MiniMax AMX5000, AMX5002, AMX5001, AMX5102, AMX5101 Instruction Manual

AMX5000
Aspirating smoke detector
From production number 060608 and SW version 01.02.01
The AMX5000 aspirating smoke detector performs the task of taking continuous air samples via one or two sampling pipe net­works from a monitored area and feeding the samples to one or two smoke sensors.
The AMX5000 consists of the detector housing and one or two sampling pipe tube networks. The sampling pipes have several sampling holes whose size is such that each hole draws the same amount of air. The sampling pipes may be I-, U-, T-, H-, or E-shaped. The sampling pipes are usually symmetrically de­signed. Asymmetrical sampling pipe tube networkscan also be implemented using the “HELIOS PipeCalc” calculation soft­ware.
Description
You find all necessary Information for setting up AMX5000 fire alarm systems in the short instruction; for the complete information and specifications refer t th
e Technical Description AMX5000, FHB 34 (908146)
Integrated in the detector housing is a high-speed fan which, in conjunction with the sampling pipe, ensures uninterrupted air supply to the detector housing. Airflow monitoring detects any block-ages or breaks in each of the sampling pipe networks.
The AMX5000 is available in four versions:
AMX5001 for 1 sampling tube, and 1 smoke sensor
AMX5002 for 2 sampling tubes, and 2 smoke sensors
AMX5101 for 1 sampling tub
AMX5102 for 2 sampling tubes, and 2 smoke sensors
The AMX5000 can be equipped with the following smoke sen­sor types:
OMX5005 Sensitivity range 0.5%/m to 10%/m
OMX5010 Sensitivity range 0.1%/m to 10%/m
OMX5020 Sensitivity range 0.02%/m to 10%/m
The AMX5000 aspirating smoke detector has four slots for ex­pansion modules. The following modules can be added:
KMX5005 RK Relay Interface Module with 5 relays (max.
MMX5005 Memory module
Other In preparation (interface module) The AMX5000 can be linked to a higher level FACP by means
of relays. The AMX5000 can be connected to a fire alarm system by
using potential free contacts. Integration in the System FMZ5000 Loop Ap is possible by mo-
dules. Displaying status and control of the AMX device can thus be performed directly from the FACP.
without smoke level indicator;
without smoke level indicator;
e, and 1 smoke sens
with smoke level indicator;
with smoke level indicator.
(0.15%/ft to 3.15%/ft)
(0.03%/ft to 3.15%/ft)
(0.006%/ft to 3.15%/ft)
2 units);
or
Short instruction
Fig. 1 AMX5102
A further expansion option is the KMX5005 RK Relay Interface Module. This module enables the availability of all three pre-si­gnal levels as well as the states “smoke sensor dirty” and “LS­Ü blockage” as relay contacts. The relays are also freely confi-
o
gurable via the HELIOS Config configuration software. The MMX5005 Memory module serves to record operating data The AMX5000 aspirating smoke detector can be used for:
Equipment monitoring:
• switch cabinets, etc.
Space surveillance:
• high-rack storage buildings, hollow floors, protection of cul­tural objects, transformer stations, prison cells, etc.
The AMX5000 is also deployed in areas where conventional point type detectors are used. The local provisions and regula­tions must be observed from case to case.
The response behavior of the AMX5000 has been tested in compliance with EN 54-20, Class A, B and C (or NFPA 72).
When setting up AMX5000 fire alarm systems, the in­formation and specifications in “Technical Descripti- on AMX5000” must be observed and adhered to. This includes among others:
General
Planning Section 4
Mounting Section 5
Installation Section 6
Commissioning Section 7
EDP systems, electrical distributors,
EDP rooms, clean rooms, warehouses,
Section 1
Opening the detector housing
Press the rotary snap locks firmly with the screwdri­ver (min. No. 5) toward the housing base and then turn 90°. The position of the lock slit shows the cur­rent state:
approx. 45° angled toward detector housing corne = closed
approx. 45° angled toward detector housing edge
= open The rotary snap locks must snap into place. The housing cover (control unit) is connected to the Main Board
by a flat cable. Make sure that when the housing cover is lifted away the flat cable does not become damaged.
.
r
MINIMAX GmbH & Co. KG Industriestrasse 10/12 23840 Bad Oldesloe Germany FHK34, 908143 1 / 10
Form No. F_102011
Short instruction
Bottom part of detector box
3 x M20 cable screw unions Reserve openings for cable screw unions
1 x M20 / 1 x M25
Fan unit
Air outlet
Main Board Device termina ls Indicators and control elements
for co mmissioning USB interface
4 x slots for expansion modules Internal connection elements Airflow sensor s
2 x mounting p o ints for op e ned ho u s ing cover ( commiss ioning/ m aintenance)
Smoke sensor chamber I
4 x mounting points closed housing c over
4 x fastening holes Connection Connection for sampling pipe I
Connection
Smoke sensor chamber II
MAIN BOARD device connections
The electrical connection is implemented by means of plug-in terminals.
