Minuteman BP192RTXL, BP240RTXL User Manual

Para Systems, Inc.
1455 Lemay Dr.
Carrollton, TX 75007
Phone: 1-972-446-7363
Fax: 1-972-446-9011 Internet: minutemanups.com UPS Sizing: sizemyups.com
BP192RTXL BP240RTXL
Battery Packs
P/N 34000472 R2
Table Of Contents
1. Introduction 2
2. Rear Panels 6
3. Installation 7
4. Operation 12
5. Replacing the Battery 12
6. Obtaining Service 18
7. Specifications 19
8. Limited Product Warranty 20
1
Chapter 1: Introduction
Thank you for purchasing this power protection product. It has been de­signed and manufactured to provide many years of trouble free service. Please read this manual before installing your BPRTXL Battery Pack, models BP192RTXL, BP240RTXL as it provides important information that should be followed during installation and maintenance of the Battery Packs and batter­ies allowing you to correctly set up your system for the maximum safety and performance. Included is information on customer support and factory ser­vice if it is required. If you experience a problem with the Battery Packs please refer to Obtaining Service section in this manual to collect enough information so that the Technical Support Department can rapidly assist you.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS !
CAUTION! This Battery Pack series is ONLY intended to be installed in an
indoor temperature controlled environment that is free of conductive contami­nants. This Battery Pack series is not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment ANSI/NFP A 75. Select a location which will provide good air circu­lation for the Battery Pack and UPS at all times.
CAUTION! The maximum ambient operating temperature for this Battery Pack series is 40°C (“0 ~ 40°C” for Ambient Operation). The external vents and openings on the Battery Pack are provided for ven-
tilation. To ensure reliable operation of the UPS and to protect the UPS from overheating, these vents and openings must not be blocked or cov­ered. Do not insert any object into any of the vents or openings that may hinder the ventilation.
Install the Battery Pack in a well ventilated area, away from excess mois-
ture, heat, dust, flammable gas or explosives.
Leave adequate space (at least 15cm) around all sides of the Battery
Pack for proper ventilation.
Do not mount the Battery Pack with its front or rear panel facing down at
any angle.
Before usage, you must allow the Battery Pack to adjust to room temper-
ature (20°C~25°C or 68°F~77°F) for at least one hour to avoid moisture condensing inside the UPS.
2
WARNING: These Battery Packs contains potentially hazardous voltages.
Do not attempt to disassemble the Battery Pack beyond the battery replace­ment procedure. These Battery Packs contain no user serviceable parts. Repairs and Battery replacement must be performed by QUALIFIED SER-
VICE PERSONNEL ONL Y.
WARNING: Risk of Electrical Shock. Hazardous live p arts inside these Bat-
tery Packs are energized from the battery .
CAUTION! To de-energize the Battery Pack:
1. If the UPS is on press and release the On/Off/Test button.
2. Turn off the input breaker on the rear panel of the UPS.
3. Turn off the DC breaker on the rear p anel of the Battery Pack.
4. Disconnect the battery cable from the rear panel of the UPS.
5. T o de-energize the Battery Pack completely, disconnect the batteries.
WARNING: Qualified Service Personnel ONLY must perform the Installa­tion and Servicing of these Battery Packs. MINUTEMAN accepts no liabilities and is not limited to: injury to the Service Personnel, or damages to; the Bat­tery Pack, the UPS, or the connected equipment caused by the incorrect installation or servicing of the Battery Packs. These Battery Packs MUST be operated with their respective UPS models, see the table below:
Battery Pack
UPS
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE BA T ­TERY P ACK. The mounting brackets are ONLY for securing the Battery Pack
to the rack.
BP192RTXL
ED5000RT -CU ED6000RT -CU
BP240RTXL
ED8000RT -CU ED10000RT-CU
3
NOTICE: This equipment has been tested and found to comply with the limits
for a Class A computing device in accordance with the specifications in Sub­part J of Part 15 of FCC Rules and the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference of the Canadian De­partment of Communications. These limits are designed to provide reason­able protection against such interference in a residential installation. This equipment generates and uses radio frequency and if not installed and used properly , that is, in strict accordance with the manufacturer's instructions, this equipment may cause interference to radio and television reception. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Re-orient the receiving antenna.Relocate the computer with respect to the receiver.Move the computer away from the receiver.Plug the computer into a different outlet so that the computer and receiver
are on different branch circuits.
