Minco TT269 Operating Instructions

MINCO
TT269
3-wire Temperature Transmitter
Installation and Operating Instructions
Description
Model TT269 is a 3-wire temperature transmitter for RTD (resistance temperature detector) thermometers. The TemptranTM converts the RTD's signal into a 0 to 1 mA current. The current changes according to the range marked on the Temptran: 0 mA at the lowest temperature of the range, rising to 1 mA at the top of the range.
Installation
Locate the Temptran near the RTD, in an area where the ambient temperature stays between ­40 and 85 °C (-40 and 185 °F). Mount with #8 machine screws using the two mounting holes provided in the Temptran case.
Connect the Temptran as shown below, observing the +/- polarity of the power supply connections. Maximum DC supply voltage = 35 VDC. The maximum load resistance for the 0 to 1 mA output is 1000 Ω. The RTD connections for the Temptran in the wiring diagram below must be connected as shown or the transmitter will not function properly.
Wiring Diagram
7300 Commerce Lane, Minneapolis, MN 55432-3177 U.S.A. Telephone: (763)571-3121 / FAX: (763)571-0927
PRODUCTS, INC
.
Calibration
NOTE: Because the transmitter cannot output a negative current, the calibration of the zero cannot be performed at 0 °C (0 mA). The zero calibration should be performed at 6 °C (.05 mA) to ensure proper calibration of the transmitter. If the transmitter is calibrated at 0 °C, the output of the transmitter may not be linear.
1. Select the desired temperature range by soldering the two designated pins together. For 0 to 120 °C Solder jumper 1 to A For 0 to 160 °C Solder jumper 2 to A For 0 to 180 °C Solder jumper 3 to A
2. Connect a power supply of 24 VDC, a 1000Ω load resistor (decade box), and a digital
multimeter (4-½ digit minimum) as shown below. The load resistor should have an accuracy of 1000Ω +/- .1 Ω. If unsure of the decade box's accuracy, measure using the DMM. Other load resistances can be used as long as the maximum of 1000Ω is not exceeded. The required calibration voltage measured on the DMM is dependent on the value of Rload according to the following formula: V(DMM) = Rload x Current (Ohm's Law)
3. Connect a resistance decade box with a resolution of at least .01 ohms to the input of the transmitter. If unsure or concerned about the decade box's accuracy, measure the zero and span resistance settings using a known-accurate ohmmeter and record decade box settings before connecting decade box to the transmitter.
4. Set decade box resistance to simulate 6 °C (102.34 Ω).
5. Adjust ZERO potentiometer until the meter reads .05 volts (.05 volts x 1000 Ω = .05 mA).
6. Set decade box resistance to simulate the desired span temperature.
For 120 °C R = 146.061 For 160 °C R = 161.043 For 180 °C R = 168.478
Ω Ω Ω
7. Adjust SPAN potentiometer until the meter reads 1 volt (1 volt x 1000 Ω = 1 mA).
8. Repeat steps 4 - 7 until no further adjustment is necessary. The zero and span pots are non­interacting so further adjustment should be minimal.
2
Loading...
+ 1 hidden pages