Milton Roy MILROYAL G Instruction Manual

Page 1
MILROYAL® G Pump
Instruction Manual
Manual No : 53942 Rev. : 01 Rev. Date
: 05/2019
Page 2
PRECAUTIONS
The following precautions should be taken when working with metering pumps. Please read this section carefully prior to installation.
Protective Clothing
ALWAYS wear protective clothing, face shield, safety glasses and gloves when working on or near your metering pump. Additional precautions should be taken depending on the solution being pumped. Refer to Safety Data Sheets for the solution being pumped.
Hearing Protection
It is recommended that hearing protection be used if the pump is in an environment where the time- weighted average sound level (TWA) of 85 decibels is exceeded (as measured on the A scale- slow response).
Electrical Safety
• Remove power and ensure that it remains off while maintaining pump.
DO NOT FORGET TO CONNECT THE PUMP TO EARTH/ GROUND.
• Electric protection of the motor (Thermal protection or by means of fuses) is to correspond
to the rated current indicated on the motor data plate.
Liquid Compatibility
Verify if the materials of construction of the wetted components of your pump are recommended for the solution (chemical) to be pumped.
Pumps Water “Primed”
All pumps are tested with water at the factory. If your process solution is not compatible with water, ush the Pump Head Assembly with an appropriate solution before introducing the process solution.
Plumbing and Electrical Connections
Always adhere to your local plumbing and electrical codes.
Line Depressurization
To reduce the risk of chemical contact during disassembly or maintenance, the suction and discharge lines should be depressurized before servicing.
Over Pressure Protection
To ensure safe operation of the system it is recommended that some type of safety/pressure­relief valve be installed to protect the piping and other system components from damage due to over- pressure.
Lifting
This manual should be used as a guide only- Follow your company’s recommended lifting procedures. It is not intended to replace or take precedence over recommendations, policies and procedures judged as safe due to the local environment than what is contained herein. Use lifting equipment that is rated for the weight of the equipment to be lifted.
Page 3
TABLE OF CONTENTS
SECTION 1 - DESCRIPTION................................................................. 1
1.1 GENERAL ...................................................................... 1
1.2 PRINCIPLES OF OPERATION ...................................................... 1
1.3 GENERAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 PRODUCT CODE ................................................................ 4
SECTION 2 - INSTALLATION ................................................................ 5
2.1 UNPACKING ....................................................................5
2.2 SAFETY PRECAUTIONS .......................................................... 5
2.3 STORAGE ......................................................................5
2.3.1 Temporary Storage .............................................................. 5
2.3.2 Long Term Storage ..............................................................5
2.3.3 Pump Drive.................................................................... 5
2.3.4 Electrical Equipment............................................................. 6
2.4 MOUNTING ..................................................................... 6
2.5 CONVERSION PROCEDURE.......................................................6
2.6 PIPING CONNECTIONS........................................................... 6
2.6.1 NPSH Considerations............................................................ 6
2.6.2 General Piping Considerations..................................................... 7
2.6.3 Suction Piping Considerations .....................................................7
2.6.4 Discharge Piping Considerations ...................................................8
2.6.5 Back Pressure Valves ............................................................8
2.6.6 Pulsation Dampeners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.6.7 Safety Valves .................................................................. 9
2.6.8 Check Valves .................................................................. 9
2.6.9 Shut- OFF Valves ............................................................... 9
2.7 ELECTRICAL CONNECTIONS...................................................... 9
SECTION 3 - OPERATION ................................................................. 10
3.1 INITIAL START-UP............................................................... 10
3.1.1 Start- Up for New Pump ......................................................... 10
3.1.2 Start- Up of Pump Containing No Oil in Casing and Displacement Chamber................. 11
3.2 REFILL VALVE ADJUSTMENT ..................................................... 12
3.2.1 Relief Valve Adjustment (With an Adjustable System Back Pressure Valve). ................. 12
3.2.2 Relief Valve Adjustment (Without an Adjustable System Back Pressure Valve). ............... 13
3.3 USE OF AIR PURGE BUTTON ..................................................... 13
3.4 MANUAL CAPACITY CONTROL .................................................... 14
3.5 FILLING PUMPING SYSTEM ...................................................... 14
3.6 CAPACITY CALIBRATION ......................................................... 14
ii Instruction Manual
Page 4
SECTION 4 - MAINTENANCE............................................................... 15
4.1 RECOMMENDED SPARE PARTS .................................................. 15
4.2 SHIPPING PUMPS FOR REPAIR .................................................. 15
4.3 ROUTINE PREVENTIVE MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.3.1 Oil Replacement ............................................................... 15
4.3.2 Check Valves ................................................................. 16
4.3.3 Cleaning Fouled Check Valves .................................................... 16
4.3.4 Check Valve Replacement ....................................................... 16
4.3.5 Oil Strainer Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.4 CORRECTIVE MAINTENANCE .................................................... 21
4.4.1 3- Function Hydraulic Valve.......................................................21
4.4.2 “MARS” Valve Assembly ......................................................... 21
4.4.3 Rell Valve Assembly ...........................................................22
4.4.4 Diaphragm Replacement ........................................................22
4.4.5 Removal of Pump Liquid End .....................................................23
SECTION 5 - TROUBLESHOOTING .......................................................... 24
5.1 SYMPTOMS & REMEDIES ........................................................24
SECTION 6 - PART NUMBERS.............................................................. 26
6.1 BASIC PARTS LIST- PUMP DRIVE .................................................. 26
6.2 BASIC PARTS LIST- LIQUID END................................................... 28
6.2.1 Mars Valve ................................................................... 28
6.2.2 Rell Valve ................................................................... 28
6.2.3 3- Function Valve ..............................................................29
6.2.4 Check Valve Parts.............................................................. 29
6.2.5 PVC Liquid End ...............................................................30
6.2.6 Metallic Liquid End .............................................................31
6.3 REMAINING LIQUID END PARTS ..................................................33
LIST OF ILLUSTRATIONS
FIGURE 1. Model/Product Code ............................................................... 4
FIGURE 2. Sample Nameplate............................................................... 34
FIGURE 3. Mounting Hole Dimensions. ........................................................34
FIGURE 4. Typical Recommended Pump Installation Scheme ...................................... 34
FIGURE 5. Pump Drive Parts- Side View ....................................................... 35
FIGURE 6. Pump Drive Parts- Top View........................................................ 36
FIGURE 7. Liquid End- Top View.............................................................. 37
FIGURE 8. Liquid End- Cutaway View ......................................................... 38
FIGURE 9. Mars Value .....................................................................39
FIGURE 10. Double- Ball Check Valve Parts (1-1/4”-plastic;1-3/4, 2-1/2”-PVC & metallic) .................. 40
FIGURE 11. Plastic Single- Ball Check Valve Parts: 1-3/4, 2-1/2, & 3” Plungers.......................... 40
FIGURE 12. Plastic Check Valves for 1-1/4” Plunger .............................................. 41
FIGURE 13. Metallic Check Valves for 1-1/4” Plunger.............................................. 42
FIGURE 14. PVC 4- Function Bleed Valve for 1-1/4” Plunger ........................................ 43
iii Instruction Manual
Page 5
SECTION 1 - DESCRIPTION
1.1 GENERAL
MILROYAL® G pumps are reciprocating, chemical dosing pumps capable of producing controlled
ows up to 130 gallons per hour (492 L/H) at pressures up to 600 psi (41 BAR) (depending on the model). These pumps feature the robust High Performance Diaphragm (HPD) liquid end, which
eliminates the need for contour plates, and a non-lost motion stroke adjustment mechanism based on the variable eccentric principle. This non­lost motion design substantially reduces pressure
and ow pulsations which in turn increases the
life of system components and results in a more continuous chemical injection. It is designed for industrial service and offers an accuracy of
±1% of 100% rated ow between 10% and 100% of its ow range.
