All rights reserved. All MINUTEMAN trademarks are property of Para Systems, Inc.
Other trademarks are property of their respective owners.
1
English
Thank you for purchasing this power protection product. It has been designed
and manufactured to provide many years of trouble free service.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
Please read this manual before installing your PRO Rack/Tower Series UPS,
models PRO1000RT, PRO1500RT as it provides important information that
should be followed during installation and maintenance of the UPS and batteries allowing you to correctly set up your system for the maximum safety and
performance. Included is information on customer support and factory service
if it is required. If you experience a problem with the UPS please refer to the
Troubleshooting guide in this manual to correct the problem or collect enough
information so that the Technical Support Department can rapidly assist you.
This symbol indicates "ATTENTION"
This symbol indicates "Risk of Electrical Shock"
This symbol indicates "Direct Current Supply"
This symbol indicates "Equipment Grounding Conductor"
English
CAUTION! Connect the UPS to a two pole, three wire grounding
AC wall outlet. The receptacle must be connected to the appropriate
branch protection (circuit breaker or fuse). Connection to any other
type of receptacle may result in a shock hazard and violate local
electrical codes. Do not use extension cords, adapter plugs, or surge
strips.
CAUTION! To reduce the risk of fire, connect only to a circuit
provided with 20 amperes maximum branch circuit over-current protection in accordance with the National Electric Code, ANSI/NFPA
70.
CAUTION! T o reduce the risk of electrical shock with the installa-
tion of this UPS equipment and the connected equipment, the user
must ensure that the combined sum of the AC leakage current does
not exceed 3.5mA.
CAUTION! To reduce the risk of electrical shock in conditions
where the load equipment grounding cannot be verified, disconnect
the UPS from the AC wall outlet before inst alling a computer interface
cable. Reconnect the power cord only after all signaling connections
are made.
WARNING:This Uninterruptible Power Supply contains potentially
hazardous voltages. Do not attempt to disassemble the UPS beyond
the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and Battery replacement must be performed
by QUALIFIED SERVICE PERSONNEL ONL Y.
WARNING: Risk of Electrical Shock. Hazardous live p arts inside
these power supplies are energized from the battery even when the
This symbol indicates "Alternating Current Supply Phase"
AC input is disconnected.
CAUTION! T o de-energize the outputs of the UPS:
1. If the UPS is on press and release the On/Off/Test Button.
This symbol indicates "Alternating Current Supply"
2
2. Disconnect the UPS from the AC wall outlet.
3. T o de-energize the UPS completely, disconnect the battery .
3
English
CAUTION! This UPS series is only intended to be install in an
indoor temperature controlled environment that is free of conductive
contaminants.
CAUTION! The Maximum ambient operating temperature for this
UPS series is 40°C (“0 ~ 40°C” for Ambient Operation).
ON / OFF / TEST BUTTON: To turn the UPS on: press and hold the
On/Off/T est Button until the alarm sounds one beep and then release.
The UPS will perform a five second self-test. Once the UPS has
passed its self-test the UPS will provide an output and the load will be
powered. T o turn the UPS off: press and hold the On/Of f/T est Button
until the alarm sounds one beep and then release. T o perform a tensecond battery test: With the UPS in the AC mode, press and hold
the On/Off/Test Button until the alarm sounds four beeps, and then
release. During the test, the UPS will switch to the Battery mode, the
On-Battery icon will illuminate and the alarm will sound.
Receiving Inspection
After removing your UPS from its carton, it should be inspected for damage that
may have occurred in shipping. Immediately notify the carrier and place of
purchase if any damage is found. Warranty claims for damage caused by the
carrier will not be honored. The packing materials that your UPS was shipped
in are carefully designed to minimize any shipping damage. In the unlikely
case that the UPS needs to be returned to the manufacturer, please use the
original packing material. Since the manufacturer is not responsible for shipping damage incurred when the system is returned, the original packing material is inexpensive insurance. PLEASE SA VE THE P ACKING MA TERIALS!
English
NOTICE! The output of this device is not sinusoidal. It has a total
harmonic distortion and maximum single harmonic as below:
PRO1000RTTotal harmonic 57.2%Single harmonic 46.1%
PRO1500RTTotal harmonic 42.8%Single harmonic 26.6%
NOTICE: This equipment has been tested and found to comply with the limits
for a Class B computing device in accordance with the specifications in Subpart J of Part 15 of FCC Rules and the Class B limits for radio noise emissions
from digital apparatus set out in the Radio Interference of the Canadian Department of Communications. These limits are designed to provide reasonable
protection against such interference in a residential installation. This equipment generates and uses radio frequency and if not installed and used properly ,
that is, in strict accordance with the manufacturer's instructions, this equipment may cause interference to radio and television reception. If this equipment does cause interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
Re-orient the receiving antenna.