Terminal Signal
1 +10.5 to +30 VDC 20 V 3 +10.5 to +30 VDC 40 V 5 + Supply (for OC consumers) 6 Output fault, OC (all events) 7 Output alarm I, OC 8 Output alarm II or freely programmable, OC
9Free 10 Rel. 1 „(NO)“ Fault 11 Rel. 1 „NC“ 12 Rel. 1 „COM“ 13 Rel. 2 „NO“ 14 Rel. 2 „NC“ 15 Rel. 2 „COM“ 16 Rel. 3 „NO“ 17 Rel. 3 „NC“ 18 Rel. 3 „COM“ 19 External reset input + 20 External reset input ­21 + F 22 DF 23 ­24 + S 25 DS 26 -
Main power supply line
Redundant supply line
Contact (te. 10/12) closed in idle state
Alarm I
Alarm II or freely programmable
Optocoupler input
Connection for modules (available later)
Connection for modules (available later)
for sampling pipe II
MAIN BOARD internal connections
Terminal Signal
MOT / M- Fan - (black wire)
MOT / T Fan tacho signal (white wire)
MOT / M+ Fan + (red wire)
OEM2 / Al-
OEM2 / Al+
OEM2 / St-
Optocoupler inputs for smoke sensor/ detector 2
OEM2 / St+
OEM1 / Al-
OEM1 / Al+
OEM1 / St-
Optocoupler inputs for smoke sensor/ detector 1
OEM1 / St+
Terminal assignmentsKMX5005 RK
For the terminal assignment of the KMX5005 RK please refer to the corresponding data sheet FHK 34.1 (908144).
Wiring principle
Examples of and information about wiring are found in Technical Description AMX5000, FHB 34 (908146), section 6.
Deploying smoke sensors
Smoke sensors are not fitted when the AMX5000 is delivered. They are application specific (according to required sensitivity range), purchased from the manufacturer and installed after the detector housing is mounted (see Fig. 3).
• The smoke sensors should always be removed from their protective packaging just before deploy­ment in the detector housing.
• Depending on the situation (e.g. if there is a long time between mounting and commissioning or if the environment is very dusty due, for example, to construction), the smoke sensors should be ins­talled just before commissioning the AMX5000.
• Before installing the smoke sensors, check that the protective screens against insects are properly fitted to the air inlet and outlet in the smoke sensor chambers.
• The smoke sensor chamber must be absolutely free of dirt and dust. Any waste or other materials
resultingfrom mounting the detector housing must
be removed.
The installation position of the smoke sensors depends on the particular smoke sensor chamber (I or II). The connectors of the smoke sensors are oriented toward the outside of the AMX housing. Incorrect installation positioning is prevented by the anti-twist rib on the smoke sensor housing.
The smoke sensors are fastened with the two lock clamps in the AMX housing. The electrical connection to the Main Board is accomplished with the supplied ribbon cable.
The smoke sensor chamber II on the AMX5001 and AMX5101 (o
nly one smoke sensor) remains open (insect protection
screens and lock clamps are not fitted, air channels
are closed).
2 / 10 FHK34, 908143 AMX5000
Short instruction
Anti-twist rib
Flat cable
Smoke sensor chamber I Smoke sensor chamber II
Smoke sensor I
Smoke sensor II
Connection for smoke sensor I / II
AMB 35
Insect protection scree
Lock clamps
IIII
Displays on the Main Board
On the Main Board there is a 3-digit segment display which can have the following outputs and displays:
flashing point and AL = Autolearning running;
flashing point and point continuously lit = day/night control
II
active;
switch setting E = event memory (99 events E01 to E99), for more information see FHB 34 (908142), section 8.5.3;
switch setting F = operating software version (firmware), for more information see FHB 34 (908142), section 7.3.6;
pushbutton “UP” = the set configuration (A11 to C32,W01 to W48, X01 to X03), see also “Programming”;
switch setting V = airflow values (airflow rate), for more in­formation see Technical Description, section 7.6.1
Fig. 3 Deploying the smoke sensors
Displays on the control unit
Several LEDs on the control unit indicate the current state of the AMX5000. The table below lists only the states for the AMX5001 and AMX5101 (one smoke sensor / one sampling pipe). Except for the operation display, for the AMX5002 and AMX5102 (I and II)
Function / state
green red yell. yell. yell.
