Minuteman CP, CP500, CP500/2, CP1K, CP1K/2 User Manual

...
Page 1
CP SERIES
User's Manual
Page 2
Table of Contents
1. INTRODUCTION
1.1 Systems Description ……………………………………………………….1
1.2 Product Specification ……………………………………………………...3 Electrical Specification …………………………………………………… 4 Mechanical Specification …………………………………………………4 Operating Environment ……………………………………………………4 Typical Battery Backup Time ……………………………………………..4
1.3 Safety ……………………………………………………………………….5
1.4 Displays and Switch ……………………………………………………….6
1.5 Communication Port ……………………………………………………….7
PAGE
2. INSTALLATION AND OPERATION
2.1 Unpacking and Inspection ………………………………………………… 9
2.2 Installation …………………………………………………………………... 9
2.3 Storage Instruction ………………………………………………………….12
3. TROUBLESHOOTING
3.1 Troubleshooting Tips ……………………………………………………….12
3.2 Troubleshooting Charts …………………………………………………….13
Page 3
1. INTRODUCTION
1.1 SYSTEM DESCRIPTION
The MINUTEMAN CP Series UPS is an advanced true on-line sinewave uninterruptible power system with bypass switch. It provides reliable, regulated, transient-free AC power to your sensitive equipment, ranging from computers and telecommunication systems to computerized instruments. Because the UPS is an on-line design, conditioned power is provided continuously to the attached devices. Unlike the standby UPS, its on-line structure is constantly regulating, filtering the output power when commercial power is present. During electrical power failure, the unit employs its internal maintenance-free battery to supply back-up power without any transfer time.
In the event of overload or inverter failure, the UPS will transfer to the bypass as an alternate source. The UPS can transfer back to the inverter automatically after the overload condition has been cleared. All the above transfer time is within four (4) milliseconds that can ensure your equipment operating uninterruptedly.
Output Receptacle is optional, NEMA 5-15R or IEC 320.
1
Page 4
Output Receptacle is optional, NEMA 5-15R or IEC 320.
2
Page 5
1.2 PRODUCT SPECIFICATION ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Series
500VA/350W
Series
100VA/700W
CP2K/2
200VA/1400W
CP3K/2
3000VA/2100W
NOTE: The power factor of CP2K/2 and CP3K/2 is 0.97.
INPUT
I nput Fr eq uency Range: ± 5%
I nput Volt age Range: + 10%, - 15%
Frequency
No.
CP500 60 120VAC 6.0A 120VAC 4.2ACP500
CP500/2 50 220VAC 3.1A 220VAC 2.3A
CP1K 60 120VAC 11A 120VAC 8.3ACP1K
CP1K/2 50 220VAC 6.2A 220VAC 4.5A CP2K/2 50 220VAC 8.3A 220VAC 9.1A
CP3K/2 50 220VAC 12.0A 220VAC 13.6A
(HZ)
Voltage Current Voltage Current
Input OutputPower Rating Model
OUTPUT
O utput Frequency Regulation: Phase lock to input under normal condition
± 0.5% at free running.
Output Voltage Regulation: ± 2%
Dist or tion: Less than 3% under linear load.
BYPASS TRANSFER TIME
UPS Failur e: 2.5 ms typical, 4 ms max. (from inverter to bypass and vice
versa).
3
Page 6
MECHANICAL SPECIFICATION
MECHANICAL SPECIFICATION
Dimension
No.
CP500 5.6 x 17.5 x 7.5 25 28
CP1K 7.5 x 17.7 x 10.4 50 56 CP2K/2 7.5 x 18.1 x 18.4 99 108 CP3K/2 7.5 x 20.7 x 19.8 120 124
OPERATING ENVIRONMENT
T emper ature: 0º C to 40º C
Relat ive Humidity: 0 to 95%, non-condensing.
TYPICAL BATTERY BACK-UP TIME
W x D x H (inches)
Weights (lbs)Model
Net Gross
4
Page 7
IMPORTANT SAFETY INSTRUCTION -- SAVE THESE INSTRUCTIONS
1.3 SAFETY
This manual contains important instructions for MINUTEMAN CP series that should be followed during installation and maintenance of the UPS and Batteries.
CAUTION:
The UPS contains voltages, which are potentially hazardous. Qualified service personnel
should perform all repairs.
The UPS has its own internal energy source (battery). The output receptacles maybe live
even when the UPS is not connected to an AC supply.
Symbol meaning:
Alternating current supply
Symbol for equipment grounding conductor.
On and standby symbol for 220V, 230V, 240V version.
On and Off symbol for 110V, 120V version.
Internal Battery supply voltage _______ UPS MODEL CP500: 24V _ _ _ UPS MODEL CP1K: 60V _ _ _
An insulated grounding conductor —— The wire shall be 18 AWG minimum PVC UL
1015 green or green with yellow strip.
