7.Limited Product Warranty18
A1 .Declaration of Conformity19
1
Page 3
Chapter 1: Introduction
Thank you for purchasing this power protection product. It has been designed
and manufactured to provide many years of trouble free service. Please read
this manual before installing your Endeavor Series step down transformer
(ED-XFR), models ED5000RT-XFR, ED6000RT-XFR, ED8000RT-XFR and
ED10000RT-XFR as it provides important information that should be followed
during installation and maintenance of the ED-XFR allowing you to correctly
set up your system for the maximum safety and performance. Included is
information on customer support and factory service if it is required. If you
experience a problem with the ED-XFR please refer to Obtaining Service section in this manual to collect enough information so that the T echnical Support
Department can rapidly assist you.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
CAUTION! This ED-XFR series is ONLY intended to be installed in an indoor
temperature controlled environment that is free of conductive contaminants.
This ED-XFR series is not intended for use in a computer room as defined in
the Standard for the Protection of Electronic Computer/Dat a Processing Equipment ANSI/NFPA 75. The AC inputs of these Step Down Transformers are
ONLY intended to be connected to the output of their respective UPS models.
The ED-XFR's input voltage setting must be the same as the UPS's output voltage
setting.
CAUTION! The maximum ambient operating temperature for this ED-XFR
series is 40°C (“0 ~ 40°C” for Ambient Operation).
The external vents and openings on the unit are provided for ventilation.
T o ensure reliable operation of the unit and to protect the unit from overheating, these vents and openings must not be blocked or covered. Do not
insert any object into any of the vents or openings that may hinder the ventilation.
Install the unit in a well ventilated area, away from excess moisture, heat,
dust, flammable gas or explosives.
Leave adequate space (at least 15cm) around all sides of the unit for pr-
oper ventilation.
Do not mount the unit with its front or rear panel facing down at any angle.
Before usage, you must allow the unit to adjust to room temperature
(20°C~25°C or 68°F~77°F) for at least one hour to avoid moisture cond ensing inside the unit.
CAUTION! The ED5000RT-XFR and ED6000R T-XFR come with an attached
#10 AWG input power cord. Connect the input power cord to the output
terminal block on the UPS. The AC input s of these Step Down Transformers
are ONLY intended to be connected to the output of their respective UPS
models. Do not use extension cords, adapter plugs, or surge strips. The
installation of upstream and downstream protective devices is highly recommended when the UPS system is connected to the mains and the load.
CAUTION! The ED8000RT -XFR and ED10000RT-XFR come with an #6 A WG
input power cable in the box. The pins for the input and output cables are
included. Connect one end of the input power cable to the input terminal block
on the ED-XFR. Connect the other end of the input power cable to the output
terminal block on the UPS. The AC inputs of these Step Down T ransformers
are ONLY intended to be connected to the output of their respective UPS
models. Do not use extension cords, adapter plugs, or surge strips. The
installation of upstream and downstream protective devices is highly recommended when the UPS system is connected to the mains and the load.
CAUTION! To reduce the risk of electrical shock with the installation of this
unit and the connected equipment, the user must ensure that the ED-XFR is
properly grounded due to a possible risk of AC current leakage.
WARNING: Qualified Service Personnel ONLY must perform the Installation and Servicing of these ED-XFR. MINUTEMAN accepts no liabilities and is
not limited to: injury to the Service Personnel, or damages to; the Step Down
Transformer , the UPS, the Battery Pack, or the connected equipment caused
by the incorrect installation or servicing of the UPS system. These ED-XFR
MUST be operated with their respective UPS models, see the table below:
ED-XFR
UPS
WARNING: When using these S tep Down T ransformers with their respective
UPS models, the load capacity of the UPS MUST be derated as follows:
ED5000RT -CU
ED5000RT -XFR
4556V A
4100Watts
ED5000RT -XFR
ED6000RT -XFR
ED5000RT -CU
ED6000RT -CU
ED6000RT -CU
ED6000RT -XFR
5556VA
5000Watts
ED8000RT -XFR
ED10000RT -XFR
ED8000RT -CU
ED10000RT -CU
ED8000RT -CU
ED8000RT -XFR
6889V A
6200Watts
ED10000RT-CU
ED10000RT -XFR
8889V A
8000Watts
WARNING: This ED-XFR contains potentially hazardous voltages. Do not
attempt to disassemble the unit. This unit contains no user serviceable parts.