System off (no voltage) System inactive (external reset) Smoke sensor off (from FACP) Idle state
Blockage / pipe breakage, delay time running
Blockage / pipe breakage, fault triggered Fan tacho signal lacking On On
Fault triggered Pre-signal 1 (AMX5001/ 5002) Pre-signal 2 (AMX5001/ 5002) Pre-signal 3 (AMX5001/ 5002)
Smoke level 1–10 (AMX5101/
5102)
Pre-signal 1, 2, 3 (AMX5101/
5102)
Alarm Dusty smoke sensor Dirty smoke sensor Smoke sensor fault
Additional for AMX5101 and AMX5102

No fault triggered (triggers only after the delay time
expires  “Fault” LED display continuously lit).
The LED of the respective smoke level 1–10 (cor-
responds to 10–100% of alarm threshold) is conti-
AMX5000 FHK34, 908143 3 / 10
nuously lit when exceeded. If a pre-signal is programmed on this level, the begins to flash (default: VS 1 = level 3, VS 2 = level 5, VS 3 = level 7).
T = Flashing indicator; ½s cycle / 1s cycle / 2s cycle
the displays are doubled .
Operation
Alarm
Fault
Det. dusty / dirty
On On
1 1
/2 T /2 T
On On 1 T
On On
On On On 2 T On 1 T
1
On
/2 T
On On On 1 T
On On On 1 T On
1
/2 T
On On
LED subsequently
Smoke level
Programming
The AMX5000 has several switch settings which are configu­red with permanently assigned parameters:
normative system limits according to EN 54-20, Class A to C (or NFPA 72), settings A11 to C32;
non-normative system limits, settings W01 to W48;
configurable settings for saving settings after using "HELI-
OS PipeCalc" and/or changing the device configuration via the “HELIOS Config” configuration software, X01 to X03.
The parameters are configured post-factory with de­faultstates and values so that the triggering proper­ties comply with EN 54-20 (NFPA 72). Changing the parameters may result in non-compliance with EN 5
the AMX5000 via“HELIOS Config” may be performed
4-20 (NFPA 72). Any adjustments or m
only by the manuf
acturer or by persons under
supervision of and trained by the manufacturer.
Switch settings on the Main Board
Pos. Range / Display Purpose
Normative system limits
A A11 / A12
b b11 / b12 / b21 / b22
C11 / C12 / C21 / C22 /
C
C31 / C32 E01 to E99
E
G00 to G99
FF00 to F99 (3 x)
oo00
Y05 to Y99 / M01 to M12
T
d01 to d31 / H00 to H23 M00 to M59
UU01 Execute initial reset V V01 / V02, each000 to 255
WW11 to W48
XX01 to X03
The table lists only the available switch settings. Information about entry procedure is found in Tech­nical Description FHB 34 (908142), section 8.3.
according to EN 54-20, Class A (or NFPA 72) Normative system limits in compliance with EN 54-20, Class B (or NFPA 72) Normative system limits in compliance with EN 54-20, Class C (or NFPA 72) Event memory E01 – E99
Event group G00 – G99
Display of operating soft­ware version (firmware) Log off expansion modules (optional modules)
Setting the date Setting the time
Output airflow rate in % Pipe I (=V01), pipe II (=V02) Non-normative system limits Configurable switch set­tings
odifications to
the
Short instruction
S
ystem limits without “HELIOS PipeCalc”calculation
The system limits apply to planning without the“HELIOS Pipe­Calc” calculation software. There are two areas with the fol­lowing meaning:
Normative system limits compliant to EN 54-20, Class A to C (or NFPA 72), switch settings A11 to C32;
Non-Normative system limits, switch settings W01 to W48.
Normative system limits
Switch settings A11 to C32 have configured values which are necessary for alarm response sensitivity and airflow monitoring compliance with EN 54-20 Class A to C (or NFPA 72). The switch setting designation is deciphered as follows:
First figure Response class A, b, C compliant with EN
Second figure System limit 1, 2, 3 (pipe topology);
Third figure Number of pipe networks 1, 2 on the AMX.
Example: b22 Response class b / system limit 2 / 2 pipe networks.
54-20 (or NFPA 72);
Non-normative system limits
Switch settings W01 to W48 contain system limits which fulfill
only
the alarm response sensitivity for EN 54-20 Class A to C (or NFPA 72) but not monitoring. Since these are identical to system limits A11 to C32 concerning pipe topology (pipe network length, number of sampling holes), switch settings W01 to W48 are also included in the tables below in section 4.4.4.3. Additional information about switch settings W01 to W48 concerning number of pipe networks and airflow monitoring can be found in Technical De­scription FHB 34 (908142), section 4.4.4.4.
Switch settings W01 to W48 may be used only after consulting with the manufacturer. The configured va­lues theycontain concerning airflow monitoring are
not
tested inaccordance with EN (or NFPA 72).
