All rights reserved. No part of this manual may be reproduced or transmitted in
any form without written permission from Minarik Corporation. The information
and technical data in this manual are subject to change without notice. Minarik
Corporation and its Divisions make no warranty of any kind with respect to this
material, including, but not limited to, the implied warranties of its merchantability
and fitness for a given purpose. Minarik Corporation and its Divisions assume no
responsibility for any errors that may appear in this manual and make no
commitment to update or to keep current the information in this manual.
Printed in the United States of America.
Safety Warnings
• This symbol denotes an important safety tip or warning.
Please read these sections carefully prior to performing any of
the instructions contained in that section.
• Have a qualified electrical maintenance technician install,
adjust and service this equipment. Follow the National
Electrical Code and all other applicable electrical and safety
codes, including the provisions of the Occupational Safety
and Health Act (OSHA), when installing equipment.
• Reduce the chance of an electrical fire, shock, or explosion by
• It is possible for a drive to run at full speed as a result of a
component failure. Please ensure that a master switch has
been placed in the AC line to stop the drive in an emergency.
• This drive is not isolated from earth ground. Circuit
potentials are at 115 VAC or 230 VAC above earth ground.
Avoid direct contact with the printed circuit board or with
circuit elements to prevent the risk of serious injury or fatality.
Use a non-metallic screwdriver for adjusting the calibration
trimpots.
† Maximum armature current and horsepower range apply when drive is attached to
additional heat sink: Minarik part number 223-0235. Use heat sink when armature
current is above 7 ADC. Heat sinks are pre-mounted on RG500 cased drives.
* See page 2 for suffix descriptions.
AC Line Voltage115/230 VAC, ±10%, 50/60 Hz, single phase
Armature Voltage (115 VAC Input)0–90 VDC
Armature Voltage (230 VAC Input)0–180 VDC
Form Factor1.37 at base speed
Field Voltage (115 VAC Input)50 VDC (F1 to L1); 100 VDC (F1 to F2)
Field Voltage (230 VAC Input)100 VDC (F1 to L1); 200 VDC (F1 to F2)
Max. Field Current1 ADC
Accel. Time Range (with no load) 0.5 – 15 seconds
Decel. Time Range (with no load)0.5 – 15 seconds
Analog Input Voltage Range (signal must be isolated; S0 to S2)0–10 VDC
Input Impedance (S0 to S2)32K ohms
Load Regulation
with Armature Feedback1% of base speed or better
with Tachogenerator Feedback0.1% of base speed
Ambient Temp. Range (chassis drives)10°C–55°C
Ambient Temp. Range (cased drives)10°C–40°C
Vibration 0.5g max (0 – 50 Hz)
Currentwith 115 VACwith 230 VAC
0.1g max (above 50 Hz)
1
2
Specifications
Drive option description (by suffix)
Terminal
SuffixStyleBlock Type
ANEMA 4XCage-Clamp
UAChassisCage-Clamp
Dimensions
FU501
FU502
0.93[24]
3.50[89]
0.64[16]
8.90[226]
.70[18]
8.40 [213]
1.85[47]
0.125[3]REF
4.78[121]
4.000[102]
0.28[7]
IC501
IC502
S3 S2
C505
TB502
S0S1 RB1 -15RB2 +15
P501
MIN SPD
T2T1
INHIBIT
FWD TQ REV TQ
INV
P502 P503
230V
C502
SW502
C503
A2 A1
TB501
F2
SW501
GND F1
115V
L2
115 230230 115
SO502
SO501
INH-RU N
T505
T501
FU504
R501
T502
C504
L2
L1
FAST ACTING
FUSES ONLY
L2L1
SCR501 SCR502SCR504
C501
SCR503
P509
TACHFWD ACCMAX SPDIR COMP
P505P504P506
REV ACC DB
P507 P508
SW504
T503
T504
SW503
ARM TACH
FEEDBACK
R503
90 180
ARMATURE
R502
R505R504
SCR505 SCR506
R506
SCR507 SCR508
C510
0.188[5]
3
4.78 [121]
0.28 [7]
0.93 [24]
0.84 [18]
0.125 [3] REF
8.40 [213]
4.000 [102]
0.70 [18]
8.90 [228]
3.50 [89]
0.188 [5]
1.85 [47]
Figure 1. RG500UA and RG510UA Dimensions
Optional 223-0235 Heatsink Dimensions: 9.8" x 6.9" x 1"
S0
S1
S2
S3
grey
grey/white
green
blue
REV
FWD
BRAKE
CW
10K
W
blue/white
4
Dimensions
6.90 [175]
6.30 [160]
10.20 [259]
9.80 [249]
FOUR (4) EACH MOUNTING SLOTS.
6.3 [160] x 7.0 [178]
ON CENTERS
5.50 [140]
4.78 [121]
2.30 [58]
1.50 [38]
Figure 2. RG500A and RG510A Cased Drive Dimensions
THREE 0.88 [22] KNOCKOUTS
ALL DIMENSIONS IN INCHES [MILLIMETERS]
1.45 [37]
1.50 [38]
1.40 [36]
0.12 [3]
Regenerative Drives
In most non-regenerative, variable speed, DC drives control
current flows to a motor in one direction. The direction of
current flow is the same direction as the motor rotation.
Non-regenerative drives operate in Quadrant 1, and also in
Quadrant 3 if the drive is reversible (see Figure 3, page 6).
Motors must stop before reversing direction. Non-regenerative
drives cannot oppose an overhauling load, and cannot
decelerate a load faster than coasting to a lower speed.
Regenerative drives operate in two additional quadrants:
Quadrant 2 and Quadrant 4. In these quadrants, motor torque
is in the opposite direction of motor rotation.
Regenerative drives can reverse a motor without contactors,
switches, brake resistors, and inhibit plugs. They can also
control an overhauling load and decelerate a load faster than it
would take to coast to a lower speed.
5
6
Regenerative Drives
Figure 3. Four Quadrant Operation
Installation
Mounting chassis drives
Drive components are sensitive to electrostatic fields. Avoid
contact with the circuit board directly. Hold the drive by the
chassis only.
Protect the drive from dirt, moisture, and accidental contact.
Provide sufficient room for access to the terminal block and
calibration trimpots.
Mount the drive away from other heat sources. Operate
the drive within the specified ambient operating temperature
range.
Prevent loose connections by avoiding excessive vibration
of the drive.
Mount the drive with its board in either a horizontal or
vertical plane. Six 0.18 inch (4.57 mm) wide slots in the
chassis accept #8 pan head screws. Fasten either the large
base or the narrow flange of the chassis to the subplate.
7
The chassis must be earth grounded for noise suppression. To
ground the chassis, connect earth ground to the GND terminal
on terminal block TB501.
