Minuteman E750RM2U, E1500RMT2U, E2000RM2U, E3000RM2U, E3000RMT2U User Manual

...
Page 1
User's Manual
Enterprise Plus
Series UPS
Page 2
1
© Copyright 2006
1. Introduction 2
3. Installation 9
4. Operation 15
5. Troubleshooting 18
6. Replacing the Battery 19
7. Obtaining Service 22
8. Specifications 23
9. Configurable Parameters & Settings 25
10. Limited Product Warranty 26 A1 . Declaration of Conformity 28
English
Page 3
2
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
English
Thank you for purchasing this power protection product. It has been designed and manufactured to provide many years of trouble free service.
Please read this manual before installing your Enterprise Plus Series UPS, models E750RM2U, E1000RM2U, E1500RM2U, E1500RMT2U, E2000RM2U, E3000RM2U, E3000RMT2U as it provides important information that should be followed during installation and maintenance of the UPS and batteries allowing you to correctly set up your system for the maximum safety and performance. Included is information on customer support and factory service if it is required. If you experience a problem with the UPS please refer to the Troubleshooting guide in this manual to correct the problem or collect enough information so that the Technical Support Dep artment can rapidly assist you.
This symbol indicates "A TTENTION"
This symbol indicates "Risk of Electrical Shock"
This symbol indicates "Alternating Current Supply"
This symbol indicates "Alternating Current Supply Phase"
Page 4
3
WARNING: Risk of Electrical Shock. Hazardous live parts inside
these power supplies are energized from the battery even when the AC input is disconnected.
CAUTION! T o de-energize the output s of the UPS:
1. If the UPS is on press and release the On/Off/Test button. NOTE: For the 208V models; turn the input circuit breaker to the off posi­tion.
2. Disconnect the UPS from the AC wall outlet.
3. To de-energize the UPS completely , disconnect the battery .
CAUTION! To reduce the risk of electrical shock in conditions
where the load equipment grounding cannot be verified, disconnect the UPS from the AC wall outlet before inst alling a computer interface cable. Reconnect the power cord only after all signaling connections are made.
CAUTION! Connect the UPS to a two pole, three wire grounding
AC wall outlet. The receptacle must be connected to the appropriate branch protection (circuit breaker or fuse). Connection to any other type of receptacle may result in a shock hazard and violate local electrical codes. Do not use extension cords, adapter plugs, or surge strips.
English
CAUTION! T o reduce the risk of electrical shock with the installa-
tion of this UPS equipment and the connected equipment, the user must ensure that the combined sum of the AC leakage current does not exceed 3.5mA.
This symbol indicates "Direct Current Supply"
This symbol indicates "Equipment Grounding Conductor"
W ARNING: This Uninterruptible Power Supply contains potentially
hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure. This UPS contains no user ser­viceable parts. Repairs and Battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONL Y.
Page 5
4
English
After removing your UPS from its carton, it should be inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored. The packing materials that your UPS was shipped in are carefully designed to minimize any shipping damage. In the unlikely case that the UPS needs to be returned to the manufacturer, please use the original packing material. Since the manufacturer is not responsible for ship­ping damage incurred when the system is returned, the original packing mate­rial is inexpensive insurance. PLEASE SA VE THE P ACKING MA TERIALS!
Receiving Inspection
NOTICE: This equipment has been tested and found to comply with the limits
for a Class B computing device in accordance with the specifications in Sub­part J of Part 15 of FCC Rules and the Class B limits for radio noise emissions from digital apparatus set out in the Radio Interference of the Canadian Depart­ment of Communications. These limits are designed to provide reasonable protection against such interference in a residential installation. This equip­ment generates and uses radio frequency and if not installed and used properly , that is, in strict accordance with the manufacturer's instructions, this equip­ment may cause interference to radio and television reception. If this equip­ment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Re-orient the receiving antenna. Relocate the computer with respect to the receiver. Move the computer away from the receiver . Plug the computer into a different outlet so that the computer and receiver
are on different branch circuits.
Shielded communications interface cables must be used with this product.
WARNING: Changes or modifications to this unit not expressly ap-
proved by the party responsible for compliance could void the user's authority to operate the equipment.
NOTE: These UPSs are shipped with the batteries disconnected. The batter­ies must be connected before putting these UPSs into service. Refer to Sec­tion 3 "Installation" for connecting the batteries.
Page 6
5
English
Life Support Policy
As a general policy , we do not recommend the use of any of our products in life support applications where failure or malfunction of the product can be reason­ably expected to cause failure of the life support device or to significantly affect its safety or effectiveness. We do not recommend the use of any of our prod­ucts in direct patient care. We will not knowingly sell our products for use in such applications unless it receives in writing assurances satisfactory to us that (a) the risks of injury or damage have been minimized, (b) the customer assumes all such risks, and (c) our liability is adequately protected under the circumstances.
Examples of devices considered to be life support devices are neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators for both adults and infants, anesthesia ventilators, and infusion pumps as well as any other devices desig­nated as “critical” by the United States FDA.
Hospital grade wiring devices and leakage current may be ordered as options on many of our UPS systems. We do not claim that units with this modification are certified or listed as Hospital Grade by us or any other organization. There­fore, these units do not meet the requirements for use in direct patient care.
Page 7
6
English
The AC normal (green) LED illuminates in a steady st ate when the UPS is on and operating in the AC normal mode. The AC normal LED will extinguish when operating in the Battery mode.