Further information about using the system limits table is found in Technical Description FHB 34
(908142), sections 4.4.4.3 and 4.4.4.4.
the normative limits concerning airflow
System limits table for planning without “HELIOS PipeCalc” calculation EN 54-20 compliance, Class A (highly sensitive) (or NFPA 72)
Shape
System limit
I 1 A11 A12 W01 – W04 W05 – W08 20 0.03 (0.01) --- 50 m (164 ft) 1 – 7 50 m (164 ft)
U / T 1 A11 A12 W01 – W04 W05 – W08 20 0.03 (0.01) 3’-3”– 65’-6” (1 – 20 m) 40 m (131 ft) 1 – 4 80 m (262 ft)
H 1 A11 A12 W01 – W04 W05 – W08 20 0.03 (0.01) 3’-3”– 65’-6” (1 – 20 m) 40 m (131 ft) 1 – 2 100 m (328 ft) E 1 A11 A12 W01 – W04 W05 – W08 20 0.03 (0.01) 3’-3”– 65’-6” (1 – 20 m) 40 m (131 ft) 1 – 3 100 m (328 ft)
EN 54-20 compliance, Class B (sensitive) (or NFPA 72)
1 b11 b12 W09 – W12 W13 – W16 20 0.09 (0.03) --- 50 m (164 ft) 1 – 7 50 m (164 ft)
I
2 b21 b22 W17 – W20 W21 – W24 20 0.06 (0.02) --- 70 m (229 ft) 5 – 9 70 m (229 ft) 1 b11 b12 W09 – W12 W13 – W16 20 0.09 (0.03) 3’-3”– 65’-6” (1 – 20 m) 40 m (131 ft) 1 – 3 80 m (262 ft)
U / T
2 b21 b22 W17 – W20 W21 – W24 20 0.06 (0.02) 3’-3”– 65’-6” (1 – 20 m) 55 m (180 ft) 3 – 5 110 m (360 ft) 1 b11 b12 W09 – W12 W13 – W16 20 0.09 (0.03) 3’-3”– 65’-6” (1 – 20 m) 35 m (114 ft) 1 – 2 140 m (459 ft)
H
2 b21 b22 W17 – W20 W21 – W24 20 0.06 (0.02) 3’-3”– 65’-6” (1 – 20 m) 455 m (147 ft) 2 – 3 140 m (459 ft) 1 b11 b12 W09 – W12 W13 – W16 20 0.09 (0.03) 3’-3”– 65’-6” (1 – 20 m) 40 m (131 ft) 1 – 2 120 m (393 ft)
E
2 b21 b22 W17 – W20 W21 – W24 20 0.06 (0.02) 3’-3”– 65’-6” (1 – 20 m) 50 m (164 ft) 2 – 3 140 m (459 ft)
EN 54-20 compliance, Class C (standard) (or NFPA 72)
1 C11 C12 W25 – W28 W29 – W32 05 0.8 (0.266) --- 40 m (131 ft) 1 – 5 40 m (131 ft)
I
2 C21 C22 W33 – W36 W37 – W40 10 0.35 (0.116) --- 80 m (262 ft) 3 – 9 80 m (262 ft) 3 C31 C32 W41 – W44 W45 – W48 10 0.13 (0.043) --- 110 m (360 ft) 7 – 16 110 m (360 ft) 1 C11 C12 W25 – W28 W29 – W32 05 0.8 (0.266) 1 – 20 m (3’-3”– 65’-6”) 30 m (98 ft) 1 – 3 60 m (196 ft)
U / T
2 C21 C22 W33 – W36 W37 – W40 10 0.35 (0.116) 1 – 20 m (3’-3”– 65’-6”) 60 m (196 ft) 3 – 5 120 m (393 ft) 3 C31 C32 W41 – W44 W45 – W48 10 0.13 (0.043) 1 – 20 m (3’-3”– 65’-6”) 70 m (229 ft) 5 – 9 140 m (459 ft) 1 C11 C12 W25 – W28 W29 – W32 05 0.8 (0.266) 2 C21 C22 W33 – W36 W37 – W40 10 0.35 (0.116)
H
3 C31 C32 W41 – W44 W45 – W48 10 0.13 (0.043) 1 C11 C12 W25 – W28 W29 – W32 05 0.8 (0.266) 1 – 20 m (3’-3”– 65’-6”) 30 m (98 ft) 1 – 2 90 m (295 ft)
E
2 C21 C22 W33 – W36 W37 – W40 10 0.35 (0.116) 1 – 20 m (3’-3”– 65’-6”) 50 m (164 ft) 2 – 3 150 m (492 ft) 3 C31 C32 W41 – W44 W45 – W48 10 0.13 (0.043) 1 – 20 m (3’-3”– 65’-6”) 60 m (196 ft) 3 – 6 180 m (590 ft)
to EN 54-20
(or NFPA 72)
Switch setting
1 tube 2 tube 1 tube 2 tube
Switch setting
Non-normative
Smoke sensor
type OMX50xx
% / m (% / ft)
Alarm threshold
1 – 25 m (3’-3”– 82’­1 – 25 m (3’-3”– 82’­1 – 25 m (3’-3”– 82’-
Length from AMX
to the last
T-piece/cross
sampling hole
Max. length from
AMX to the farthes
1
35 m (114 ft) 1 – 2 140 m (459 ft)
/4”)
1
45 m (147 ft) 2 – 3 180 m (590 ft)
/4”)
1
60 m (196 ft) 3 – 5 200 m (656 ft)
/4”)
branch
per pipe network
holes per sampling
Number of sampling
the sampling pipe
Max. total length of
(smoke sensor)
4 / 10 FHK34, 908143 AMX5000
Short instruction
Sampling holes for planning without “HELIOS PipeCalc”-calculation
The tables below show the respective hole diameters for the numbers in Fig. 4 as a function of the number of sampling holes per sampling branch.
