28
4. BEFORE INSTALLATION
Use the catalogue to choose a suitable convector for wet or dry
environment - see paragraph 4.1.
Select correct convector position - see paragraph 4.2.
Leave enough space for placement and installation - see paragra-
ph 4.3. Consider using thermal insulation, anti-vibration foil, or bra-
ces into
hollow fl oors - see paragraph 4.4.
Do not forget drainage pipes or other condensate removal sys-
tems - see paragraph 4.5.
4.1 Suitable Convector Type
Decide whether the convector will act as the main source of heat, an
additional heating element or a thermal barrier.
As the main source of heat in your apartment / room, the convector
should suffi ciently cover the entire thermal loss of the room. Therefore,
choose a heating unit with a capacity that is higher than the thermal
loss of your apartment, room, or other premises.
Make sure that you have enough space for convector installation - both
from the wall (window) and in the fl oor (see paragraph 4.3).
Determine whether the convector will be used in a dry or wet environment. A dry environment is an environment where the average
annual relative humidity does not exceed 85%. A wet environment is
an environment where such average annual value is equal or greater
than 85%. In terms of convector selection, a dry environment is in general any environment where no precipitation of vapor occurs in the
convector unit. Convectors intended for a wet environment have more
resistant stainless material and a feature for condensate drainage.
4.2 Convector Position
Consult the convector position with an expert or your designer.
MINIB fl oor convectors are intended for embedding in fl oors in order
to avoid disturbance to the overall aesthetic appearance of the room.
If the convector is intended to be the main source of heat, it must be
placed with a heat exchanger in the room (Figure 2). If the convector
serves as an additional source of heat or as a thermal barrier, it is
placed with a heat exchanger towards the window (Figure 3). If the
convector is equipped with a heat exchanger over its entire width, it
is recommended that the convector be positioned with the fan facing
into the room.
4.3 Installation Space
MINIB, s.r.o. recommends leaving suffi cient space for convector
installation. For installation in older fl oors, during reconstruction, or
whenever suffi cient space is not available, the dimensions of the installation hole should be equal to the convector height + at least 20
mm. The width and/or length (if only 1 convector is concerned) of the
installation hole should correspond to the convector width (length) +
at least 60 mm - see Figure 4. Clearance around the convector should
provide enough space for the connection of water, cabling, and convector embedding in concrete. For new fl oors, MINIB recommends at
least +100 mm of free space around the convector; the height remains
identical to the previous case (H + at least 20 mm).
The position and location of the convector fully depend on the client's
requirements, particularly, what and how they need to heat or cool.
MINIB, s.r.o. recommends installing convectors acting as the main
source of heat under windows with a heat exchanger into the room.
The recommended distance from the wall is 200 – 350mm. If the
customer wishes to use the convector as an additional source of heat
only (i.e., the convector does not serve as the main source of heat),
the heat exchanger can be turned towards the window. The exchanger location on the window side is recommended in cases where the
convector is used as an additional source of heat or when it acts as a
thermal barrier in front of the window.
4.4 Principles of Convector Installation in Floors
MINIB fl oor convectors are intended for installation in solid or hollow
fl oors where certain principles apply. Before you start, please read
the following instructions.
At your own discretion (parquet, fl oating, or wooden fl oors), install
thermal insulation on the outside of the convector vat on the heat
exchanger side. (Figure 6).
If the convector is installed at a frequented spot where people of-
ten step on the cover grille or walk past the convector, it is recommended that anti-vibration foil be used to reduce structure-borne
noise, particularly, in multi-story buildings (Figure 7).
installation manuals - fl oor convectors with fan
Figure 4: B - maximum width of convector; L - convector length; H - convector
height (without adjustment legs)
Recommended MINIMUM clearance for installation: B + 60 mm; L + 60 mm;
H + 20 mm
Figure 2: Convector with exchanger
in the room as the main source of
heat.
Figure 3: Convector with exchan-
ger towards the window as an
additional source of heat.
window
exchanger
window
exchanger
Figure 3-1