The On-Battery (green) LED illuminates in a steady state when the UPS is operating in the Battery mode. The On-Battery LED will extinguish when operating in the AC normal, Boost and Buck modes.
The Boost (yellow) LED illuminates in a blinking state when the UPS is operating in the Boost mode. The Boost LED will extinguish when operating in the AC normal, Buck and Battery modes.
The Buck (yellow) LED illuminates in a blinking state when the UPS is operating in the Buck mode. The Buck LED will extinguish when operating in the AC normal, Boost and Battery modes.
The Fault (red) LED illuminates in a steady state when the UPS detects an internal fault. The Fault LED is extinguished when the UPS is operating properly .
The Weak/Bad Battery (red) LED illuminates in a steady state when the UPS detects a weak battery, bad battery or if the battery is disconnected. The Weak/Bad Battery LED is extinguished when the battery's condition is good.
The Site Wiring Fault (red) LED (120V models) illuminates in a steady state when the UPS detects a site wiring problem. The SWF LED is extinguished when the UPS is connected to proper site wiring.
CONTROL PANEL
Page 8
7
English
The Load Level Bar Graph (AC mode only) operates as follows: LED #10: >10% load (green/red/yellow) LED will be green and illu­minated when there is at least 10% of the rated capacity . LED #30: >30% load (green/yellow) LED will be green and illumi­nated when there is at least 30% of the rated capacity . LED #50: >50% load (green/yellow) LED will be green and illumi­nated when there is at least 50% of the rated capacity . LED #70: >70% load (green/yellow) LED will be green and illumi­nated when there is at least 70% of the rated capacity . LED #90: >90% to approximately 109% load (red/yellow) LED will be yellow and illuminated when there is approximately 90% of the rated capacity to indicate that unit is near full capacity. The LED will turn red at 110% load capacity to indicate an Overload condi­tion.
The Battery Capacity Bar Graph (Battery mode only) operates as follows: LED #90: >90% battery capacity (red/yellow) LED will be yellow and illuminated until the battery’s capacity drops below 80% ca­pacity and then it will extinguish. LED #70: >70% battery capacity (green/yellow) LED will be yellow and illuminated until the battery’s capacity drops below 60% ca­pacity and then it will extinguish. LED #50: >50% battery capacity (green/yellow) LED will be yellow and illuminated until the battery’s capacity drops below 40% ca­pacity and then it will extinguish. LED #30: >30% battery capacity (green/yellow) LED will be yellow and illuminated until the battery’s capacity drops below 30% ca­pacity and then it will extinguish. LED #10: >30% battery capacity (green/red/yellow) LED will be yel­low and illuminated until the unit issues a Low Battery Warning Alarm and then it will turn red to indicate a Low Battery Warning.
The Multi-Function On/Off/Test Button functions as follows: When the UPS is Off, press and release the On/Off/Test button after one beep to turn the UPS On. NOTE: The input circuit breaker MUST be in the on position for the 208V models. When the UPS is On, press and release the On/Off/Test Button after one beep to turn the UPS Off. NOTE: Turn the input circuit breaker to the off position for the 208V models. When the UPS is On, press and hold the On/Off/Test button for four beeps, then release the button. The UPS will perform a 5-second Self T est.
Page 9
8
English
REAR PANEL
1. The RS232 Communications Interface Port is for UPS monitoring and control.
2. The USB Communications Interface Port is for UPS monitoring and control.
3. The RJ1 1 REPO (Remote Emergency Power Off) Port is for UPS control.
4. The option slot is for option cards.
5. The External Battery Connector is for connecting External Battery Packs.
6. The output circuit breaker will trip in the event the load exceeds the UPS’s power rating.
7. The Battery Backup output power receptacles. The output receptacles are electrically wired into two segments to support the "Load Shedding Function". The locking receptacle does not support the Load Shedding Function. NOTE: The locking recptacle is not on all models.
8. The input circuit breaker will trip in the event the load exceeds the UPS’s power rating.
9. The input power cord (120V models). The AC Power Inlet IEC320 (208V models).
10. The dipswitch is for setting the Inverter (On-Battery) output voltage. 1 1. The External Ground Stud is for connecting an external ground wire.
12. The R-J1 1/R-J45 modular connectors are used for 10/100 Base-T Network/single line Phone/Fax/Modem protection.
Output Power Receptacles
E750RM2U
NEMA 5-15P
Model #
E1500RM2U E2000RM2U
E1000RM2U
E3000RM2U
E1500RMT2U E3000RMT2U
NEMA 5-15P NEMA 5-15P
NEMA 5-20P
NEMA L5-30P
NEMA L6-30P
NEMA 6-15P
6-NEMA 5-15R 6-NEMA 5-15R 6-NEMA 5-15R
6-NEMA 6-15R
6-NEMA 5-15/20R 1-NEMA L5-20R
6-NEMA 5-15/20R 1-NEMA L5-30R
6-NEMA 6-15/20R 1-NEMA L6-30R
Input Power Plug
(All power cords are 10ft)
Page 10
9
English
INSTALLATION PLACEMENT
This UPS series is intended to be install in a temperature controlled environ­ment that is free of conductive contaminants. Select a location which will provide good air circulation for the UPS at all times. A void locations near heat­ing devices, water or excessive humidity , or where the UPS is exposed to direct sunlight. Route power cords so they cannot be walked on or damaged. Operating T emperature (Maximum): 0 to 40 degrees C (+32 to +104 degrees F) Operating Elevation: 0 to 3,000m (0 to +10,000 ft) Operating and Storage Relative Humidity: 95%, non-condensing Storage T emperature: -15 to +45 degrees C (+5 to +113 degrees F) Storage Elevation: 0 to 15,000m (0 to +50,000 ft)
INSTALLATION
Be sure to read the installation placement and all the cautions before installing the UPS. Place the UPS in the final desired location and complete the rest of the installation procedure. These UPSs are shipped with the internal batteries disconnected. The batteries must be connected before putting these UPSs into service. See the connecting the batteries procedure to connect the batter­ies and see the Rackmount Configuration to install the UPS into the rack. USE CAUTION: The UPS is heavy . Use the appropriate number of personnel when installing the UPS.