per sampling branch
Number of sampling holes
1 5.0 2 4.0 5.0
3 4.0 4.0 5.0 4 3.5 3.5 4.0 5.0 5 3.5 3.5 3.5 4.0 5.0 6 2.5 2.5 2.5 2.5 3.0 5.0 7 2.5 2.5 2.5 2.5 2.5 2.5 5.0 8 2.5 2.5 2.5 2.5 2.5 2.5 2.5 5.0
9 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 5.0 10 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 3.0 7.0 11 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 4.0 7.0 12 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 4.0 7.0 13 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 4.0 7.0 14 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 2.5 4.0 7.0 15 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.5 2.5 4.0 7.0 16 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.5 4.0 7.0
I-shaped sampling pipes
Hole diameter in mm for the sampling hole number from AMX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
U/T-shaped sampling pipes
Hole diameter in mm for the sampling hole
branch
Number of
per sampling
sampling holes 1
2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
5.0
4.0 5.0
4.0 4.0 5.0
4.0 4.0 4.0 5.0
4.0 4.0 4.5 5.0 6.5
3.0 3.0 3.5 3.5 4.0 6.5
2.5 3.0 3.0 3.5 3.5 4.0 6.5
2.5 2.5 3.0 3.0 3.5 3.5 3.5 7.0
2.5 2.5 3.0 3.0 3.5 3.5 3.5 3.5 7.0
number from AMX
H/E-shaped sampling pipes
Hole diameter in mm for the sampling hole
branch
Number of
per sampling
sampling holes 1 5.0
2 4.0 5.0 3 4.0 4.0 5.5 4 3.0 3.0 3.5 5.5
6 (E-shaped only) 2.5 2.5 3.0 3.0 3.0 6.0
5 2.5 3.0 3.0 3.0 6.0
1 2 3 4 5 6
number from AMX
AMX5000 FHK34, 908143 5 / 10
Short instruction
Configuration options, Table A:
The following criteria can be set for each smoke sensor / sampling pipe. Also, the criteria for day/night control can be separately set.
Configuration changes are saved on one of the freely programmable switch settings X01 to X03.
Sector
• Parameter
Alarm
• Alarm threshold (dependent on smoke sensor type and response class according to EN 54-5 or NFPA 72)
• Smoke level average value formation 4 s 1 – 10 s 1 s X01 – X03
• Alarm delay 2 s 0 s – 60 s 1 s X01 – X03
• Alarm self-hold On On/Off X01 – X03
Pre-signal
• Pre-signal 1 On/Off On On/Off X01 – X03
• Pre-signal 2 On/Off On On/Off X01 – X03
• Pre-signal 3 On/Off On On/Off X01 – X03
• Pre-signal 1 (100% = alarm threshold) 30% 10 – 90% 10% X01 – X03
• Pre-signal 2 (100% = alarm threshold) 50% VS 1 + 10 – 90% 10% X01 – X03
• Pre-signal 3 (100% = alarm threshold) 70% VS 2 + 10 – 90% 10% X01 – X03
• Pre-signal delay (VS 1 – VS 3) 2 s 0 s – 60 s 1 s X01 – X03
• Pre-signal self-hold Off Off/On X01 – X03
Smoke sensor dust/dirt
• Smoke sensor dust On/Off On On/Off X01 – X03
• Smoke sensor dirt On/Off On On/Off X01 – X03
• Dust threshold (% of Al) 50% 5 – 60% 5% X01 – X03
• Dirt threshold (% of Al) 75% 65 – 90% 5% X01 – X03
• Dust self-hold On On/Off X01 – X03
• Dirt self-hold On On/Off X01 – X03
• Fault delay of smoke sensor 30 s 0 s – 60 s 1 s X01 – X03
Airflow monitoring
• LS-Ü blockage On/Off On On/Off X01 – X03
• LS-Ü pipe breakage On/Off On On/Off X01 – X03
• LS-Ü sensitivity ±20% ±10 – ±70% ± 10% X01 – X03
• LS-Ü average value formation 20 s 1 – 30 s 1 s X01 – X03
• LS-Ü delay time 300 s 2 min – 60 min 10 s / 1 min X01 – X03
The default settings of the LS-Ü sensitivity and LS-Ü delay time correspond to the above specifications for switch
settings A01 to C32. Increased values are configured for switch settings W01 to W48; these are not NFPA 72 compliance (see Technical Description FHB 34 (908142), section 4.4.4.4).