Repairs must be performed by QUALIFIED SERVICE PERSONNEL ONLY.
2
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE STEP
DOWN TRANSFORMER. The mounting brackets are ONLY for securing the
unit to the rack.
3
Page 4
CAUTION! T o de-energize the output s of the ED-XFR:
1. Turn off the Load breakers on the rear p anel of the ED-XFR.
2. If the UPS is on press and release the On/Off/Test button after the second beep.
2. Turn off the input circuit breaker on the rear p anel of the UPS.
3. Turn off the DC breaker on the rear p anel of the Battery Pack.
4. Disconnect the UPS from the AC source.
NOTICE: This equipment has been tested and found to comply with the limits
for a Class B computing device in accordance with the specifications in Subpart J of Part 15 of FCC Rules and the Class B limits for radio noise emissions
from digital apparatus set out in the Radio Interference of the Canadian Department of Communications. These limits are designed to provide reasonable
protection against such interference in a residential installation. This equipment generates and uses radio frequency and if not installed and used properly ,
that is, in strict accordance with the manufacturer's instructions, this equipment may cause interference to radio and television reception. If this equipment does cause interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
Re-orient the receiving antenna.
Relocate the computer with respect to the receiver.
Move the computer away from the receiver.
Plug the computer into a different outlet so that the computer and receiver
are on different branch circuits.
Shielded communications interface cables must be used with this product.
WARNING: Changes or modifications to this unit not expressly approved by
the party responsible for compliance could void the user's authority to operate
the equipment.
RECIEVING INSPECTION
Once you receive the product it should be visually inspected for damage that
may have occurred in shipping. Immediately notify the carrier and place of
purchase if any damage is found. Warranty claims for damage caused by the
carrier will not be honored by the manufacturer. The packing materials that
the product was shipped in were carefully designed to minimize any shipping
damage. In the unlikely case that the product needs to be returned to the
manufacturer, use the original packing material. Since the manufacturer is
not responsible for shipping damage incurred when the product is returned,
the original packing material is inexpensive insurance. PLEASE SAVE THE
PACKING MATERIALS!
LIFE SUPPORT POLICY
As a general policy , Para Systems does not recommend the use of any of our
products in life support applications where failure or malfunction of the product
can be reasonably expected to cause failure of the life support device or to
significantly affect its safety or effectiveness. We do not recommend the use of
any of our products in direct patient care. We will not knowingly sell our products for use in such applications unless it receives in writing assurances satisfactory to us that (a) the risks of injury or damage have been minimized, (b) the
customer assumes all such risks, and (c) our liability is adequately protected
under the circumstances.
Examples of devices considered to be life support devices are neonatal oxygen
analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other
purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia
detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis
systems, neonatal ventilator incubators, ventilators for both adults and infants,
anesthesia ventilators, and infusion pumps as well as any other devices designated as “critical” by the United States FDA.
All Rights Reserved. All right s of this User Manual (“Manual”), including but not
limited to the content, information, and figures are solely owned and reserved
by Para Systems, Inc. (“Para Systems”). The Manual can only be applied to
the operation or the use of this product. Any disposition, duplication, dissemination, reproduction, modification, translation, extraction, or usage of this
Manual in whole or in part is prohibited without the prior written permission of
Para Systems. Given that Para Systems will continuously improve and develop
the product, changes may be made to the information in this Manual at any
time without obligation to notify any person of such revision or changes. Para
Systems will make all possible efforts to secure the accuracy and the integrity
of this Manual. Para Systems disclaims any kinds or forms of warranty , guarantee, or undertaking, either expressly or implicitly , including but not limited to
the completeness, faultlessness, accuracy , non-infringement, merchantability
or fitness for a particular purpose of the Manual.
4
5
Page 5
Chapter 2: Rear Panels
1. The Load 4 circuit breaker will trip in the event the load exceeds the power
rating.
5. The Load 2 circuit breaker will trip in the event the load exceeds the power
rating.
6. Load 3: 208V output receptacle (1 - L6-20R).
7. The Load 1 circuit breaker will trip in the event the load exceeds the power
rating.
