Minuteman 1000 VA, 3000 VA, 2000 VA Specifications

Page 1
MINUTEMAN
®
CPE
Series
On-line uninterruptible power supplies with optional extended runtime
800.238.7272 | +1 972.446.7363 www.minutemanups.com
Page 2
MINUTEMAN
Features at a Glance
Compact Tower Design to Meet Your Installation Needs UnityInputPowerFactorforMaximumEfciency Easy Maintenance and Swappable Battery Smart Battery Management Matching Battery Cabinets Complete Circuitry Protection
The CPE is a sophisticated yet affordable single-phase UPS system. It offers on-line technology and a wide input voltage range to provide a constant clean, steady sine wave to protected equipment, even without going to battery mode. It can instantly switch to battery, and its battery management system and easy, swappable battery packs make maintenance trouble free.
The CPE is Ideal for Protecting
Servers & Networks Telecommunications Equipment Industrial Equipment Medical Imaging Equipment Any Sensitive Electronic Devices
CPE
®
Series
User-Friendly Control Panel
The user-friendly display clearly communicates the UPS status, and makes diagnostics a trouble-free task. The standard com­munications software allows for easy control and shutdown of your protected equipment during a blackout, and also lets you remotely perform diagnostics, communicate to the UPS via SNMP/web/network adapter, access UPS functions through the web,andreceivealertsaboutspeciceventsviaSMSmes­sages. The free software supports Novell NetWare, Windows 95/98/2000/Me/XP/NT, Linux, and FreeBSD. Major UNIX
platforms are also available.
Communications
The CPE comes standard with shutdown software. The soft­ware gives you control of the UPS, and allows a graceful shut­down when the utility power fails, and gives you the ability to:
Remotely test major operating functions of the UPSCommunicate via SNMP/web/network (with adapter card)Access UPS functions via the webReceiveSMSalertswhenspeciceventsoccur
The unity input power factor meets today’s industry standard
forenergysavingsandlowreectedharmonics,soyougetthe
maximum protection available.
Microprocessor Control
The CPE’s advanced microprocessor control gives you greater reliability, functionality and smaller size than other designs. The systems feature high overload handling without transfer to the bypass. You are also protected in case of short circuit or over-
temperature conditions.
Easy Plug and Play Design
The CPE is easy to install. All models come standard with input cables, so all you have to do is plug the unit into your utility power and plug the equipment you want protected into the back of the unit. Turn it on and you’re done! Every CPE unit automatically senses the operating frequency, and adjusts accordingly.
A standard RS232 interface allows you to communicate with the UPS through a network or computer. The standard software is compatible with Novell NetWare, Windows 95/98, Windows NT, Windows XP, or other Windows systems, Linux, and FreeBSD.
The CPE also has SNMP adaptability through an optional SNMP card. Optional AS/400 or True Relay Interface cards also give the ability to remotely monitor the UPS using a variety of computing platforms.
Precision Power Conditioning
Tight Voltage Regulation Frequency Isolation Good Harmonic Reduction Unity Power Factor Input, with 0.5 Lagging to Unity Short Circuit Protection Transient Protection
www.minutemanups.com
800.238.7272| +1 972.446.7363
Page 3
Batteries
Batteries are the most expensive component of a UPS sys­tem. Protect them and extend their life with the Smart Battery Management System (SBMS). SBMS continuously monitors battery status and recharges whenever necessary, so you have worry-free battery power.
Matching battery cabinets make your CPE look great and allow you easy battery access.
Battery Specications
Battery Type: Sealed Lead Acid Maintenance Free
Quantity (pcs) (1kVA / 2kVA / 3kVA) 3 6 8
Voltage (VDC) (1kVA / 2kVA / 3kVA) 36 72 96
Recharge Time 8 hours to 90%
Battery Run Time Reference (Internal Battery)
Load 1 kVA 2 kVA 3 kVA
400VA / 280W 28 Min. 63 Min. 96 Min.
800VA / 560W 9 Min. 25 Min. 72 Min.
1000VA / 700W 8 Min. 17 Min. 24 Min.
1500VA / 1050W 10 Min. 18 Min.
2000VA / 1400W 7 Min. 14 Min.
2500VA / 1750W 10 Min.
3000VA / 2100W 8 Min.
Extended
batteries with
matching
cabinets can
extend run times
to virtually any
length of time.
Communications Options
True Relay Card
A 10-pin terminal is supported to offer the signals of Bypass, Utility Normal/Failure, Inverter On, Battery Low, Battery Bad, UPS Alarm, and UPS Shutdown.
AS/400 Card
A DB9 port is supported to offer the signals of Bypass, Utility Normal/Failure, Inverter On, Battery Low, and UPS Shutdown.
WEB/SNMP Card
Integrates multi-network communication protocols to enable comprehensive, easy-to-understand and secure remote monitoring and management of the UPS via the Internet.
www.sizemyups.com
800.238.7272 | +1 972.446.7363
Page 4
MINUTEMAN
Model 1000 VA 2000 VA 3000 VA
Input
Voltage (VAC) 80 - 140 Frequency 50/60 +/- 5% (Auto Sensing) Phase Single Input Power Factor Correction >0.98 (Full Load) Input Power Cord (NEMA) 5-15P 5-20P L5-30P Output Voltage (VAC) 100/110/115/120 Capacity (VA/W) 1000VA/700W 2000VA/1400W 3000VA/2100W Rated Power Factor 0.7 Lagging Load Power Factor Range 0.5 Lagging to Unity within KW Rating of Unit Wave Form Sine Wave, THD <3% (no load to full load) Voltage Regulation +/- 2% Transient Response (ms) +/- 4% Under Full Load, Change and Corrected within 60 ms Frequency Stability +/- 0.5 Hz (Free Running) Synchronization Slew Rate: 1 Hz/Sec. Max Synchronizing Window +/-5% Transfer Time 0 ms Crest Factor 3:1 Runtime (Full Load) >8 min. >7 min. >8 min. DC Start Yes Outlets (NEMA) 120 VAC 4 x 5 - 15R 4 x 5 - 15R + 2 x 5 - 15/20R 6 x 5 - 15R + 2 x 5 - 15/20R
Display
LED Indicators Utility, Battery Low, Inverter, Bypass, Test OK, Overload Fault, Load/Battery Level, and System Fault Conditions Self Diagnostics On-Demand Push Button
Alarms
Audible and Visual Line Failure, Battery Low, Transfer to Bypass, Overload, System Fault Conditions
Physical
Tower Net Dimensions (WxHxD, in.) 5.8 x 8.78 x 15.8 5.1 x 14.4 x 18.9 7.5 x 14.4 x 17.8 Tower Net Weight (lbs. / kg) 33 / 15 60 / 27 79 / 36
Environmental
Operating Temperature 0° C - 40° C Altitude 0 to +10,000 ft Humidity 30 to 90% RH Maximum, Non-condensing Noise < 45 dB at 1 meter Safety Conformance Safety Standard EN500091-1, UL1778, CSA 22.2 EMC Standard EN500091-2, EN61000-3-2, EN61000-3-3, FCC Class A Agency Marks UL, CE, cUL
®
CPE
Series Specifications
MINUTEMAN UPS / Para Systems, Inc.
1455 LeMay Drive, Carrollton, TX 75007
Phone 800.238.7272 +1 972.446.7363 Fax +1 972.446.9011
© Copyright 2006, Para Systems, Inc. Product specications are subject to change without notice. MINUTEMAN is a registered trademark and MINUTEMAN CPE is a trademark of Para Systems,
Inc.
Tower Models (Rear View)
PN-34000289 - 10-09