8
Installation
Mounting cased drives
NEMA 4X cased drives come with three 0.88 inch (22 mm)
conduit knockout holes at the bottom of the case. The units
may be vertically wall mounted using the four 0.25 inch
(6 mm) slotted holes on the attached heat sink. For motor
loads less than 5 ADC, the drive may be bench mounted
horizontally, or operated without mounting.
1. Set the POWER switch to the “0” or OFF position before
applying the AC line voltage.
2. Install the mounting screws.
3. For access to the terminal strip, turn the slotted screw on
the front cover counterclockwise until it is free from the
case. The right side of the cover is hinged to the case. Lift
or pull the slotted screw to open the case.
4. Carefully remove the conduit knockouts by tapping them
into the case and twisting them off with pliers.
5. Install conduit hardware through the 0.88 inch (22 mm)
conduit holes. Connect external wiring to the terminal
block.
6. Grasp the slotted screw and tilt the front cover back into
place. Avoid pinching any wires between the front cover
and the case.
7. Turn the slotted screw clockwise until tight to secure the
front cover.
S3 S2
C505
TB502
230V
A2 A1
TB501
F2GND F1
115V
L2
C504
L2
L1
A
ARMATURE
OUTPUT
FIELD
OUTPUT
FORSHUNTWOUND
MOTORSONLY.
Seefieldoutputsection
forconnections.
230VAC
115VAC
ACLINE
INPUT
115OR230VAC
Installation
Heat sinking
Chassis RG500 models require an additional heat sink
when the continuous armature current is above 7 ADC. Use
®
Minarik
part number 223-0235. All cased drives have
sufficient heat sinking in their basic configurations. Use a
thermally conductive heat sink compound (such as Dow
®
Corning
340 Heat Sink compound) between the drive chassis
and the heat sink surface for optimum heat transfer.
AC line and motor connections
Use 14 AWG or 16 AWG standard wire for connecting the
line and the armature. Use 16 AWG or 18 AWG standard wire
when connecting the field of a shunt wound motor. Strip the
wire insulation 0.25 inches (6 mm). See Figures 4 and 5
(page 10) for AC line and motor connections to chassis and
cased drives.
9
AC LINE
115 OR 230 VAC
INPUT
Figure 4. Chassis Drive Connections
115 VAC
230 VAC
FIELD OUTPUT
For Shunt Wound
Motors Only.
See field output section
for connections
A
ARMATURE
OUTPUT
10
IC50 1
IC50 2
S3 S2
C505
TB502
S0S1 RB1 -15RB2 +15
P501
MIN SPD
T2T1
INHIB IT
FWD TQ REV
P502 P50
230V
C502
SW502
C503
A2 A1
TB501
F2
SW501
GND F1
115V
L2
115 230 230 115
SO502
SO501
INH- RUN
T502
C504
L2
L1
FAST ACTING
FUSES ONLY
L2
FU502
L1
FU501
SCR504
C501
123
A
115
VAC
230 VAC
AC LINE INPUT
115 OR 230 VAC
Installation
FIELD OUTPUT
For shunt wound motors
only. See field output
section for connections.
Figure 5. Cased Drive Connections
ARMATURE
OUTPUT
Installation
Cage-clamp terminal block
Connections to RG500 Series drives are made to a cage-clamp
terminal block (see Figure 6). To insert a wire into the
terminal block, press down on the lever arm using a small
screwdriver. Insert stripped wire into the large opening in front
of the terminal block. Release the lever arm to clamp the wire.
Lever Arm
Wire Clamp
11
Figure 6. Cage-Clamp Terminal Block
12
Installation
Field output
The field output is for shunt wound motors only. Do not
make any connections to F1 and F2 when using a
permanent magnet motor.
Use 18 AWG wire to connect the field output to a shunt
wound motor. Table 1 lists the field output connections.
Table 1. Field Output Connections
Line VoltageApproximateConnect Motor
(VAC)Field Voltage (VDC)Field To
11550F1 and L1
115100F1 and F2
230100F1 and L1
230200F1 and F2
Tachogenerator feedback
Using tachogenerator feedback improves speed regulation
from approximately 1% of motor base speed to approximately
0.1% of motor base speed. Use tachogenerators rated from
7 VDC per 1000 RPM to 50 VDC per 1000 RPM. Connect the
tachogenerator to terminals T1 and T2 of terminal block
TB502. The polarity is + for T1 and – for T2 when the motor
running in the forward direction. The polarity is reversed
when the motor is running in the reverse direction.
Speed adjust potentiometer installation
POTTABASSIGNMENTS
WIPER
CW
CCW
SPEEDADJUST
POTENTIOMETER
INSULATINGDISK
PANEL
STAR
WASHER
NUT
MOUNTTHROUGHA0.38IN.(10MM)HOLE
Warning
Be sure that the potentiometer tabs do not make contact with
the potentiometer enclosure. Grounding the input will cause
damage to the drive.
On chassis drives, install the circular insulating disk between
the panel and the 10KΩ speed adjust potentiometer. Mount the
speed adjust potentiometer through a 0.38 in. (0.96 cm) hole
with the hardware provided (see Figure 7). Twist the speed
adjust potentiometer wire to avoid picking up unwanted
electrical noise. If potentiometer leads are longer than 18 in.
(46 cm), use shielded cable. Speed adjust potentiometers are
installed on all cased drives.
MOUNT THROUGH A 0.38 IN. (10 MM) HOLE
NUT
STAR
WASHER
SPEED ADJUST
POTENTIOMETER
INSULATING DISK
PANEL
Figure 7. Speed Adjust Potentiometer
POT TAB ASSIGNMENTS
Installation
WIPER
CW
13
CCW
FU501
FU502
IC501
IC502
S3S2
C505
TB502
S0S1RB1-15RB2+15
P501
MINSPD
T2T1
INHIBIT
INV
230V
C502
SW502
C503
A2A1
TB501
F2
SW501
GNDF1
115V
L2
115230230115
SO502
SO501
INH-RUN
T505
T501
FU504
R501
C504
L2
L1
FASTACTING
FUSESONLY
L2L1
SCR501SCR502SCR5
DS501
1718
K502
1416151312
K501
IC502
1011
IL501
POWER
123456
21
200-0386A
LIMITSWITCH
LOGICBOARD
TB502ON
RG500SERIES
DRIVE
14
S0
S1
S2
TB502
10KOHM
SPEEDADJUST
POTENTIOMETER
CCW
S1
S2
S3
CW
10KOHM,2W
SPEEDADJUST
POTENTIOMETER
TB502
REV
FWD
Installation
Speed adjust potentiometer connections
The motor can operate in one direction (unidirectional) or in
two directions (bidirectional) depending on how the speed
adjust potentiometer is connected to the drive.
Connect the speed adjust potentiometer as shown in Figure
8(a) for speed control in one direction.
Connect the speed adjust potentiometer as shown in Figure
8(b) for speed control in two directions. The motor does not
rotate when the wiper is in the center position. Turning the
wiper CW from the center position causes the motor to rotate
in one direction, while turning the wiper CCW from the center
position causes the motor to rotate in the opposite direction.