Relocate the computer with respect to the receiver.
Move the computer away from the receiver.
Plug the computer into a different outlet so that the computer and receiver
are on different branch circuits.
Shielded communications interface cables must be used with this product.
WARNING: Changes or modifications to this unit not expressly ap-
proved by the party responsible for compliance could void the user's
authority to operate the equipment.
4
NOTE: These UPSs are shipped with the batteries disconnected. The batter-
ies must be connected before putting these UPSs into service. Refer to Section 3 "Installation" for connecting the batteries.
Life Support Policy
As a general policy , we do not recommend the use of any of our products in life
support applications where failure or malfunction of the product can be reasonably expected to cause failure of the life support device or to significantly affect
its safety or effectiveness. We do not recommend the use of any of our products in direct patient care. We will not knowingly sell our products for use in
such applications unless it receives in writing assurances satisfactory to us
that (a) the risks of injury or damage have been minimized, (b) the customer
assumes all such risks, and (c) our liability is adequately protected under the
circumstances.
Examples of devices considered to be life support devices are neonatal oxygen
analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other
purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia
detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis
systems, neonatal ventilator incubators, ventilators for both adults and infants,
anesthesia ventilators, and infusion pumps as well as any other devices designated as “critical” by the United St ates FDA.
Hospital grade wiring devices and leakage current may be ordered as options
on many of our UPS systems. We do not claim that units with this modification
are certified or listed as Hospital Grade by us or any other organization. Therefore, these units do not meet the requirements for use in direct patient care.
5
English
CONTROL PANEL
REAR P ANEL
English
1. RS232 Comminucations Port is for UPS monitoring and control.
2. USB Communications Port is for UPS monitoring and control.
3. The RJ1 1/45 are used for phone/fax/modem and network protection.
6. Surge ONL Y output receptacles for non-critical equipment.
7. Input power cord is for connecting to the Utility Power.
8. Input circuit breaker is for protection against an excessive overload.
1. Scroll Button: To scroll through the UPS parameters.
2. Battery Capacity Bar Graph: Displays the amount of Battery Capacity
available in the AC and Battery mode.
3. Load Capacity Bar Graph: Displays the amount of load connected to the
UPS in the AC and Battery mode.
4. AC normal and Boost/Buck mode Icon: Illuminates when the UPS is in the
AC normal mode and flashs when the UPS is in the Boost or the Buck
mode.
5. On-Battery Icon: Illuminates when the UPS is operating in the Battery mode.
6. Overload Icon: Illuminates when the amount of load attached to the UPS
exceeds its power rating,
7. UPS Parameters and Error codes:
Input - Volt age and Frequency.
Output - Volt age and Frequency.
Estimated Runtime (minutes) - AC normal and Battery mode.
S.L.F - A site wiring fault has been detected.
FAL - An internal fault has been detected.
8. On/Off/Test Button: T o turn the UPS On/Off and to perform a ten-second
battery test.
6
Model #Input Power Plug
PRO1000RT
PRO1500RT
NEMA 5-15P W/10 ft cord
Output Power Receptacles
6-NEMA 5-15R Battery Backup & Surge
2-NEMA 5-15R Surge Only
INST ALLATION PLACEMENT
This UPS series is only intended to be install in an indoor temperature controlled environment that is free of conductive contaminants. DO NOT operate
the UPS in: extremely dusty and/or unclean areas, locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct
sunlight. Select a location, which will provide good air circulation for the UPS at
all times. Route power cords so they cannot be walked on or damaged. Typical battery life is 3 to 5 years. Environmental factors do affect battery life. High
temperatures, poor utility power, and frequent, short duration discharges have a
negative impact on battery life.
7
INST ALLATION
Be sure to read the installation placement and all the cautions before installing
the UPS. Place the UPS in the final desired location and complete the rest of
English
the installation procedure. These UPSs are shipped with the internal batteries
disconnected. The batteries must be connected before putting these UPSs
into service. See the Connecting The Batteries procedure to connect the batteries.
CONNECTING THE BA TTERIES
(QUALIFIED SERVICE PERSONNEL ONL Y)
Please read all of the WARNINGS and CAUTIONS before attempting to connect the batteries.
1. Remove the UPS from the shipping box and set on the floor or a bench top.
2. Remove the front panel retaining screws.
3. Lay the front panel on top of the UPS.
4. Verify proper polarity. Connect the battery connectors (red and black) to gether.
NOTE: Some sparking might occur, this is normal.
5. Re-install the front panel onto the UPS.
6. Re-install the front panel retaining screws.
7. Continue with the rest of the Installation.
RACKMOUNT CONFIGURA TION
This UPS comes with mounting brackets for the standard 19" (46.5cm) rack.
The mounting brackets to fit a 23" (59.2cm) standard rack are also available.
