rackmount UPS system to achieve higher than 6kVA loads.
Currently, parallel capacity congurations can be used
to accommodate output loads of 12, 18, and 24kVA for
208V/240V systems.
Parallel for Capacity Conguration Table
ModelED12000RMED18000RMED24000RM
Input12kVA
208V/240V
18kVA
208V/240V
24kVA
208V/240V
MAin control ModUle - ed6200rM
The Main Control module takes only 2U in rack height
and provides 208/240V input and output. Input is hardwired
to the unit. The main control module has a LCD/LED display.
Each control module must have at least one battery back
(EDBP6000RM). Parallel functions are available for up to 208V
24kVA. N+1 full-redundancy function is available up to 18kVA for
208/240V applications and 6kVA for 120V applications. Optional
receptacle boxes are available for 6kVA units.
trAnSForMer ModUle - ed6000rMXFMr
The transformer module steps down the 208/240V input to
120/208/240V output, takes 2U in rack height, and requires a
control module (ED6200RM), and Battery Pack (EDBP6000RM) to
work. It has an internal bypass switch for single 6kVA installations
(Not available on parallel installations). It handles 208/240V input
and 120/208/240V output.
BAttery PAck ModUle - edBP6000rM
Each battery pack module (EDBP6000RM) occupies 3U
in rack height and requires a control module (ED6200RM) to
operate. Multiple battery packs can be daisy chained. Only one
receptacle box can be attached to a battery pack module.
Battery packs are charged through the main UPS.
PArAllel conFigUrAtionS
In addition to a stand-alone conguration, the Endeavor
6kVA rackmount UPS can be congured as:
Parallel for capacity (12, 18 and 24kVA output load)
•
Redundancy (N+1) (6, 12, and 18kVA). This allows all
•
of the load to be shifted to the other UPS units when
one is taken ofine. Congurations using more than two
control modules will require a parallel kit and an external
maintenance bypass switch.
NOTE: 120V output from the Endeavor 6kVA rackmount UPS is
available only in a 6kVA stand-alone conguration or a Parallel
for Redundancy (N+1) 6kVA 208V/240V input and 6kVA 120V
output made up of two ED6200RM control units, two EDBP6000RM
battery packs and two ED6000RMXFMR transformers.
Output Load12kVA
Watts84001260016800
Rack height10 U15 U20 U
ED6200RM234
EDBP6000RM
Battery Pack
ED6-PARALLEL
Parallel kit
External
Maintenance
Bypass Switch
edUndAncy (n+1) conFigUrAtionS
r
208V/240V
234
111
1
ED6-MTBS21 ED6-MTBS41 ED6-MTBS4
18kVA
208V/240V
24kVA
208V/240V
This conguration is used to provide redundancy
backup. When one UPS is taken ofine, this conguration
allows the load to be redistributed to the remaining UPS
units.
Redundancy (N+1) Conguration Table
ModelTBAED12000RM ED18000RMED24000RM
Input6kVA
Output Load6kVA
Watts42004200840012600
Rack height 14 U10 U15 U20 U
ED6200RM2234
EDBP6000RM
Battery Pack
ED6000RMXFMR2n/an/an/a
ED6-PARALLEL
Parallel kit
External
Maintenance
Bypass Switch
208V/240V
120V
2234
1111
N/A1
6kVA
208V/240V
6kVA
208V/240V
ED6-MTBS21 ED6-MTBS4
12kVA
208V/240V
12kVA
208V/240V
18kVA
208V/240V
18kVA
208V/240
1
ED6-MTBS4
oPtionAl recePtAcle BoXeS
Special
Log In/
Log Out
UPS
Off
Switch
Next
Page
UPS On Switch
&
Alarm Silence
Enter or
Reconfirm
Previous Page
or Setting
Change
Utility
Input
Normal
LEDs
Bypass
Input
Normal
UPS in
Redundancy
Mode
UPS in
ECO
Mode
UPS Fault
or
Abnormal
Warning
V
Two receptacle boxes are available. One for
208V/240V output only (ED6-208RB) and one for both
120V and 208V/240V output (ED6-120RB).
208V-Only Receptacle Box- ED6-208RB
Receptacles: (1) L6-30R, (1) L6-20R and (4) 6-15/20R. Only
one receptacle box can be connected to a battery
pack.