10K OHM, 2W
SPEED ADJUST
POTENTIOMETER
REV
FWD
CW
Refer to the Application Notes section for additional speed
adjust potentiometer connections.
10K OHM
SPEED ADJUST
POTENTIOMETER
Figure 8. Speed Adjust Potentiometer Connections
for (a) Unidirectional Operation and (b) Bidirectional Operation
CCW
(a)(b)
TB502
S2
S1
S0
TB502
S3
S2
S1
Installation
S3S2
TB502
S0S1RB1-15RB2+15T2T1
+15 and –15 terminals
Warning
Do not short the +15 and -15 terminals for any reason.
Shorting these terminals may damage the drive.
RG500 Series drives can supply a regulated +15 and –15 VDC
signal (each sourcing 15 mA maximum) to isolated, external
devices. These voltage supply terminals are located on
terminal block TB502 (see figure 9).
TB502
S3S2S1S0 RB1 RB2 -15 +15 T1T2
Figure 9. TB502 Terminal Assignments
15
16
Installation
Line Fusing for RG Series Drives
Minarik drives require fuses for protection. Use fast acting fuses
rated for 250 VAC or higher, and approximately 150% of the
maximum armature current. Fuse L1 when using 115 VAC line
voltage. Fuse both L1 and L2 when the line voltage is 230 VAC.
The fuse chart below lists the recommended line fuse sizes.
Table 2. Fuse Chart
90 VDC Motor180 VDCAC Line Fuse
HorsepowerHorsepowerSize (amps)
1/201/103
1/151/83
1/81/45
1/61/35
1/41/28
1/33/48
1/2110
3/41 1/215
1220
Minarik Corporation offers two fuse kits: part number 050–0069
(3–8A Fuse Kit) and 050–0073 (5–20A Fuse Kit). Both fuse kits
include a 1/2A pico fuse (part number 050–0064) which protects the
transformer and logic.
Installation
RB1
S1
S2±10VDC
COMMON
All drives have line fuses installed (see Replacement Parts
section for installed line fuse size). Line fuses are rated for
maximum rated curent. Use line fuses rated for 20 A or less on
RG500 drives (8 A or less on RG501 drives).
Voltage follower
The drive may be wired to follow a floating (isolated)
0 to ±10V signal that is isolated from earth ground instead of
using a speed adjust potentiometer. Connect the signal input to
S2, and the signal common to RB1 (see Figure 10).
17
±10 VDC
COMMON
Figure 10. Voltage Follower Connection
S2
S1
RB1
DBDB
60Hz
Applications
50Hz
Applications
18
Operation
Warning
Dangerous voltages exist on the drive when it is powered.
BE ALERT. High voltages can cause serious or fatal
injury. For your safety, use personal protective equipment
(PPE) when operating this drive.
Before applying power
1. Check connections before applying AC line voltage to the
drive.
2. Check that no conductive material is present on the printed
circuit board.
3. Verify that all selector switches are set correctly (see the
following section for selector switch settings).
Operation
Selector switch settings
1. Set the line voltage selector switches (SW501 and SW502)
to 115 if using 115 VAC line voltage, or to 230 if using
230 VAC line voltage.
2. Set the armature voltage selector switch (SW503) to 90 if
using a 90 VDC motor, or to 180 if using a 180 VDC
motor.
3. Set the feedback selector switch (SW504) to TACH if
using a tachogenerator; otherwise set to ARM for armature
feedback.
Note: You may be required to derate a 90 VDC motor
when 230 VAC is applied to the drive. Contact the
factory for details.
See Figure 11 (page 21) for all switch locations.
Startup
Chassis drives
1. Set the speed adjust potentiometer for zero speed.
2. Apply AC line voltage.
3. Slowly advance the speed adjust potentiometer clockwise
(CW). The motor slowly accelerates as the potentiometer is
turned CW. Continue until the desired speed is reached.
4. Remove AC line voltage from the drive to coast the motor
to a stop.
19
20
Operation
Cased drives
1. Set the FORWARD/BRAKE/REVERSE switch to the
BRAKE position.
2. Set the speed adjust potentiometer to “0” (full CCW).
3. Apply AC line voltage.
4. Set the POWER switch to the “I” (ON) position.
5. Set the FORWARD/BRAKE/REVERSE switch to the
desired direction of rotation.
7. Slowly advance the speed adjust potentiometer clockwise
(CW). The motor slowly accelerates as the potentiometer is
turned CW. Continue until the desired speed is reached.
8. To brake the motor, set the FORWARD/BRAKE/REVERSE
switch to the BRAKE position. To coast the motor to a stop,
set the POWER switch to the “O” (OFF) position.
9. To reverse direction:
a. Set the FORWARD/BRAKE/REVERSE switch to the
BRAKE position.
b. After the motor comes to a complete stop, set the
FORWARD/BRAKE/REVERSE switch to the desired
direction of rotation.
10. Set the POWER switch to “O” (OFF) to remove power
from the drive.
Operation
FU501
FU502
IC501
IC502
S3 S2
C505
TB502
S0S1 RB1 -15RB2 +15
P501
MIN SPD
T2T1
INHIBIT
FWD TQ REV TQ
INV
P502 P503
230V
C502
SW502
C503
A2 A1
TB501
F2
SW501
GND F1
115V
L2
115 230 230 115
SO502
SO501
INH-R U N
T505
T501
FU504
R501
T502
C504
L2
L1
FAST ACTING
FUSES ONLY
L2L1
SCR501SCR502SCR504
C501
SCR503
P509
TACHFWD AC CMAX SPDIR COM P
P505P504P506
REV ACC DB
P507 P508
SW504
T503
T504
SW503
ARM TACH
FEEDBACK
R503
90 180
ARMATURE
R502
R505R504
SCR505SCR506
R506
SCR507SCR508
C510
21
Figure 11. Selector Switch Locations
Selector Switch
Armature Voltage
Selector Switch
Line Voltage
Selector Switches
Feedback
22
Starting and Stopping Methods
Line starting and line stopping
Line starting and line stopping (applying and removing
AC line voltage) is recommended for infrequent starting and
stopping of a drive only. When AC line voltage is applied to
the drive, the motor accelerates to the speed set by the speed
adjust potentiometer. When AC line voltage is removed, the
motor coasts to a stop.
Automatic restart upon power restoration
All drives automatically run to set speed when power is
applied. Wiring a latching relay into the AC line is one way
to prevent automatic restarting following a power outage.
Regenerative deceleration
Short terminals RB1 and RB2
to regeneratively decelerate a
motor to a stop (Figure 12).
Since terminal RB1 bypasses
the MIN SPD circuit, shorting
RB1 and RB2 will decelerate a
motor to a stop instead of
minimum speed. Calibrate the
deceleration time
by adjusting the oppositedirection acceleration trimpot.