The screws for mounting the UPS to the rack are not included (screw size
varies with rack size).
1. Locate the mounting bracket screw holes on the side panels of the UPS, at
the front of the UPS. NOTE: The mounting brackets can also be mounted
in the middle of the UPS.
2. Align the mounting bracket with the mounting bracket screw holes.
3. Att ach the mounting bracket with the retaining screws.
4. Mount the UPS into the rack and secure with the retaining screws.
WARNING: Use two or more people when installing the UPS. Use CAUTION,
the UPS is extremely heavy . Do not move the rack after the unit s have been
installed. The rack may be unstable due to the weight distribution.
5. The Rackmount Configuration is complete. See Connecting your Equipment
English
TOWER CONFIGURA TION
The tower configuration allows the user to install the UPS in the up-right position next to the tower computer. The tower brackets are provided with the UPS.
WARNING: Use two or more people when installing the UPS. Use CAUTION,
the UPS is extremely heavy .
1. Once the location of the UPS has been determined, place the tower brack ets in the desired location.
WARNING: The UPS must be installed in the proper up-right position. If the
UPS is not installed in the proper up-right position the Batteries will be damaged. Once the UPS is placed in the tower position, looking at the front panel
the YELLOW Battery disconnected label on the top cover of the UPS MUST be
on your left hand side.
8
9
2. The LCD face plate can be rotated to read in the up-right position. Remove
the front panel from the UPS. On the backside of the front panel, push the
English
LCD face plate outwards the face plate will pop out. Position the LCD face
plate so that it reads in the up-right position. Re-install the front panel on
the UPS.
3. The two rackmount brackets are used for the two tower brackets. Remove
the retaining screws and attached the tower brackets as shown. The tower
brackets go on both sides of the UPS. Make sure that the UPS is stable.
4. The Tower Configuration is complete. See Connecting your Equipment.
4. Use the template to mark the screw hole position on the wall. CAUTION,
you should always were protective gear for your hands and eyes when
operating power tools.
5. Att ach the four retaining screws to the wall and make sure that all of the
retaining screws are screwed into structural material. Then clean the area
of any loose material. Do not tighten the retaining screws all the way , leave
approximately 3/8" of the retaining screws sticking out.
6. Position the UPS, so that the mounting bracket keyed holes line up with the
four retaining screws. Slide the UPS down until its resting securely on the
four retaining screws.
7. Tighten the four retaining screws to secure the UPS to the wall.
8. The Wallmount Configuration is complete. See Connecting your Equipment.
English
WALLMOUNT CONFIGURATION
The wallmount configuration allows the user to mount the UPS on the wall.
There is a wallmount bracket kit available for the UPS. The kit includes two wall
mounting brackets, ten retaining screws, and the wallmount template. WARN-ING: Use two or more people when installing the UPS. Use CAUTION, the
UPS is extremely heavy. The UPS's side panels have mounting bracket screw
holes for attaching the wall mounting brackets.
1. Once the location and position of the UPS has been determined, lay the
UPS down flat.
WARNING: The UPS must be installed in the proper up-right position. If the
UPS is not installed in the proper up-right position the Batteries will be damaged. Once the UPS is placed on the wall, looking at the front panel the
YELLOW Battery disconnected label on the top cover of the UPS MUST be on
your left hand side.
2. Align the mounting brackets with the mounting bracket screw holes and
attach with the six retaining screws.
3. The LCD face plate can be rotated to read in the up-right position. Remove
the front panel from the UPS. On the backside of the front panel, push the
LCD face plate outwards the face plate will pop out. Position the LCD face
plate so that it reads in the up-right position. Re-install the front panel on
the UPS.
10
CONNECTING YOUR EQUIPMENT
Plug the mission critical equipment into the Battery Backup & Surge output
receptacles on the rear panel of the UPS. Plug the non-critical equipment into
the Surge Only output receptacles on the rear panel of the UPS. Ensure that
the connected equipment does not exceed the maximum output rating of the
UPS (refer to the information label on the UPS or the electrical specifications in
this manual). DO NOT PLUG EXTENSION CORDS, ADAPTER PLUGS, SURGE
STRIPS OR POWER STRIPS INTO THE OUTPUT RECEPT ACLES OF THE
UPS. NOTE: Risk of damaging the UPS and/or connected equipment.
CAUTION! DO NOT connect a laser printer to the output of the UPS.
11
CONNECTING THE UPS TO AN AC SOURCE
CAUTION - To reduce the risk of fire, connect only to a circuit provided with 20
amperes maximum branch circuit over-current protection in accordance with
English
the National Electric Code, ANSI/NFPA 70. Plug the UPS into a two pole, three
wire, grounded receptacle only. DO NOT PLUG THE UPS INTO EXTENSION
CORDS, ADAPTER PLUGS, SURGE STRIPS OR POWER STRIPS. DO NOT
CUT THE INPUT PLUG OFF AND ATTEMPT TO HARDWIRE THIS UPS, DOING SO WILL VOID THE WARRANTY.