Default Setting
C11 / C12
Range
0.02 – 10%/m (0.006 –3 .15%/ft)
0.1 – 10%/m (0.03 – 3.15%/ft)
0.5 – 10%/m (0.15 – 3.15%/ft)
Resolution /
Levels
0.001%/m
(0.0003%/ft)
Saving after
change
X01 – X03
tested for EN or
Configuration options, Table B:
The following criteria apply to the entire AMX5000. Saving a configuration after changes is performed in the context of the adaptations in Table A on one of the freely programmable switch settings X01 to X03.
Sector
• Parameter
Autolearning
• Autolearning On/Off Off On X01 – X03
• Autolearning duration 3 days 1 min to 14 days min, h, days X01 – X03
• Autolearning factor (of measured Al threshold) 1.5 1.1 – 10 x X01 – X03
Day/night control
• Day/night control On/Off Off On/Off X01 – X03
• Day start time 06:00 00:00 – 24:00 15 min X01 – X03
• Night start time 20:00 00:00 – 24:00 15 min X01 – X03
General faults
• Lithium battery / clock fault On On/Off X01 – X03
Ventilator
• Fan speed Level III Level I to V 1 X01 – X03
6 / 10 FHK34, 908143 AMX5000
Default Setting
Range
Resolution /
Levels
Saving after
change
Short instruction
Configuration options, Table C:
Independent configurations. These can be changed independently of the switch settings in the AMX5000.
Sector
Time
• Year, month, day, hour, minute --- Minutes - year
Relay / OC output / reset button
• Relay 3 and OC module 3, MAIN BOARD Alarm II
• Relay 1, 1st KMX5005 RK Pre-signal 1 smoke sensor I
• Relay 2, 1st KMX5005 RK Pre-signal 2 smoke sensor I
• Relay 3, 1st KMX5005 RK Pre-signal 3 smoke sensor I
• Relay 4, 1st KMX5005 RK Smoke sensor I dirty
• Relay 5, 1st KMX5005 RK Sampling tube I pipe blockage
• Relay 1, 2nd KMX5005 RK Pre-signal 1 smoke sensor II
• Relay 2, 2nd KMX5005 RK Pre-signal 2 smoke sensor II
• Relay 3, 2nd KMX5005 RK Pre-signal 3 smoke sensor II
• Relay 4, 2nd KMX5005 RK Smoke sensor II dirty
• Relay 5, 2nd KMX5005 RK Sampling tube II pipe blockage
• Reset button On/Off On On/Off
• Start initial reset --- On/Off
Default Selection
According to
“Configuration options
relay allocation”
Relay allocation configuration options:
The following criteria can be programmed on a max. of 11 relays (1 Main Board unit on AMX5001and AMX5101, 6 units on 1st KMX5005 RK, 5 units on 2nd KMX5005 RK):
Smoke sensor I / LS-Ü I Smoke sensor II / LS-Ü II General
Smoke sensor I alarm Smoke sensor II alarm Fan fault Pre-signal 1 smoke sensor I Pre-signal 1 smoke sensor II Operating voltage fault Pre-signal 2 smoke sensor I Pre-signal 2 smoke sensor II Initial reset fault Pre-signal 3 smoke sensor I Pre-signal 3 smoke sensor II Lithium battery / clock fault
Smoke sensor I dusty Smoke sensor II dusty
Smoke sensor I dirty Smoke sensor II dirty Smoke sensor I fault Smoke sensor II fault
Sampling tube I blockage Sampling tube II blockage
Sampling tube I pipe breakage Sampling tube II pipe breakage
The criteria can also be allocated with the or
function (example: smoke sensor dust or dirt together on one relay).
AMX5000 FHK34, 908143 7 / 10
Short instruction
Commissioning
When commissioning the AMX5000, it is necessary to perform an initial reset in order to collect basic data (e.g. connected sampling pipe, motor data). An initial reset also performs an au­tomatic adjustment of the airflow monitoring on the connected sampling pipe(s).
If the AMX5000 is operated within the system limits without “HELIOS PipeCalc” calculation, commissioning with the “Ea- syConfig” method can be carried out directly on the AMX5000.
For projects in which the “HELIOS PipeCalc” calculation soft­ware was used or in which customer-specific adaptations have to be made in the device configuration, the “HELIOS Config” configuration software has to be used.
Starting up
Before the AMX5000 is switched on, it is absolutely necessary that all of the required measures have been performed (see FHB 34 (908142), section 7.1).