The grounding conductor described in above item is to be grounded to earth at the
service equipment.
Plug the UPS into a grounded 3-wire AC receptacle.
Replacement of batteries should performed or supervised by personnel knowledgeable of
batteries and the required precautions. Keep unauthorized personnel away from battery.
5
Page 8
When replacing batteries, use the same number and the following type batteries:
Matsushita (or Panasonic) Electric Works. Type LCR12V6.5P, rated 12V.
Do not dispose of battery or batteries in a fire, the battery may explode.
Do not open or mutilate the battery or batteries, released electrolyte is harmful to the skin
and eyes. It may be toxic.
A battery can present a risk of electrical shock and high short circuit current. The
following precautions shou ld be obser v ed when working on batteries.
Remove watches, rings or other metal objects.
Use tools with insulated handles.
For safe and continuous operation of the UPS depend partially on the care taken by user. Please observe the following precautions:
Do not disassemble the UPS.
Do not attempt to power the UPS from any receptacle except a 2-pole 3-wire grounding
receptacle.
Do not place the UPS near water or in environment of excessive humidity.
Do not allow liquid or any foreign object to get inside the UPS.
Do not block air vents in front of the UPS or air exhausts in the back.
Do not plug appliances, such as hair dryers, into the UPS receptacles.
Do not place the UPS under direct sunshine or close to heat-emitting source.
A certified detachable power supply cord is to be used with this equipment. For a related
current up to 10A, a type not lighter than HO5VV-F3G 0.75mm CP3K/2, rated current 16A, a type not lighter than HO5VV-F3G 1.5 mm
Caution
- Electric shock hazard. Battery circuit is not isolated from the input voltage. There may be hazardous voltage between battery terminals and ground. Check that there is no voltage before touching!
Caution
-- Electric shock hazard. Even after disconnection from the mains input voltage, components inside the UPS are still connected to the battery and are at hazardous potential. Disconnect the battery supply circuit before carrying out servicing or maintenance work.
1.4 DISPLAYS AND SWITCH
MAIN switch
turn off the UPS by depressing switch to the position " ".
: Turn on the UPS by depressing the front panel switch into the position " | " and
2
shall be used. For
2
shall be used.
LINE LED BYPASS LED
: This light means that the incoming AC line is normal.
: The light means that the UPS is providing power directly from the incoming
AC line through the bypass line.
6
Page 9
FAULT LED
beeps continuously.
: The light is on when the UPS is in fault condition. In the meantime, the alarm
LOAD LEVEL LED
The lights are in 25% increments. If the UPS is overloaded, the LED's show over 100%, then you have connected too many devices into the UPS. Unplug the least critical equipment, such as a printer etc.
: The light is a bar graph and indicates how much load is on the UPS.
1.5 COMMUNICATION PORT
The communication port on the back of the UPS may be connected to a computer. This port allows the computer to monitor the status of the UPS and control the operation of the UPS in some cases. Its major functions normally include some or all of the following:
A. COMUNICATION PORT INTRODUCTION
To broadcast a warning when power fails.
To close the files before the battery reserve is exhausted.
To turn off the UPS and the computers.
Some computers are equipped with a special connector to link with this communication port. Some computers require a special plug-in card. Some computers may need a special UPS monitoring software. Contact your dealer for the detail of different interface kits.
7
Page 10
Pin 2:
The relay will close when
input power fails.
Pin 3:
The relay will become open
when input power fails.
Pin 4:
Common for pins 2, 3, and 5.
Pin 5:
The relay will close when the battery inside the UPS has less than about 3 minutes (CP500: 1.5 minutes) of backup time left.
Pin 6:
User may send a high level signal (+5V ~ + 12V) for over 500 ms to turn off the UPS. But it can only activate when input power fails.
PIN 7:
Common for pin 6.
NOTE:
1. Relay rating +24V 0.5A
2. Pin 7 should be connected to ground only.
B. RS232 COMMUNICATION PORT INTRODUCTION (FOR CP3K/2 ONLY)
INTRODUCTION:
The RS232 communication port provides the following features:
1. Monitor charger status.
2. Monitor battery status and condition.
3. Monitor inverter status.
4. Monitor UPS status.
5. Monitor the utility status.
6. Provide the power switch function for computer to turn on and off the utility to the computer on schedule for power saving.
Computer will control information exchange by a query followed by <cr>. The UPS will respond with information followed by a <cr> or action.
UPS data will be provided at 2400 baud rate and consist of 8 data bits, 1 stop bit, and no parity bit. All the information is provided in ASCII format.
8
Page 11
Hardware:
Cabling:
BAUD RATE ……………… : 2400 bps DATA LENGTH …………... : 8 bits STOP BIT …………………. : 1 bit PARITY ……………………. : NONE
COMPUTER RX →—- — — — — TX — — — — — DTR — — — — — GND — — — — —
UPS TX (PIN 9) RX (PIN 6)
DTR (PIN 1)
GND (PIN 7)
(9 PIN female D-type connector)
2. INSTALLATION AND OPERATION
2.1 UNPACKING AND INSPECTION
Examine the packing carton for damage. Notify the carrier immediately if damage is present. Retain the packing for future use.
