Minuteman ED8000RT-XFR User Manual

Page 1
Para Systems, Inc.
1455 Lemay Dr.
Carrollton, TX 75007
Phone: 1-972-446-7363
Fax: 1-972-446-9011 Internet: minutemanups.com UPS Sizing: sizemyups.com
Endeavor 5 - 10KVA
Step Down Transformer
User's Manual
PN - 34000473 R2
Page 2
Table Of Contents
1. Introduction 2
2. Rear Panels 6
3. Installation 8
4. Operation 14
5. Obtaining Service 16
6. Specifications 17
7. Limited Product Warranty 18 A1 . Declaration of Conformity 19
1
Page 3
Chapter 1: Introduction
Thank you for purchasing this power protection product. It has been designed and manufactured to provide many years of trouble free service. Please read this manual before installing your Endeavor Series step down transformer (ED-XFR), models ED5000RT-XFR, ED6000RT-XFR, ED8000RT-XFR and ED10000RT-XFR as it provides important information that should be followed during installation and maintenance of the ED-XFR allowing you to correctly set up your system for the maximum safety and performance. Included is information on customer support and factory service if it is required. If you experience a problem with the ED-XFR please refer to Obtaining Service sec­tion in this manual to collect enough information so that the T echnical Support Department can rapidly assist you.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
CAUTION! This ED-XFR series is ONLY intended to be installed in an indoor
temperature controlled environment that is free of conductive contaminants. This ED-XFR series is not intended for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Dat a Processing Equip­ment ANSI/NFPA 75. The AC inputs of these Step Down Transformers are ONLY intended to be connected to the output of their respective UPS models.
The ED-XFR's input voltage setting must be the same as the UPS's output voltage setting.
CAUTION! The maximum ambient operating temperature for this ED-XFR series is 40°C (“0 ~ 40°C” for Ambient Operation). The external vents and openings on the unit are provided for ventilation.
T o ensure reliable operation of the unit and to protect the unit from over­heating, these vents and openings must not be blocked or covered. Do not insert any object into any of the vents or openings that may hinder the ve­ntilation.
Install the unit in a well ventilated area, away from excess moisture, heat,
dust, flammable gas or explosives.
Leave adequate space (at least 15cm) around all sides of the unit for pr-
oper ventilation.
Do not mount the unit with its front or rear panel facing down at any angle. Before usage, you must allow the unit to adjust to room temperature
(20°C~25°C or 68°F~77°F) for at least one hour to avoid moisture cond­ ensing inside the unit.
CAUTION! The ED5000RT-XFR and ED6000R T-XFR come with an attached #10 AWG input power cord. Connect the input power cord to the output terminal block on the UPS. The AC input s of these Step Down Transformers are ONLY intended to be connected to the output of their respective UPS models. Do not use extension cords, adapter plugs, or surge strips. The installation of upstream and downstream protective devices is highly recom­mended when the UPS system is connected to the mains and the load.
CAUTION! The ED8000RT -XFR and ED10000RT-XFR come with an #6 A WG input power cable in the box. The pins for the input and output cables are included. Connect one end of the input power cable to the input terminal block on the ED-XFR. Connect the other end of the input power cable to the output terminal block on the UPS. The AC inputs of these Step Down T ransformers are ONLY intended to be connected to the output of their respective UPS models. Do not use extension cords, adapter plugs, or surge strips. The installation of upstream and downstream protective devices is highly recom­mended when the UPS system is connected to the mains and the load.
CAUTION! To reduce the risk of electrical shock with the installation of this unit and the connected equipment, the user must ensure that the ED-XFR is properly grounded due to a possible risk of AC current leakage.
WARNING: Qualified Service Personnel ONLY must perform the Installa­tion and Servicing of these ED-XFR. MINUTEMAN accepts no liabilities and is not limited to: injury to the Service Personnel, or damages to; the Step Down Transformer , the UPS, the Battery Pack, or the connected equipment caused by the incorrect installation or servicing of the UPS system. These ED-XFR MUST be operated with their respective UPS models, see the table below:
ED-XFR
UPS
WARNING: When using these S tep Down T ransformers with their respective UPS models, the load capacity of the UPS MUST be derated as follows:
ED5000RT -CU ED5000RT -XFR
4556V A 4100Watts
ED5000RT -XFR ED6000RT -XFR
ED5000RT -CU ED6000RT -CU
ED6000RT -CU ED6000RT -XFR
5556VA 5000Watts
ED8000RT -XFR ED10000RT -XFR
ED8000RT -CU ED10000RT -CU
ED8000RT -CU ED8000RT -XFR
6889V A 6200Watts
ED10000RT-CU ED10000RT -XFR
8889V A 8000Watts
WARNING: This ED-XFR contains potentially hazardous voltages. Do not attempt to disassemble the unit. This unit contains no user serviceable parts. Repairs must be performed by QUALIFIED SERVICE PERSONNEL ONLY.