The High Performance Diaphragm (HPD) liquid end
combines all of the best characteristics of traditional liquid ends into one technologically advanced design. Its operating characteristics and simplicity of operation make it the best liquid end to consider
rst for most metering pump applications.
Milton Roy’s HPD liquid end overcomes the net positive suction head (NPSH) restrictions
associated with conventional disc diaphragm metering pumps. This is accomplished by a unique
mechanically actuated rell system (MARS) that
eliminates the need for diaphragm support plates
thereby lowering pump NPSH requirements.
The MARS also does away with the need for eld adjustment of the rell mechanism by automatically compensating for process liquid modications.
This, combined with removable check valves,
makes the HPD an ideal choice for any process in
which downtime is critical.
The HPD features a preformed, PTFE faced
elastomer diaphragm that is compatible with a wide range of process liquids and chemicals. The convoluted design of this composite diaphragm
also offers extended life over conventional at disk
designs.
The HPD liquid end is particularly suitable for
pumping costly, aggressive or hazardous liquids without leakage.
1.2 PRINCIPLE OF OPERATION (Refer to Figure 5 Through 10)
The pump consists of two major assemblies; the drive and the liquid end. Pump delivery is a function of the drive’s stroke rate (strokes/minute),
plunger size and stroke length (% Capacity).
Stroke length can be adjusted while the pump is running or stopped by turning the stroke adjustment
knob (330).
The drive motor transmits rotary motion to a
worm gear speed reduction unit (343, 50) which in turn drives the variable eccentric crank (100).
The adjustable crank imparts reciprocating motion to the plunger/connecting rod assembly
(60, 520, 525). The stroke length is adjusted by
changing the position of the variable eccentric crank in the connecting rod assembly.
1Instruction Manual
Page 6
SECTION 1 - DESCRIPTION
The mechanical drive system of the pump drives
the plunger back and forth in the High Performance Diaphragm (HPD) liquid end supplied with the
pump. At the start of a suction stroke, the plunger moves away from the liquid end, drawing hydraulic
uid with it. As the hydraulic uid is drawn back, the exible diaphragm (510) follows, lowering the pressure of the process uid in the liquid end.
This pressure drop causes the ball(s) in the suction check valve (Figure 10) to be lifted up thereby
allowing process uid to pass through the suction line into the diaphragm head (1020). At the same
time, the pressure drop in the diaphragm head causes the ball(s) in the discharge check valve
(Figure 10) to be pulled closed, blocking ow back
through the discharge line.
Note:
It is important that the pressure in the liquid end remain above the vapor pressure of the
process uid during the suction stroke. If the uid pressure drops below the vapor pressure, cavitation will occur, negatively impacting the performance of the pump. If you suspect the possibility of cavitation, contact your Milton Roy Representative for assistance.
At the end of the suction stroke, the process reverses, beginning the discharge stroke. Now the plunger moves forward, pushing hydraulic
uid before it. The hydraulic oil must therefore press against the diaphragm, exing it forward and raising the pressure of the process uid in the liquid end. This pressure increase causes the process uid to ow outward, forcing the discharge ball check
open and the suction ball check to seat, blocking
back ow through the suction line. The process uid ows out of the diaphragm head and into the
discharge line. This suction/discharge action is repeated with every stroke of the pump plunger, and is the direct cause of the pumping action.
As the pump operates, a small quantity of hydraulic oil is continuously bled through the air bleed system (970, 960, 980 in Figure 8) in the three- function hydraulic valve (air bleed/relief/purge- Figure 8). An additional small quantity of hydraulic oil is also lost on every stroke through the clearance between the plunger and displacement chamber bore. After a while, these normal losses result in a shortage of hydraulic oil in the displacement chamber. When this happens, the diaphragm will be pulled back tight against the back contoured surface of the displacement chamber, and part of the diaphragm will press against the Mechanically Actuated Rell System (MARS) valve (Figure 9). Now, when the plunger draws back, a vacuum is created in the displacement chamber. These two factors (diaphragm pressing against MARS valve & vacuum in the displacement chamber) must occur together to trigger the MARS valve.
When both of these conditions are met, the MARS valve is forced to its rearward position, and the
poppet (760) opens, allowing hydraulic oil from
the reservoir to enter through the refill valve (740 in Figure 8) and replenish the lost oil. In this manner, proper hydraulic balance is constantly maintained in the displacement chamber.
2
Instruction Manual
Page 7
SECTION 1 - DESCRIPTION
1.3 GENERAL SPECIFICATIONS
Maximum Capacity Range 20 GPH (76 LPH) to 130 GPH (492 LPH)
Maximum Pressure Range 100 PSIG (7 Bar) to 600 PSIG (41 BAR)
Liquid End Design
Drive Design Non-Lost Motion Variable Eccentric Type.