8. Load 1: 208V output receptacle (1 - L6-30R).
9. The input circuit breaker will trip in the event the load exceeds the EDXFR's power rating.
10. ED-XFR's circuit breaker will trip in the event that the ED-XFR becomes
overheated.
1 1. Input terminal block (208V / 240V) is for connecting the input power cable
that comes from the output terminal block of the UPS.
12. Output terminal block for optional hardwiring the load. The available output
voltages are 120V / 208V / 240V. NOTE: The two 120V outputs are individual 5KV A output s and they CANNOT be paralleled.
6
7
Page 6
Chapter 3: Installation
INSTALLATION PLACEMENT
RACKMOUNT CONFIGURA TION
Use the included rackmount brackets and screws to mount the ED-XFR in a
rack by following the steps below.
USE CAUTION: The ED-XFR is extremely heavy . Use the appropriate number
of personnel when installing the UPS system.
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE
STEP DOWN TRANSFORMER. The mounting brackets are ONLY for se-
curing the unit to the rack.
This ED-XFR series is ONLY intended to be installed in an indoor temperature
controlled environment that is free of conductive contaminants. DO NOT operate the unit in: extremely dusty and/or unclean areas, locations near heating
devices, water or excessive humidity, or where the unit is exposed to direct
sunlight. Select a location, which will provide good air circulation for the unit at
all times. Route power cords so they cannot be walked on or damaged. The
AC inputs of these Step Down Transformers are ONLY intended to be con-
nected to the output of their respective UPS models. This ED-XFR series is
not intended for use in a computer room as defined in the Standard for the
Protection of Electronic Computer/Data Processing Equipment ANSI/NFPA
75.
Operating Temperature (Maximum): 0 to 40°C (+32 to +104°F)
Operating Elevation: 0 to 2,000m (0 to +6,562 ft)
Operating and Storage Relative Humidity: 95%, non-condensing
Storage Temperature: -15 to +50°C (+5 to +122°F)
Storage Elevation: 0 to 15,000m (0 to +49,213 f t)
INST ALLATION
Be sure to read the installation placement and all the cautions before installing
the ED-XFR. Place the unit in the final desired location and complete the rest
of the installation procedure. See the “Rackmount Configuration” to install the
unit into the rack. USE CAUTION: The ED-XFR, UPS and Battery Pack are
extremely heavy . Use the appropriate number of personnel when installing the
UPS system.
1. Attach the rackmount brackets to the mounting holes on the side panel of
the ED-XFR as shown below.
2. Follow steps 1 through 4 to install the ED-XFR into the Rail kit. See the
figure below.
Step 1: Adjust the length of the rail according to the rack.
Step 2: Securely tighten the wing nuts.
Step 3: Secure the rail to the rack with the enclosed screws.
Step 4: Slide the ED-XFR onto the rail and secure to the rack with the
enclosed screws.
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE STEP
DOWN TRANSFORMER. The mounting brackets are ONLY for securing the
unit to the rack.
NOTE: The ED-XFR, UPS and Battery Pack are extremely heavy. Use the
following placement when rack mounting:
1. The ED-XFR should be installed close to the bottom of the rack.
2. Then install the Battery Pack right above the ED-XFR.
3. Then install the UPS right above the Battery Pack.
8
9
Page 7
TOWER CONFIGURA TION
The tower configuration allows the user to install the ED-XFR in the up-right
position. The tower stands are provided with the UPS. The tower stand extenders are provided with the ED-XFR. WARNING: Use two or more people
when installing the ED-XFR. USE CAUTION: The ED-XFR is extremely
heavy. Use the appropriate number of personnel when installing the UPS
system.
1. Once the location of the ED-XFR has been determined, place the tower
stands in the desired location.
WARNING: The ED-XFR must be installed in the proper up-right position.
Once the ED-XFR is placed in the tower stands, the vent holes on the side
panels must be facing upwards to provide proper ventilation.
2. Slide the ED-XFR into the tower stands. Make sure that the ED-XFR is
stable.
3. The name plate panel can be rotated to read in the up-right position. Remove the front panel from the ED-XFR. On the backside of the front panel,
push the name plate panel outwards, the panel will pop out. Rotate the
name plate panel counter clockwise so that it reads in the upright position.