Shielded communications interface cables must be used with this product. WARNING: Changes or modifications to this unit not expressly approved by
the party responsible for compliance could void the user's authority to operate the equipment.
RECIEVING INSPECTION
Once you receive the product it should be visually inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored by the manufacturer. The packing materials that the product was shipped in were carefully designed to minimize any shipping damage. In the unlikely case that the product needs to be returned to the manufacturer, use the original packing material. Since the manufacturer is not responsible for shipping damage incurred when the product is returned, the original packing material is inexpensive insurance. PLEASE SA VE THE
PACKING MATERIALS!
LIFE SUPPORT POLICY
As a general policy, we do not recommend the use of any of our products in life support applications where failure or malfunction of the product can be reasonably expected to cause failure of the life support device or to signifi­cantly affect its safety or effectiveness. We do not recommend the use of any of our products in direct patient care. We will not knowingly sell our products for use in such applications unless it receives in writing assurances satisfac­tory to us that (a) the risks of injury or damage have been minimized, (b) the customer assumes all such risks, and (c) our liability is adequately protected under the circumstances.
Examples of devices considered to be life support devices are neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators for both adults and infants, anesthesia ventilators, and infusion pumps as well as any other devices desig­nated as “critical” by the United States FDA.
© COPYRIGHT 2014 BY PARA SYSTEMS, INC.
All Rights Reserved. All rights of this User Manual (“Manual”), including but not limited to the content, information, and figures are solely owned and reserved by Para Systems, Inc. (“Para Systems”). The Manual can only be applied to the operation or the use of this product. Any disposition, duplication, dissemi­nation, reproduction, modification, translation, extraction, or usage of this Manual in whole or in part is prohibited without the prior written permission of Para Systems. Given that Para Systems will continuously improve and develop the product, changes may be made to the information in this Manual at any time without obligation to notify any person of such revision or changes. Para Systems will make all possible efforts to secure the accuracy and the integrity of this Manual. Para Systems disclaims any kinds or forms of warranty , guar­antee, or undertaking, either expressly or implicitly , including but not limited to the completeness, faultlessness, accuracy , non-infringement, merchantability or fitness for a particular purpose of the Manual.
4
5
Chapter 2: Rear Panels
Chapter 3: Installation
INST ALLATION PLACEMENT
This Battery Pack series is ONLY intended to be installed in an indoor tem- perature controlled environment that is free of conductive contaminants. DO NOT operate the Battery Pack in: extremely dusty and/or unclean areas, loca­tions near heating devices, water or excessive humidity , or where the Battery Pack is exposed to direct sunlight. Select a location, which will provide good air circulation for the Battery Pack at all times. Route cables so they cannot be walked on or damaged. This Battery Pack series is not for use in a com­puter room as defined in the Standard for the Protection of Electronic Com­puter/Data Processing Equipment ANSI/NFP A 75. T ypical battery life is 3 to 5 years. Environmental factors do affect battery life. High temperatures, poor ventilations and frequent, short duration discharges have a negative impact on battery life.
Operating Temperature (Maximum): 0 to 40°C (+32 to +104°F) Operating Elevation: 0 to 2,000m (0 to +6,562 ft) Operating and Storage Relative Humidity: 95%, non-condensing Storage Temperature: -15 to +50°C (+5 to +122°F) Storage Elevation: 0 to 15,000m (0 to +49,213 f t)
1. The DC Circuit Breaker connects and disconnects the DC bus voltage from the Battery Pack to the UPS. The DC Circuit Breaker will trip in the event of a DC overcurrent condition.
2. The top External Battery connector is for connecting to the UPS and/or for Daisy Chaining additional Battery Packs.
3. The bottom External Battery connector is for Daisy Chaining additional Battery Packs and/or connecting an external battery charger.