• sampling pipe correctly mounted and connected to the AMX;
• smoke sensors and expansion modules installed in
the AMX and connected;
• isolation strip on the Lithium battery (MAIN
BOARD) removed.
Sequence and procedure for starting up:
1. Switch on supply voltage (FACP); while the fan accelerates
incrementally to its final speed (takes about 100 s), the next procedure can be carried out. The system is immediately
armed for alarm.
2. “EasyConfig”: select necessary switch setting for operati-
on according to “System limit table” (e.g. “b2”) see “Re-programming”.
- or: “HELIOS Config”: after adapting the configuration (alarm
threshold according to “HELIOS PipeCalc” and other crite­ria in Tables A and B), select switch setting “X01”, “X02" or “X03”.
3. Set date and time via MAIN BOARD with “EasyConfig” or from “HELIOS Config” (adoption by PC).
4. Following a minimum waiting time of 5 min after swit­ching on, an initial reset must be performed (possible only via MAIN BOARD) see “Initial reset”.
5. The AMX5000 is now ready for operation.
Re-programming
Example: Response class B, system limit 2, AMX5102 (2 sam­pling tubes), required switch setting b22.
Measure
Press the "UP”
6.
button Press "UP”
7.
twice until dis­play shows b
Press the "OK"
8.
button Press "UP”
9.
until display shows b22
Press the "OK"
10.
button Check: Press
11.
the "UP” button
Display / indication
Switch settings W01 to W48 may be used only after consulting with the manufacturer. The configured values they contain concerning airflow monitoring are not
tested in accordance with EN (or NFPA).
Flashing C32
In sequence:
A / b
b11
In sequence:
b11 / b12 / b21 / b22
Flashing b - - (approx. 4 x)
Flashing b22
Procedure Remark
• Display of the default
setting
• Display switch setting
group b
• Display of the smallest possible setting in group b
• Display of the possible settings in group b
• New setting is pro­ grammed
• Display of the new set­ ting
Initial reset
Measure
Press the "UP”
1.
button Press "UP”
several times
2.
until display shows U
Press the "OK"
3.
button Press the "OK"
4.
button again
5. Wait
Display / indication
Before performing an initial reset after switching on the AMX5000, a waiting time of at least 5 min must be observed.
Flashing C32 or other
In sequence:
A to U
U01 • Display initial reset On
Flashing U - -
(5 to max. 120 s)
Flashing point (watchdog indi­cator)
Procedure Remark
• Display of the default setting or the installa­ tion-specific switch set­ ting
• Display of the switch setting group U
• Initial reset runs
• Initial reset completed
8 / 10 FHK34, 908143 AMX5000
Measurements / commissioning protocol
Carry out the following measurements:
• Measure operating voltage on terminals 1 (+), 2 (-) (if redun­dant supply, then also terminals 3 & 4) target value = 12.3 to 13.8 VDC (in 12 VDC operation) or 21.6 to 27.6 VDC (in 24 VDC operation).
• Airflow values in switch settings V (see Technical Description FHB 34 (908142), section 7.6.1)
• The commissioning protocol is like a persona l history of the AMX5000 and should therefore be filled out conscientiously and completely and stored in the AMX5000. If required, a copy can be made and stored in the installation dossier.
Short instruction
Checking fault and alarm actuation
Test Procedure Action
Block or switch off fire control installations and remote alarms on the superordinate FACP.
• As soon as the resul­ting change in the air­flow is exceeded by ±20% (can be che­cked via the switch setting V) the “Fault” LED begins to flash.
• When the LS-Ü delay expires (300 s), the AMX triggers a fault fault on FACP
• AMX actuates an alarm alarm on FACP; correct alarm actuati­on checked (zone and range actuation) on the FACP
• If there are pre-signals they are also actua­ted.
/ .
/ .
Check airflow monitoring
Check alarm actuation
Tape sampling holes (adhesive tape); number depends on the pipe configuration
Subject mainte­nance sampling hole or sampling hole to smoke.
Between each check the AMX5000 must be reset (cau-
tion: a reset on the AMX does not reset the FACP).
For the AMX5002 and AMX5102, checks have to be car-
ried out for both sampling pipes.