CHECKING THE SITE WIRING FAULT
After plugging the UPS into the wall outlet, check the LCD screen on the front
panel of the UPS for a Site Wiring Fault (S.L.F). If the S.L.F is illuminated, the
UPS is plugged into an improperly wired wall outlet. If the UPS indicates a Site
Wiring Fault (S.L.F), have a Qualified Electrician correct the problem.
CHARGING THE BATTERY
The UPS will charge the internal batteries whenever the UPS is connected to
an AC source and there is an acceptable AC voltage present (90 - 150VAC). It
is recommended that the UPS's batteries be charged for a minimum of 4 hours
before use. The UPS may be used immediately, however, the “On Battery”
runtime may be less than normally expected. Typical battery life is 3 to 5
years. Environmental factors do affect battery life. High temperatures, poor
utility power, and frequent, short duration discharges have a negative impact on
battery life. NOTE: If the UPS is going to be out of service or stored for a
prolonged period of time, the batteries must be recharged for at least twentyfour hours every ninety days.
COMMUNICATIONS PORT CONNECTION (OPTIONAL)
The power monitoring software and interface cables can be used with the UPS.
Use only the interface cables that come with these UPSs. Connect the interface cable (Serial or USB) to the appropriate communications port on the rear
panel of the UPS. Connect the other end of the cable to the device that will be
monitoring/controlling the UPS. NOTE: Connecting to the Communications
Port is optional. The UPS works properly without this connection.
ACCESSORY SLOT (OPTIONAL)
The Accessory slot on the rear panel of the UPS is for an SNMP Card or a Dry
Contact Relay card. Contact your local dealer for the available option cards.
NOTE: Connecting to the Communications Port is optional. The UPS works
properly without this connection.
NETWORK/PHONE/FAX/MODEM PROTECTION CONNECTION (OPTIONAL)
Connect a 10/100 Base-T network, single line phone, Fax or Modem line to the
RJ11/45 modular connectors on the rear panel of the UPS. This connection will
require another length of telephone or network cable. The cable coming from
the telephone service or networked system is connected to the port marked
“IN”. The equipment to be protected is connected to the port marked "OUT".
NOTE: Connecting to the Network/Phone/Fax/Modem modular connectors is
optional. The UPS works properly without this connection.
CAUTION! The TNV connector shall use the same type of RJ45.
12
English
SYSTEM OVERVIEW
This Line-Interactive UPS protects computers, servers, telecom systems, VoIP
systems, security systems, and a variety of electronic equipment from blackouts, brownouts, overvoltages, and surges. The AVR function continuously
corrects the voltages, in-between the brownout and overvoltage transfer points
(90 - 150VAC), to a safe usable level. When the UPS is operating in the AVR
mode the audible alarm will remain silent and the AC normal mode indicator will
blink. During normal AC operation, the UPS will quietly and confidently protect
your system from power anomalies.
The UPS will charge the batteries with the UPS in the on or off position when
the UPS is plugged into the wall outlet and there is an acceptable AC voltage
present (90 - 150V AC). When a blackout, brownout, or an overvolt age condition
occurs; the UPS will transfer to the battery mode, the On Battery indicator will
illuminate and the audible alarm will sound once every five seconds indicating
that the commercial power is lost or unacceptable. When the commercial
power returns or is at an acceptable level, the UPS will automatically transfer
back to the AC normal mode and start recharging the batteries. During an
extended outage when there is approximately two minutes of backup time remaining the audible alarm will sound twice every five seconds. This Low Battery Warning is informing the user that they should save all open files and turn
off their computer. When the batteries reach the predetermined level the UPS
will automatically shutdown protecting the batteries from over discharging. Once
the commercial power returns the UPS will automatically restart, providing safe
usable power to the connected equipment and start recharging the batteries.
TURNING THE UPS ON / OFF
To turn the UPS on: press and hold the On/Off/Test Button until the alarm
sounds one beep and then release. The UPS will perform a five second internal
self-test. Once the UPS has passed its internal self-test the UPS will provide
an output and the load will be powered. To turn the UPS off: press and hold the
On/Off/Test Button until the alarm sounds one beep and then release.
TEST BUTTON
To perform a ten-second user invoked battery test: With the UPS in the AC
normal mode, press and hold the On/Off/Test Button until the alarm sounds four
beeps, and then release. During the test, the UPS will switch to the Battery
mode, the On-Battery icon will illuminate and the alarm will sound.
SCROLL BUTTON
Press the Scroll Button to scroll through the UPS parameters. The UPS parameters are displayed on the LCD screen.