2
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE STEP DOWN TRANSFORMER. The mounting brackets are ONLY for securing the
unit to the rack.
3
Page 4
CAUTION! T o de-energize the output s of the ED-XFR:
1. Turn off the Load breakers on the rear p anel of the ED-XFR.
2. If the UPS is on press and release the On/Off/Test button after the sec­ond beep.
2. Turn off the input circuit breaker on the rear p anel of the UPS.
3. Turn off the DC breaker on the rear p anel of the Battery Pack.
4. Disconnect the UPS from the AC source.
NOTICE: This equipment has been tested and found to comply with the limits for a Class B computing device in accordance with the specifications in Sub­part J of Part 15 of FCC Rules and the Class B limits for radio noise emissions from digital apparatus set out in the Radio Interference of the Canadian Depart­ment of Communications. These limits are designed to provide reasonable protection against such interference in a residential installation. This equip­ment generates and uses radio frequency and if not installed and used properly , that is, in strict accordance with the manufacturer's instructions, this equip­ment may cause interference to radio and television reception. If this equip­ment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Re-orient the receiving antenna.Relocate the computer with respect to the receiver.Move the computer away from the receiver.Plug the computer into a different outlet so that the computer and receiver
are on different branch circuits.
Shielded communications interface cables must be used with this product. WARNING: Changes or modifications to this unit not expressly approved by
the party responsible for compliance could void the user's authority to operate the equipment.
RECIEVING INSPECTION
Once you receive the product it should be visually inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored by the manufacturer. The packing materials that the product was shipped in were carefully designed to minimize any shipping damage. In the unlikely case that the product needs to be returned to the manufacturer, use the original packing material. Since the manufacturer is not responsible for shipping damage incurred when the product is returned, the original packing material is inexpensive insurance. PLEASE SAVE THE
PACKING MATERIALS!
LIFE SUPPORT POLICY
As a general policy , Para Systems does not recommend the use of any of our products in life support applications where failure or malfunction of the product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness. We do not recommend the use of any of our products in direct patient care. We will not knowingly sell our prod­ucts for use in such applications unless it receives in writing assurances satis­factory to us that (a) the risks of injury or damage have been minimized, (b) the customer assumes all such risks, and (c) our liability is adequately protected under the circumstances.
Examples of devices considered to be life support devices are neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators for both adults and infants, anesthesia ventilators, and infusion pumps as well as any other devices desig­nated as “critical” by the United States FDA.
© COPYRIGHT 2014 BY PARA SYSTEMS, INC.
All Rights Reserved. All right s of this User Manual (“Manual”), including but not limited to the content, information, and figures are solely owned and reserved by Para Systems, Inc. (“Para Systems”). The Manual can only be applied to the operation or the use of this product. Any disposition, duplication, dissemi­nation, reproduction, modification, translation, extraction, or usage of this Manual in whole or in part is prohibited without the prior written permission of Para Systems. Given that Para Systems will continuously improve and develop the product, changes may be made to the information in this Manual at any time without obligation to notify any person of such revision or changes. Para Systems will make all possible efforts to secure the accuracy and the integrity of this Manual. Para Systems disclaims any kinds or forms of warranty , guar­antee, or undertaking, either expressly or implicitly , including but not limited to the completeness, faultlessness, accuracy , non-infringement, merchantability or fitness for a particular purpose of the Manual.
4
5
Page 5
Chapter 2: Rear Panels
1. The Load 4 circuit breaker will trip in the event the load exceeds the power rating.
2. Load 4: 120V output receptacles (3 - 5-15/20R).
3. The Load 3 circuit breaker will trip in the event the load exceeds the power rating.
4. Load 3: 120V output receptacles (3 - 5-15/20R).
5. The Load 2 circuit breaker will trip in the event the load exceeds the power
rating.