Plunger Diameters 1-1/4”(32mm), 1-3/4”(45mm), 2-1/2”(63mm), 3”(75mm)
Liquid End Materials of Construction
Steady State Accuracy ±1% of 100% rated ow between 10% and 100% of rated ow
Capacity Adjustment
Temperature Limits
Suction Pressure Limits
Lubrication Oil bath drive lubrication.
Paint Two part epoxy, yellow RAL 1018
Hydraulically Actuated Diaphragm with Mechanically Actuated Rell
System (MARS).
PVC, 316 SS, Alloy 20.
Micrometer (Standard): Lockable micrometer is adjustable from
0% to 100% while pump is running or stopped
Electronic (Optional): Electronic stroke length adjustment from 4-20ma input.
Ambient Limit:
Note: Limited by standard lubricants. Modications are available through Applications Engineering.
Plastic Liquid Ends: 20ºF to 140ºF
Metallic Liquid Ends: 20ºF to 190ºF
Minimum Internal Pressure: 3 psia (11.5 psi maximum vacuum)
Maximum Suction Pressure: 100 psig at 80ºF and below.
130ºF Maximum
0ºF Minimum
Liquid Temperature Limits:
3Instruction Manual
Page 8
SECTION 1 - DESCRIPTION
1.4 PRODUCT CODE
MILROYAL® G pumps are available in a variety of different congurations. The complete product code
is composed of the pump “model number” + “product code”. For a breakdown of the options included in a specic pump, compare the pump model number and product code found on the pump nameplate
with the model/product code breakdown shown in Figure 1. A sample nameplate is shown in Figure 2.
MODEL NUMBER
MGH
4 5 6
Digit 4 & 5: Plunger Size Digit 6: Liquid End Material
Description
1-1/4”(32mm)
1-3/4”(45mm)
2-1/2”(63mm)
3”(75mm)
PRODUCT CODE
7 8 9 10 11 12 13 14 15 16 17 18 19 20
Code Description Code
20
28
40
48
316 SS
Plastic (PVC)
Alloy 20
PVDF
1
2
5
7
Digit 7 & 8: Stroking Speed
Description
173 spm 10 No motor, Flange Mount, NEMA 56C CB
120 spm 14 No motor, Flange Mount, NEMA 145TC CC
86 spm 20 No motor, Flange Mount, NEMA 182TC CD 43 spm 30 No motor, Flange Mount, IEC80, F165 Flange MD
*Note: SPM’s for 60 Hz, 1725 rpm motor
Code
Digits 9 & 10: Motor
Description Code
Digits 11 & 12: Capacity Adjustment Connection Digit 13 & 14: Check Valve
Description Code Description Code
Manual, Plastic micrometer knob Electronic(4-20 ma input) M2 Pipe- NPT SE
NEMA 4, 115V E1 Pipe- BSP SN NEMA 4, 230V E2 Pipe- DN (Socket Weld) SQ Explosion Proof, 115V EA Explosion Proof, 230V EB Electronic 4-20 ma input, 24 VDC EG
Digit 15 & 16: Base Diaphragm Digits 17 & 18: Rupture Detection/Double
Description Code Description Code
No Base (Standard) NN No Rupture Detection, Single Diaphragm (Standard) NN No Base (Optional) 11 No Rupture Detection, Double Diaphragm (Optional) DD
Rupture Detection (Gauge), Double Diaphragm (Optional) C5
Rupture Detection (Gauge + NEMA 4 Pressure Switch),
DD (Opt.)
Rupture Detection (Gauge + Exp Pr Switch), DD (Optional) SE
Digit 19 & 20: Check Valve Type
Description Code
Single Ball 11 Double Ball 22
Note: Degassing options are available. Consult MRC factory or representative for details
SN
Figure 1. Model/Product Code
4
Instruction Manual
Page 9
SECTION 2 - INSTALLATION
2.1 UNPACKING
Pumps are shipped Free on Board (FOB) factory
or representative warehouse and the title passes to the customer when the carrier signs for receipt of the pump. In the event that damages occur during shipment, it is the responsibility of the customer to
notify the carrier immediately and to le a damage
claim.
Carefully examine the shipping crate upon receipt
from the carrier to be sure there is no obvious damage to the contents. Open the crate carefully so accessory items fastened to the inside of the crate
will not be damaged or lost. Examine all material
inside the crate and check against packing list to be sure that all items are accounted for and intact.
2.2 SAFETY PRECAUTIONS
When installing, operating, and maintaining the MILROYAL® G pump, keep safety considerations foremost. Use proper tools, protective clothing, and eye protection when working on the equipment and install the equipment with a view toward ensuring safe operation. Follow the instructions in this manual and take additional safety measures appropriate to the liquid being pumped.
Be extremely careful in the presence of hazardous substances (e.g., Corrosives, toxins, solvents, acids, caustics, ammables etc.).
2.3 STORAGE
2.3.1 Temporary Storage (Less than 6 Months)
It is preferable to store the material under a shelter in its original package to protect it from adverse weather conditions. In condensing atmospheres, follow the long term storage procedure.
2.3.2 Long Term Storage
(Longer than 6 Months) Primary Considerations
The primary consideration in storage of pump equipment is to prevent corrosion of external and internal components. This corrosion is caused by natural circulation of air as temperature of the surroundings change from day to night, day to day, and from season to season. It is not practical to prevent this circulation which carries water vapor and other corrosive gasses, so it is necessary to protect internal and external surfaces from their effects to the extent possible.
When the instructions given in this section are completed, the equipment is to be stored sheltered/ protected from direct exposure to weather. The prepared equipment should be covered with a plastic sheet or a tarpaulin, but in a manner which will allow air circulation and prevent capture of
moisture. Equipment should be stored 12” or more
above the ground.
If equipment is to be shipped directly from Milton Roy into long term storage, contact Milton Roy to arrange for factory preparation.
2.3.3 Pump Drive
1. Flood the pump drive housing with a high grade
lubricating oil/rust preventative such as Mobile
Oil Corporation product “Mobilarma 524”.
Fill the housing completely to minimize air space and water vapor condensation. After storage,
drain this material and rell the equipment to the
correct oil level with the recommended lubricant for equipment commissioning.
