Minuteman Smart Up, MSU 700, MSU 1000, MSU 1400 User Manual

Smart Up Series
Uninterruptible Power Supply
User’s Manual
Smart Up Series User’s Manual
1. Introduction 2
2. Controls and Indicators 4
4. Operation 7
5. Troubleshooting 1 1
6. Replacing the Battery 12
7. Obtaining Service 15
8. Specifications 16
9. Limited Warranty 17
ã Copyright Para Systems, Inc., 1999
1
Thank you for purchasing a Minuteman power protection product. It has been designed and manufactured to provide many years of trouble free service.
Please read the manual before installing your Smart Up Series UPS as it provides the information that should be followed during installation and main­tenance of the UPS and batteries allowing you to correctly set up your sys­tem for the maximum safety and performance.
Included is information on customer support and factory service if it is required. If you experience a problem with the UPS, please refer to the Troubleshooting guide in this manual to correct the problem or collect enough information so that the Minuteman technical support department can rapidly assist you.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
NOTICE: This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense.
This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference regula­tions of the Canadian Department of Communications.
Le présent appareil numérique n’emit pas de bruits radioélectriques dépassant les limites applicables aux appareils numérique de la Class A presc rites dans le Règlement sur le brouillage radioélectrique édicte
CAUTION: WHEN DISCONNECTING THE INTERNAL BATTERIES, THE UPS
CANNOT BE RUNNING IN THE BA TTERY MODE. THE UPS MUST BE OFF OR SUPPLYING POWER T O THE LOAD FROM THE UTILITY MAINS.
W ARNING: CHANGES OR MODIFICATIONS TO THIS UNIT NOT EXPRESSL Y
APPROVED BY THE P ARTY RESPONSIBLE FOR COMPLIANCE COULD VOID THE USER’S AUTHORITY TO OPERA TE THE EQUIPMENT .
2
Receiving Inspection
After removing your Minuteman UPS from its carton, it should be inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored. The packing materials that your UPS was shipped in are carefully designed to minimize any shipping damage. In the unlikely case that the UPS needs to be returned to Minute­man, please use the original packing material. Since Minuteman is not responsible for shipping damage incurred when the system is returned, the original packing material is inexpensive insurance.
PLEASE SA VE THE P ACKING MA TERIALS!
W ARNING: RISK OF ELECTRICAL SHOCK. HAZARDOUS LIVE PARTS
INSIDE THIS POWER SUPPL Y ARE ENERGIZED FROM THE BA TTERY EVEN WHEN THE AC INPUT POWER IS DISCONNECTED.
TO DE-ENERGIZE THE OUTPUTS OF THE UPS:
1. IF THE UPS IS ON PRESS THE ON/OFF BUTTON FOR 1 SECOND.
2. DISCONNECT THE UPS FROM THE AC POWER OUTLET .
3. TO DE-ENERGIZE THE UPS COMPLETEL Y , DISCONNECT THE BA TTERY .
(SEE SECTION 6 FOR INSTRUCTIONS)
CAUTION! TO REDUCE THE RISK OF ELECTRICAL SHOCK IN CONDI-
TIONS WHERE LOAD EQUIPMENT GROUNDING CANNOT BE VERIFIED, DISCONNECT THE UPS FROM THE AC POWER OUTLET BEFORE INST ALLING A COMPUTER INTERFACE CABLE. RECONNECT THE POWER CORD ONL Y AFTER ALL SIGNALING CONNECTIONS ARE MADE.
CAUTION! CONNECT THE UPS TO A TWO POLE, THREE WIRE GROUND-
ING AC POWER OUTLET . THE RECEPT ACLE MUST BE CONNECTED TO APPROPRIA TE BRANCH PROTECTION (CIRCUIT BREAKER OR FUSE). CONNECTION TO ANY OTHER TYPE OF RECEPT ACLE MA Y RESUL T IN A SHOCK HAZARD AND VIOLA TE LOCAL ELECTRICAL CODES.