6. Load 2: 208V output receptacle (1 - L6-20R). NOTE: The default output
voltage is 208V. 240V is available, but must be configured at the factory .
7. The Load 1 circuit breaker will trip in the event the load exceeds the power
rating.
8. Load 1: 208V output receptacle (1 - L6-30R).
9. The input circuit breaker will trip in the event the load exceeds the ED-
XFR's power rating.
10. The input power cord is for connecting to the output terminal block on the
UPS.
1 1. ED-XFR's circuit breaker will trip in the event that the ED-XFR becomes
overheated.
12. Input voltage selection switch (208 / 240V). The default setting is 208V.
1. The Load 4 circuit breaker will trip in the event the load exceeds the power rating.
2. Load 4: 120V output receptacles (4 - 5-15/20R).
3. The Load 2 circuit breaker will trip in the event the load exceeds the power rating.
4. Load 2: 120V output receptacles (4 - 5-15/20R).
5. The Load 2 circuit breaker will trip in the event the load exceeds the power rating.
6. Load 3: 208V output receptacle (1 - L6-20R).
7. The Load 1 circuit breaker will trip in the event the load exceeds the power rating.
8. Load 1: 208V output receptacle (1 - L6-30R).
9. The input circuit breaker will trip in the event the load exceeds the ED­XFR's power rating.
10. ED-XFR's circuit breaker will trip in the event that the ED-XFR becomes overheated.
1 1. Input terminal block (208V / 240V) is for connecting the input power cable
that comes from the output terminal block of the UPS.
12. Output terminal block for optional hardwiring the load. The available output voltages are 120V / 208V / 240V. NOTE: The two 120V outputs are ind­ividual 5KV A output s and they CANNOT be paralleled.
6
7
Page 6
Chapter 3: Installation
INSTALLATION PLACEMENT
RACKMOUNT CONFIGURA TION
Use the included rackmount brackets and screws to mount the ED-XFR in a rack by following the steps below. USE CAUTION: The ED-XFR is extremely heavy . Use the appropriate number of personnel when installing the UPS system.
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE STEP DOWN TRANSFORMER. The mounting brackets are ONLY for se-
curing the unit to the rack.
This ED-XFR series is ONLY intended to be installed in an indoor temperature controlled environment that is free of conductive contaminants. DO NOT oper­ate the unit in: extremely dusty and/or unclean areas, locations near heating devices, water or excessive humidity, or where the unit is exposed to direct sunlight. Select a location, which will provide good air circulation for the unit at all times. Route power cords so they cannot be walked on or damaged. The AC inputs of these Step Down Transformers are ONLY intended to be con- nected to the output of their respective UPS models. This ED-XFR series is not intended for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment ANSI/NFPA
75. Operating Temperature (Maximum): 0 to 40°C (+32 to +104°F)
Operating Elevation: 0 to 2,000m (0 to +6,562 ft) Operating and Storage Relative Humidity: 95%, non-condensing Storage Temperature: -15 to +50°C (+5 to +122°F) Storage Elevation: 0 to 15,000m (0 to +49,213 f t)
INST ALLATION
Be sure to read the installation placement and all the cautions before installing the ED-XFR. Place the unit in the final desired location and complete the rest of the installation procedure. See the “Rackmount Configuration” to install the unit into the rack. USE CAUTION: The ED-XFR, UPS and Battery Pack are extremely heavy . Use the appropriate number of personnel when installing the UPS system.
1. Attach the rackmount brackets to the mounting holes on the side panel of
the ED-XFR as shown below.
2. Follow steps 1 through 4 to install the ED-XFR into the Rail kit. See the
figure below. Step 1: Adjust the length of the rail according to the rack. Step 2: Securely tighten the wing nuts. Step 3: Secure the rail to the rack with the enclosed screws. Step 4: Slide the ED-XFR onto the rail and secure to the rack with the
enclosed screws.
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE STEP DOWN TRANSFORMER. The mounting brackets are ONLY for securing the
unit to the rack. NOTE: The ED-XFR, UPS and Battery Pack are extremely heavy. Use the
following placement when rack mounting:
1. The ED-XFR should be installed close to the bottom of the rack.
2. Then install the Battery Pack right above the ED-XFR.
3. Then install the UPS right above the Battery Pack.
8
9
Page 7
TOWER CONFIGURA TION
The tower configuration allows the user to install the ED-XFR in the up-right position. The tower stands are provided with the UPS. The tower stand ex­tenders are provided with the ED-XFR. WARNING: Use two or more people when installing the ED-XFR. USE CAUTION: The ED-XFR is extremely heavy. Use the appropriate number of personnel when installing the UPS system.