2. Remove drive motor and brush all unpainted
metal surfaces with multipurpose grease
(NLGI grade 2 or 3). Store motor unattached.
5Instruction Manual
Page 10
SECTION 2 - INSTALLATION
2.3.4 Electrical Equipment
1. Motors should be prepared in the manner
prescribed by their manufacturer. If information is not available, dismount and store motors as
indicated in step 3 below.
2. Dismount electrical equipment (including
motors) from the pump.
3. For all electrical equipment, place packets of Vapor Phase Corrosion Inhibitor (VPCI) inside of
the enclosure, then place the entire enclosure, with additional packets, inside a plastic bag.
Seal the bag tightly closed. Contact Milton Roy Service Department for recommended VPCI
materials.
2.4 MOUNTING
Support the pump rmly in a level position on a
solid, vibration- free foundation, preferably with
the base above oor level to protect the pump
from wash downs and to provide easier access
for service. Be sure to allow enough space around
the pump for easy access during maintenance
operations, pump adjustments, and/or oil lling or
draining procedures.
MILROYAL® G pumps are provided with mounting holes to accommodate anchor bolts. Refer to Figure 3 for mounting hole dimensions.
Some MILROYAL® G pumps are shipped with motors dismounted. After anchoring pump in position, install motor, referring to Figure 5.
To avoid damage to pump drive during operation, make sure spring (360) provided with pump is installed in worm shaft prior to motor installation. Pumps installed outdoors should be
protected by a shelter.
2.5 CONVENTION PROCEDURE
A MILROYAL® G pump can, in some cases, be converted from one liquid end plunger size or material of construction to another. For more information on converting between different liquid end models, please contact the Milton Roy factory or your local authorized representative.
2.6 PIPING CONNECTIONS
2.6.1 NPSH Considerations
The MILROYAL® G HPD liquid end is far superior to conventional diaphragm liquid ends for suction
lift and many other NPSH- critical applications.
In these demanding applications, the patented
diaphragm and rell mechanism give this liquid
end truly exceptional performance.
For NPSH apply a 3 psia limitation (instead of 9 psia) in evaluating applications for this liquid end.
Size piping to accommodate peak instantaneous
flow. Because of the reciprocating motion of
the pump diaphragm, pump delivery follows an approximate sine curve with a peak instantaneous
ow equal to pi (3.14) times the average ow. Therefore, piping must be designed for a ow
3.14 times the pump capacity; this means that a pump rated for 100 gallons per hour (379 L/hr.) requires piping sufcient for 3.14 x 100 gph, or 314 gph (1188 L/hr.).
To minimize viscous ow losses when handling
viscous liquids, it may be necessary to use suction piping up to four times larger than the size of the suction connection on the pump. If in doubt, contact your nearest Milton Roy representative to determine the necessary pipe size.
6
Instruction Manual
Page 11
SECTION 2 - INSTALLATION
2.6.2 General Piping Considerations
1. Use extreme care in piping to plastic liquid end pumps with rigid pipe such as PVC. If any stresses or vibration are unavoidable, exible
connections are recommended.
2. Use piping materials that will resist corrosion by
the liquid being pumped. Use care in selecting materials to avoid galvanic corrosion at pump liquid end connections.
3. Use piping heavy enough to withstand maximum
pressures.
4. Remove burrs, sharp edges, and debris from inside piping. Blow out all pipelines before making nal connections to pump.
5. Because vapor in the liquid end will cause
inaccurate pump delivery, piping should be sloped down to pump suction check valve to prevent vapor pockets.
6. When pumping suspended solids (such as
slurries), install plugged crosses at all 90° line
turns to permit line cleaning without dismantling piping.
7. See Figure 4 for a typical recommended pump installation scheme.
2.6.3 Suction Piping Considerations
1. It is preferable to have the suction of the pump ooded by locating the liquid end below the
lowest level of the liquid in the supply tank. Installing the supply vessel on the suction line in close proximity to the pump will help ensure
a ooded suction line.
2. Avoid negative suction pressure conditions
(suction lift), as such conditions adversely
affect metering accuracy. A lift of 20 Ft. of water
column straight out of a supply tank is the maximum suction lift permissible.
3. MILROYAL® G pumps are intended to be
operated with process liquid supplied at or above atmospheric pressure. Although these pumps can move liquids supplied at less than atmospheric pressure, in these negative pressure applications it is important that all connections be absolutely drip free and vacuum tight.
4. When pumping a liquid near its boiling point,
provide enough suction head to prevent the
liquid from “ashing” into vapor when it enters
the pump liquid end on the suction stroke.
5. If possible use metal or plastic tubing for the suction line because such tubing has a smooth inner surface and can be formed into long, sweeping bends to minimize frictional flow losses.
6. A strainer should be used in the suction line to prevent foreign particles from entering the liquid end. This and any other measures to prevent debris from entering and fouling the ball-checks will give increased maintenance-free service.
Check strainer frequently to prevent blockage
which could lead to cavitation.
7. Keep suction piping as short and straight as
possible.
8. Piping size should be one or two sizes larger
than the liquid end suction tting to prevent
pump starvation.
9. If long suction lines are unavoidable, install a
stand pipe or suction accumulator dampener near the pump in the suction line.
10. Suction piping must be absolutely airtight to
ensure accurate pumping. After installation, test suction piping for leaks with air and soap solution.
7Instruction Manual
Page 12
SECTION 2 - INSTALLATION
2.6.4 Discharge Piping Considerations
1. Install pipe large enough to prevent excessive
pressure losses on the discharge stroke of the pump. Maximum pressure at the discharge
tting on the liquid end must be kept at or below
the rated pressure (Max. allowable working pressure shown on the pump nameplate).
2. The pump will not deliver a controlled ow unless the discharge line pressure is 35 psi greater than
the suction line pressure. There are a number of
ways to create an articial pressure, such as by
installing a back pressure valve. (Please contact Milton Roy for recommendations to increase back pressure in slurry applications.)
3. When pumping water-treatment chemicals
directly into boiler drums, use one liquid end assembly for each boiler drum. Discharging into a manifold having the slightest pressure difference between its several discharge connections can diminish metering accuracy as the outlet with the lowest pressure will receive more liquid than the outer outlets.