Para Systems Life Support Policy
As a general policy, Para Systems, Inc. (Para Systems) does not recommend the use of any of its products in life support applications where failure or malfunction of the Para Systems product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness. Para Systems does not recommend its products for use in direct patient care. Para Systems will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to Para Systems that (a) the risks of injury or damage have been minimized, (b) the customer assumes all such risks, and (c) the liability of Para Systems, Inc. is adequately protected under the circumstances.
Examples of devices considered to be life support devices are neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief or other purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators for both adults and infants, anesthesia ventilators, and infusion pumps as well as any other devices designated as “critical” by the United States FDA.
Hospital grade wiring devices and leakage current may be ordered as options on many PARA SYSTEMS UPS systems. PARA SYSTEMS does not claim that units with this modification are certified or listed as Hospital Grade by PARA SYSTEMS or any other organization. Therefore, these units do not meet the requirements for use in direct patient care.
3
FRONT PANEL
Press and release the On/Test/Alarm Silence button to turn on, test or silence the alarm.
Press and release the OFF button to turn the UPS OFF.
The Buck LED illuminates when the UPS is correcting for a high utility line voltage.
The On Battery LED illuminates when the UPS is supplying power from the battery.
The AC Normal LED illuminates when the utility voltage is normal.
The Boost LED illuminates when the UPS is correcting for a low utility line voltage. The Overload LED illuminates when the loads connected to the UPS exceeds the
UPS power rating (see Section 4). The Replace battery LED illuminates when the UPS has detected that battery
replacement is required (see Section 6). The Load Level LEDs illuminate to show the percentage of load connected to the
UPS: 20%, 40%, 60% or 80%.
The Battery Level LEDs illuminate to show the percentage of battery capacity remaining: 25%, 50%, 75% or 100%.
4
On/T est/Alarm Silence Off On Battery
Buck Normal Boost Overload Replace Battery Load Battery
Minuteman Smart Up
Rear Panel
Site Wiring Fault
DB9
Connector
Accessory Slot
Option Slot
Output Receptacles
Input Circuit
Breaker
Surge Only Receptacle
Input Power
Site Wiring Fault
DB9 Connector
Accessory Slot
Option Slots
Output Receptacles
Input Circuit
Breaker
Surge Only Receptacle
Input Power
DB9
Connector
Accessory Slot
Option Slot
Output Receptacles
Input Circuit
Breaker
Surge Only Receptacle
Input Power
MSU 1000i &1400i
DB9 Connector
Accessory Slot
Option Slots
Output Receptacles
Input Circuit
Breaker
Surge Only Receptacle
Input Power
5
MSU 1000 &1400
MSU 700
MSU 700i
REAR PANEL
The Accessory Slot is used for SNMP UPS monitoring. Available from Minuteman. The DB9 connector is used for UPS monitoring and control through a computer’s serial port
(see Section 3). The Option Slots are for adding RJ-45/RJ-11 surge protection cards. Available from Min-
uteman. The Site Wiring Fault LED illuminates when the UPS detects an improperly wired AC power
outlet (see Section 3). The Output Power receptacles are NEMA 5-15R type for 120V units and IEC 320 for 230V
units. The Input Power receptacle is a IEC 320. The Input Circuit Breaker will trip in the event the load exceeds the UPS’s power rating.
INSTALLATION PLACEMENT
Please observe the following items: n Install the UPS in a temperature-controlled, indoor environment that is free of conduc-
tive contaminants. Select a location which will provide good air circulation for the UPS at all times. Avoid locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct sunlight.
n Plug the UPS into a two pole, three wire, grounded receptacle only. Do not use exten-
sion cords or adapter plugs.
DB9 CONNECTOR
Minuteman Power Management software and interface cable kits are used with this port (software and cables are optional and available from Minuteman). Use only Minuteman or Minuteman approved interface cables with these UPS’s. Connect the interface cable to the DB9 connector on the rear of the UPS. Secure the connector to the UPS via the screws on the connector housing. Connect the other end of the cable to the device that will be monitor­ing/controlling the UPS.
NOTE: CONNECTING TO THE DB9 IS OPTIONAL. THE UPS WORKS PROPERL Y
WITHOUT A CONNECTION.
6
Loading...
+ 16 hidden pages