1. Once the location of the ED-XFR has been determined, place the tower stands in the desired location.
WARNING: The ED-XFR must be installed in the proper up-right position. Once the ED-XFR is placed in the tower stands, the vent holes on the side panels must be facing upwards to provide proper ventilation.
2. Slide the ED-XFR into the tower stands. Make sure that the ED-XFR is stable.
3. The name plate panel can be rotated to read in the up-right position. Rem­ove the front panel from the ED-XFR. On the backside of the front panel, push the name plate panel outwards, the panel will pop out. Rotate the name plate panel counter clockwise so that it reads in the upright position. Re-install the front panel on the ED-XFR.
CONNECTING THE STEP DOWN TRANSFORMER TO THE UPS WARNING: Qualified Service Personnel ONLY must perform the Installa-
tion and Servicing of these ED-XFR.
1. Before connecting to the input / output terminals read all of the Cautions and Warning, then observe the following:
a) Ensure that the UPS is turned off and not connected to the AC sour-
ce or the battery source before any connections are made.
b) Calculate the power consumption of the load to ensure that an over-
load condition does not occur.
c) Ensure that the terminal block screws are secured after connecting
the input / output wires. The terminal block screws should be torque to 18±2Kgf.cm (requires a 3/16" flat-head screwdriver).
d) Ensure that the ED-XFR and the UPS are properly grounded.
2. The input power for the ED-XFR must be single-phase in accordance with its rating label and the specifications in this manual. The ED-XFR's input
voltage setting must be the same as the UPS's output voltage setting.
NOTE: The AC input s of these Step Down Transformers are ONLY intend­ed to be connected to the output of their respective UPS models.
The ED5000RT-XFR and ED6000RT-XFR come with an attached #10 AWG input power cord. Connect the input power cord to the output terminal block on the UPS. The AC inputs of these Step Down Transformers are ONLY intended to be connected to the output of their respective UPS models. Do not use extension cords, adapter plugs, or surge strips. The installation of up­stream and downstream protective devices is highly recommended when the UPS system is connected to the mains and the load.
10
11
Page 8
The ED8000RT -XFR and ED10000RT -XFR come with an #6 A WG input power cable in the box. The pins for the input cable are included. Connect one end of the input power cable to the input terminal block on the ED-XFR. Connect the other end of the input power cable to the output terminal block on the UPS. The AC inputs of these Step Down Transformers are ONLY intended to be connected to the output of their respective UPS models. Do not use extension cords, adapter plugs, or surge strips. The installation of upstream and down­stream protective devices is highly recommended when the UPS system is connected to the mains and the load.
INPUT / OUTPUT CONNECTIONS: WARNING: Qualified Service Personnel ONLY must perform the Installa-
tion and Servicing of these ED-XFR.
1. Remove the terminal block cover box from the rear panel of the UPS (re­quires a phillips screwdriver). Refer to the figure below for the input / out­put connections for the UPS. See the UPS user's manual for connecting
the UPS's input and output cables.
12
2. Input / Output cable selection: T emperature Rating
60°C / 75°C
5/6KV A
#10 AWG (Cu)
8/10KVA
#6 AWG (Cu)
(In accordance with National Electrical Code (NEC), install suitable con­duit and bushing.) NOTE: Use copper wire only .
3. Before connecting to the input / output terminals read all of the Cautions and
Warning. The AC inputs of these S tep Down T ransformers are ONLY intend- ed to be connected to the output of their respective UPS models. NOTE: The ED-XFR's input voltage setting must be the same as the UPS's output voltage setting.
ED5000RT-XFR and ED6000RT-XFR:
See the UPS users manual for UPS input and output connections. Connect the attached #10 A WG input power cord on the ED-XFR to the output terminal block on the UPS.
1. Connect the black wire labeled L on the attached input power cord to the UPS
output terminal block labeled L and secure.
2. Connect the white wire labeled N on the attached input power cord to the UPS
output terminal block labeled N and secure.
3. Connect the green wire labeled G on the attached input power cord to the UPS
output terminal block ground terminal and secure.
4. Before re-installing the terminal block cover box on the UPS, see the UPS us-
ers manual for the UPS input and output connections.