Re-install the front panel on the ED-XFR.
CONNECTING THE STEP DOWN TRANSFORMER TO THE UPS
WARNING: Qualified Service Personnel ONLY must perform the Installa-
tion and Servicing of these ED-XFR.
1. Before connecting to the input / output terminals read all of the Cautions
and Warning, then observe the following:
a)Ensure that the UPS is turned off and not connected to the AC sour-
ce or the battery source before any connections are made.
b)Calculate the power consumption of the load to ensure that an over-
load condition does not occur.
c)Ensure that the terminal block screws are secured after connecting
the input / output wires. The terminal block screws should be torque
to 18±2Kgf.cm (requires a 3/16" flat-head screwdriver).
d)Ensure that the ED-XFR and the UPS are properly grounded.
2. The input power for the ED-XFR must be single-phase in accordance with
its rating label and the specifications in this manual. The ED-XFR's input
voltage setting must be the same as the UPS's output voltage setting.
NOTE: The AC input s of these Step Down Transformers are ONLY intended to be connected to the output of their respective UPS models.
The ED5000RT-XFR and ED6000RT-XFR come with an attached #10 AWG
input power cord. Connect the input power cord to the output terminal block
on the UPS. The AC inputs of these Step Down Transformers are ONLY
intended to be connected to the output of their respective UPS models. Do not
use extension cords, adapter plugs, or surge strips. The installation of upstream and downstream protective devices is highly recommended when the
UPS system is connected to the mains and the load.
10
11
Page 8
The ED8000RT -XFR and ED10000RT -XFR come with an #6 A WG input power
cable in the box. The pins for the input cable are included. Connect one end
of the input power cable to the input terminal block on the ED-XFR. Connect
the other end of the input power cable to the output terminal block on the UPS.
The AC inputs of these Step Down Transformers are ONLY intended to be
connected to the output of their respective UPS models. Do not use extension
cords, adapter plugs, or surge strips. The installation of upstream and downstream protective devices is highly recommended when the UPS system is
connected to the mains and the load.
INPUT / OUTPUT CONNECTIONS:
WARNING: Qualified Service Personnel ONLY must perform the Installa-
tion and Servicing of these ED-XFR.
1. Remove the terminal block cover box from the rear panel of the UPS (requires a phillips screwdriver). Refer to the figure below for the input / output connections for the UPS. See the UPS user's manual for connecting
the UPS's input and output cables.
12
2. Input / Output cable selection:
T emperature Rating
60°C / 75°C
5/6KV A
#10 AWG (Cu)
8/10KVA
#6 AWG (Cu)
(In accordance with National Electrical Code (NEC), install suitable conduit and bushing.) NOTE: Use copper wire only .
3. Before connecting to the input / output terminals read all of the Cautions and
Warning. The AC inputs of these S tep Down T ransformers are ONLY intend-
ed to be connected to the output of their respective UPS models. NOTE:
The ED-XFR's input voltage setting must be the same as the UPS's output
voltage setting.
ED5000RT-XFR and ED6000RT-XFR:
See the UPS users manual for UPS input and output connections. Connect the
attached #10 A WG input power cord on the ED-XFR to the output terminal block on
the UPS.
1. Connect the black wire labeled L on the attached input power cord to the UPS
output terminal block labeled L and secure.
2. Connect the white wire labeled N on the attached input power cord to the UPS
output terminal block labeled N and secure.
3. Connect the green wire labeled G on the attached input power cord to the UPS
output terminal block ground terminal and secure.
4. Before re-installing the terminal block cover box on the UPS, see the UPS us-
ers manual for the UPS input and output connections.
5. Set the input voltage select switch on the rear panel of the ED-XFR to the appropr-
iate voltage (208V / 240V). NOTE: The default setting is 208V. The EDXFR's input voltage setting must be the same as the UPS's output voltage setting.
6. Plug the equipment into the output receptacles on the rear panel of the ED-
XFR.
NOTE: Default voltages for the output receptacles are 120V and 208V. Load 2
ouput receptacle can be changed to supply 240V , but this change must be done at
the factory .