STOP
RUN
Figure 12. Regenerative
Deceleration Switch
Connection
RB1
RB2
Starting and Stopping Methods
FU501
FU502
IC501
IC502
S3 S2
C505
TB502
S0S1 RB1 - 15RB2 +15
P501
MIN SPD
T2T1
INHIBIT
FWD
INV
P502
230V
C502
SW502
C503
A2 A1
TB501
F2
SW501
GND F1
115V
L2
115 230 230 115
SO502
SO501
INH-R U N
T505
T501
FU504
R501
C504
L2
L1
FAST ACTING
FUSES ONLY
L2L1
SCR501SCR502S
C501
SCR503
Regenerative brake
Short the INHIBIT terminals to regeneratively brake the motor
(see Figure 13 for INHIBIT terminal location). Reopening the
INHIBIT terminals causes the motor to accelerate to set speed.
The INHIBIT terminals bypass both the MIN SPD circuit
and the deceleration circuit. This causes the motor to stop
rapidly when the INHIBIT terminals are shorted. Braking
torque is determined by the opposite-direction torque setting.
23
Figure 13. INHIBIT Terminals
INHIBIT
Terminals
24
Starting and Stopping Methods
Minarik Corporation offers two accessory plug harnesses for
the INHIBIT terminals:
Minarik
®
Part NumberDescription
201-0024Inhibit plug with 18 in. (46 cm) wires
201-0079Inhibit plug with 36 in. (91 cm) wires
Twist inhibit wires and separate them from other powercarrying wires or sources of electrical noise. Use shielded
cable if the inhibit wires are longer than 18 in. (46 cm). If
shielded cable is used, ground only one end of the shield to
earth ground. Do not ground both ends of the shield.
Coast to a stop
To coast the motor to a stop without
removing power to the drive, jumper
INHIBIT–RUN terminals 1 and 2
(see Figure 14, page 25). To restart
the motor, jumper INHIBIT–RUN
terminals 2 and 3. A single-pole,
double-throw switch may be used as
a COAST/RUN switch (see Figure
15, page 25).
Each drive is assembled with
INHIBIT–RUN terminals 2 and 3
jumpered. These terminals must
be connected for the motor to run.
1 2 31 2 3
INHIBITRUN
Figure 14. Inhibit -
Run Jumper
Settings
IC501
IC502
S3 S2
C505
TB502
S0S1 RB1 -15RB2 +15
P501
MIN SPD
T2T1
INHIB IT
FW
INV
P
230V
C502
SW502
C503
A2 A1
TB501
F2
SW501
GND F1
115V
L2
115 230 230 115
SO502
SO501
INH- RUN
T505
T501
FU504
R501
L2
123
Starting and Stopping Methods
SO502
INH-RUN
123
RUN
COAST
TOSTOP
25
COAST TO
STOP
COAST / RUN
SWITCH
123
INH-RUN
Figure 15. Inhibit - Run Terminals Location
and Run / Coast Switch
RUN
S0502
INHIBIT- RUN
TERMINALS
26
S3
S2
S1
S0
DECELTO
ZEROSPEED
RUN
CW
10KOHM
SPEEDADJUST
POTENTIOMETER
REV
FWD
Starting and Stopping Methods
Decelerate to zero speed
The circuit shown in Figure 16 may be used to decelerate a
motor to a zero speed. Closing the switch between S2 and S0
decelerates the motor from set speed to zero speed. The
DECEL trimpot setting determines the rate at which the drive
decelerates. Set the switch to the RUN position to accelerate
the motor to set speed at a rate determined by the ACCEL
trimpot setting.
10K OHM
SPEED ADJUST
POTENTIOMETER
REV
CW
(shown with bidirectional speed adjust
potentiometer connection)
FWD
Figure 16. Run/Decelerate to Zero Speed Switch
RUN
DECEL TO
ZERO SPEED
S3
S2
S1
S0
Starting and Stopping Methods
Warning
For frequent starts and stops, use regenerative deceleration
(shorting RB1 and RB2), regenerative braking (shorting
INHIBIT terminals to each other), coasting to a stop
(shorting INHIBIT–RUN terminals 1 and 2), or
decelerating to minimum speed (shorting S2 to S0). Do
not use any of these methods for emergency stopping.
They may not stop a drive that is malfunctioning.
Removing AC line power (both L1 and L2) is the only
acceptable method for emergency stopping.
CURRENT LIMIT (FWD TQ and REV TQ on regenerative
drives) is still active while the drive is regeneratively braking.
Frequent regenerative deceleration, regenerative braking,
coasting to a stop, or decelerating to minimum speed produces
high torque. This may cause damage to motors, especially
gearmotors that are not properly sized for the application.
27
IC501
IC502
S3S2
C505
TB502
S0S1RB1-15RB2+15
P501
MINSPD
T2T1
INHIBIT
FW
INV
P
230V
C502
SW502
C503
A2A1
TB501
F2
SW501
GNDF1
115V
L2
115230230115
SO502
SO501
INH-RUN
T505
T501
FU504
R501
L2
123
SO502
INH-RUN
123
RUN
COAST
TOSTOP
28
Calibration
Warning
Dangerous voltages exist on the drive when it is powered.
When possible, disconnect the voltage input from the drive
before adjusting the trimpots. If the trimpots must be
adjusted with power applied, use insulated tools and the
appropriate personal protection equipment. BE ALERT.
High voltages can cause serious or fatal injury.
Each drive is factory calibrated to its maximum current rating.
Readjust the calibration trimpot settings to accommodate
lower current rated motors.
All adjustments increase with CW rotation, and decrease with
CCW rotation. Use a non-metallic screwdriver for calibration.
Each trimpot is identified on the printed circuit board.
Calibration
MINIMUM SPEED (MIN SPD)
The MIN SPD trimpot setting determines the motor speed
when the speed adjust potentiometer is turned full CCW. It is
factory set to zero speed. The minimum speed feature
applies only when the drive is operating in unidirectional
mode.
To calibrate, set the speed adjust potentiometer full CCW.
Adjust the MIN SPD trimpot until the motor turns at the
desired minimum speed.
MAXIMUM SPEED (MAX SPD)
The MAX SPD setting determines the maximum motor speed
when the speed adjust potentiometer is turned full CW. It is
factory set for maximum rated motor speed.
To calibrate, set the speed adjust potentiometer full CW.
Adjust the MAX SPD trimpot until the motor turns at the
desired maximum speed.
29
FU501
FU502
IC501
IC502
S3S2
C505
TB502
S0S1RB1-15RB2+15
P501
MINSPD
T2T1
INHIBIT
FWD
INV
P502
230V
C502
SW502
C503
A2A1
TB501
F2
SW501
GNDF1
115V
L2
115230230115
SO502
SO501
INH-RUN
T505
T501
FU504
R501
C504
L2
L1
FASTACTINGFUSESONLY
L2L1
SCR501SCR502S
C501
SCR503
30
Calibration
FORWARD TORQUE (FWD TQ)
FWD TQ should be set to 120% of drive nameplate current
rating. Continuous operation beyond this rating may
damage the motor. If you intend to operate beyond the
rating, contact your Minarik representative for assistance.
