Minib NKF1, NKF2, NUF1, NUF2, NMF1 Installation Manual

...
INSTALLATION GUIDE – WALL-MOUNTED CONVECTORS
1. UNIT DESCRIPTION
A wall-mounted heating unit. Models NUF1, NUF2, NMF1, NWF1, NWF2, NPF1, and NPF2 use the natural convection heating principle, models NKF1 and NKF2 are equipped with a fan for forced convection. Since the heater uses physical laws of thermodynamics it represents one of the most effi cient methods of interior heating.
Benefi ts of heating convectors:
High output Silent operation or low noise for units with fan Lightweight compared to heating units with similar
output which use radiation principle Low hot water consumption Short response time Design Minimum requirements for operation and mainte-
nance A great advantage of these convectors is the small
required installation space. This is benefi cial par-
ticularly in a situation where the heating units are
used in interior renovation and replacement of old
heaters with new ones and in situations where suf-
fi cient heating output is required.
3. TECHNICAL PARAMETERS
Use: Convectors without fan are designed for dry
and wet environment, and convectors with a fan
are designed for dry environment only.
Maximum operating pressure: 1 MPa.
Maximum operating temperature: 110 °C.
Operating medium: Water. It is not allowed to use a
medium other than water. Water may not be mixed
with other substances, such as antifreeze fl uids!
Environment: interiors with temperatures ranging
between +5 °C and +40 °C.
1. CONVECTOR BODY – Aluminum convector frame painted with color shade according to the catalog.
2. HEAT EXCHANGER – Copper pipes with pressed-
-on aluminum fi ns through which the heating water fl ows. The heat exchanger design differs according to the convector model.
3. COVERING GRILLE – Grille used to cover the convec­tor outlet; with color shade according to the catalog.
4. AXIAL FAN (models with a fan) – Set of fan modules for forced convection of the heated air. The number differs according to the length of the convector.
5. EB CONTROL UNIT (models with a fan) – Fan motor control unit.
6. EB CONTROL UNIT BRACKET (models with a fan) – Used for fi tting the control unit on the convector casing.
7. TEMPERATURE SENSOR (models with a fan) – Used for sensing temperature for the EB control unit.
8. THERMOSTATIC HEAD – Used for temperature con­trol and operation of the axial valve.
9. AXIAL THERMOSTATIC VALVE – A valve used for incoming heating water fl ow control.
10. CONTROL SCREW FITTING – A valve which cont­rols/adjusts the heating water fl ow.
11. GASKET RING – A gasket in the connection be­tween the valve and the heat exchanger.
12. WALL SCREW – A screw used to attach the convec­tor to the wall.
13. SCREW ANCHOR – For attaching the convector to the wall.
Each position in the table corresponds to Figure No. 1.
FIG. 1: COMPONENTS AND DESCRIPTION OF THE CONVECTOR PARTS
Contents of the box NKF1 NKF2 NUF1 NUF2 NMF1 NWF1 NWF2 NPF1 NPF2
Convector
Grille 1 1 1 1 1 1 1 1 1
Convector body 1 1 1 1 1 1 1 1 1
Heat exchanger 1 1 1 1 1 1 1 1 1
Grille reinforcement 1 1 1 1 1 1 1 1 1
Cable grommet 1 1 - - - - - - -
Fan – assembly of modules 2-4 2-4 - - - - - - -
EB control unit 1 1 - - - - - - -
Accessories
Axial radiator valve 1 1 1 1 1 1 1 1 1
Thermostatic head 1 1 1 1 1 1 1 1 1
Control Screw fitting 1 1 1 1 1 1 1 1 1
2. CONTENTS OF THE BOX
4. DESIGN DETAILS, CONNECTION DIMENSIONS, PLACEMENT
FIG. 2: Rear view
L = Standard CONVECTOR LENGTH: 900, 1000, 1250, 1500, 1750, 2000 mm
TABLE 1: applies to all lengths L 900, 1000, 1250, 1500, 1750, 2000 mm
HEAD OFFICE
MINIB,a.s. Střešovická 465/49 162 00 Prague 6 Czech Republic
Tel.: +420 220 180 809 Fax: +420 220 180 779 Email: export@minib.cz www.minib.com
PRODUCTION
Manufacturing plant of MINIB, a.s. Býkev u Mělníka 84 276 01 Býkev Czech Republic
WWW.MINIB.COM
FIG. 5: Close-up view of the connection between the valves
and the heat exchanger (the heat exchanger design differs according to the model)
FIG. 6: Close-up view of the power line connection to the EB
control unit (models with a fan)
Supply cabel
Union nut
Decide whether the convector will act as the main source of heat, or an additional heating element or, if applicable, as a thermal barrier.
