Sinewave
Over-current and short circuit protected, latching shutdown on
overload
480J
6500A max
0 ns (instantaneous) normal mode, <5 ns common mode
< 0.3 % of peak typical
Normal and common mode EMI / RFI suppression,
100Khz to 10Mhz
2 x 12V7AH
3 to 5 years depending on number of discharges and ambient
temperature
2 to 4 hours from 50% discharge
0 to 40 degrees C (+32 to 104 degrees F)
-15 to +45 degrees C ( +5 to +113 degrees F) 0 to 95% non-condensing
0 to +3,000 m (0 to +10,000 ft. )
0 to 15,000 m ( 0 to +50,000 ft. )
IEC 801-2 LEVEL IV, 801-4 LEVEL IV, 801-5 LEVEL III
<45 dBA
15.6 x 13.8 x 40 cm
6.14 x 5.43 x 15.7 in. 14 Kg 31 lb.
UL, CUL, TUV/GS, CE
FCC Class A, TUV/EMC
MSU 1000
1000VA 670W
5 (8) 1 (1)
2 x 12V11AH
17 x 22 x 42 cm
6.69 x 8.66 x 16.5 in. 21 Kg 46 lb.
MSU 1400
1400VA 950W
5 (8) 1 (1)
2 x 12V17AH
17 x 22 x 42 cm
6.69 x 8.66 x 16.5 in. 26 Kg 57 lb.
16
Page 19
LIMITED PRODUCT W ARRANTY
Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of original purchase by the end user. For equipment sites within the United States and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center. Replacement parts and warranty labor will be borne by Para Systems. For equipment located outside of the United States and Canada, Para Systems only covers faulty parts. Para Systems products repaired or replaced pursuant to this warranty shall be warranted for the unexpired portion of the warranty applying to the original product. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.
The warranty shall be void if (a) the equipment is damaged by the customer, is improp­erly used, is subjected to an adverse operating environment, or is operated outside the limits of its electrical specifications; (b) the equipment is repaired or modified by anyone other than Para Systems or Para Systems-approved personnel; or (c) has been used in a manner contrary to the product’s operating manual or other written instructions.
Any technical advice furnished before or after delivery in regard to use or application of Para Systems’ equipment is furnished without charge and on the basis that it represents Para Systems’ best judgment under the circumstances, but it is used at the recipient’s sole risk.
EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO WARRANTIES, EX­PRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation of implied warranties; therefore, the aforesaid limitation(s) may not apply to the purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARIS­ING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, Para Systems is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, cost of substitutes, claims by third parties, or otherwise. The sole and exclusive remedy for breach of any warranty, expressed or implied, concerning Para Systems’ products and the only obligation of Para Systems hereunder, shall be the repair or replacement of defective equipment, compo­nents, or parts; or, at Para Systems’ option, refund of the purchase price or substitution with an equivalent replacement product. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
Longer term and F.O.B. job site warranties are available at extra cost. Contact Para Systems (1-972-446-7363) for details.