The FWD TQ trimpot setting determines the maximum torque
for accelerating and driving the motor in the forward direction. It
also sets the maximum torque for decelerating the motor in the
reverse direction. Refer to Figure 17 (page 34) for
recommended FWD TQ trimpot settings or recalibrate using the
following procedure:
1. With the power disconnected from the drive, connect a DC
ammeter in series with the armature.
2. Set the FWD TQ trimpot to minimum (full CCW).
3. Set the speed adjust potentiometer to maximum forward
4. Lock the motor shaft. Be sure that the motor is firmly
5. Apply line power. The motor should be stopped.
6. Slowly adjust the FWD TQ trimpot CW until the armature
7. Set the speed adjust potentiometer to minimum.
8. Remove the power from the drive and unlock the motor shaft.
9. Remove the ammeter in series with the motor armature if it is
speed.
mounted to withstand maximum torque generated by the
motor.
current is 120% of rated drive current.
no longer needed and re-apply power to the drive.
Warning
REVERSE TORQUE (REV TQ)
Calibration
31
REV TQ should be set to 120% of drive nameplate current
rating. Continuous operation beyond this rating may
damage the motor. If you intend to operate beyond the
rating, contact your Minarik representative for assistance.
The REV TQ trimpot setting determines the maximum torque
for accelerating and driving the motor in the reverse direction. It
also sets the maximum torque for decelerating the motor in the
forward direction. Refer to Figure 17 (page 34) for
recommended REV TQ trimpot settings or recalibrate using the
following procedure:
1. With the power disconnected from the drive, connect a DC
ammeter in series with the armature.
2. Set the REV TQ trimpot to minimum (full CCW).
3. Set the speed adjust potentiometer to maximum reverse
speed.
4. Lock the motor shaft. Be sure that the motor is firmly
mounted to withstand maximum torque generated by the
motor.
5. Apply line power. The motor should be stopped.
6. Slowly adjust the REV TQ trimpot CW until the armature
current is 120% of rated drive current.
7. Set the speed adjust potentiometer to minimum.
8. Remove the power from the drive and unlock the motor shaft.
9. Remove the ammeter in series with the motor armature if it is
no longer needed and re-apply power to the drive.
Warning
FU501
FU502
IC501
IC502
S3S2
C505
TB502
S0S1RB1-15RB2+15
P501
MINSPD
T2T1
INHIBIT
FWDTQREVTQ
INV
P502P503
230V
C502
SW502
C503
A2A1
TB501
F2
SW501
GNDF1
115V
L2
115230230115
SO502
SO501
INH-RUN
T505
T501
FU504
R501
T502
C504
L2
L1
FASTACTING
FUSESONLY
L2L1
SCR501SCR502SCR504
C501
SCR503
P509
TACHFWDACCMAXSPDIRCOMP
P505P504P506
REVACCDB
P507P508
SW504
T503
T504
SW503
ARMTACH
FEEDBACK
R503
90180
ARMATURE
R502
R505R504
SCR505SCR506
R506
SCR507SCR508
C510
32
Calibration
IR COMPENSATION (IR COMP)
The IR COMP trimpot setting determines the degree to which
motor speed is held constant as the motor load changes. It is
factory set for optimum motor regulation.
Recalibrate the IR COMP setting when using a lower curernt
rated motor. See Figure 17 (page 34), for typical IR COMP
trimpot settings, or recalibrate using the following procedure:
1. Set the IR COMP trimpot to minimum (full CCW).
2. Rotate the speed adjust potentiometer until the motor runs
3. Load the motor armature to its full load armature current
4. While keeping the load on the motor, rotate the IR COMP
5. Unload the motor.
at midspeed without load (for example, 900 RPM for an
1800 RPM motor). A hand held tachometer may be used to
measure motor speed.
rating. The motor should slow down.
trimpot until the motor runs at the speed measured in
step 2. If the motor oscillates (overcompensation), the IR
COMP trimpot may be set too high (CW). Turn the IR
COMP trimpot CCW to stabilize the motor.
Calibration
FORWARD ACCELERATION (FWD ACC)
The FWD ACC trimpot setting determines the time the motor
takes to ramp to either a higher speed in the forward direction
or a lower speed in the reverse direction, within the limits of
available torque. The FWD ACC setting is factory set for its
fastest forward acceleration time.
Turn the FWD ACC trimpot CW to increase the forward
acceleration time, and CCW to decrease the forward
acceleration time.
REVERSE ACCELERATION (REV ACC)
The REV ACC trimpot setting determines the time the motor
takes to ramp to either a higher speed in the reverse direction
or a lower speed in the forward direction, within the limits of
available torque. The REV ACC setting is factory set for its
fastest reverse acceleration time.
Turn the REV ACC trimpot CW to increase the reverse
acceleration time, and CCW to decrease the reverse
acceleration time.
33
34
FWDTQREVTQIRCOMP
FWDTQREVTQIRCOMP
FWDTQREVTQIRCOMP
FWDTQREVTQIRCOMP
FWDTQREVTQIRCOMP
FWDTQREVTQIRCOMP
FWDTQREVTQIRCOMP
FWDTQREVTQIRCOMP
1HP90VDC10ADC
3/4HP90VDC
7.6ADC
1/2HP90VDC5ADC
1/4HP90VDC
2.7ADC
1/2HP180VDC
2.5ADC
3/4HP180VDC
3.8ADC
1HP180VDC5ADC
2HP180VDC
9.2ADC
FWDTQREVTQIRCOMPFWDTQREVTQIRCOMP
1/8HP90VDC
1.3ADC
1/4HP180VDC
1.4ADC
FWDTQREVTQIRCOMPFWDTQREVTQIRCOMP
1/10HP90VDC
1.1ADC
1/8HP180VDC
0.67ADC
FWDTQREVTQIRCOMP
1/20HP90VDC
0.56ADC
Calibration
FWD TQ REV TQ IR COMP
RG500 Models
1 HP
90 VDC
10 ADC
FWD TQ REV TQ IR COMP
2 HP
180 VDC
9.2 ADC
3/4 HP
90 VDC
FWD TQ REV TQ IR COMP
FWD TQ REV TQ IR COMP
FWD TQ REV TQ IR COMP
FWD TQ REV TQ IR COMP
7.6 ADC
1/2 HP
90 VDC
5 ADC
1/4 HP
90 VDC
2.7 ADC
RG510 Models
1/8 HP
90 VDC
1.3 ADC
FWD TQ REV TQ IR COMP
FWD TQ REV TQ IR COMP
FWD TQ REV TQ IR COMP
FWD TQ REV TQ IR COMP
1/10 HP
90 VDC
FWD TQ REV TQ IR COMP
FWD TQ REV TQ IR COMP
Figure 17. Typical FWD TQ, REV TQ, and IR COMP Settings
1.1 ADC
1/20 HP
90 VDC
0.56 ADC
FWD TQ REV TQ IR COMP
1 HP
180 VDC
5 ADC
3/4 HP
180 VDC
3.8 ADC
1/2 HP
180 VDC
2.5 ADC
1/4 HP
180 VDC
1.4 ADC
1/8 HP
180 VDC
0.67 ADC
(actual settings may vary with each application)
DBDB
60Hz
Applications
50Hz
Applications
Calibration
DEADBAND (DB)
The deadband trimmer potentiometer determines the time
that will elapse between the application of current in one
direction before current is applied in the opposite direction.