5. Set the input voltage select switch on the rear panel of the ED-XFR to the appropr-
iate voltage (208V / 240V). NOTE: The default setting is 208V. The ED­XFR's input voltage setting must be the same as the UPS's output voltage set­ting.
6. Plug the equipment into the output receptacles on the rear panel of the ED-
XFR. NOTE: Default voltages for the output receptacles are 120V and 208V. Load 2 ouput receptacle can be changed to supply 240V , but this change must be done at the factory .
ED8000RT-XFR and ED10000RT-XFR:
1. Remove the terminal block cover plate from the rear panel of the ED-XFR
(requires a phillips screwdriver). Refer to the figure below for the input / output
connections for the ED8000RT-XFR / ED10000R T -XFR. Connect the end of
the #6 A WG input power cable labeled "TO XFR" to the appropriate terminals
on the AC input terminal block on the ED-XFR and secure. The pins for thein-
put cable are included.
a) Connect the black wire labeled L1 / L2 on the input power cable to the ED-
XFR AC input terminal block labeled L1 for 240V or L2 for 208V and se­cure. NOTE: The ED-XFR's input voltage setting must be the same as the UPS's output voltage setting.
b) Connect the white wire labeled L3 on the input power cable to the ED-
XFR AC input terminal block labeled L3 and secure.
13
Page 9
c) Connect the green wire labeled G on the input power cable to the ED-
XFR AC input terminal block ground terminal and secure.
2. Connect the other end of the #6 AWG input power cable labeled "TO UPS" to the output terminal block on the UPS and secure. a) Connect the black wire labeled L on the input power cable to the UPS out-
put terminal block labeled L and secure.
b) Connect the white wire labeled N on the input power cable to the UPS out-
put terminal block labeled N and secure.
c) Connect the green wire labeled G on the input power cable to the UPS out-
put terminal block ground terminal and secure.
3. Re-install the terminal block cover plate on the ED-XFR.
4. Before re-installing the terminal block cover box on the UPS, see the UPS us­ers manual for the UPS input and output connections.
5. Plug the equipment into the output receptacles on the rear panel of the ED­XFR. The ED8000RT -XFR and ED10000RT -XFR have a terminal block for ha­rdwiring the output. Refer to the figure below for the input / output connections. The pins for the output cable are included.
NOTE: The two 120V outputs are individual 5KV A outputs and they CANNOT be paralleled.
Input / Output terminal block for the ED8000RT -XFR and ED10000RT -XFR:
1. Turn on the input breaker on the rear panel of the UPS. The fans will turn on, the AC normal icon will flash off/on and the LCD will display ‘bPS’. The UPS is now in the Bypass mode. NOTE: If there is a power interruption while the UPS is in the Bypass mode the load will not be backed up.
2. Turn on all of the Load breakers on the rear panel of the ED-XFR.
3. Turn on the connected equipment one at a time.
4. Press and release the On/Off/Test Button after the first beep to turn the UPS on.
5. The UPS will start-up and perform a self-diagnosis for approximately 10­seconds. The UPS system is ready for normal opeartion. See the UPS user's manual for more information.
START-UP IN THE BATTERY MODE:
The Battery Pack(s) must be connected to the UPS and the DC breaker(s) on the rear panel of the Battery Pack(s) must be in the on position. The input of the ED-XFR must be connected to the output of the UPS. The equipment must be plugged into the output receptacles on the ED-XFR.
1. Turn on the input breaker on the rear panel of the UPS.
2. Press and release the On/Off/Test Button after the first beep to turn the
UPS on.
3. The fans will turn on, then the UPS will start-up and perform a self-diagno-
sis for approximately 10-seconds.
4. Turn on all of the Load breakers on the rear panel of the ED-XFR.
5. Turn on the connected equipment one at a time. See the UPS user's ma-
nual for more information.
120V outputs: La - N: 50A max, Lb - N: 50A max, the combined total for both: 83.4A max 208V output: Lc - Ld: 48.1A max 240V output: La - Lb: 41.7A max
NOTE: Default voltages for the output receptacles are 120V and 208V. 240V is available, but only as a hardwire option at the output terminal block.
Chapter 4: Operation
START-UP IN THE NORMAL AC MODE:
The UPS must be connected to utility power and there must be an acceptable AC voltage present. The Battery Pack(s) must be connected to the UPS and the DC breaker(s) on the rear panel of the Battery Pack(s) must be in the on position. The input of the ED-XFR must be connected to the output of the UPS. The equipment is plugged into the output receptacles on the ED-XFR.