2.6.6 Pulsation Dampeners
An accumulator, surge chamber, surge suppressor, or pulsation dampener should be used with the back pressure valve in the discharge line to
absorb the ow peaks between the pump and
the back pressure valve. Without the pulsation dampener the valve mechanism will snap open and closed with the surge from each pump stroke. The pulsation dampener will allow the back pressure valve to oscillate about a partly-closed position, thus minimizing wear on the valve. Discharge line pulsation dampeners offer the
further advantage of limiting the ow and pressure
variations characteristic of this kind of pump. Installing a properly sized pulsation dampener will improve pump performance and may reduce system costs dramatically by permitting the substitution of smaller piping. Please contact Milton Roy for further information on pulsation dampeners.
2.6.5 Back Pressure Valves
A Milton Roy Back Pressure Valve should be
installed in the discharge line near the pump to ensure sufficient discharge head pressure for proper pump metering action. Normally, the valve
should be located near the pump. However, back
pressure valves for large pumps with long and extremely small discharge lines may have to be installed near the point of discharge into the process (to minimize siphoning tendencies).
8
Instruction Manual
Page 13
SECTION 2 - INSTALLATION
2.6.7 Pressure Relief Valve (PRV)
Maximum safety and reliability may be ensured by protecting liquid ends and piping with an external pressure relief valve installed in the system discharge line. Although the pump is protected against excessive pressure by an internal relief valve, to prevent a blocked discharge line from causing damage to the piping or process equipment, install a Milton Roy pressure relief valve in the pump discharge line. This valve is designed and sized to
handle system ow rates and pressures safely
while resisting corrosion by the process liquid. Install the safety valve in the discharge line between the pump and the nearest shut- OFF valve. (This will prevent potential system damage from accidental valve closure.) Pipe the pressure relief valve outlet back to the suction tank or to drain, but in either case ensure that the pipe end is continuously visible so pressure relief valve leakage may be detected. Milton Roy pressure relief valve must be installed in accordance with its user manual top of supply tank in order to function properly.
2.6.8 Check Valves
A check valve should be installed at the point where the discharge line enters a boiler or other
high-pressure vessel. This will prevent back ow
through the discharge piping and will isolate the pump discharge from system pressures (a safety consideration).
2.6.9 Shut- OFF Valves
In order to isolate the pump during maintenance, provide shut- OFF valves in both suction and discharge lines next to the pump. Locate discharge line shut- OFF valve downstream from the inlet connection of the safety valve. Figure 4 shows recommended valve locations.
2.7 ELECTRICAL CONNECTIONS
Ensure that the electrical supply matches the pump motor nameplate characteristics. Before operating
the pump, check the direction of rotation of the motor to be sure it matches the direction of the arrow stamped on the motor (rotation should be clockwise when viewed from the top of the motor). If motor rotation is incorrect, refer to the motor data plate or motor manufacturer’s instructions for reversing.
OPERATION WITH THE WRONG
MOTOR ROTATION WILL DAMAGE
THE PUMP AND MOTOR AND VOID THE WARRANTY.
DO NOT FORGET TO CONNECT
THE PUMP TO AN EARTH
GROUND!
Electric protection of the motor (fuses, overload
meters or relays) should correspond to the rated current indicated on the motor data plate.
9Instruction Manual
Page 14
SECTION 3 - OPERATION
3.1 INITIAL START- UP
Check that all mounting bolts are tight, piping is
installed properly, and the discharge line is open.
Check oil drain plug for tightness. Remove the orange oil ll cap and ll the pump casing until
level is between the top two marks on the oil cap
dipstick. (approximately 3-1/2 quarts). DO NOT OVERFILL ABOVE TOP DASH!
Note:
The oil furnished with the pump is grade AGMA No. 5 EP with a viscosity of 1000 SSU at 100°F (218.4 cSt at 40°C). For operation in ambient temperatures below 50°F (10°C), substitute AGMA No. 2 EP with a viscosity of 400 SSU at 100°F (86.4 cSt at 40°C). Manufacturers’ equivalent oils are shown below.
DO NOT START UP PUMP DRIVE
MOTOR BEFORE FILLING GEAR
BOX WITH OIL OR SERIOUS DAMAGE WILL OCCUR.
Chevron N.L. Gear Compound 220
ABOVE 50°F:
BELOW 50°F:
Food Grade
Alteration
Exxon Spartan E.P. 220
Mobil Mobilgear 630
Texaco Meropa 220
Chevron N.L. Gear Compound 68
Exxon Spartan E.P. 68
Mobil Mobilgear 626
Texaco Meropa 68
Shell Omaha 68
Nevastane EP220
3.1.1 Start- Up for New Pump
For pumps received from the factory, the
displacement chamber (600) is already lled with oil. Simply remove the orange oil ll cap from the pump casing and ll the casing with the specied
oil to a level between the top two dashes on the dipstick. DO NOT OVERFILL ABOVE TOP DASH! Pump is now ready for operation. Operation of the air purge button may be required to remove air that may have come out of solution from the
oil during shipment and storage. Refer to “USE OF AIR PURGE BUTTON” section for operation
instructions. The integral pump relief valve is
factory adjusted according to customer specied
setting. For instructions on adjustment of the pump relief valve please refer to the next section.
BEFORE SWITCHING ON POWER
TO THE PUMP, TURN THE
CAPACITY ADJUSTMENT KNOB TO ZERO. CHECK THAT ALL
SHUT- OFF VALVES IN THE SUCTION AND DISCHARGE LINES
ARE OPEN BEFORE INCREASING THE CAPACITY
ADJUSTMENT FROM ZERO.
10
Instruction Manual
Page 15
SECTION 3 - OPERATION
3.1.2 Start- Up of Pump Containing No Oil in Casing and Displacement Chamber
The following instructions assume that both the pump casing and liquid end (displacement chamber) contain no oil. This condition typically exists when the pump is subjected to annual maintenance during which oil may be drained from the pump casing and oil may escape from the displacement chamber during diaphragm replacement. New pumps received from the factory will have
an empty pump casing and a lled displacement
chamber (liquid end). Please refer to the previous section for start- up of new pumps. After pump
casing is lled to correct oil level (between top two
dashes on oil cap dipstick), perform the following operations before placing the pump into service. Numbers refer to item numbers shown in assembly drawings (Figures 7-9) located in the back of this manual.