Page 11
10
English
CONNECTING THE BA TTERIES
(QUALIFIED SERVICE PERSONNEL ONLY) Please read all of the WARNINGS and CAUTIONS before attempting to con-
nect the batteries.
1. Remove the UPS from the shipping box and set on the floor or a bench top.
2. Remove the front panel retaining screws.
3. Lay the front panel on top of the UPS.
4. Verify proper polarity . Connect the battery connectors (red and black) toge­ ther. NOTE: Some sparking might occur , this is normal.
5. Re-install the front panel onto the UPS.
6. Re-install the front panel retaining screws.
7. Continue with the rest of the Installation.
Page 12
11
English
RACKMOUNT CONFIGURA TION
This UPS comes with mounting brackets for the standard 19" (46.5cm) rack. The mounting brackets to fit a 23" (59.2cm) standard rack are also available. The screws for mounting the UPS to the rack are not included (screw size varies with rack size).
1. Locate the mounting bracket screw holes on the side panels of the UPS, at the front of the UPS. NOTE: The mounting brackets can also be mounted in the middle of the UPS.
2. Align the mounting bracket with the mounting bracket screw holes.
3. Attach the mounting bracket with the ret aining screws.
4. Mount the UPS into the rack and secure with the retaining screws. W ARN- ING: Use two or more people when installing the UPS. Use CAUTION, the UPS is extremely heavy . Do not move the rack after the units have been in­ stalled. The rack maybe unstable due to the weight distribution.
5. The Rackmount Configuration is complete. See Connecting your Equipm­ ent.
Page 13
12
English
TOWER CONFIGURATION
The tower configuration allows the user to install the UPS in the up-right position next to the tower computer. The tower brackets are provided with the UPS. WARN- ING: Use two or more people when installing the UPS. Use CAUTION, the UPS is extremely heavy .
1. Once the location of the UPS has been determined, place the tower brackets in the desired location. WARNING: The UPS must be installed in the proper up-right position. If the UPS is not installed in the proper up-right position the Batteries will be damaged. Once the UPS is placed in the tower brackets, looking at the front panel the YELLOW Battery disconnected label on the top cover of the UPS MUST be on your left hand side.
2. Slide the UPS into the tower brackets. Make sure that the UPS is stable.
3. The LED face plate can be rotated to read in the up-right position. Remove the front panel from the UPS. On the backside of the front panel, push the LED face plate outwards the face plate will pop out. Position the LED face plate so that it reads in the up-right position. Re-install the front panel on the UPS.
4. The Tower Configuration is complete. See Connecting your Equipment.
DESKTOP CONFIGURA TION
The desktop configuration allows the user to install the monitor, the computer and the UPS in one single stack. WARNING: Use two or more people when installing the UPS. Use CAUTION, the UPS is extremely heavy .
1. Once the location of the UPS has been determined, lay the UPS down flat on the desk.
2. St ack the computer and then the monitor on top of the UPS. NOTE: Do not stack the UPS on top of the computer. The UPS is heavy and may damage the other equipment.
3. The Desktop Configuration is complete. See Connecting your Equipment.
Page 14
13
English
WALLMOUNT CONFIGURA TION
The wallmount configuration allows the user to mount the UPS on the wall. There is a wallmount bracket kit available for the UPS. The kit includes two wall mounting brackets, ten retaining screws, and the wallmount template. WARNING: Use two or more people when installing the UPS. Use CAUTION, the UPS is extremely heavy. The UPS's side panels have mounting bracket screw holes for attaching the wall mounting brackets.
1. Once the location and position of the UPS has been determined, lay the UPS do­ wn flat. WARNING: The UPS must be installed in the proper up-right position. If the UPS is not installed in the proper up-right position the Batteries will be damaged. Once the UPS is placed on the wall, looking at the front panel the YELLOW Battery discon­nected label on the top cover of the UPS MUST be on your left hand side.
2. Align the mounting brackets with the mounting bracket screw holes and attach w­ ith the six retaining screws.
3. Use the template to mark the screw hole position on the wall. CAUTION, you sh­ ould always were protective gear for your hands and eyes when operating power tools.
4. Attach the four retaining screws to the wall and make sure that all of the retaining screws are screwed into structural material. Then clean the area of any loose m­ aterial. Do not tighten the retaining screws all the way , leave approximately 3/8" of the retaining screws sticking out.
5. Position the UPS, so that the mounting bracket keyed holes line up with the four retaining screws. Slide the UPS down until its resting securely on the four retai­ ning screws.
6. Tighten the four retaining screws to secure the UPS to the wall.
7. The LED face plate can be rotated to read in the up-right position. Remove the front panel from the UPS. On the backside of the front panel, push the LED face plate outwards the face plate will pop out. Position the LED face plate so that it reads in the up-right position. Re-install the front panel on the UPS.