6
INST ALLATION
Be sure to read the installation placement and all the cautions before installing the Battery Pack. Place the Battery Pack in the final desired location and complete the rest of the installation procedure.
WARNING! These Battery Packs are extremely heavy. Any time the Battery Pack has to be handled be sure to use, enough personnel, strong supports and equipment to safely handle the Battery Pack.
NOTE: If you are using more than one of these Battery Packs with the Endeavor 5-10KVA RT series UPS, the UPS must be configured so that the UPS will report the correct estimated runtime on the LCD screen and in the Power Monitoring software and/or the SNMP card. See the Power Monitoring software or the SNMP card’s User's Manual to configure the UPS.
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE BA T ­TERY P ACK. The mounting brackets are ONLY for securing the Battery Pack
to the rack.
7
RACKMOUNT CONFIGURA TION
Use the included rackmount brackets and screws to mount the Battery Pack in a rack by following the steps below . USE CAUTION: These Battery Packs are extremely heavy . Use two or more people when installing the Battery Pack.
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE BA T ­TERY P ACK. The mounting brackets are ONLY for securing the Battery Pack
to the rack.
1. Attach the rackmount brackets to the mounting holes on the side panels of
the Battery Pack as shown below.
2. Follow steps 1 through 4 to install the Battery Pack into the Rail kit. See the
figure below. Step 1: Adjust the length of the rail according to the rack. Step 2: Securely tighten the wing nuts. Step 3: Secure the rail to the rack with the enclosed screws. Step 4: Slide the Battery Pack onto the rail and secure to the rack with the
enclosed screws.
TOWER CONFIGURA TION
The tower configuration allows the user to install the Battery Pack in the up­right position. The tower stands are provided with the Battery Pack. WARN-
ING: Use two or more people when installing the Battery Pack. Use CAU­TION, these Battery Packs are extremely heavy .
1. Once the location of the Battery Pack has been determined, place the to­wer stands in the desired location.
WARNING: The Battery Pack must be installed in the proper up-right posi­tion. Once the Battery Pack is placed in the tower stands, looking at the front panel the the top cover of the Battery Pack MUST be on your left hand side.
2. Slide the Battery Pack into the tower stands. Make sure that the Battery Pack is stable.
3. The name plate panel can be rotated to read in the up-right position. Re­move the front panel from the UPS. On the backside of the front panel, p­ush the name plate panel outwards, the panel will pop out. Rotate the name plate panel counter clockwise so that it reads in the upright position. Re­install the front panel on the Battery Pack.
CONNECTING THE BA TTERY PACK
(QUALIFIED SERVICE PERSONNEL ONL Y) Please read all of the WARNINGS and CAUTIONS before attempting to con­nect or service the batteries or the Battery Pack. The installation and servic­ing of the batteries and the Battery Pack must be performed by Qualified Service Personnel ONL Y.
Replace the batteries and/or Battery Pack with the same number and type as originally installed.
CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.
CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
8
9
NOTE: If you are using more than one of these Battery Packs with the
Endeavor 5-10KVA RT series UPS, the UPS must be configured so that the UPS will report the correct estimated runtime on the LCD screen and in the Power Monitoring software and/or the SNMP card. See the Power Monitoring software or the SNMP card’s User's Manual to configure the UPS.
1. The UPS MUST be in the off position.
2. The DC breaker(s) on the rear panel of the Battery Pack(s) MUST be in the off position.
3. Remove the External Battery Connector's cover plate from the rear panel of the UPS (requires a phillips screwdriver).
4. Remove the top External Battery Connector's cover plate from the rear panel of the Battery Pack.
5. Connect the one end of the #8 A WG premolded battery cable to the Exter­nal Battery Connector on the rear panel of the UPS and secure with the retaining screws.
6. Connect the other end of the #8 A WG premolded battery cable to the Exte­rnal Battery Connector on the rear panel of the Battery Pack and secure with the retaining screws.
7. Turn on the DC breaker on the rear panel of the Battery Pack.
8. The Battery Pack is ready for normal operation, see the UPS User's Manual
for the normal startup of the UPS.