The deadband trimmer potentiometer affects the
resistance that a motor has to changes in shaft position at
zero speed. It does this by applying AC voltage to the motor
armature.
Deadband is factory calibrated to approximately the
3 o’clock position for 60 Hz AC line operation. Recalibrate
the deadband to the 9 o’clock position for 50 Hz AC line
operation. See Figure 18, for recommended deadband settings.
35
60 Hz
APPLICATIONS
Figure 18. Deadband Settings
50 Hz
APPLICATIONS
DBDB
RB1
S1
S2±10VDC
COMMON
36
Calibration
TACHOGENERATOR (TACH)
Calibrate the TACH setting only when a tachogenerator is
used. The TACH setting, like the IR COMP setting,
determines the degree to which motor speed is held constant
as the motor load changes.
To calibrate the TACH trimpot:
1. Remove power from the drive.
2. Rotate the TACH trimmer pot to full clockwise (full CW),
3. Rotate the MAX SPD trimmer pot to full counterclockwise
(full CCW).
4. Rotate the IR COMP trimmer pot to full CCW.
5. Place the feedback selector switch (SW504) to the
ARMATURE (ARM) position.
6. Rotate the main speed potentiometer to midrange.
7. Wire the DC tach to the RG500UA. Note: The polarity of
the Tach voltage input to the RG500UA should be T1 (+)
and T2 (-). This polarity may be measured with a DC
voltmeter. If the polarity is incorrect, swap the two tach
input leads to the T1 and T2 terminals on TB502.
8. Apply power to the drive. The motor should be running at
minimum speed.
9. Rotate the main speed potentiometer to full speed in the
forward direction.
10. Turn the maximum speed trimmer pot clockwise until the
desired maximum speed is reached.
11. Remove all power from the drive. The motor should stop.
Calibration
12. Place the Feedback selector switch (SW504) to the
Tachogenerator (TACH) position.
13. Apply power to the drive. The motor should run in the
forward direction.
14. Rotate the TACH trimmer pot CCW so that the maximum
speed is reached. this is the same speed as was obtained
in step 10.
15. Rotate the main speed potentiometer to the reverse
direction (S2 should be negative with respect to S1). The
motor speed should follow the speed potentiometer
position.
Check that the tachogenerator is properly calibrated. The
motor should run at the same set speed when SW504 is set to
either armature or tachogenerator feedback
37
S3S2
TB502
S0S1RB1-15RB2+15T2T1
38
S2
RB1
S2
S1
RG500SERIES
DRIVE
RG500SERIES
DRIVE
RB11
S22
DLC600
DIGI-LOCCONTROLS
PCM4
SIGNALISOLATOR
TB502
TB502TB501
Application Notes
Connection to other Minarik devices
TB502
S2
RG500 SERIES
DRIVE
RB1
TB502TB501
RG500 SERIES
DRIVE
Figure 19. RG500 Connections to DLC600 and PCM4
S2
RB1
S2
DIGI-LOC CONTROL
S1
2
SIGNAL ISOLATOR
1
DLC600
PCM4
Application Notes
FU501
FU502
IC501
IC502
S3 S2
C505
TB502
S0S1 RB1 -15RB2 +15
P501
MIN SPD
T2T1
INHIBIT
INV
230V
C502
SW502
C503
A2 A1
TB501
F2
SW501
GND F1
115V
L2
115 230 230 115
SO502
SO501
INH-RUN
T505
T501
FU504
R501
C504
L2
L1
FAST ACTING
FUSES ONLY
L2L1
SCR501SCR502SCR5
DS501
17 18
K502
1416151312
K501
IC502
10 11
IL501
POWER
123456
21
200-0386A
LIMITSWITCH
LOGICBOARD
TB502ON
RG500SERIES
DRIVE
The RG500 can be connected to an optional 200-0386A limit
switch logic board. The 200-0386A provides the logic
interface between the regenerative drive and pushbutton
stations, foot switches, or programmable controls. See Figure
20 for RG500 connections to the 200-00386A limit switch
logic board. For more information on Minarik’s limit switch
logic board, refer to User’s Manual 250-0222 or the Minarik
Product Catalog.
39
200-0386A
LIMIT SWITCH
LOGIC BOARD
Figure 20. RG500 connection to 200-0386A
Limit Switch Logic Board
TB502 ON
RG500 SERIES
DRIVE
POTTABASSIGNMENTS
WIPER
CW
CCW
SPEEDADJUST
POTENTIOMETER
INSULATINGDISK
PANEL
STAR
WASHER
NUT
MOUNTTHROUGHA0.38IN.(10MM)HOLE
40
Application Notes
Optional speed adjust potentiometer
connections
Forward-Reverse Switch
Use a single-pole, twoposition switch with a
single speed adjust
potentiometer to plug
reverse the motor (Figure
21). The MIN SPD setting
is in effect for either
direction.
Figure 21. Forward-Reverse Switch
Forward-Stop-Reverse Switch
Use a single-pole, threeposition switch with a
single speed adjust
potentiometer to stop a
motor between reversals
(Figure 22). Set the switch
to the center position to
decelerate the motor to a
stop.
Figure 22. Forward-Stop-Reverse Switch
S0
S1
S2
S3
REV
FWD
S0
S1
S2
REV
S3
STOP
FWD
10K
OHM
CW
10K
OHM
CW
Application Notes
Independent Adjustable Speeds (Forward
Direction Only)
Connect two speed adjust potentiometers with a single-pole
two-position switch to select between two independent speeds
shown in the forward direction (Figure 23). The speed adjust
potentiometers can be mounted at two separate operating
stations.
41
S0
S1
S2
SPEED 1
SPEED 2
P1
20K OHM
P2
20K OHM
CWCW
Figure 23. Independent Adjustable Speeds
(Forward Direction)
42
Application Notes
Independent Forward and Reverse Speeds
Connect two speed adjust potentiometers as shown in Figure
24 to select between independent forward and reverse speeds.