14
TURNING OFF THE STEP DOWN TRANSFORMER IN THE NORMAL AC MODE:
1. Press and release the On/Off/T est Button on the front p anel of the UPS aft­er the second beep to transfer the UPS to the Bypass mode.
2. Turn off all of the connected equipment.
3. Turn off all of the Load breakers on the rear p anel of the ED-XFR.
4. Turn off the input breaker on the rear panel of the UPS.
5. Turn off the DC breaker(s) on the rear p anel of the Battery Pack(s).
TURNING OFF THE STEP DOWN TRANSFORMER IN THE BATTERY MODE:
1. Turn off all of the connected equipment.
2. Turn off all of the Load breakers on the rear p anel of the ED-XFR.
3. Press and release the On/Off/T est Button after the second beep to turn the UPS off.
4. Turn off the input breaker on the rear panel of the UPS.
5. Turn off the DC breaker(s) on the rear p anel of the Battery Pack(s).
15
Page 10
Chapter 5: Obtaining Service
Chapter 6: Specifications
IF THE STEP DOWN TRANSFORMER REQUIRES SERVICE
1. Use the Troubleshooting section in the UPS user's manual to eliminate ob­vious causes.
2. Verify there are no tripped circuit breakers. A tripped circuit breaker is the most common issue.
3. Call your dealer for assistance. If you cannot reach your dealer , or if they cannot resolve the issue call or fax the Technical Support department at the following numbers; Voice phone (972) 446-7363, FAX line (972) 446­901 1 or visit our Web site at www .minutemanups.com the "Discussion Board". Before calling the Technical Support Department have the follow­ing information available: a) Contact name and address. b) Where and when the unit was purchased. c) All of the model information about your unit. d) The serial number of your unit. e) Any information on the failure, including LEDs that may be illuminat-
ed or error codes displayed.
f) A description of the protected equipment including model numbers, if
possible.
g) A technician will ask you for the above information and if possible,
help solve the issue over the phone. In the event that the unit requires factory service, the technician will issue you a Return Material Autho­rization Number (RMA #).
h) If the unit is under warranty, the repairs will be done at no charge. If
the unit is not under warranty there will be a charge for the repair.
4. Pack the unit in its original packaging. If the original packaging is no lon­ger available, ask the T echnical Support T echnician about obtaining a new set. It is important to pack the unit properly in order to avoid damage in transit. Never use Styrofoam beads for a p acking material. a) Include a letter with your name, address, day time phone number,
RMA number, a copy of your original sales receipt, and a brief desc­ription of the problem.
5. Mark the RMA # on the outside of all packages. The factory cannot accept any package without the RMA # marked on the outside.
6. Return the unit by insured, prepaid carrier to:
Para Systems Inc. MINUTEMAN UPS
1809 W. Frankford Road, Suite 150
Carrollton, TX 75007
A TTN: RMA # _______
16
SYSTEM SPECIFICA TIONS
Model Number
Topology
ED5000RT-XFR ED6000RT-XFR
Isolation, Step Down Tansformer, Sine Wave
ED8000RT-XFR ED10000RT-XFR
INPUT
Number of Phase
Voltage (Selectable) 208 (default) / 240VAC
Frequency Current (Max)
Protection Connection
208VAC - 24Amps 240VAC - 21Amps
Attached 2' open-end #10 AWG power cord
Single (1 2W +G)
50 / 60Hz
208VAC - 49Amps 240VAC - 42.5Amp s
Resettable Circuit Breaker
T erminal Block Hardwire only
OUTPUT
Voltage (Selectable)
Voltage Regulation Frequency 50 / 60Hz Power (Max)
Harmonic Distortion Efficiency
Waveform T ype
Protection Resettable Circuit Breaker
208 & 120V AC (Default) / 240VAC (Optional)
Nominal +/-3%
5KVA / 5K Watts
<3% (Full Linear Load)
>95% (Full Load)
True Sine Wave
10KVA / 10K Watts
ENVIRONMENT AL
Operating T emperature (max) Storage T emperature Operating/Storage Humidity
Operating Elevation Storage Elevation Audible Noise at 1 m (3 ft.)