8. The Wallmount Configuration is complete. See Connecting your Equipment.
Page 15
14
English
CHARGING THE BATTERY
The UPS will charge the internal batteries whenever the UPS is connected to an AC source and there is an acceptable AC voltage present. NOTE: The input circuit breaker MUST be in the on position for the 208V models. It is recom­mended that the UPS's batteries be charged for a minimum of 4 hours before use. The UPS may be used immediately, however, the “On-Battery” runtime may be less than normally expected. NOTE: If the UPS is going to be out of service or stored for a prolonged period of time, the batteries must be recharged for at least twenty-four hours every ninety days.
CHECKING THE SITE WIRING FAULT (120V Models)
After plugging in the UPS, check the Site Wiring Fault (SWF) LED on the front panel of the UPS. If the SWF LED is illuminated, the UPS is plugged into an improperly wired AC outlet. If the UPS indicates a Site Wiring Fault (SWF), have a Qualified Electrician correct the problem.
COMMUNICATIONS PORT CONNECTION (OPTIONAL) The Power Monitoring Software and interface cables can be used with the UPS. Use only the interface cables that come with these UPSs. Connect the inter­face cable (Serial or USB) to the appropriate communications port on the rear panel of the UPS. Connect the other end of the cable to the device that will be monitoring/controlling the UPS. NOTE: Connecting to the Communications Port is optional. The UPS works properly without this connection.
CONNECTING THE UPS TO AN AC SOURCE
Plug the UPS into a two pole, three wire, grounded receptacle only. Do not use extension cords, adapter plugs, or surge strips.
NETWORK/PHONE/FAX/MODEM PROTECTION CONNECTION (OPTIONAL) Connect a 10/100 Base-T network, single line phone, Fax or Modem line to the RJ11/45 modular connectors on the rear panel of the UPS. This connection will require another length of telephone or network cable. The cable coming from the telephone service or networked system is connected to the port marked “IN”. The equipment to be protected is connected to the port marked "OUT". NOTE: Connecting to the Network/Phone/Fax/Modem modular connectors is optional. The UPS works properly without this connection.
CONNECTING YOUR EQUIPMENT
Plug the equipment into the output receptacles on the rear panel of the UPS. Do not use extension cords, adapter plugs or surge strips on the output of the UPS. Ensure that you do not exceed the maximum output rating of the UPS (refer to the information label or the Electrical Specifications in this manual).
CAUTION!
DO NOT connect a laser printer to the output receptacles on the
UPS, unless the UPS is rated 2000VA or greater. A laser printer draws significantly more power when printing than at idle and may overload the UPS.
RJ11 REPO (Remote Emergency Power Off) PORT (OPTIONAL) Connect one end of the RJ11 cable to the REPO port and the other end of the RJ11 cable to the EPO switch. In the AC or the Battery mode short pin4 to pin5 for approximately 0.5-seconds to shutdown the UPS. The UPS must be turned off and then back on again to restart the UPS. NOTE: Connecting to the REPO port is optional. The UPS works properly without this connection.
Page 16
15
English
SYSTEM OVERVIEW
This Line-Interactive UPS protects computers, internetworking, and telecom­munications equipment from blackouts, brownouts, overvoltages, and surges. The A VR function continuously corrects the voltages, in-between the brownout and overvoltage transfer points (80 - 164V AC/150 - 271V AC), to a safe usable level. When the UPS is operating in the AVR mode the audible alarm will remain silent and the Boost or the Buck indicator will blink. During normal A C operation, the UPS will quietly and confidently protect your system from power anomalies.
The UPS will charge the batteries with the UPS in the on or off position as long as the UPS is plugged into the wall outlet and there is an acceptable AC volt age present (80 - 164V AC/150 - 271V AC). NOTE: The input circuit breaker MUST be in the on position for the 208V models. When a blackout, brownout, or an overvoltage condition occurs; the UPS will transfer to the battery mode, the On­Battery indicator will illuminate and the audible alarm will sound once every ten­seconds indicating that the commercial power is lost or unacceptable. When the commercial power returns or is at an acceptable level, the UPS will auto­matically transfer back to the AC normal mode and st art recharging the batter­ies. During an extended outage when there is approximately two-minutes of backup time remaining the audible alarm will sound twice every five-seconds. This Low Battery Warning is letting the user know that they should save all open files and turn off their computer . When the batteries reach the predeter­mined level the UPS will automatically shutdown protecting the batteries from over discharging. Once the commercial power returns the UPS will automati­cally restart, providing safe usable power to the connected equipment and start recharging the batteries.
TURNING THE UNIT ON/OFF
On / Off / T est Button
Press and release the On/Off/Test Button after one beep to turn the UPS on and supply power to the load. NOTE: The input circuit breaker MUST be in the on position for the 208V models to turn the UPS on. The load is immediately powered while the UPS runs a five-second self test. Press and release the On/ Off/T est Button af ter one beep to turn the UPS off. NOTE: T urn the input circuit breaker to the off position for the 208V models. The UPS will continue to charge the batteries whenever it is plugged into a wall outlet and there is ac­ceptable AC voltage present.