1. Remove hydraulic 3- function valve (refer to Figure 8):
a. Remove relief valve cap piece (850).
b. Make sure relief valve locknut (900) is tight
to maintain previous relief valve setting upon start- up.
c. Remove purge button and relief valve
adjustment assembly by removing large
adjustment nut (910).
d. Using needle-nose pliers, remove spring
(950).
e. Using same pliers, remove relief valve poppet
by gently gripping the top of the valve body
(960).
2. Make sure pump capacity adjustment is set to 100%.
3. Fill the opening in the displacement chamber (600) through the port uncovered by removal of the 3- function valve in step 1 with the same oil used to ll the pump casing. Fill the chamber
slowly, allowing air bubbles to escape, until the oil level reaches the level of the drain tube
(640).
4. Reinstall 3- function valve:
a. Gently gripping the top of the relief valve
poppet (960) with needle-nose pliers, drop
the poppet assembly down into the empty relief valve port.
b. Drop spring (950) back into relief valve port.
c. Make sure washer (935) is in place above
the O-ring (940) on purge stem (930) and
reinstall purge and relief valve adjustment assembly by screwing large adjustment nut
(910) back into place. Make sure adjustment nut (910) is tight.
d. Reinstall relief valve cap piece (850).
5. The pump is now properly lled with oil and ready for service. If the relief valve locking nut (900)
remained tight during the above procedure, the relief valve setting should remain unchanged. If not, refer to next section for instructions on how to set relief valve.
BEFORE SWITCHING ON POWER
TO THE PUMP, TURN THE CAPACITY
ADJUSTMENT KNOB TO ZERO. CHECK THAT ALL SHUT- OFF VALVES
IN THE SUCTION AND DISCHARGE LINES ARE OPEN BEFORE
INCREASING THE CAPACITY ADJUSTMENT FROM ZERO.
6. Make sure that all air has been bled from the suction piping and pump head. This can be accomplished by opening all suction line valves as well as the system drain (Prime/Air Purge) valve shown in Figure 4 and allowing uid to ow into drain until all air has been purged. If drain valve not present, with the pump capacity set
to 100%, operate the pump under no discharge
pressure until the entire pumping system has
been lled.
11Instruction Manual
Page 16
SECTION 3 - OPERATION
3.2 RELIEF VALVE ADJUSTMENT
All MILROYAL® G liquid ends have a built in relief
valve which allows hydraulic uid to return to the
pump casing if excessive pressure builds up in the discharge line. This effectively stops the pump from pumping, since the forward stroke of the piston
will not displace the hydraulic uid and force the diaphragm to ex. During operation of the pump, a
relief condition caused by over pressurization can easily be seen by looking through the sight glass
(630, Figure 7) for excessive oil ow from the drain tube (640, Figure 8).
Note:
Under normal operation, a few drops of oil
should escape from the drain tube during each
pump stroke due to normal oil ow through the air bleed ball (970, gure 8). If a stream of oil
from the drain tube is evident on each pump
stroke, the system pressure has exceeded the
pump relief valve setting and the pump is in a
relief condition.
The MILROYAL® G liquid end relief valve may be adjusted to operating conditions by the following
procedure. Adjust the relief valve after rst installing
the pump and after any maintenance procedures.
THE PRESSURE RELIEF VALVE IS
FACTORY SET TO OPEN AT A
PRESSURE 15% OVER THE CUSTOMER SPECIFIED OPERATING
PRESSURE OR AT 15% ABOVE THE MAXIMUM PRESSURE
RATING OF THE PUMP IF NO OPERATING PRESSURE IS
SPECIFIED BY THE CUSTOMER. WHEN ADJUSTING THE VALVE
SETTING, NEVER SET THE VALVE AT A PRESSURE GREATER
THAN 15% OVER THE PUMP MAXIMUM PRESSURE RATING.
3.2.1 Relief Valve Adjustment (With an Adjustable System Back pressure Valve). Refer to Figures 7 & 8.
The following procedure assumes that a back pressure valve and pressure gauge are installed in the discharge line. If these components are not installed, refer to next section.
1. Make sure all system shut- OFF valves are
open and that the back pressure valve is backed
out to allow for ow against zero discharge
pressure.
2. Start pump and set capacity at 100%. If a drain
valve is present in the discharge line, pump process liquid to drain or other safe point to
establish proper pumping action. Close drain.
3. Slowly increase system pressure until:
a. Signicant ow is observed from the drain
tube (640, gure 8) as viewed through the sight glass (630, gure 7) or
b. The system pressure reaches 15% over the
desired system pressure.
4. For condition (a) in step 4, if relief condition occurs at less than 15% above desired pump
operating pressure, the relief valve setting must be increased. Remove valve cover
(850) and increase relief valve setting by turning the adjustment screw (890) clockwise
until only a few drops of oil escape on each pump stroke (normal leakage past air bleed
ball-980). Increase system pressure to 15%
above desired operating pressure to verify that pump is now in relief condition. If it is not, reduce relief valve setting by turning adjustment screw
(890) counterclockwise until relief is observed
in sight glass drain tube at a pressure equal to
15% greater than desired operating pressure.
Lock-in relief valve setting by tightening locking
nut (900) while holding adjustment screw (890)
stationary. The relief valve is now properly
adjusted. Reinstall valve cover (850).
5. For condition (b) in step 4, the setting of the
relief valve should be reduced. Remove valve
cover (850) and turn adjustment screw (890)
counterclockwise until relief is observed in sight glass drain tube at a pressure equal to
15% greater than desired operating pressure.
Lock-in relief valve setting by tightening locking
nut (900) while holding adjustment screw (890)
stationary. The relief valve is now properly
adjusted. Reinstall valve cover (850).
12
Instruction Manual
Page 17
SECTION 3 - OPERATION
3.2.2 Relief Valve Adjustment (Without an Adjustable System Back Pressure Valve).
If no adjustable back pressure valve is present
in the discharge line, use the following simplied
procedure to check and/or set the relief valve setting.
1. If pump is in a relief condition at normal
operating pressure, the relief valve setting
should be increased. Remove valve cover (850)
and increase relief valve setting by turning the
adjustment screw (890) clockwise until only a
few drops of oil escape on each pump stroke
(normal leakage past air bleed ball) (970).