S0
S1
S2
S3
FORWARD
REVERSE
FWD
10K OHM
CWCW
REV
10K OHM
Figure 24. Independent Forward and Reverse Speeds
Application Notes
Independent Forward and Reverse Speeds
with FWD-STOP-REV Switch
Use a single-pole, three-position switch to stop the motor
when the switch is in the center position (Figure 25).
43
S0
S1
S2
S3
FORWARD
STOP
REVERSE
FWD
10K OHM
CWCW
REV
10K OHM
Figure 25. Independent Forward and Reverse Speeds
with a Forward-Stop-Reverse Switch
S3S2
C505
TB502
230V
A2A1
TB501
F2GNDF1
115V
L2
C504
L2
L1
A
ARMATURE
OUTPUT
FIELD
OUTPUT
FORSHUNTWOUND
MOTORSONLY.
Seefieldoutputsection
forconnections.
230VAC
115VAC
ACLINE
INPUT
115OR230VAC
44
Troubleshooting
Warning
Dangerous voltages exist on the drive when it is powered.
When possible, disconnect the drive while troubleshooting.
High voltages can cause serious or fatal injury.
Check the following steps before proceeding:
1. The AC line voltage must match the voltage on the drive
nameplate.
2. On dual voltage drives, check that the voltage switches are
set to the correct position.
3. The deadband (DB) must be set approximately at the
3 o’clock position for 60 Hz AC line frequency or at
9 o’clock for 50 Hz AC line frequency.
4. The motor must be rated for the drive’s rated armature
(all motors) and field outputs (shunt wound motors only).
5. Do not make any connections to F1 and F2 if using a
permanent magnet motor.
6. Terminal block connections should be consistent with the
connections shown in this manual.
7. Check that line fuse FU501 (and FU502 for 230 VAC line
voltage) is properly sized and not blown.
8. Check that field fuse FU503 is 1.5 A and not blown.
Troubleshooting
Field fuse blows
1. Disconnect AC line voltage from the drive.
2. Verify that the fuse is 1.5 A.
3. Check motor cable for shorts.
4. Check motor field for shorts.
a. Disconnect field leads from terminals F1 and F2
b. Motor field resistance should measure approximately
100 to 1000 ohms, depending on motor horsepower.
c. A resistance reading from the motor frame to either
side of the field should show open when an ohmmeter
is used on its high resistance scale.
5. Reconnect field leads to the drive.
6. Reconnect AC line voltage to the drive.
7. Advance the speed adjust potentiometer to the desired
speed.
Line fuse blows
1. Disconnect AC line voltage from the drive.
2. Check that the motor cable and armature is not shorted or
grounded.
a. The motor’s armature resistance should measure
approximately 1 to 100 ohms, depending on motor
horsepower.
b. A resistance reading from the motor frame to either
armature side should show open when an ohmmeter is
used on its high resistance scale.
3. Check that the field circuit is not open.
45
46
Troubleshooting
Motor pulsates or surges under load
1. Readjust the IR COMP setting slightly CCW until the
motor speed is stabilized.
2. Verify that the motor is not going in and out of current
limit. If so, re-adjust FWD TQ and REV TQ pots.
Line fuse does not blow, but the motor does not run
1. Verify that the speed adjust potentiometer is not set to its
zero speed position. If in voltage follower mode, verify
that reference voltage is not set to zero.
2. Check the speed adjust potentiometer for continuity.
3. Verify that the inhibit pins are not shorted together.
4. Check that INHIBIT–RUN terminals 2 and 3 are
connected.
5. Verify that the drive is receiving AC line voltage.
6. Check that the drive is not in current limit. If the drive is in
current limit, verify that the motor is not jammed. It may
be necessary to increase the FWD TQ or REV TQ setting if
it is set lower than the current rating of the motor.
7. Check that the speed adjust potentiometer connections to
the terminal block are correct and not open.
Motor runs too fast at the maximum speed setting
1. Check that the MIN SPD and MAX SPD setting are not set
too high.
2. Check that the field output connections are secure if you
are using a shunt wound motor.
Troubleshooting
Motor will not reach the desired speed
1. Check the MAX SPD setting and increase if necessary.
2. Check that the IR COMP setting is not set too low.
3. Check that the motor is not overloaded.
For additional assistance, contact your local Minarik® distributor,
or the factory direct at: PHONE: (800) MINARIK
FAX: (800) 394-6334
47
48
Factory Prewired Connections
(for Cased Drives)
123
WHITE
BLACK
BLACK
BLACK
WHITE/BLACK
POWER
LIGHT
BLACK/WHITE
L2 (230)
L1
WHITE/BLACK
L2 (115)
Figure 26. Prewired Connections to L1, L2(115) and L2(230)
S0
S1
S2
S3
grey
grey/white
green
blue
REV
FWD
BRAKE
CW
10K
W
blue/white
Factory Prewired Connections
GREY
S0
S1
S2
S3
GREY/WHITE
GREEN
BLUE
FWD
REV
BRAKE
BLUE/
WHITE
Figure 27. Prewired Speed Adjust Potentiometer
Connections
CW
49
10K
OHM
FU501
FU502
0.93[24]
3.50[89]
0.64[16]
8.90[226]
.70[18]
8.40[213]
1.85[47]
0.125[3]REF
4.78[121]
4.000[102]
0.28[7]
IC501
IC502
S3S2
C505
TB502
S0S1RB1-15RB2+15
P501
MINSPD
T2T1
INHIBIT
FWDTQREVTQ
INV
P502P503
230V
C502
SW502
C503
A2A1
TB501
F2
SW501
GNDF1
115V
L2
115230230115
SO502
SO501
INH-RUN
T505
T501
FU504
R501
T502
C504
L2
L1
FASTACTING
FUSESONLY
L2L1
SCR501SCR502SCR504
C501
SCR503
P509
TACHFWDACCMAXSPDIRCOMP
P505P504P506
REVACCDB
P507P508
SW504
T503
T504
SW503
ARMTACH
FEEDBACK
R503
90180
ARMATURE
R502
R505R504
SCR505SCR506
R506
SCR507SCR508
C510
0.188[5]
50
Replacement Parts
Replacement parts are available form Minarik Corporation and its
distributors for this drive series.
Table 3. Replacement Parts
Model No.SymbolDescriptionMinarik®P/N
RG500UAR5010.01Ω, 5 W Resistor032-0129
RG500ASame parts as RG500UA except 202-0003 and 223-0258.