<50 dBA
0 to 40°C (+32 to +104°F)
-15 to +50°C (+5 to +122°F) 0 ~ 95% Non-Condensing
0 to 2,000m (0 to +6,562 ft)
0 to 15,000m (0 to +49,213 ft)
PHYSICAL
Size - Net L X W X H
Weight - Net Size - Shipping
L X W X H Weight - Shipping
26.2 x 17.3 x 3.5" 665 x 440 x 88.5 mm
82.7 lbs / 35.5 Kgs
31.6 x 24.4 x 9.1" 802 x 620 x 230 mm
123.5 lbs / 56.0 Kgs
25.9 x 17.3 x 5.14" 659 x 440 x 130.6 mm
158.7 lbs / 72.0 Kgs
30.7 x 23.6 x 10.9" 780 x 600 x 276 mm
196.2 lbs / 89.0 Kgs
REGULA TORY COMPLIANCE
Safety and Approvals
(Conforms to UL60950-1:2007 R12.11, CSA-C22.2 No.60950-1-07-A1:2011)
EMC Verification
NOTE: Specifications are subject to change without notice.
FCC Class B, CE certified
cTUVus
<60 dBA
17
Page 11
Chapter 7: Limited Product Warranty
Para Systems, Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a pe­riod of three years from the date of purchase. For equipment sites within the United States and Canada, this warranty covers depot rep air or replacement of defective equip­ment at the discretion of Para Systems. Depot repair will be from the nearest authorized service center. The customer pays for shipping the product to Para Systems. Para Systems pays ground freight to ship the product back to the customer. Replacement parts and warranty labor will be borne by Para Systems. For equipment located outside of the United States and Canada, Para Systems only covers faulty p arts. Para Systems products that are depot repaired or replaced pursuant to this warranty shall only be warranted for the unexpired portion of the warranty applying to the original product. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.
The warranty shall be void if (a) the equipment is damaged by the customer, is improp­erly used, is subjected to an adverse operating environment, or is operated outside the limits of its electrical specifications; (b) the equipment is repaired or modified by anyone other than Para Systems or Para Systems approved personnel; or (c) has been used in a manner contrary to the product’s User's Manual or other written instructions.
Any technical advice furnished before or after delivery in regard to use or application of Para Systems’ equipment is furnished without charge and on the basis that it represents Para Systems’ best judgment under the circumstances, but it is used at the recipient’s sole risk.
A1. DECLARATION OF CONFORMITY
Application of Council Directive(s): 2004/108/EC
St andard(s) to which Conformity is declared: EN 50091-2:1995 Class A, IEC61000-4-2: level4, IEC61000-4-3: level3,
IEC61000-4-4: level4, IEC61000-4-5: level4, IEC61000-4-6: level3, IEC61000­4-8: level3, IEC 62040-2: 2005, IEEE C62.41 Category A1
Manufacturer’s Name: Para Systems, Inc. (MINUTEMAN UPS) Manufacturer’s Address: 1455 LeMay Drive
Carrollton, Texas 75007 USA
Type of Equipment: Uninterruptible Power Supplies (UPS) Model No: ED5000RT-XFR, ED6000RT-XFR,
ED8000RT-XFR, ED10000RT-XFR
Year of Manufacture: Beginning April 1, 2014
EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO W ARRANTIES, EX­PRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANT ABILITY AND FIT­NESS FOR A P ARTICULAR PURPOSE. Some states do not permit limitation of implied warranties; therefore, the aforesaid limitation(s) may not apply to the purchaser .
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE LIABLE FOR DIRECT , INDIRECT , SPECIAL, INCIDENT AL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSI­BILITY OF SUCH DAMAGE. Specifically , Para Systems is not liable for any costs, such as; labor for on-site installation, on-site maintenance or on-site service, lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, cost of substitutes, claims by third parties, or otherwise. The sole and exclusive remedy for breach of any warranty , expressed or implied, concerning Para Systems’ products and the only obligation of Para Systems hereunder, shall be depot rep air or replacement of defective equipment, components, or parts; or, at Para Systems’ option, refund of the purchase price or substitution with an equivalent replacement product. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
No employee, salesman, or agent of Para Systems is authorized to add to or vary the terms of this warranty .
18
I hereby declare that the equipment specified above conforms to the above Directive(s).
Robert Calhoun (Name)
Place: Carrollton, Texas, USA
Manager Engineering (Position)
Date: April 1, 2014
19
Page 12
Notes:
Notes:
20
21
Loading...