ED8000RT-XFR and ED10000RT-XFR:
1. Remove the terminal block cover plate from the rear panel of the ED-XFR
(requires a phillips screwdriver). Refer to the figure below for the input / output
connections for the ED8000RT-XFR / ED10000R T -XFR. Connect the end of
the #6 A WG input power cable labeled "TO XFR" to the appropriate terminals
on the AC input terminal block on the ED-XFR and secure. The pins for thein-
put cable are included.
a)Connect the black wire labeled L1 / L2 on the input power cable to the ED-
XFR AC input terminal block labeled L1 for 240V or L2 for 208V and secure. NOTE: The ED-XFR's input voltage setting must be the same as
the UPS's output voltage setting.
b)Connect the white wire labeled L3 on the input power cable to the ED-
XFR AC input terminal block labeled L3 and secure.
13
Page 9
c)Connect the green wire labeled G on the input power cable to the ED-
XFR AC input terminal block ground terminal and secure.
2. Connect the other end of the #6 AWG input power cable labeled "TO UPS" to
the output terminal block on the UPS and secure.
a)Connect the black wire labeled L on the input power cable to the UPS out-
put terminal block labeled L and secure.
b)Connect the white wire labeled N on the input power cable to the UPS out-
put terminal block labeled N and secure.
c)Connect the green wire labeled G on the input power cable to the UPS out-
put terminal block ground terminal and secure.
3. Re-install the terminal block cover plate on the ED-XFR.
4. Before re-installing the terminal block cover box on the UPS, see the UPS users manual for the UPS input and output connections.
5. Plug the equipment into the output receptacles on the rear panel of the EDXFR. The ED8000RT -XFR and ED10000RT -XFR have a terminal block for hardwiring the output. Refer to the figure below for the input / output connections.
The pins for the output cable are included.
NOTE: The two 120V outputs are individual 5KV A outputs and they CANNOT be
paralleled.
Input / Output terminal block for the ED8000RT -XFR and ED10000RT -XFR:
1. Turn on the input breaker on the rear panel of the UPS. The fans will turn
on, the AC normal icon will flash off/on and the LCD will display ‘bPS’. The
UPS is now in the Bypass mode. NOTE: If there is a power interruption
while the UPS is in the Bypass mode the load will not be backed up.
2. Turn on all of the Load breakers on the rear panel of the ED-XFR.
3. Turn on the connected equipment one at a time.
4. Press and release the On/Off/Test Button after the first beep to turn the
UPS on.
5. The UPS will start-up and perform a self-diagnosis for approximately 10seconds. The UPS system is ready for normal opeartion. See the UPS
user's manual for more information.
START-UP IN THE BATTERY MODE:
The Battery Pack(s) must be connected to the UPS and the DC breaker(s) on
the rear panel of the Battery Pack(s) must be in the on position. The input of
the ED-XFR must be connected to the output of the UPS. The equipment must
be plugged into the output receptacles on the ED-XFR.
1. Turn on the input breaker on the rear panel of the UPS.
2. Press and release the On/Off/Test Button after the first beep to turn the
UPS on.
3. The fans will turn on, then the UPS will start-up and perform a self-diagno-
sis for approximately 10-seconds.
4. Turn on all of the Load breakers on the rear panel of the ED-XFR.
5. Turn on the connected equipment one at a time. See the UPS user's ma-
nual for more information.
120V outputs:
La - N: 50A max, Lb - N: 50A max, the combined total for both: 83.4A max
208V output: Lc - Ld: 48.1A max
240V output: La - Lb: 41.7A max
NOTE: Default voltages for the output receptacles are 120V and 208V. 240V is
available, but only as a hardwire option at the output terminal block.
Chapter 4: Operation
START-UP IN THE NORMAL AC MODE:
The UPS must be connected to utility power and there must be an acceptable AC
voltage present. The Battery Pack(s) must be connected to the UPS and the DC
breaker(s) on the rear panel of the Battery Pack(s) must be in the on position. The
input of the ED-XFR must be connected to the output of the UPS. The equipment is
plugged into the output receptacles on the ED-XFR.
14
TURNING OFF THE STEP DOWN TRANSFORMER IN THE NORMAL AC
MODE:
1. Press and release the On/Off/T est Button on the front p anel of the UPS after the second beep to transfer the UPS to the Bypass mode.