Page 17
16
English
COMMUNICATIONS PORTS (RS232 and USB)
The RS232 communication port is a standard DB9 female with both RS232 and simulated contact closure capability. The UPS will poll the port and activate the port for RS232 or contact closure in accordance with the type of cable it finds connected to the port. To change the port configuration requires the unit be turned off and restarted with the desired cable connected. The pinout for the port is depicted per the chart below: Pin 1: Simulated contact closure Low Battery Warning, NO Pin 2: /TXD Pin 3: /RXD and receive UPS shutdown command (connect to pin 9 for 4­seconds. The shutdown command is only active in the battery mode) Pin 4: Not Used Pin 5: Ground Pin 6: Not Used Pin 7: Not Used Pin 8: Simulated contact closure AC fail, NO Pin 9: Atx Signal (high level: +12V +/-2V, low level: -15V +/- -2V)
DIPSWITCH SETTINGS
The dipswitch setting may be changed by the user to set the desired Inverter (On-Battery) output voltage. The dipswitch must be set to the desired Inverter (On-Battery) output voltage and then the UPS must be turned off and restarted to reconfigure the microprocessor and save the changes. The Inverter (On­Battery) output voltage setting can be either 120V AC (208V AC) default or 127VAC (240V AC). Changing the Inverter (On-Battery) output voltage to 127V AC, will also change the Buck setpoint. Changing the Inverter (On-Battery) output volt­age to 240V AC, will also change the Brownout, Boost, Buck and Overvoltage setpoints.
SELF TEST
The self test feature is useful to verify the correct operation of the UPS and the condition of the batteries. With the UPS in the AC normal mode, press and hold the On/Off/Test Button for four beeps, then release the button. The UPS will perform a ten-second self test. During the self test, the UPS will switch to battery power and the On-Battery LED will illuminate and the audible alarm will sound. The length of the test that is automatically performed every two weeks is longer than the start-up or user invoked test. This test will run for approxi­mately fifteen-seconds to measure the battery’s capability to provide an ac­ceptable amount of runtime. If the UPS fails a self test, one of the LEDs will remain illuminated indicating the type of problem. NOTE: The UPS will auto­matically perform a self test on start-up and every two weeks.
LOAD SHEDDING FUNCTION
The output receptacles are electrically wired into two segments to support the "Load Shedding Function". The user can control the two segments individually or both at the same time. The Load Shedding Function is controllable by the Power Monitoring Software or the SNMP card.
Page 18
17
English
WEAK/BAD BATTERY
The UPS automatically tests the battery’s condition and will illuminate the Weak/ Bad Battery LED and sound the alarm. This alarm will be repeated until the batteries pass a self test. If the battery is weak, bad or disconnected, the Weak/Bad Battery LED will illuminate and the alarm will beep three times every five-minutes until the battery is reconnected or replaced. It is recommended that the UPS be allowed to charge overnight before performing a battery test to confirm a Weak/Bad Battery condition. NOTE: If the UPS has a Weak/Bad Battery Alarm after reconnecting or replac­ing the batteries, the user must initiate a self test to clear the Weak/Bad Bat­tery Alarm. To initiate a self test see section 4 "SELF TEST ".
OVERLOAD
When the amount of load attached to the UPS exceeds its power rating, the Overload LED will illuminate (AC mode only) and the UPS will sound a constant alarm (AC and Battery modes). This alarm will remain on until the excess load is removed or the UPS’s self protection circuit shuts the UPS down. If the UPS shuts down because of an Overload condition in the battery mode, the UPS must perform an Inverter function or a Self Test to clear the Overload Alarm.
POWER MONITORING SOFTWARE
The UPS comes with a Power Monitoring Software CD. See the software CD for the installation of the Power Monitoring Software.
USB PORT
The USB protocol is HID. The HID USB driver is standard in the Windows OS. Simply plug the USB cable into the UPS and the computer then follow the prompts on the screen.
OPTION SLOT
The option slot on the rear panel of the UPS is for option cards. Contact your local dealer for the available option cards.
ALARMS
ON BATTERY
When the UPS is operating on the batteries, the On-Battery LED will illuminate and the audible alarm will sound once every ten-seconds. The alarm will stop once the UPS returns to the AC normal mode.
LOW BATTERY WARNING
The UPS will sound two beeps every five-seconds when the battery reserve runs low. This condition will continue until AC returns or the UPS shuts down from battery exhaustion.
UPS FAULT
When the UPS detects a hardware fault, the Fault LED will illuminate and the UPS will sound a constant alarm. The fault condition, in some instances, may be reset by turning the UPS off and then on.
RJ11 REPO (Remote Emergency Power Off) PORT
Connect one end of the RJ11 cable to the REPO port and the other end of the RJ11 cable to the EPO switch. In the AC or the Battery mode short pin4 to pin5 for approximately 0.5-seconds to shutdown the UPS. The UPS must be turned off and then back on again to restart the UPS.
Page 19
18
English
Possible Cause
Symptom
What To Do
Press and release the On/Off/ Test button to start UPS
On/Off/Test button not pushed
UPS will not turn on
Reset circuit breaker by pressing the plunger back in. If the AC circuit breaker trips after UPS starts up, reduce the load on the UPS
UPS operates in battery mode only, even though there is normal AC present
Input AC circuit breaker is tripped
UPS has detected an internal fault
Call for service
Fault LED is illuminated
The AC normal LED is illuminated, but there is no out­put
Incorrect service wiring
Disconnect the computer cable from the UPS and press the On button. If UPS works normally, the software has control of the UPS
The UPS is being controlled via its communications port
Site Wiring Fault LED is illuminated
Have a Qualified Electrician correct the service wiring
The batteries may be weak or at the end of useful service life
Charge the batteries for 8­hours and retest. If the runtime is still less than expected, the batteries may need to be replaced, even though the Weak/Bad Battery LED is not illuminated
UPS does not provide expected runtime
Weak/Bad Battery LED is illuminated
Overload LED is illuminated and a constant alarm The Boost LED or Buck LED is blink­ing.