13
LCD SCREEN
The LCD provides the user with a variety of useful information. The LCD has a real-
time meter to display, in numeric fashion, the following data:
English
Input Voltage and Frequency
Output Voltage and Frequency
Connected Load Capacity
Battery Capacity
Estimated runtime in the AC and DC mode
The LCD will include dedicated icons for the following information:
AC Normal
On Battery
AVR Mode (Boost and Buck) – The AC Normal icon will flash
Overload
Weak/Bad Battery (Battery Capacity Bar Graph will flash)
Site Wiring Fault (S.L.F. will be displayed)
UPS Fault (FAL will be displayed)
The LCD does have a backlight that will turn on when the UPS is turned on. After
approximately 20-seconds the backlight will turn off to conserve energy. When an
event (alarm) occurs, such as going to the battery mode, the backlight will turn on for
approximately 20-seconds to alert the user that an event has occurred and then the
backlight will turn off. While the Scroll button is in use the backlight will remain on.
Approximately 20-seconds after the Scroll button has stopped being used the backlight will turn off to conserve energy.
SELF-TEST
The self-test feature is useful to verify the correct operation of the UPS and the
condition of the batteries. The length of the test that is automatically performed every
two weeks is longer than the start-up or user invoked test. This every two week test
will run for approximately fifteen-seconds to measure the battery’s capability to support the output load. The start-up and user invoked test will run for approximately
ten-seconds. If the UPS fails one of these tests, one of the icons or the information
displayed on the LCD will remain illuminated indicating the type of problem. NOTE:
The UPS will automatically perform a self-test on start-up and every two weeks.
RS232 COMMUNICATIONS PORT
The power monitoring software and interface cables can be used with the UPS. Use
only the interface cables that come with these UPSs. The RS232 communication
port is a standard DB9 female with both RS232 and simulated contact closure
capability. The pinout for the port is depicted per the chart below:
Pin 1: Simulated contact closure Low Battery Warning, NO
Pin 2: /TXD
Pin 3: /RXD and receive UPS shutdown command (connect a minimum of +5VDC
to a maximum of +12VDC for 4-seconds to completely shutdown the
UPS. The shutdown command is ONLY active in the battery mode)
Pin 5: Ground
Pin 8: Simulated contact closure AC fail, NO
Pins 4, 6, 7, 9: Not Used
ACCESSORY SLOT
The Accessory slot on the rear panel of the UPS is for an SNMP Card or a Dry Contact
Relay card. Contact your local dealer for the available option cards.
14
USB COMMUNICATIONS PORT
This UPS series supports USB communications. Use the interface cable that comes
with the UPS. The USB communications protocol is HID. The HID USB driver
comes standard in the Windows OS. Simply plug the USB cable into the UPS and
the computer then follow the prompts on the screen.
POWER MONITORING SOFTW ARE
The UPS comes with power monitoring software. See the software CD for the
installation of the power monitoring software.
ALARMS
ON BA TTERY
When the UPS is operating on the batteries, the AC normal icon will extinguish, the
On-Battery icon will illuminate and the alarm will sound one beep every five seconds. Once the UPS returns to the normal AC mode, the alarm will stop, the OnBattery icon will extinguish and the AC normal icon will illuminate.
LOW BATTER Y WARNING
When the batteries reach the predetermined level, the alarm will sound two beeps
every five seconds and the Battery Bar Graph will display the remaining battery
capacity. This condition will continue until either AC returns or the UPS’s self protection circuit shuts the UPS down to protect the battery from over discharging.
WEAK/BAD BA TTERY
The UPS automatically tests the battery’s condition. If the battery is weak, bad or
disconnected, the Battery Capacity Bar Graph will flash and the alarm will sound
three beeps every five minutes until the battery is either reconnected or replaced.
This alarm will be repeated until the batteries pass a self-test. It is recommended
that the UPS be allowed to charge overnight before performing a battery test to
confirm a Weak/Bad Battery condition.
OVERLOAD
When the amount of load attached to the UPS exceeds its power rating, the Overload
icon will illuminate and the alarm will sound continuously (AC and Battery modes).
This alarm will remain on until the excess load is removed or the UPS’s self protection circuit shuts the UPS down. To clear the overload alarm when the UPS has
shutdown requires that the UPS perform a battery test. First remove part of the load,
then turn the UPS on, the Overload icon and the alarm will be on. Second either use
the Test Button or unplug the input power cord to perfom the battery test.
UPS FAULT
When the UPS detects an internal fault, "FAL" will be displayed on the LCD screen,
the alarm will sound continuously and the output will be turned off. The fault condition, in some instances, may be reset by turning the UPS off and then on. If the fault
condition does not clear the UPS must be sent in for service.