Turn adjustment screw an additional ½ turn to provide an adequate buffer zone. Lock-in relief
valve setting by tightening locking nut (900) while holding adjustment screw (890) stationary.
The relief valve is now properly adjusted.
Reinstall valve cover (850).
2. If pump is not in a relief condition at normal
operating pressure, and the operator wishes
to reset the valve setting to approximately 15%
above operating pressure(recommended), use the following procedure. Remove valve
cover (850) and decrease the relief valve setting by turning the adjustment screw (890) counterclockwise until a stream of oil ows from the drain tube (640) on each pump stroke.
Now slowly turn adjustment screw clockwise until only a few drops of oil escape on each pump stroke (normal leakage past air bleed ball). Turn screw an additional ½ turn to provide an adequate buffer zone. Lock-in relief valve
setting by tightening locking nut (900) while holding adjustment screw (890) stationary.
The relief valve is now properly adjusted.
Reinstall valve cover (850).
3.3 USE OF AIR PURGE BUTTON Refer to Figure 7 & 8:
As with any hydraulically actuated diaphragm pump, dissolved air will come out of solution during normal operation which can negatively impact pump performance if not removed from the pump displacement chamber. The MILROYAL® G hydraulic 3- function valve is equipped with two mechanisms for removal of this gas: a continuous air bleed and an air purge button. The continuous air bleed portion of the valve is
composed of a sealed ball (970) which allows for a
controlled leakage of a few drops of oil, and any small accumulations of evolved gas, on each pump stroke. Larger quantities of air can be quickly removed by
pressing the spring-loaded purge button (860), until
it reaches its mechanical stop, for a few seconds. Upon doing so, the operator will observe a stream
of oil and air escaping from the drain tube (640).
The need for use of the purge button to remove a large quantity of air can be caused by several factors:
1. Blocked suction line: A partially or fully blocked
suction line can create a vacuum pressure condition in the hydraulic system which pulls significant quantities of dissolved gas from solution.
2. Oil Change: The recommended annual
changing of the oil in the pump drive can lead to the presence of air pockets in the displacement
chamber (600).
3. Diaphragm Replacement: Results in signicant
loss of oil from the displacement chamber.
4. Pump Start- up After Long Idle Period: If the pump has sat idle for a signicant time, gas
may come out of solution from the oil and collect into pockets which can negatively impact pump
ow. Depression of the purge button will quickly
evacuate these pockets and restore the pump to desired performance.
13Instruction Manual
Page 18
SECTION 3 - OPERATION
The operator should only activate the purge button if some type of pump upset occurs such as the
above 4 examples. When activating the purge, only press button for 2-3 seconds or until a stream of oil owing from the drain tube (640) is seen through the sight glass (630). Immediately after activation of the purge button, a temporary reduction in ow will occur as the rell system replenishes oil lost during the purge. However, the pump should return to normal operation within 1 to 2 minutes after
activation of the purge button. If after that time, the
pump ow rate is still less than it should be, repeat the purge operation and wait another 2 minutes. If ow has still not resumed to expected levels,
consult the troubleshooting section of this manual.
3.4 MANUAL CAPACITY CONTROL
To adjust pump capacity on standard pumps equipped with manual stroke adjustment, first loosen the stroke locking screw located in the pump side cover. Pump capacity is then adjusted by turning the micrometer-type stroke adjustment knob clockwise to decrease capacity or counterclockwise to increase capacity as required.
The adjustment scale is marked in percent (%)
of full stroke, with calibration lines on the knob at
1% intervals. After adjusting the knob to the desired
capacity setting, hand tighten the stroke locking screw to maintain the capacity setting.
3.5 FILLING PUMPING SYSTEM
For proper pump operation, it is especially important that pump suction and discharge lines be free of entrained air. To ensure this condition, operate the
pump without any discharge pressure and ll the
entire pumping system with liquid before starting pressure tests. A simple method to assure priming of the pump is to install a tee and a shut- OFF valve at the discharge connection of the pump.
If the pump is idle for long periods, temperature changes in the process liquid may produce air in the system. To discharge the air, install a valve in the discharge line which will allow the process liquid to be pumped to a drain when starting the pump.
3.6 CAPACITY CALIBRATION
After the rst 12 hours of operation, the pump should be tested and calibrated to nd the exact pump capacity under specic operating conditions and capacity settings for the specic uid being pumped. Typically, calibrating the pump at 100, 50, and 10 percent capacity settings is enough to
establish a pump performance curve throughout the adjustment range.
The pump can be calibrated by measuring the decrease in liquid level pumped from a calibrated vessel. This method is recommended for hazardous liquids because it eliminates operator contact
with the liquid. Milton Roy test-tube Calibration Columns are available for convenient and accurate
calibration of any pump. The pump can also be calibrated by collecting and measuring pumped liquid at the pump discharge port in which case it will be necessary to create discharge head at the liquid takeoff point so that the pump will operate properly. (See Section 2 for recommended ways
to do this.)
14
THIS METHOD IS NOT
GENERALLY RECOMMENDED
AS IT MAY EXPOSE OPERATING PERSONNEL TO HAZARDOUS
LIQUIDS.
Instruction Manual
Page 19
SECTION 4 - MAINTENANCE
4.1 RECOMMENDED SPARE PARTS
To avoid delays in repairs, a Routine Preventative
Maintenance Kit should be ordered for each pump.
The RPM kit contains an oil strainer and check valve parts. Part orders must include the following information:
1. Quantity required.
2. Part Number.
3. Part Description.
4. Pump serial number (found on pump
nameplate).
5. Pump model number (found on pump nameplate).
6. Pump product code (found on pump nameplate).
Always include the serial number, model number, and product code in all correspondence regarding this unit.
4.2 SHIPPING PUMPS FOR REPAIR
Pumps can not be accepted for repair without a Return Material Authorization. Pumps should be clearly labeled to indicate the liquid being pumped.
Process liquid should be ushed from the pump
liquid end and oil should be drained from the pump housing and displacement chamber. To drain oil
from the displacement chamber, unscrew the rell valve body (660, gure 8) from the displacement
chamber. Allow oil to drain into a waste container.