UPS occasionally emits a beep
Loose connections at the batteries, Weak batteries, Bad batteries
Normal operation
The load has exceeded the UPS's capacity
The UPS is in either the Boost mode or the Buck mode
Check battery connections, charge the batteries for 8­hours, replace the batteries
The UPS is performing its intended function
Check the specifications (see section 8). Remove part of the load The UPS is performing its intended function
Page 20
19
English
REPLACING THE BATTERY
W ARNING!
This Uninterruptible Power Supply contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and Battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONL Y .
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.
CAUTION:
(QUALIFIED SERVICE PERSONNEL ONL Y)
CAUTION:
Do not dispose of batteries in a fire. The batteries may explode. The batteries in this UPS are recyclable. Dispose of the batter­ies properly . The batteries contain lead and pose a hazard to the environment and human health if not disposed of properly . Refer to local codes for proper disposal requirements or return the battery to the supplier .
Although battery system voltages are only 36VDC and 72VDC the battery system can still present a risk of electrical shock. These batteries produce sufficient current to burn wire or tools very rapidly , producing molten metal. Observe these precautions when replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disco­ nnecting the battery terminals.
6. Determine if the battery is inadvertently grounded. If the bat­ tery is, remove the source of the grounding. Contact with any part of a grounded battery can result in an electrical shock. The likelihood of such shock will be reduced, if such grounds are removed during installation and maintenance.
CAUTION:
This UPS has an easy to replace hot-swappable batteries. Please read all of the WARNINGS and CAUTIONS before attempting to service the batteries. NOTE: If there is a power interruption while replacing the hot-swappable batter­ies, with the UPS on, the load will not be backed up.
Page 21
20
English
BATTERY REPLACEMENT PROCEDURE
PLEASE READ THE CAUTIONS AND W ARNINGS BEFORE A TTEMPTING TO REPLACE THE BA TTERIES
Hot-swappable batteries mean that the batteries can be replaced without powering down the whole UPS system. NOTE: If there is a power interruption while replacing the hot-swappable batter­ies, with the UPS on, the load will not be backed up. To hot-swap the batteries start with step number 6.
1. Turn off the equipment that is plugged into the output receptacles of the UPS.
2. Press and release the On/Off/Test button on the front panel to turn the UPS OFF. NOTE: Turn the input circuit breaker to the off position for the 208V models.
3. Unplug the UPS's AC power cord from the AC wall outlet.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the rear panel of the UPS.
6. Remove the front panel retaining screws. (FIG. 2)
7. Lay the front panel on top of the UPS.
E750RM2U E1000RM2U
E2000RM2U
Battery Qty/Rating
3-12V7.2Ah 6-12V7.2Ah
E3000RM2U E3000RMT2U
6-12V8.5Ah
Model #
Replace batteries with the same number and type as originally installed in the UPS. These batteries have pressure operated vents. These UPSs contain sealed non-spillable maintenance-free lead acid batteries.
CAUTION:
Panasonic Part #
Yuasa Part #
NP-7.2-12
CSB Part #
NP-7.2-12
REW45-12
LC-R127.2
LC-R127.2
LC-R129
GP 1272 F2
GP 1272 F2
HR 1234W F2
FIG. 1
FIG. 2
E1500RM2U E1500RMT2U
3-12V8.5Ah
REW45-12
LC-R129
HR 1234W F2
Page 22
21
English
8. Remove the two retaining screws for the battery retaining bracket. (FIG. 3)
9. Remove the battery retaining bracket. (FIG. 3)
10. Disconnect the Battery connectors (red and black). (FIG. 4) 1 1. Grasp the battery pull tab and gently pull the battery module out of the UPS and set on the floor . (FIG. 4) NOTE: Use Caution, the battery module is heavy .
12. Disconnect the battery positive (red) wire.
13. Disconnect the battery negative (black) wire.
14. Remove the battery jumper wires.
15. Remove the old batteries from the battery module.
16. Install the new batteries into the battery module in the same position as the original batteries.
17. Verify proper polarity. Re-install the battery jumper wires on the new batt­ eries.
18. Verify proper polarity. Reconnect the battery negative (black) wire.
19. Verify proper polarity. Reconnect the battery positive (red) wire.
20. Slide the battery module into the UPS.
21. Verify proper polarity. Reconnect the battery connectors (red and black). NOTE: Some sparking might occur , this is normal.
22. Re-install the battery retaining bracket.
23. Re-install the two retaining screws for the battery retaining bracket.
24. Re-install the front panel on the UPS.
25. Re-install the front panel retaining screws.
26. Properly dispose of the old batteries at an appropriate recycling facility or return them to the supplier in the packing material for the new batteries.
27. The UPS is now ready for the normal operation. NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the batteries, the user must initiate a self test to clear the Weak/Bad Battery Alarm. To initiate a self test see section 4 "SELF TEST".