BA TTERY OVER CHARGE PROTECTION
If the charger is providing too much voltage to the battery the UPS will turn off the
charger to protect the battery . When the charger voltage exceeds 14.52V/battery the
charger will turn off. The alarm will sound three beeps every five seconds and the
Battery Capacity Bar Graph will flash. In some instances, the charger may be reset
by turning the UPS off and then on. When the charger voltage exceeds 15.0V/battery
the charger will turn off. The alarm will sound three beeps every five seconds and
the Battery Capacity Bar Graph will flash. The UPS will automatically transfer to the
battery mode and operate until the UPS shuts down due to battery exhaustion. The
UPS must be sent in for service.
15
English
English
English
Symptom
UPS will not turn on
UPS operates in
battery mode only,
even though there
is normal AC
present
"FAL" is displayed
on the LCD
The AC mode icon
is illuminated, but
there is no output
UPS does not
provide expected
runtime
The Battery Capacity Bar Graph is
flashing
Overload icon is
illuminated
The AC mode icon
is flashing and the
alarm is silent
"S.L.F" is displayed on the LCD
Possible Cause
On/Off/Test button not
pressed
Input AC circuit breaker is
tripped
UPS has detected an internal fault
The UPS is being controlled via its communications port
The batteries may be
weak or at the end of their
useful service life
Loose connections at the
batteries, Weak batteries,
Bad batteries
The output load has exceeded the UPS's capacity
The UPS is operating in
the Boost or the Buck
mode
The UPS has detected an
improperly wired wall outlet.
What T o Do
Press, hold and then release
the On/Off button to start UPS
Reset circuit breaker by
pressing the plunger back in.
If the AC circuit breaker trips
after UPS starts up, reduce
the load on the UPS
Call for service
Disconnect the computer
cable from the UPS and press
the On button. If UPS works
normally, the software has
control of the UPS
Charge the batteries for 8hours and retest. If the runtime
is still less than expected, the
batteries may need to be
replaced, even though the
Weak/Bad Battery LED is not
illuminated
Check battery connections,
charge the batteries for 8hours, replace the batteries
Check the specifications (see
section 8). Remove part of
the load
The UPS is performing its intended function
Contact a Qualified Electrician
to correct the problem.
REPLACING THE BATTERY
(QUALIFIED SERVICE PERSONNEL ONL Y)
Please read all of the WARNINGS and CAUTIONS before attempting to service
the batteries. Typical battery life is 3 to 5 years. Environmental factors do
affect battery life. High temperatures, poor utility power, and frequent, short
duration discharges have a negative impact on battery life.
WARNING!
CAUTION:
CAUTION:
CAUTION:
This UPS contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement
procedure. This UPS contains no user serviceable parts. Repairs and battery replacement must be performed by QUALIFIED
SERVICE PERSONNEL ONL Y .
Do not open or mutilate batteries. Released electrolyte is harmful
to the skin and eyes and may be toxic.
Do not dispose of batteries in a fire. The batteries may explode.
The batteries in this UPS are recyclable. Dispose of the batteries properly . The batteries contain lead and pose a hazard to the
environment and human health if not disposed of properly . Refer
to local codes for proper disposal requirements or return the
battery to the supplier.
The battery system can present a risk of electrical shock. These
batteries produce sufficient current to burn wire or tools very rapidly , producing molten met al. Observe these precautions when
replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disco nnecting the battery terminals.
6. Determine if the battery is inadvertently grounded. If the bat tery is, remove the source of the grounding. Contact with any
part of a grounded battery can result in an electrical shock.
The likelihood of such shock will be reduced, if such grounds
are removed during installation and maintenance.
16
17
CAUTION:
English
Replace batteries with the same number and type as originally
installed in the UPS. These batteries have pressure operated vents.
These UPSs contain sealed non-spillable maintenance-free lead
acid batteries.
6. Remove the front panel retaining screws. (FIG. 2)
7. Lay the front panel on top of the UPS.
FIG. 2
Model #
Battery Module Part #
PRO1000RT
BM0043
PRO1500RT
BM0044
BATTERY REPLACEMENT PROCEDURE
PLEASE READ THE CAUTIONS AND W ARNINGS BEFORE A TTEMPTING
TO REPLACE THE BA TTERIES
Hot-swappable batteries mean that the batteries can be replaced without powering down the whole UPS system.
NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up. To hot-swap the battery
module start with step number 6.
1. Turn off the equipment that is plugged into the output of the UPS.
2. Press the On/Off/Test Button on the front panel to turn the UPS off.
3. Unplug the UPS's AC power cord from the AC wall outlet.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the rear panel of the UPS.
FIG. 1
English
8. Remove the two retaining screws for the battery retaining bracket. (FIG. 3)
9. Remove the battery retaining bracket.
FIG. 3
18
19
10. Disconnect the Battery connectors (red and black). (FIG . 4)
1 1. Grasp the battery pull tab and gently pull the battery module out of the UPS
English
and set aside.
