Minuteman CP, CP500, CP500/2, CP1K, CP1K/2 User Manual

...
CP SERIES
User's Manual
Table of Contents
1. INTRODUCTION
1.1 Systems Description ……………………………………………………….1
1.2 Product Specification ……………………………………………………...3 Electrical Specification …………………………………………………… 4 Mechanical Specification …………………………………………………4 Operating Environment ……………………………………………………4 Typical Battery Backup Time ……………………………………………..4
1.3 Safety ……………………………………………………………………….5
1.4 Displays and Switch ……………………………………………………….6
1.5 Communication Port ……………………………………………………….7
PAGE
2. INSTALLATION AND OPERATION
2.1 Unpacking and Inspection ………………………………………………… 9
2.2 Installation …………………………………………………………………... 9
2.3 Storage Instruction ………………………………………………………….12
3. TROUBLESHOOTING
3.1 Troubleshooting Tips ……………………………………………………….12
3.2 Troubleshooting Charts …………………………………………………….13
1. INTRODUCTION
1.1 SYSTEM DESCRIPTION
The MINUTEMAN CP Series UPS is an advanced true on-line sinewave uninterruptible power system with bypass switch. It provides reliable, regulated, transient-free AC power to your sensitive equipment, ranging from computers and telecommunication systems to computerized instruments. Because the UPS is an on-line design, conditioned power is provided continuously to the attached devices. Unlike the standby UPS, its on-line structure is constantly regulating, filtering the output power when commercial power is present. During electrical power failure, the unit employs its internal maintenance-free battery to supply back-up power without any transfer time.
In the event of overload or inverter failure, the UPS will transfer to the bypass as an alternate source. The UPS can transfer back to the inverter automatically after the overload condition has been cleared. All the above transfer time is within four (4) milliseconds that can ensure your equipment operating uninterruptedly.
Output Receptacle is optional, NEMA 5-15R or IEC 320.
1
Output Receptacle is optional, NEMA 5-15R or IEC 320.
2
1.2 PRODUCT SPECIFICATION ELECTRICAL SPECIFICATION
ELECTRICAL SPECIFICATION
Series
500VA/350W
Series
100VA/700W
CP2K/2
200VA/1400W
CP3K/2
3000VA/2100W
NOTE: The power factor of CP2K/2 and CP3K/2 is 0.97.
INPUT
I nput Fr eq uency Range: ± 5%
I nput Volt age Range: + 10%, - 15%
Frequency
No.
CP500 60 120VAC 6.0A 120VAC 4.2ACP500
CP500/2 50 220VAC 3.1A 220VAC 2.3A
CP1K 60 120VAC 11A 120VAC 8.3ACP1K
CP1K/2 50 220VAC 6.2A 220VAC 4.5A CP2K/2 50 220VAC 8.3A 220VAC 9.1A
CP3K/2 50 220VAC 12.0A 220VAC 13.6A
(HZ)
Voltage Current Voltage Current
Input OutputPower Rating Model
OUTPUT
O utput Frequency Regulation: Phase lock to input under normal condition
± 0.5% at free running.
Output Voltage Regulation: ± 2%
Dist or tion: Less than 3% under linear load.
BYPASS TRANSFER TIME
UPS Failur e: 2.5 ms typical, 4 ms max. (from inverter to bypass and vice
versa).
3
Loading...