2. Turn off all of the connected equipment.
3. Turn off all of the Load breakers on the rear p anel of the ED-XFR.
4. Turn off the input breaker on the rear panel of the UPS.
5. Turn off the DC breaker(s) on the rear p anel of the Battery Pack(s).
TURNING OFF THE STEP DOWN TRANSFORMER IN THE BATTERY
MODE:
1. Turn off all of the connected equipment.
2. Turn off all of the Load breakers on the rear p anel of the ED-XFR.
3. Press and release the On/Off/T est Button after the second beep to turn the
UPS off.
4. Turn off the input breaker on the rear panel of the UPS.
5. Turn off the DC breaker(s) on the rear p anel of the Battery Pack(s).
15
Page 10
Chapter 5: Obtaining Service
Chapter 6: Specifications
IF THE STEP DOWN TRANSFORMER REQUIRES SERVICE
1. Use the Troubleshooting section in the UPS user's manual to eliminate obvious causes.
2. Verify there are no tripped circuit breakers. A tripped circuit breaker is
the most common issue.
3. Call your dealer for assistance. If you cannot reach your dealer , or if they
cannot resolve the issue call or fax the Technical Support department at
the following numbers; Voice phone (972) 446-7363, FAX line (972) 446901 1 or visit our Web site at www .minutemanups.com the "Discussion
Board". Before calling the Technical Support Department have the following information available:
a)Contact name and address.
b)Where and when the unit was purchased.
c)All of the model information about your unit.
d)The serial number of your unit.
e)Any information on the failure, including LEDs that may be illuminat-
ed or error codes displayed.
f)A description of the protected equipment including model numbers, if
possible.
g)A technician will ask you for the above information and if possible,
help solve the issue over the phone. In the event that the unit requires
factory service, the technician will issue you a Return Material Authorization Number (RMA #).
h)If the unit is under warranty, the repairs will be done at no charge. If
the unit is not under warranty there will be a charge for the repair.
4. Pack the unit in its original packaging. If the original packaging is no longer available, ask the T echnical Support T echnician about obtaining a new
set. It is important to pack the unit properly in order to avoid damage in
transit. Never use Styrofoam beads for a p acking material.
a)Include a letter with your name, address, day time phone number,
RMA number, a copy of your original sales receipt, and a brief description of the problem.
5. Mark the RMA # on the outside of all packages. The factory cannot accept
any package without the RMA # marked on the outside.
6. Return the unit by insured, prepaid carrier to:
Para Systems Inc.
MINUTEMAN UPS
1809 W. Frankford Road, Suite 150
Carrollton, TX 75007
A TTN: RMA # _______
16
SYSTEM SPECIFICA TIONS
Model Number
Topology
ED5000RT-XFR
ED6000RT-XFR
Isolation, Step Down Tansformer, Sine Wave
ED8000RT-XFR
ED10000RT-XFR
INPUT
Number of Phase
Voltage (Selectable)208 (default) / 240VAC
Frequency
Current (Max)
Protection
Connection
208VAC - 24Amps
240VAC - 21Amps
Attached 2' open-end
#10 AWG power cord
Single (1∅2W +G)
50 / 60Hz
208VAC - 49Amps
240VAC - 42.5Amp s
Resettable Circuit Breaker
T erminal Block
Hardwire only
OUTPUT
Voltage (Selectable)
Voltage Regulation
Frequency50 / 60Hz
Power (Max)
Harmonic Distortion
Efficiency
Waveform T ype
ProtectionResettable Circuit Breaker
208 & 120V AC (Default) / 240VAC (Optional)
Nominal +/-3%
5KVA / 5K Watts
<3% (Full Linear Load)
>95% (Full Load)
True Sine Wave
10KVA / 10K Watts
ENVIRONMENT AL
Operating T emperature (max)
Storage T emperature
Operating/Storage Humidity
Operating Elevation
Storage Elevation
Audible Noise at 1 m (3 ft.)