SCR501-508800 V, 25 A SCR072-0042
T5053FD-436 Transformer230-0072
10KΩ Potentiometer Kit202-0003
Chassis223-0258
20 A, 3AB Line Fuse050-0019
Include:
Line Fuse Kit (5 – 20A)050-0073
Pico fuse, 63mA050-0081
10KΩ, 2W Potentiometer120-0047
Potentiometer Knob140-0013
Case223-0209
240 V Pilot Light040-0043
FWD/BRAKE/REV Switch080-0031
Power Switch080-0022
Toggle Switch Boot155-0078
Chassis223-0260
Heat Sink223-0232
Replacement Parts
Table 3. Replacement Parts (Continued)
Model No.SymbolDescriptionMinarik®P/N
RG510UAR5010.05Ω, 5 W Resistor032-0146
SCR501-508800 V, 25 A SCR072-0042
T5053FD-436 Transformer230-0072
10KΩ Potentiometer Kit202-0003
Chassis223-0258
8 A, 3AB Line Fuse050-0023
Line Fuse Kit (3 – 8A)050-0069
Line Fuse Kit (5 – 20A)050-0073
Pico fuse, 1/2A050-0074
51
RG510ASame parts as RG500UA except 202-0003 and 223-0258.
Include:
10KΩ, 2W Potentiometer120-0047
Potentiometer Knob140-0013
Case223-0209
240 V Pilot Light040-0043
FWD/BRAKE/REV Switch080-0004
Power Switch080-0031
Toggle Switch Boot155-0078
Chassis223-0260
Heat Sink223-0232
52
Certificate of Compliance
Minarik Corporation hereby certifies that its RG500 series
drives have been approved to bear the “CE” mark provided the
conditions of approval (listed in Exhibit “A”) have been met by
the end user.
The RG500 series has been tested to the following test
specifications: EN55011:1991 (emissions), and EN50082-1:1992
(immunity).
Compliance allows Minarik’s RG500 series to bear the CE mark.
The end user, as described herein, falls into one of two
categories:
1. The Consumer will deploy a stand-alone unit as an
integral, yet external, portion of the machine he/she is
operating.
2. The Original Equipment Manufacturer (OEM) will
implement the product as a component of the machine
being manufactured.
CE Addendum
Exhibit “A”
In addition to EMI/RFI safeguards inherent in the RG500 series’
design, external filtering is required.
®
Minarik requires the Corcom
filter is not available, the specifications are as follows:
L = 1.8 milliHenries.
C = 0.01 microFarad (Line to Ground); 1.1 microFarads
(Line to Line).
Discharge Resistor = 330Kohms.
Rated current: 1.4 times maximum DC motor current.
Filter type: Balanced 2-section.
Table 4. Corcom
Nameplate Current of
Motor Wired to the DriveCorcom®Filter Part Number
0 to 4 amps6VV1
4.1 to 13 amps20VV1
The filters in Table 4 should be wired to the AC line within 0.25
meters of the drive. The ground connection from the filter must
be wired to solid earth ground (resistance less than 500 ohms);
machine ground. This is very important!
not
filters listed in Table 4. If the exact
®
Filters
53
If the end-user is using a CE-approved motor, the correct filter
from Table 4 is all that is necessary to meet the EMC directives
listed herein.
54
CE Addendum
If the end-user is not using a CE-approved motor, a second
filter, part number CEXXRG, must be deployed on the output.
XX = rated current of the filter.
The CEXXRG is a Real-Pole Balanced-Pi 3-pole filter. If the
exact filter is not available, the specifications are as follows:
L & L1 = 2 x (0.8) milliHenries.
C & C1 = 2 x (0.1) microFarads @ 400W VDC.
Rin = 0.1 ohm; Rout = 1.2 ohm.
Table 5. Minarik Filters
Nameplate Current of
Motor Wired to the DriveMinarik Filter Part Number
0 to 4 ampsCE04RG
4.1 to 13 ampsCE20RG
The filters in Table 5 must be wired to the DC output of the
drive, as close to the drive as possible. The ground connection
from the filter must be wired to solid earth ground (resistance
less than 500 ohms); not
machine ground. This is very
important!
The end user must use the filtration listed in Exhibit A to comply
with CE. The OEM may choose to provide alternative filtering
that encompasses the Minarik drive and other electronics within
the same panel.
The OEM has this liberty because CE is a machinery directive.
Whether or not every component in the OEM’s machinery meets
CE, the OEM must still submit his machine for CE approval.
meet CE, the machine will not necessarily meet CE as a
machine.
CE Addendum
55
Thus, no component must necessarily meet CE within the
machine, as long as the OEM takes the necessary steps to
guarantee the machine does meet CE. By the same token, even
if every component in the OEM’s machine does meet CE, the
machine will not necessarily meet CE as a machine.
Use of CE-approved wiring practices, such as proper shielding,
and the filters listed in Exhibit A guarantee the drive will meet
EN55011 (1991 emissions standard) and EN50082-1 (1992
immunity standard).
Minarik Corporation (referred to as "the Corporation") warrants that its products will be
free from defects in workmanship and material for twelve (12) months or 3,000 hours,
whichever comes first, from date of manufacture thereof. Within this warranty period,
the Corporation will repair or replace, at its sole discretion, such products that are
returned to Minarik Corporation, 901 East Thompson Avenue, Glendale, CA 912012011 USA.
This warranty applies only to standard catalog products, and does not apply to
specials. Any returns for special controls will be evaluated on a case-by-case basis.
The Corporation is not responsible for removal, installation, or any other incidental
expenses incurred in shipping the product to and from the repair point.
B. Disclaimer
The provisions of Paragraph A are the Corporation's sole obligation and exclude all
other warranties of merchantability for use, express or implied. The Corporation further
disclaims any responsibility whatsoever to the customer or to any other person for
injury to the person or damage or loss of property of value caused by any product that
has been subject to misuse, negligence, or accident, or misapplied or modified by
unauthorized persons or improperly installed.
C. Limitations of Liability
In the event of any claim for breach of any of the Corporation's obligations, whether
express or implied, and particularly of any other claim or breech of warranty contained
in Paragraph A, or of any other warranties, express or implied, or claim of liability that
might, despite Paragraph B, be decided against the Corporation by lawful authority, the
Corporation shall under no circumstances be liable for any consequential damages,
losses, or expense arising in connection with the use of, or inability to use, the
Corporation's product for any purpose whatsoever.
An adjustment made under warranty does not void the warranty, nor does it imply an
extension of the original 12-month warranty period. Products serviced and/or parts
replaced on a no-charge basis during the warranty period carry the unexpired portion
of the original warranty only.
If for any reason any of the foregoing provisions shall be ineffective, the Corporation's
liability for damages arising out of its manufacture or sale of equipment, or use thereof,
whether such liability is based on warranty, contract, negligence, strict liability in tort, or
otherwise, shall not in any event exceed the full purchase price of such equipment.
Any action against the Corporation based upon any liability or obligation arising
hereunder or under any law applicable to the sale of equipment or the use thereof,
must be commenced within one year after the cause of such action arises.
Minarik Drives
www.minarikdrives.com
14300 De La Tour Drive, South Beloit, IL 61080
Phone: (800) MINARIK or 646-2745;
Fax: (800) 394-6334 or (815) 624-6960
Document number 250–0210, Revision 4
Printed in the U.S.A. -- March 2006
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.