NOTE: If using more than one Battery Pack see Daisy Chaining.
4. Remove both of the External Battery Connector's cover plates from the rear panel of the first Battery Pack.
5. Remove the top External Battery Connector's cover plate from the rear panel of the second Battery Pack.
6. Connect the first #8 A WG premolded battery cable to the External Battery Connector on the rear panel of the UPS and secure with the retaining screws.
7. Connect the other end of the first #8 A WG premolded battery cable to the External Battery Connector on the rear panel of the first Battery Pack and secure with the retaining screws.
8. Connect the second #8 A WG premolded battery cable to the bottom Exte­rnal Battery Connector on the rear panel of the first Battery Pack and se­cure with the retaining screws.
9. Connect the other end of the second #8 A WG premolded battery cable to the top External Battery Connector on the rear panel of the second Battery Pack and secure with the retaining screws.
10. Turn on all of the DC breakers on the rear panel of the Battery Packs.
1 1. The Battery Packs are ready for normal operation, see the UPS User's
Manual for the normal startup of the UPS. NOTE: There is no maximum number for Daisy Chaining the Battery Packs, however the recharge time will increase exponentially for every Battery Pack added.
DAISY CHAINING
(QUALIFIED SERVICE PERSONNEL ONL Y) "Daisy Chaining" means connecting one Battery Pack to another Battery Pack to another Battery Pack, this chain could go on indefinitely . Follow the steps below to Daisy Chain the Battery Packs. Please read all of the WARNINGS and CAUTIONS before attempting to connect the external battery pack.
1. The UPS MUST be in the off position.
2. The DC breakers on the rear panel of the Battery Packs MUST be in the off position.
3. Remove the External Battery Connector's cover plate from the rear panel of the UPS (requires a phillips screwdriver).
10
11
Chapter 4: Operation
SYSTEM OVERVIEW
These Battery Packs will extend the runtime capabilities of the UPS. These Battery Packs do not have internal chargers and are charged by the UPS to properly maintain the batteries. There is no maximum number for Daisy Chain­ing the Battery Packs, however the recharge time will increase exponentially for each Battery Pack added. NOTE: If you are using more than one of these Battery Packs with the Endeavor 5-10KVA RT series UPS, the UPS must be configured so that the UPS will report the correct estimated runtime on the LCD screen and in the Power Monitoring software and/or the SNMP card. See the Power Monitoring software or the SNMP card’s User's Manual to configure the UPS.
CHARGING THE BA TTERY
These Battery Packs do not have internal chargers. The Battery Packs are charged by the UPS. It is recommended that the Battery Packs be charged for a minimum of 4-hours before use. The Battery Pack maybe used immedi­ately , however, the “On-Battery” runtime of the UPS may be less than normally expected. NOTE: If the Battery Pack is going to be out of service or stored for a prolonged period of time, the batteries must be recharged for at least 24­hours every ninety days.
TURNING THE BA TTERY PACK ON/OFF
Turning on the DC circuit breaker on the rear panel of the Battery Pack will connect the DC bus voltage from the Battery Pack to the UPS. Turning of f the DC circuit breaker on the rear panel of the Battery Pack will disconnect the DC bus voltage from the Battery Pack to the UPS.
Chapter 5: Replacing The Battery
Replace the batteries and/or Battery Pack with the same number and type as originally installed.
CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.
CAUTION: Do not dispose of batteries in a fire. The batteries may explode. The batteries in these Battery Pack are recyclable. Dispose of the batteries
properly. The batteries contain lead and pose a hazard to the environment and human health if not disposed of properly . Refer to local codes for proper disposal requirements or return the battery to the supplier.
CAUTION: The battery can present a risk of electrical shock. These batter­ies produce sufficient current to burn wire or tools very rapidly, producing molten metal. Observe these precautions when installing or replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disconnecting the battery terminals.
6. Determine if the battery is inadvertently grounded. If the battery is, rem­ove the source of the grounding. Contact with any part of a grounded ba­ttery can result in an electrical shock. The likelihood of such shock will be reduced, if such grounds are removed during installation and maintenance.