<50 dBA
0 to 40°C (+32 to +104°F)
-15 to +50°C (+5 to +122°F)
0 ~ 95% Non-Condensing
0 to 2,000m (0 to +6,562 ft)
0 to 15,000m (0 to +49,213 ft)
PHYSICAL
Size - Net
L X W X H
Weight - Net
Size - Shipping
L X W X H
Weight - Shipping
26.2 x 17.3 x 3.5"
665 x 440 x 88.5 mm
82.7 lbs / 35.5 Kgs
31.6 x 24.4 x 9.1"
802 x 620 x 230 mm
123.5 lbs / 56.0 Kgs
25.9 x 17.3 x 5.14"
659 x 440 x 130.6 mm
158.7 lbs / 72.0 Kgs
30.7 x 23.6 x 10.9"
780 x 600 x 276 mm
196.2 lbs / 89.0 Kgs
REGULA TORY COMPLIANCE
Safety and Approvals
(Conforms to UL60950-1:2007 R12.11, CSA-C22.2 No.60950-1-07-A1:2011)
EMC Verification
NOTE: Specifications are subject to change without notice.
FCC Class B, CE certified
cTUVus
<60 dBA
17
Page 11
Chapter 7: Limited Product Warranty
Para Systems, Inc. (Para Systems) warrants this equipment, when properly applied and
operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equipment sites within the United
States and Canada, this warranty covers depot rep air or replacement of defective equipment at the discretion of Para Systems. Depot repair will be from the nearest authorized
service center. The customer pays for shipping the product to Para Systems. Para
Systems pays ground freight to ship the product back to the customer. Replacement
parts and warranty labor will be borne by Para Systems. For equipment located outside
of the United States and Canada, Para Systems only covers faulty p arts. Para Systems
products that are depot repaired or replaced pursuant to this warranty shall only be
warranted for the unexpired portion of the warranty applying to the original product. This
warranty applies only to the original purchaser who must have properly registered the
product within 10 days of purchase.
The warranty shall be void if (a) the equipment is damaged by the customer, is improperly used, is subjected to an adverse operating environment, or is operated outside the
limits of its electrical specifications; (b) the equipment is repaired or modified by anyone
other than Para Systems or Para Systems approved personnel; or (c) has been used in
a manner contrary to the product’s User's Manual or other written instructions.
Any technical advice furnished before or after delivery in regard to use or application of
Para Systems’ equipment is furnished without charge and on the basis that it represents
Para Systems’ best judgment under the circumstances, but it is used at the recipient’s
sole risk.
A1.DECLARATION OF CONFORMITY
Application of Council Directive(s): 2004/108/EC
St andard(s) to which Conformity is declared:
EN 50091-2:1995 Class A, IEC61000-4-2: level4, IEC61000-4-3: level3,
Manufacturer’s Name: Para Systems, Inc. (MINUTEMAN UPS)
Manufacturer’s Address: 1455 LeMay Drive
Carrollton, Texas 75007 USA
Type of Equipment: Uninterruptible Power Supplies (UPS)
Model No: ED5000RT-XFR, ED6000RT-XFR,
ED8000RT-XFR, ED10000RT-XFR
Year of Manufacture: Beginning April 1, 2014
EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO W ARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANT ABILITY AND FITNESS FOR A P ARTICULAR PURPOSE. Some states do not permit limitation of implied
warranties; therefore, the aforesaid limitation(s) may not apply to the purchaser .
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE LIABLE
FOR DIRECT , INDIRECT , SPECIAL, INCIDENT AL, OR CONSEQUENTIAL DAMAGES
ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically , Para Systems is not liable for any costs, such
as; labor for on-site installation, on-site maintenance or on-site service, lost profits or
revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, cost
of substitutes, claims by third parties, or otherwise. The sole and exclusive remedy for
breach of any warranty , expressed or implied, concerning Para Systems’ products and
the only obligation of Para Systems hereunder, shall be depot rep air or replacement of
defective equipment, components, or parts; or, at Para Systems’ option, refund of the
purchase price or substitution with an equivalent replacement product. This warranty
gives you specific legal rights and you may also have other rights which vary from state
to state.
No employee, salesman, or agent of Para Systems is authorized to add to or vary the
terms of this warranty .
18
I hereby declare that the equipment specified above conforms to the above
Directive(s).
Robert Calhoun
(Name)
Place: Carrollton, Texas, USA
Manager Engineering
(Position)
Date: April 1, 2014
19
Page 12
Notes:
Notes:
20
21
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.