Article numbers / spare parts
Brief description Article number
Aspirating smoke detector AMX5001 908095 Aspirating smoke detector AMX5002 908096 Aspirating smoke detector AMX5101 908097 Aspirating smoke detector AMX5102 908098 Sm
oke s
ensor OMX5005,
Smoke sensor OMX5010; ( Smoke sensor OMX5020; ( Relay Interface Module KMX5005 RK 908103 Memory module MMX5005 908104 SD memory card (min. 1 GB) USB cable, 4.5 m (14’ – 9”) CD with “HELIOS Config” configuration soft­ware CD with “HELIOS PipeCalc” calculation soft ware Aspirating fan unit AMX5000, complete Airflow sensor AMX5000 Lithium battery Cable screw union M20 Cable screw union M25 Universal Module Support AMX5000 Technical Description AMX5000 Material for the sampling pipe Commissioning protocol AMX5000 Short instruction KMX5005 RK data sheet Short instruction MMX5005 data sheet Installation instructions aspirating fan unit AMX5000
0.5%/m –10%/m
(
0.15%/ft – 3.15%/ft
0.1%/m – 10%/m
0.03%/ft – 3.15%/ft
0.02%/m – 10%/m
0.006%/ft – 3.15%/f t
)
)
)
-
FHB 34 / 908142
FHK 34.2 / 908145
FHK 34.1 / 908144
908099
908100
908101
908105
Dimensional drawing
Fig. 5 Detector housing AMX5000 dimensional drawing
AMX5000 FHK34, 908143 9 / 10
Short instruction
Technical data
Type AMX5000 Supply voltage range 10.5 to 30 VDC
Max. current consumption, measured in 12 VDC operation 24 VDC operation Typical Fan speed level V and at
AMX5001 Idle/fault approx. 575 approx. 340 approx. 260 mA
Alarm I approx. 660 approx. 390 approx. 295 mA
AMX5002 Idle/fault approx. 645 approx. 380 approx. 290 mA
Alarm I + II approx. 745 approx. 450 approx. 350 mA
AMX5101 Idle/fault approx. 575 approx. 340 approx. 260 mA
Alarm I approx. 695 approx. 405 approx. 310 mA
AMX5102 Idle/fault approx. 645 approx. 380 approx. 290 mA
Alarm I + II approx. 820 approx. 490 approx. 385 mA Additionally with 1 KMX5005 RK units approx. 15 approx. 10 approx. 7 mA Additionally with 2 KMX5005 RK units approx. 30 approx. 20 approx. 14 mA Additionally with MMX5005 approx. 25 approx. 15 approx. 10 mA
Switch-on current peak (caused by EMC protection elements on the AMX supply input) approx. 5 A
Sampling pipe length See FHB 34 (908142), section 4.2.1 Sampling pipe Ø, typical (inner/outer)
Max. number of sampling holes See FHB 34 (908142), section 4.2.1 Sampling hole diameter Response range EN 54-20, Class A, B, C (NFPA 72) Protection type acc. to IEC 529 / EN 60529 (1991) 54 IP Ambient conditions acc. to IEC 721-3-3 / EN 60721-3-3 (1995) 3K5 / 3Z1 Class
Extended ambient conditions:
• Detector housing temperature range
• Sampling pipe temperature range
• Max. approved temperature fluctuation in detector housing and sampling pipe operation
• Max. storage temperature deflector housing (no condensation)
• Ambient pressure difference of detector housing to sampling pipe (sampling holes) Must be identical
• Detector housing humidity ambient condition (transient without condensation) 95 % rel.
• Humidity ambient temperature (continuous) 70 % rel.
Max. loading capacity relay contact 50 VDC
Max. loading capacity per open collector output 100 mA Plug-in terminals
Cable entry for cable Ø Ø 5 – 12 (M20) / Ø 9 – 18 (M25) mm Noise level (at fan speed level III) 43 dB (A) Housing material ABS blend, UL 94-V0 Housing color Grey 280 70 05 / anthracite violet 300 20 05 RAL Approval G208193 EN 54-20
Dimensions (W x H x D) Weight (AMX5102, incl. expansion modules)
10.5 VDC
18 VDC
Ø 2 / 2.5 / 3 / 3.5 / 4 / 4.5 / 5 / 5.5 / 6 / 6.5 / 7
24 VDC
for max. 1
(0.001
Ø (20 / 25
Ø 25/32 / 1
-30 – +60
(-4 – +140
-30 – +60
(-4 – +140
20
(68
-30 – +70
(-4 – +158
(265 x 397 x 146)
10-7/16 x 15-5/8 x 5-3/
max. 3850
(max. 135
1A
30 W
2.5 12
4
Current consumption at maximum permitted voltage drop in the electrical installation (guideline value for calculating
the conductor cross-section).
May cause an immediate actuation of the protection circuit in power supplies with overload protection circuits (pri-
marily in devices with no emergency power supply and output current of < 1.5 A).
Lower or higher temperature ranges are possible after consulting with the manufacturer. The manufacturer must be
consulted if deployment is to be in the condensation range.
ms
mm
inch)
mm
°C
°F)
°C
°F)
°C
°F)
°C
°F)
mm
ga
mm
inch)
oz)
s)
2
g
10 / 10 Second edition: 02.09.2009 Kro FHK34, 908143 © Copyright by Minimax AMX5000 The product specifications contained in this document are subject to change without notice.