NOTE: Use Caution, the battery module is heavy .
FIG. 4
12. Slide the new battery module into the UPS.
13. Re-install the battery retaining bracket.
14. Re-install the two retaining screws for the battery retaining bracket.
15. Verify proper polarity. Reconnect the battery connectors (red and black).
NOTE: Some sparking might occur, this is normal.
16. Re-install the front panel on the UPS.
17. Re-install the front panel retaining screws.
18. Properly dispose of the old batteries at an appropriate recycling facility or
return them to the supplier in the packing material for the new batteries.
19. The UPS is now ready for the normal operation.
NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the battery
module, the user must initiate a self-test to clear the Weak/Bad Battery Alarm.
To initiate a self-test see section 4 "TEST BUTTON".
English
IF THE UPS REQUIRES SERVICE
1. Use the TROUBLESHOOTING section to eliminate obvious causes.
2. Verify there are no circuit breakers tripped. A tripped circuit breaker is the
most common problem.
3. Call your dealer for assistance. If you cannot reach your dealer, or if they
cannot resolve the problem call or fax the Technical Support department at
the following numbers; Voice phone (972) 446-7363, F AX line (972) 446-901 1
or contact Minuteman UPS at mmsupport@minutemanups.com.
Please have the following information available BEFORE calling the T echni-
cal Support Department.
A. Your name and address.
B. Where and when the unit was purchased.
C. All of the model information about your UPS.
D. Any information on the failure, including LEDs that may be illuminated.
E. A description of the protected equipment, including model numbers if
possible.
F . A technician will ask you for the above information and, if possible, help
solve your problem over the phone. In the event that the unit requires
factory service, the technician will issue you a Return Material Authoriza tion Number (RMA #).
G . If the UPS is under warranty , the repairs will be done at no charge. If not,
there will be a charge for repair.
4. Pack the UPS in its original packaging. If the original packaging is no longer
available, ask the T echnical Support T echnician about obtaining a new set.
It is important to pack the UPS properly in order to avoid damage in transit.
Never use Styrofoam beads for a p acking material.
A. Include a letter with your name, address, day time phone number , RMA
number, a copy of your original sales receipt, and a brief description of the
problem.
5. Mark the RMA # on the outside of all packages. The factory cannot accept
any package without the RMA # marked on the outside.
6. Return the UPS by insured, prepaid carrier to:
20
Para Systems Inc.
MINUTEMAN UPS
1455 LeMay Drive
Carrollton, TX 75007
A TTN: RMA # _______
21
English
SYSTEM SPECIFICA TIONS
Model Number
Topology
Maximum Power Capacity
PRO1000RT
Line-Interactive, Simulated Sine Wave
1000VA
700W
PRO1500RT
INPUT
Number of PhaseSingle (1∅2W +G)
Nominal Voltage120VAC
Acceptable Input voltage
Voltage Range
Frequency Limits
Low Voltage Transfer Point
High Voltage Transfer Point
Input Protection
50 or 60 Hz, +/-5Hz, autosensing
90V resets to Utility Power at 94V or higher
150V resets to Utility Power at 146V or lower
0 - 160VAC
90 - 150VAC
Resettable Circuit Breaker
OUTPUT NON-BATTER Y OPERA TION
Voltage Range
Voltage Regulation120VAC: -13.3% - +10.0%
Frequency Range60Hz: 55 - 65Hz or 50Hz: 45 - 55Hz
Efficiency (Line Mode)
104 - 132VAC
>90% (Full Load)
OUTPUT BATTER Y OPERA TION
Waveform Type
Nominal Voltage
Voltage RegulationNominal +/-5% (until Low Battery Warning)
Frequency
Transfer Time
Overload Capacity
Protection
DC Mode: 110% for 10-seconds then shutdown, 120% Shutdown Immediately
Over-Current, Short-Circuit Protected and Latching Shutdown
Simulated Sine Wave (Step Wave)
120VAC
50/60Hz, +/-0.5Hz (unless synchronized to utility)
6 ms Typical
AC Mode: 110% for 5-seconds then fault, 120% Shutdown Immediately
REGULA TORY COMPLIANCE
1500VA
1050W
BA TTERY SYSTEM
Battery Type
Typical Recharge T ime
Typical Battery Life
Battery Module Part #
Runtime: Half Load (minutes)
Runtime: Full Load (minutes)
Sealed, Non-Spillable, Maintenance Free, V alue Regulated Lead Acid
From Full load dishcarge: 4-hours to 80%, 8-hours to 90%
3 to 5 years. Environmental factors do affect battery life.
High temperatures, poor utility power, and frequent, short
duration discharges have a negative impact on battery life.