CAUTION: Replace the batteries with the same number and type as originally installed in the Battery Pack. These batteries have pressure operated vents. These Battery Packs contain sealed non-spillable maintenance free lead acid batteries.
(QUALIFIED SERVICE PERSONNEL ONL Y)
Please read all of the WARNINGS and CAUTIONS before attempting to con­nect or service the batteries or the Battery Pack. The installation and servic­ing of the batteries and the Battery Pack must be performed by Qualified Service Personnel ONL Y. T ypical battery life is 3 to 5 years. Environmental factors do affect battery life. High temperatures, poor utility power, and fre­quent, short duration discharges have a negative impact on battery life. NOTE: If there is a power interruption while replacing the batteries, with the UPS on, the load will not be backed up.
WARNING! This Battery Pack contains potentially hazardous voltages. Do not attempt to disassemble the Battery Pack beyond the battery replacement procedure. These Battery Packs contain no user serviceable parts.
12
Model
Battery B00056
BP192RTXL
BP240RTXL
B00058
13
BATTERY REPLACEMENT PROCEDURE (QUALIFIED SERVICE PERSONNEL ONL Y)
PLEASE READ THE CAUTIONS AND W ARNINGS BEFORE A TTEMPTING TO REPLACE THE BA TTER Y MODULES
The batteries can be replaced without powering down the whole UPS system. NOTE: If there is a power interruption while replacing the batteries, with the UPS on, the load will not be backed up. To replace the batteries without powering down the UPS system start with step number 6.
BP240RTXL
1. Turn off the equipment that is plugged into the output recept acles of the UPS.
2. Press and release the On/Off/Test button on the front panel to turn the UPS off.
3. Disconnect the UPS from the utility power.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the rear panel of the UPS.
6. Turn off all of the DC circuit breakers on the rear p anel of all of the Battery Packs.
7. Disconnect all of the battery cables.
8. Remove the Battery Pack from the rack and lay on the floor or a tabletop.
USE CAUTION: These Battery Packs are extremely heavy . Use two or more people when removing the Battery Pack.
9. Remove the cover screws from the top cover.
10. Remove the cover and set aside.
1 1. Remove the retaining screws for the battery retaining brackets.
12. Remove the battery retaining brackets and set aside.
NOTE: Before disconnecting the battery wires it is recommended that you draw a diagram of how the batteries are connected.
13. Disconnect the battery positive (red) and battery negative (black) wires.
14. Disconnect all of the battery wires.
15. Remove all of the defective batteries and set aside.
16. Install the new batteries in the same orientation as the original batteries.
17. Verify proper polarity. Re-install the battery wires.
18. Reconnect the battery positive (red) and battery negative (black) wires.
19. Re-install the battery retaining brackets and secure with the retaining screws.
20. Re-install the top cover and secure with the retaining screws
21. Re-install the Battery Pack in the rack.
22. Reconnect all of the battery cables.
23. Turn on all of the DC circuit breakers on the rear panel of all of the Battery Packs.
24. Properly dispose of the old batteries at an appropriate recycling facility or return them to the supplier in the packing material for the new batteries.
25. The Battery Pack is ready for normal operation.
NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the batter­ies, the user must initiate a self-test to clear the Weak/Bad Battery Alarm. To initiate a self-test see section 4 "ON / OFF/ TEST BUTTON" in the UPS's User's Manual.
14
15
BP192RTXL
(QUALIFIED SERVICE PERSONNEL ONL Y)
1. Turn off the equipment that is plugged into the output recept acles of the UPS.
2. Press and release the On/Off/Test button on the front panel to turn the UPS off.
3. Disconnect the UPS from the utility power.
4. Unplug the equipment from the output receptacles of the UPS.
5. Unplug the computer interface cable from the rear panel of the UPS.
6. Turn off all of the DC circuit breakers on the rear p anel of all of the Battery Packs.
7. Disconnect all of the battery cables.
8. Remove the Battery Pack from the rack and lay on the floor or a tabletop.
USE CAUTION: These Battery Packs are extremely heavy . Use two or more people when removing the Battery Pack.