As the main source of heat in your apartment or room, the convector should suffi ciently cover the entire ther­mal loss of the room. Therefore, always choose a hea­ting unit with a capacity that is higher than the thermal loss of your apartment, room, or other areas.
All wall-mounted convectors with a fan are designed for dry environment. A dry environment is an environ­ment where the average annual relative humidity does not exceed 75%. A wet environment is an environment where such average annual value is equal to or greater than 75% or where the convector is exposed to direct contact with water. In terms of convector selection, a dry environment is in general any environment where no precipitation of vapor occurs in the convector unit.
Wall-mounted convectors made by MINIB are intended for installation on the wall below window frames or sills. Make sure to follow the principle that the distance from the fl oor should never be less than 110 mm (Figu­re 3). Never cover the upper grille of the convector – this would result in fl ow reduction and a considerable decrease in the convector output.
Use the supplied attachment elements to attach the wall-mounted convector to the wall.
5.1 Installation process
According to the dimensions in table 1 and on Fig. 2: –
Measure the holes for attachment of the con­vector to the wall, drill the holes, insert the screw anchors, mark, drill the opening for power supply cable (models with a fan).
– Measure, drill the holes and install the heating
water supply pipe.
– Install the valves on the heating unit according
to section 6. Adhere to the dimensions for the particular model.
Remove the cover grille from the convector, remove the casing of convector from the heat exchanger.
Insert the wall screws in the anchors, place the heat exchanger on them, slightly tighten.
Connect the valves with the heat exchanger (pictu­red in detail on Fig. 5).
Place the convector casing on the supporting mem­ber, install the thermostatic head on the axial valve.
For models with a fan connect the power line to the EB control unit (pictured in detail on Fig. 6).
If necessary, the side walls of the casing can be re­moved. Loosen (do not remove) the top screws (1) on Fig. 4 and remove the side wall in the direction of the arrow (2). Use reverse procedure to place back the side wall.
Firmly tighten the wall screws. Install the cover grille. Check and, if necessary, adjust the vertical axle
alignment of the unit with the wall using the ad­justing screws which are located in the lower part of the casing.
Vent (bleed) the convector according to section 7.
FIG. 4
5. INSTALLATION 6. CONNECTION OF THE FITTINGS
7. VENTING THE UNIT
FIG. 3: Recommended placement of the wall-mounted convector.
A B C D E F G H I J K
NKF1
150 178 100 130 60 50 85 165 90 145 85
NKF2
150 348 265 130 200 50 85 165 90 315 90
NUF1
115 178 105 130 145 30 60 165 40 145 85
NUF2
115 348 275 130 315 30 60 165 40 190 90
NPF1
150 178 130 50 90 50 85 120 40 145 85
NPF2
150 348 195 50 320 50 85 115 50 315 90
NWF1
220 178 130 50 70 85 155 85 50 145 85
NWF2
220 348 300 50 240 85 155 85 50 190 90
NMF1
195 178 110 85 140 75 140 120 45 145 85
An axial thermostatic valve is connected to the water inlet of the heat exchanger. Control screw fi tting is to be installed on the outlet line. Insert O-rings between the axial thermostatic valve / control screw fi tting and the heat exchanger. Use gaskets for all the other con­nections.
Vent (bleed) the unit using the air vent valve during the fi rst use if necessary. The air vent valve is located on the heat exchanger pipe.
For additional options see the catalog or visit: www.minib.com.