FIG. 3
FIG. 4
Page 23
22
English
IF THE UPS REQUIRES SERVICE
1. Use the TROUBLESHOOTING section to eliminate obvious causes.
2. V erify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem.
3. Call your dealer for assistance. If you cannot reach your dealer , or if they cannot resolve the problem call or fax the Technical Support department at the following numbers; V oice phone (972) 446-7363, FAX line (972) 446-901 1 or visit our Web site at www .minutemanup s.com the "Discussion Board". Please have the following information available BEFORE calling the Techni­ cal Support Department. A. Your name and address. B. Where and when the unit was purchased. C. All of the model information about your UPS. D. Any information on the failure, including LEDs that may be illuminated. E. A description of the protected equipment, including model numbers if pos-
sible. F. A technician will ask you for the above information and, if possible, help solve your problem over the phone. In the event that the unit requires
factory service, the technician will issue you a Return Material Authoriza-
tion Number (RMA #). G. If the UPS is under warranty, the repairs will be done at no charge. If not,
there will be a charge for repair .
4. Pack the UPS in its original packaging. If the original packaging is no longer available, ask the Technical Support T echnician about obtaining a new set. It is important to pack the UPS properly in order to avoid damage in transit. Never use Styrofoam beads for a p acking material. A. Include a letter with your name, address, day time phone number, RMA
number , a copy of your original sales receipt, and a brief description of the problem.
5. Mark the RMA # on the outside of all packages. The factory cannot accept any package without the RMA # marked on the outside.
6. Return the UPS by insured, prepaid carrier to:
Para Systems Inc. MINUTEMAN UPS
1455 LeMay Drive
Carrollton, TX 75007
A TTN: RMA # _______
Page 24
23
English
Default: 120VAC (208VAC), User selectable: 127VAC (240VAC)
750VA 600W
1500VA 1200W
1000VA 800W
Protection
Waveform Type
Over-Current, Short-Circuit Protected and Latching Shutdown
Sine Wave
Frequency
50/60Hz, +/-0.1Hz (unless synchronized to utility)
Nominal Voltage
Maximum Power Capacity
2-6 ms Typical
>93% (Full Load)
Resettable Circuit Breaker
50 or 60 Hz, +/-6Hz, autosensing
0 - 165VAC (0 - 300VAC)
80 - 164VAC (150 - 271VAC)
120VAC: 105 - 134VAC (208VAC: 189 - 236VAC)
Transfer Time
Efficiency (Line Mode)
Input Protection
Frequency Limits
Voltage Range
Acceptable Input voltage
E1500RM2U
E1500RMT2U
E1000RM2U
E750RM2U
Model Number
SYSTEM SPECIFICA TIONS
Voltage Range
Topology
Line-Interactive, Sine Wave
OUTPUT NON-BA TTERY OPERA TION
INPUT
Number of Phase Single (1 2W +G)
Nominal Voltage 120VAC (208VAC)
Low Voltage Transfer Point
80V (150V) resets to Utility Power at 85V (157V) or higher
High Voltage Transfer Point
164V (271V) resets to Utility Power at 159V (264V) or lower
Volt age Regulation
120VAC: -12.5% - +11.7% (208VAC: -9.1% - +13.5%)
Frequency Range 60Hz: 54 - 66Hz or 50Hz: 44 - 56Hz
OUTPUT BA TTERY OPERA TION
Voltage Regulation Nominal +/-5% (until Low Battery Warning)
Volt age T .H.D.
<5% (Linear Load)
+/-10% @ 100% Load change in 30 ms
Dynamic Response
Slew Rate
<1Hz / second
Overload Capacity
110% for 20-seconds 125% for 10-seconds 150% Shutdown Immediately
E2000RM2U
E3000RM2U
E3000RMT2U
2000VA 1760W
3000VA 2560W
Page 25
24
English
BA TTERY SYSTEM
Typical Recharge Time Typical Battery Life
Battery: Quantity/Rating
3-5 years, depending on discharge cycles and ambient temp
3-12V7.2Ah
3-12V8.5Ah
8-hours from total discharge
6-12V7.2Ah
Battery Type
Sealed, Non-Spillable, Maintenance Free, V alue Regulated Lead Acid
System Voltage
36VDC
36VDC 72VDC
Runtime: Full Load (minutes)
Runtime: Half Load (minutes)
13
11
17
5
4
8
SURGE PROTECTION AND FIL TERING
Audible Noise at 1 m (3 ft.)