9. Remove the front panel retaining screws.
10. Remove the front panel and set aside.
1 1. Remove the cover screws from the top cover.
12. Remove the cover and set aside.
13. Remove the retaining screws for the battery retaining bracket.
14. Remove the battery retaining bracket and set aside.
NOTE: Before disconnecting the battery wires it is recommended that you draw a diagram of how the batteries are connected.
15. On the right hand side at the rear find the Anderson connector holder box. Open the box and disconnect the battery positive (red) and battery nega­tive (black) Anderson connectors.
16. On the left hand side in the middle find the Anderson connector holder box. Open the box and disconnect the Anderson connectors.
USE CAUTION: The battery modules are heavy .
17. Slide the front battery module out and set on a tabletop.
18. Slide the rear battery module out and set on a tabletop.
19. Open the battery modules one at a time.
20. Disconnect all of the battery wires.
21. Remove all of the defective batteries and set aside.
22. Install the new batteries in the same orientation as the original batteries.
23. Verify proper polarity. Re-install the battery wires.
24. Re-install the battery modules.
25. Reconnect the Anderson connector on the left hand side. Re-inst all the Anderson connector holder box.
26. Reconnect the Anderson connectors on the right hand side. Re-inst all the Anderson connector holder box.
27. Re-install the battery retaining bracket and secure with the retaining screws.
28. Re-install the top cover and secure with the retaining screws
29. Re-install the front panel and secure with the retaining screws.
30. Re-install the Battery Pack in the rack.
16
31. Reconnect all of the battery cables.
32. Turn on all of the DC circuit breakers on the rear panel of all of the Battery Packs.
33. Properly dispose of the old batteries at an appropriate recycling facility or return them to the supplier in the packing material for the new batteries.
34. The Battery Pack is ready for normal operation.
NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the batter­ies, the user must initiate a self-test to clear the Weak/Bad Battery Alarm. To initiate a self-test see section 4 "ON / OFF/ TEST BUTTON" in the UPS's
User's Manual.
17
Chapter 6: Obtaining Service
Chapter 7: Specifications
IF THE BA TTERY PACK REQUIRES SERVICE
1. Verify there are no tripped circuit breakers and that the batteries are good. A tripped circuit breaker and defective batteries are the most common iss­ues.
2. Call your dealer for assistance. If you cannot reach your dealer , or if they cannot resolve the issue call or fax the T echnical Support department at the following numbers; Voice phone (972) 446-7363, F AX line (972) 446-901 1 or visit our Web site at www .minutemanups.com the "Discussion Board". Before calling the Technical Support Department have the following infor­mation available: a) Contact name and address. b) Where and when the unit was purchased. c) All of the model information about your unit. d) The serial number of your unit. e) Any information on the failure, including LEDs that may be illuminated
or error codes displayed.
f) A description of the protected equipment including model numbers, if
possible.
g) A technician will ask you for the above information and if possible,
help solve the issue over the phone. In the event that the unit requires factory service, the technician will issue you a Return Material Autho­rization Number (RMA #).
h) If the unit is under warranty , the repairs will be done at no charge. If
the unit is not under warranty there will be a charge for the repair.
3. Pack the unit in its original packaging. If the original packaging is no lon­ger available, ask the T echnical Support T echnician about obtaining a new set. It is important to pack the unit properly in order to avoid damage in transit. Never use Styrofoam beads for a packing material. a) Include a letter with your name, address, day time phone number,
RMA number, a copy of your original sales receipt, and a brief desc­ription of the problem.
4. Mark the RMA # on the outside of all packages. The factory cannot accept any package without the RMA # marked on the outside.