120V/208V Receptacle Box - ED6-120RB
Receptacles: (1) L6-30R, (1) L5-30R, (1) L5-20R and (2)
5-15/20R. Only one receptacle box can be connected to
a battery pack.
endeAVor 6kVA UPS led/lcd
Front PAnel diSPlAy/control
The Endeavor 6kVA UPS multi-functional LCD/LED panel will
display various states of the UPS. The LED display will show the
UPS working status, Utility Status and UPS Abnormal status. The
LCD display will show the Input/Output voltage, frequency, load
status, internal temperature, and faults.
Conguring the UPS parameters are done through the LCD.
coMMUnicAtionAnd SoFtwAre
The Endeavor 6kVA UPS currently uses the NetAgent
SNMP card and includes software for monitoring the UPS.
A new version of the ED6200RM with SentryPlus/SNMP-NET
communications capability will be available in 2008.
Both versions are compatible with Minuteman’s
new SentryGold Enterprise Software which permits the
monitoring and control of Minuteman UPS and Power
Distribution Units.
BAtterieS
The Endeavor 6kVA UPS uses a battery pack
(EDBP6000RM) that contains sealed, non-spillable,
maintenance free, value regulated, lead acid batteries.
The UPS module does not have internal batteries. Typical
recharge time for the battery pack is 8 hours from total
discharge.
The battery pack contains (20) 12V 7.2Ah batteries.
Runtime at full load is 9 minutes. At half load the
runtime is 23 minutes
w
hAttheFUtUreholdS . . .
Parallel Congurations:All current
6kVA products are compliant with parallel
congurations when these options are
available. In the relatively near future you will
be able to congure your Minuteman Endeavor
6kVA into a parallel conguration increasing
system capacity up to 24kVA.
Input and output will be hardwired
•
A parallel kit will be required. It will contain all
•
the required RJ-45 cabling and an instruction
manual
It is required that a maintenance bypass switch
•
be installed
MAintenAnce ByPASS Switch
Maintenance Bypass Switch with covers off
The maintenance bypass switch removes the requirement to
power down the UPS to perform routine maintenance, replace
batteries or to change battery conguration, The maintenance
bypass switch is usually mounted adjacent to the UPS, enabling
the UPS to be isolated from the load without interrupting power
to essential applications.
oPtionS
Maintenance bypass switch
•
Galvanic isolated transformer for 120V applications.
•
Parallel kit
•
®
Endeavor
6kVA Series On-line Rackmount UPS
ModelED6200RM
Topology
Maximum power capacity
DDouble Conversion On-Line, True Sine Wave
6000VA/4200Watts
INPUT
Voltage window160~280VAC*
Frequency50/60 Hz ± 5Hz autosensing
Number of phases • Surge energy ratingSingle (1Ø 2W +G) • 1050J
Power factor correction≥98% at 100% Linear Load
OUTPUT
Voltage window200/208/240VAC selectable 120V with transformer
Voltage adjustment / Voltage regulation0%; ±1%; ±2%; ±3% /±2%
Capacity 6000VA/4200W
Rated power factor 0.7 Lagging
Wave form Sine Wave
Frequency Regulation±0.2%(Free Running) unless synchronized to utility
Transfer time 0ms
Efciency> 87% line mode
Autonomy full/half9 min/23 min
Voltage THD<3% at 100% Linear Load
BATTERY
Type Sealed non-spillable lead acid maintenance free 12V/7.2Ah
Quantity / Voltage / Recharge Time20pcs / 240VDC / 8 hours to 90%
DISPLAY
Status On LED + LCD
Readings on LCD
Self-diagnostics Upon power-on, front panel setting & software control
Line mode, backup mode, ECO mode, bypass, battery low, battery bad/disconnect,
overload, and transferring with interruption & UPS fault.
Input voltage, input frequency, output voltage, output frequency, load percentage,
battery voltage & internal temperature.
ALARMS
Audible and Visual Line failure, battery low, transfer to bypass, system fault conditions
PHYSICAL
Dimensions- WxDxH- in (mm)17.3x3.4x26.7in (440x88x680mm) - (UPS Module)