10/100 Base-T surge protec­tion let-through (as a percent­age of an applied +/-6 kV 1.2/ 50 us, 500 a 8/20 uS test)
Telephone line surge protec­tion let-through (as a percent­age of an applied +/-6 kV 1.2/ 50 us, 500a 8/20 uS test)
Noise Filter
Surge voltage let-through (as a percentage of an applied ANSI C62.41 Cat. A +/-6 kV)
Surge Response Time
Surge Current Capability
Surge Energy Rating 800 J (600 J)
0 ns (instantaneous) normal mode; <5 ns common mode
<5%
normal and common mode EMI/RFI suppression
<45 dBA
<1%
<5%
6500 Amps total
ENVIRONMENT AL
Operating Temperature (max)
Operating/Storage Humidity Operating Elevation
0 to 40°C (+32 to +104°F)
95% Non-Condensing
0 to 3,000m (0 to +10,000 ft)
PHYSICAL
Weight - Net
Size - Net D X W X H
Size - Shipping D X W X H
Weight - Shipping
46.2 lbs
21.0 Kgs
17.0 x 17.3 x 3.5" 432 x 440 x 89 mm
23.6 x 20.0 x 9.0" 600 x 508 x 230 mm
55.0 lbs
25.0 Kgs
REGULA TORY COMPLIANCE
Safety and Approvals EMC Verification
UL1778, cUL (CSA 22.2 no. 107.1)
FCC Class B, CE certified
Storage Elevation
0 to 15,000m (0 to +50,000 ft)
Storage Temperature -15 to +45°C (+5 to +1 13°F)
36VDC
72VDC
3-12V7.2Ah 6-12V8.5Ah
8
3
15
5
<60 dBA
24.0 x 17.3 x 3.5" 610 x 440 x 89 mm
39.4 x 23.6 x 9.0" 1000 x 600 x 230 mm
110.9 lbs
50.4 Kgs
127.0 lbs
57.3 Kgs
Page 26
25
English
(These items may require optional software or hardware)
Function
Factory Default
Description
User Choices
Set inverter output voltage
Shut­down T ype
Set audible alarm state
Enable/ Disable auto restart
Battery life in days
Battery install date
UPS ID
Enterprise Plus Series
Date of manufacture
1826
Enabled
Enabled
Entire UPS
120V AC
(208V AC)
Up to 64 charac­ters to define the UPS
Date of battery replacement ­month/day/year XX/XX/XXXX
Up to 5 characters
Enable or Disable
Enabled, at low battery , disabled
Entire UPS or UPS output
120, 127V AC (208, 240V AC)
At first battery replacement, reset to reflect actual number of days experience in your environment or leave factory default
Enter the current date when replacing batteries
Use this function to uniquely identify the UPS in your network configuration
Changes output voltage for bat­tery mode operation
Enabled - the UPS will emit a short beep when in the battery mode. At Low Battery the UPS will emit two beeps from low battery warning until shutdown. Disabled - Use only when software is controlling the UPS or to silence the alarm
When enabled, the UPS will automatically restart from a low battery shutdown when normal AC returns
Enable/ Disable REPO
Disabled
Enable or Disable
Enabled - the UPS will be powered off and remain off until the UPS is reset
Entire UPS - Turns off the entire UPS. UPS Output - Turns off the UPS's output receptacles only.
Page 27
26
English
Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equip­ment sites within the United S tates and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center. Replacement parts and warranty labor will be borne by Para Systems. For equipment located outside of the United S tates and Canada, Para Systems only covers faulty parts. Para Systems products repaired or replaced pursuant to this warranty shall be war­ranted for the unexpired portion of the warranty applying to the original product. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.
The warranty shall be void if (a) the equipment is damaged by the customer , is improperly used, is subjected to an adverse operating environment, or is oper­ated outside the limits of its electrical specifications; (b) the equipment is re­paired or modified by anyone other than Para Systems or Para Systems ap­proved personnel; or (c) has been used in a manner contrary to the product’s User's Manual or other written instructions.
Any technical advice furnished before or after delivery in regard to use or appli­cation of Para Systems’s equipment is furnished without charge and on the basis that it represents Para Systems’s best judgment under the circumstances, but it is used at the recipient’s sole risk.
EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO WARRAN­TIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANT­ABILITY AND FITNESS FOR A P ARTICULAR PURPOSE. Some states do not permit limitation of implied warranties; therefore, the aforesaid limitation(s) may not apply to the purchaser .
Page 28
27
English
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE LIABLE FOR DIRECT , INDIRECT , SPECIAL, INCIDENT AL, OR CONSEQUEN­TIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. S pecifically , Para Sys­tems is not liable for any costs, such as lost profits or revenue, loss of equip­ment, loss of use of equipment, loss of software, loss of data, cost of substi­tutes, claims by third parties, or otherwise. The sole and exclusive remedy for breach of any warranty , expressed or implied, concerning Para Systems’s prod­ucts and the only obligation of Para Systems hereunder , shall be the repair or replacement of defective equipment, components, or parts; or , at Para Systems’s option, refund of the purchase price or substitution with an equivalent replace­ment product. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
Longer term warranties are available at an additional cost. Contact Para Sys­tems (1-972-446-7363) for details.
LIMITED PRODUCT WARRANTY
(Continued)
Page 29
28
English
A1. DECLARATION OF CONFORMITY
Application of Council Directive(s): 89/336/EEC, 73/23/EEC
S tandard(s) to which Conformity is declared:
Manufacturer’s Name: Para Systems, Inc. (MINUTEMAN UPS) Manufacturer’s Address: 1455 LeMay Drive
Carrollton, Texas 75007 USA
T ype of Equipment: Uninterruptible Power Supplies (UPS) Model No: E750RM2U (Y), E1000RM2U (Y), E1500RM2U (Y),
E2000RM2U (Y), E3000RM2U (Y)
I hereby declare that the equipment specified above conforms to the above Directive(s).
Place: Carrollton, Texas, USA
Date: August 1, 2006
Robert Calhoun (Name)
Manager Engineering (Position)
Y ear of Manufacture: Beginning August 1, 2006
EN55022, EN55024 EN61000-6-1, EN61000-6-3 EN61000-4-5
Page 30
29
Notes:
English
Page 31
30
English
Notes:
Page 32
Para Systems, Inc.
1455 Lemay Dr .
Carrollton, TX 75007
Phone: 1-972-446-7363
Fax: 1-972-446-9011
Internet: minutemanups.com
UPS Sizing: sizemyups.com
PN - 34000271
Loading...