5. Return the unit by insured, prepaid carrier to:
Para Systems Inc. MINUTEMAN UPS
1809 W. Frankford Road, Suite 150
Carrollton, TX 75007
A TTN: RMA # _______
18
SYSTEM SPECIFICA TIONS
Model Number Format
BP192RTXL BP240RTXL
Rack/T ower Convertible
BA TTERY SYSTEM
Battery Type Typical Recharge T ime
Typical Battery Life System Voltage DC Current Battery Quantity Battery Part Number Battery Cable Type Battery Cable Length
Output Protection
Sealed, Non-Spillable, Maintenance Free, V alue Regulated, Lead Acid
8-hours to 90% after full load discharge
3-5 years, depending on discharge cycles and ambient temp
192VDC 240VDC
35.7 Amps 16 20
B00056
Premolded #8 AWG
21" / 533.4mm
Resettable Circuit Breaker
39.2 Amps
B00058
ENVIRONMENT AL
Operating Temperature (max)
Storage T emperature
Operating/Storage Humidity
Operating Elevation Storage Elevation
0 to 40°C (+32 to +104°F)
-15 to +50°C (+5 to +122°F) 95% Non-Condensing
0 to 2,000m (0 to +6,562 ft)
0 to 15,000m (0 to +49,213 ft)
PHYSICAL
Size - Net L X W X H
Weight - Net
Size - Shipping L X W X H
Weight - Shipping
25.2 x 17.3 x 3.5" 640 x 440 x 89 mm
80.5 lbs
36.5 Kgs
31.5 x 23.6 x 9.1" 800 x 600 x 230 mm
122.4 lbs
55.5 Kgs
23.4 x 17.3 x 5.14" 595 x 440 x 130.6 mm
134.5 lbs
61.0 Kgs
29.5 x 23.6 x 10.9" 750 x 600 x 276 mm
172.0 lbs
78.0 Kgs
REGULA TORY COMPLIANCE
Safety and Approvals EMC Verification
NOTE: These Battery Packs do not have internal chargers. The typical recharge time is based on the UPS charging the batteries.
NOTE: Specifications are subject to change without notice.
cTUVus (Conforms to UL1778 4th Edition & CSA 22.2 no. 107.3-05)
FCC Class B, CE certified
19
Chapter 8: Limited Product Warranty
Para Systems, Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a pe­riod of three years from the date of purchase. For equipment sites within the United States and Canada, this warranty covers depot rep air or replacement of defective equip­ment at the discretion of Para Systems. Depot repair will be from the nearest authorized service center. The customer pays for shipping the product to Para Systems. Para Systems pays ground freight to ship the product back to the customer. Replacement parts and warranty labor will be borne by Para Systems. For equipment located outside of the United States and Canada, Para Systems only covers faulty part s. Para Systems products that are depot repaired or replaced pursuant to this warranty shall only be warranted for the unexpired portion of the warranty applying to the original product. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.
The warranty shall be void if (a) the equipment is damaged by the customer, is improp­erly used, is subjected to an adverse operating environment, or is operated outside the limits of its electrical specifications; (b) the equipment is repaired or modified by anyone other than Para Systems or Para Systems approved personnel; or (c) has been used in a manner contrary to the product’s User's Manual or other written instructions.
Any technical advice furnished before or after delivery in regard to use or application of Para Systems’ equipment is furnished without charge and on the basis that it represents Para Systems’ best judgment under the circumstances, but it is used at the recipient’s sole risk.
EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO W ARRANTIES, EX­PRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANT ABILITY AND FIT­NESS FOR A P ARTICULAR PURPOSE. Some states do not permit limitation of implied warranties; therefore, the aforesaid limitation(s) may not apply to the purchaser.
Notes:
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL P ARA SYSTEMS BE LIABLE FOR DIRECT , INDIRECT , SPECIAL, INCIDENT AL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSI­BILITY OF SUCH DAMAGE. Specifically , Para Systems is not liable for any costs, such as; labor for on-site installation, on-site maintenance or on-site service, lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, cost of substitutes, claims by third parties, or otherwise. The sole and exclusive remedy for breach of any warranty, expressed or implied, concerning Para Systems’ products and the only obligation of Para Systems hereunder, shall be depot rep air or replacement of defective equipment, components, or parts; or , at Para Systems’ option, refund of the purchase price or substitution with an equivalent replacement product. This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
No employee, salesman, or agent of Para Systems is authorized to add to or vary the terms of this warranty.
20
21
Loading...