2.2 INSTALLATION
1. Connect the power cord to a verified-grounded 3-wire receptacle. CP3K/2 comes with locking casters (upward for release, downward for lock).
THE AC POWER IS PRESENT AT THE OUTPUT RECEPTACLE WHEN THE POWER CORD IS PLUGGED IN AND THE BREAKER IS TURNED ON EVEN IF YOU DO NOT PRESS THE FRONT PANEL SWITCH INTO " | " POSITION.
9
Page 12
2. Charge the batteries for ten (10) hours before use. The UPS will recharge the batteries automatically whenever its power cord is plugged into a wall outlet. You may use the UPS immediately without recharging, but the backup time may be less than the rating.
3. Connect the power cord of your computer equipment to the output receptacles of the UPS. Turn on the computer equipment.
DO NOT PLUG LASER PRINTERS INTO THE UPS BECAUSE THEY DRAW TOO MUCH POWER.
4. CP500, CP1K , CP2K/2 Turn on the UPS by depressing the front panel switch to the position " | ". The "LINE" "BYPASS" and "LOAD LEVEL" LED's will light up. After a few seconds the "INVERTER" will light up, too. About 25 seconds later, the "BYPASS" LED will go off. Now, the UPS is working properly.
5. CP3K/2 Turn on the UPS by depressing the panel switch to the position " | ". All LEDs on panel will light up. Then, check load level LED one by one, and all load seconds the "INVERTER" indic at or will li ght up. About 25 sec o nds later , the "B YP A SS" LED wi ll go off. Now, the UPS is working properly. If the "LOAD LEVEL" shows it is over 100%, buzzer beeps twice per second. It means that you have connected too many Unplug the least critical equipment, such as printer, etc.
level LEDs flash again. After a few
devices to the UP S.
10
Page 13
6. To test the UPS turn OFF commercial power by either turning OFF the breaker supplying power to the commercial receptacle, or using a switchable power strip.
7. Due to physical stability requirement for CP3K/2 series, please install the supporter to the UPS at the bottom side with two screws.
8. External battery pack installation for CP2K/2 and CP3K/2
Remove the top lid from both units.
Remove the side panel (left side for CP3K/2, two sides for CP2K/2) from the control unit,
and the right side panel from the battery pack.
Connect the cable (CP3K/2: Anderson connector, CP2K/2: Fastons connector to the
power stage connector marked CN15) at the control unit. Then connect Anderson connector to the battery pack.
Slide the units together, so that bracket "A" lines up on the left side of the control unit and
on the right side of the battery pack.
Install both top lids with screws again.
Install two brackets labeled "B" between the two units at the back.
The UPS is now ready for normal start-up and check out.
11
Page 14
2.3 STORAGE INSTRUCTION
For extended storage in moderate climates, the batteries should be charged for 12 hours every 3 months by plugging the power cord into the wall receptacle. Repeat it every 2 months in high temperature locations.
3. TROUBLESHOOTING
3.1 TROUBLESHOOTING TIPS
The TROUBLESHOOTING chart covers most of the difficulties that you may encounter under normal working conditions. If the UPS fails to operate properly, please review the following checks before calling the repair center:
1. Is the UPS plugged into a correctly working outlet?
2. Is the line voltage within the rating specified?
3. Has the fuse on the back panel on model CP500 blown?
4. Has the circuit protector on the back panel of model CP1K or CP2K/2 tripped?
5. Has the circuit breaker on the back panel of the CP3K/2 tripped?
12
Page 15
Please note the following information when you call for service:
1. Model #, Serial #
2. Date of problem
3. Full description of problem
3.2 TROUBLESHOOTING CHART
TROUBLESHOOTING CHART
PROBLEM POSSIBLE CAUSE ACTION TO TAKE
No light, no alarm (UPS
not ON)
No "LINE" light, alarms beeps every few seconds.
"FAULT" LED lights, alarm beeps continuously.
Backup time is less than the rating.
"LOAD LEVEL" LED"S show over 100%
Buzzer beat twice per second.
Front panel switch in off position Turn on switch Rear panel fuse blown or circuit
protector trip No incoming utility Check input power Breaker is off Check the breaker ON/OFF
Breaker is off Check the breaker ON/OFF No incoming utility Check input power Fuse blown or protector trip Replace fuse or reset
UPS failure Call for service
Battery is not fully charged. Dead battery. Charger failure Overloaded Remove the least critical load.
Overloaded Remove the least critical load.
Replace fuse or reset protector. Restart UPS.
protector. If problem remains call for service
Recharge the battery for at least 6 hours. Re-test the backup time. If problem remains, call for service.
13