BM0043
17
5
BM0044
17
5
SURGE PROTECTION AND FIL TERING
Surge Energy Rating1140 J
Surge Current Capability
Surge Response Time
Surge voltage let-through (as a percentage
of an applied ANSI C62.41 Cat. A +/-6 kV)
10/100 Base-T surge protection let-through
(as a percentage of an applied +/-6 kV 1.2/50
us, 500 a 8/20 uS test)
Telephone line surge protection let-through
(as a percentage of an applied +/-6 kV 1.2/50
us, 500a 8/20 uS test)
Noise Filter
Audible Noise at 1 m (3 ft.)
0 ns (instantaneous) normal mode; <5 ns common mode
>45db normal and common mode EMI/RFI suppression
6500 Amps total
< 5%
< 5%
< 1%
<45 dBA
ENVIRONMENT AL
Operating Temperature 0 to 40 degrees C (+32 to +104 degrees F) at
Operating Elevation 0 to 1,500m (0 to +5,000 ft)
Operating Temperature 0 to 35 degrees C (+32 to +95 degrees F) at
Operating Elevation 1501 to 3,000m (0 to +10,000 ft)
Storage Temperature
Operating/Storage Humidity95% Non-Condensing
Storage Elevation
-15 to +45°C (+5 to +113°F)
0 to 15,000m (0 to +50,000 ft)
PHYSICAL
Size - Net
L X W X H
Weight - Net
Size - Shipping
L X W X H
Weight - Shipping
35.1 lbs
15.9 Kgs
40.8 lbs
18.5 Kgs
15.7 x 17.3 x 3.5"
398 x 440 x 89 mm
43.0 lbs
19.5 Kgs
20.7 x 21.9 x 8.5"
526 x 555 x 215 mm
48.5 lbs
22.0 Kgs
English
Safety and Approvals
EMC Verification
22
cTUVus (conforms to UL1778, CSA 22.2 standards)
FCC Class B, CE certified
23
English
A1.DECLARATION OF CONFORMITY
Application of Council Directive(s): 89/336/EEC, 73/23/EEC
Para Systems, Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three
years from the date of purchase. For equipment sites within the United States and Canada, this
warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center. The customer pays for
shipping the unit to Para Systems. Para Systems pays ground freight to ship the unit back to the
customer. Replacement part s and warranty labor will be borne by Para Systems. For equipment located outside of the United States and Canada, Para Systems only covers faulty p arts.
Para Systems products repaired or replaced pursuant to this warranty shall be warranted for
the unexpired portion of the warranty applying to the original product. This warranty applies
only to the original purchaser who must have properly registered the product within 10 days of
purchase.
The warranty shall be void if (a) the equipment is damaged by the customer, is improperly used,
is subjected to an adverse operating environment, or is operated outside the limits of its
electrical specifications; (b) the equipment is repaired or modified by anyone other than Para
Systems or Para Systems approved personnel; or (c) has been used in a manner contrary to
the product’s User's Manual or other written instructions.
Any technical advice furnished before or after delivery in regard to use or application of Para
Systems’s equipment is furnished without charge and on the basis that it represents Para
Systems’s best judgment under the circumstances, but it is used at the recipient’s sole risk.
EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO WARRANTIES, EXPRESSED OR
IMPLIED, INCLUDING WARRANTIES OF MERCHANT ABILITY AND FITNESS FOR A P ARTICULAR
PURPOSE. Some states do not permit limitation of implied warranties; therefore, the aforesaid
limitation(s) may not apply to the purchaser.
Manufacturer’s Name: Para Systems, Inc. (MINUTEMAN UPS)
Manufacturer’s Address: 1455 LeMay Drive
Carrollton, Texas 75007 USA
Type of Equipment: Uninterruptible Power Supplies (UPS)
Model No: PRO1000RT, PRO1500RT
Y ear of Manufacture: Beginning November 1, 2009
I hereby declare that the equipment specified above conforms to the above
Directive(s).
Robert Calhoun
(Name)
Manager Engineering
(Position)
English
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL P ARA SYSTEMS BE LIABLE FOR DIRECT ,
INDIRECT , SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE
OF THIS PRODUCT , EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically ,
Para Systems is not liable for any costs, such as lost profits or revenue, loss of equipment, loss
of use of equipment, loss of software, loss of data, cost of substitutes, claims by third parties,
or otherwise. The sole and exclusive remedy for breach of any warranty, expressed or
implied, concerning Para Systems’s products and the only obligation of Para Systems hereunder, shall be the repair or replacement of defective equipment, components, or part s; or, at Para
Systems’s option, refund of the purchase price or substitution with an equivalent replacement
product. This warranty gives you specific legal rights and you may also have other rights
which vary from state to state.
No employee, salesman, or agent of Para Systems is authorized to add to or vary the terms of
this warranty.
24
Place: Carrollton, Texas, USA
Date: November 1, 2009
25
Notes:Notes:
English
English
26
27
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.