Remove diaphragm (510) and tilt up the back of
the pump until oil ceases to drain from the front of the pump.
Note:
Federal law prohibits handling of equipment that is not accompanied by an OSHA Safety Data Sheet (SDS). A completed SDS must be packed in the shipping crate with any pump shipped for repair. These safety precautions will
aid the troubleshooting and repair procedure
and preclude serious injury to repair personnel from hazardous residue in pump liquid end. A Safety Data Sheet must accompany all returns.
All inquiries or parts orders should be addressed to your local Milton Roy representative or distributor.
4.3 ROUTINE PREVENTATIVE MAINTENANCE
BEFORE ANY MAINTENANCE,
RELIEVE ALL PRESSURE
FROM SYSTEM, ISOLATE LIQUID END FROM ALL SOURCES
OF PROCESS LIQUID WITH APPROPRIATE VALVING, AND
PURGE LIQUID END OF ALL PROCESS LIQUID.
4.3.1 Oil Replacement
I n i t i a l l y , c h a n g e o i l i n p u m p c a s i n g a f t e r t h e  r s t 250 hours of operation. Then change oil after every 4000 hours of operation or every six months
whichever comes first. Oil can be drained by
removing the drain plug (20, gure 6). When oil has nished draining, make sure that the area
around the drain hole is clean. Screw drain plug back in securely. Fill the pump housing with the recommended oil until the level is between the top two marks on the dipstick. DO NOT OVERFILL(above top mark)! Replace the oil
ll cap and screw rmly in place. Dispose of oil
according to any federal, state or local codes which may apply.
Note:
It is not necessary to purge the liquid end
displacement chamber of oil during annual oil
replacement.
15Instruction Manual
Page 20
SECTION 4 - MAINTENANCE
4.3.2 Check Valves
Milton Roy recommends that check valve balls, seats, gaskets, and O-rings be replaced on an annual basis. If highly corrosive material (acids, slurries etc.) is being pumped, some applications may require more frequent replacement. Milton Roy recommends an annual tune up using
a Routine Preventive Maintenance (RPM) Kit.
RPM kits contain replacements for those parts
which are subject to wear; specically the ball
checks, check valve seats, gaskets/seals, and the strainer. Replacing these parts annually with an RPM kit can reduce the possibility of unexpected downtime and will help to extend pump life.
To determine if check valves need maintenance, disassemble the check valves following the
instructions in the following “Check Valve Replacement” section. In valves that permit
disassembly, inspect the ball check and seat for chemical or physical damage. The ball should be perfectly round and free of pits, marks, or scratches. The seat should retain a smooth edge where the ball contacts for proper sealing. If the seat edge is worn or damaged, or has any pits, marks, or scratches, it should be replaced. If the ball and/ or seat is excessively damaged, the replacement schedule should be shortened accordingly. If the ball and seat are both in good condition, the replacement schedule can be lengthened.
BEFORE CARRYING OUT ANY
SERVICING OPERATION ON THE
METERING UNIT OR PIPES, DISCONNECT ELECTRICAL
POWER FROM THE PUMP, AND TAKE THE NECESSARY STEPS
TO ENSURE THAT THE HARMFUL LIQUID THEY CONTAIN
CANNOT ESCAPE OR COME INTO CONTACT WITH
PERSONNEL. SUITABLE PROTECTIVE EQUIPMENT MUST BE
PROVIDED. CHECK THAT THERE IS NO SYSTEM FLUID
PRESSURE BEFORE PROCEEDING WITH DISMANTLING OF
LIQUID END COMPONENTS.
4.3.3 Cleaning Fouled Check Valves
Check valve assemblies are designed to be self
cleaning and should seldom need servicing. Fouled check valves can usually be cleaned by pumping a solution of mild detergent and warm water (if compatible with liquid being pumped) for
15 minutes, followed by ushing with water.
4.3.4 Check Valve Replacement
Before beginning work on the valve assemblies,
make sure the shut- OFF valves are closed and that pressure has been bled from the system. When replacing the valves, take care to systematically change their O-rings and/or gaskets. Take care to properly assemble the valve assemblies. In valves that permit replacement of ball and seat, the ball must be placed on the sharp edge of the seats.
For each plunger size, check valves are supplied
in three different congurations: plastic- single
ball, plastic-double ball, and metallic- double ball.
Be sure to refer to the appropriate instructional set
below pertaining to your plunger size and valve type.
BE SURE TO FOLLOW
INSTRUCTIONS CAREFULLY
AND REFER TO THE APPROPRIATE FIGURE WHEN
REASSEMBLING CHECK VALVES. IF CHECK VALVE
CARTRIDGES ARE INSTALLED INCORRECTLY, ONE OF THE
FOLLOWING WILL OCCUR: (A) IMMEDIATE SEVERE DAMAGE
TO PUMP MECHANISM, (B) NO PUMPING, (C) REVERSE
PUMPING ACTION (FROM DISCHARGE LINE INTO SUCTION
LINE).
16
Instruction Manual
Page 21
SECTION 4 - MAINTENANCE
1-1/4” Plunger;Plastic Single Ball Check Valves: see Figure 12
1. Unscrew the valve body (445).
2. Remove the cartridge assembly (425): includes
cartridge (ball, seat, ball guide), O-ring, and washer.
3. Clean the valve housing and mating port in the
liquid end.
4. Press a new clear plastic washer into valve
body.
5. Install new cartridge valve assembly in orientation shown in gure 12.
• Make sure that seat end of cartridge (white)
is always facing down.
• On discharge side, drop cartridge assembly
into threaded port in head. The O-ring should be stretched around outside of cartridge on same end as ball seat. Screw valve body into discharge side of diaphragm head until valve is hand tight. Do not overtighten.
• On suction side, drop cartridge assembly
into check valve body. The O-ring should be stretched around outside of cartridge on opposite end of ball seat. Screw suction valve housing with cartridge valve into suction side of head. Do not overtighten.
1-1/4” Plunger; Metallic Double Ball Check Valves: see Figure 13
The metallic check valves used on the 1-1/4”
plunger size pumps are precision assembled at the factory. Do not attempt to disassemble these
cartridges. If they become inoperative, ush them
with solvent, wash them with warm detergent and blow them out with compressed air to remove any foreign matter. If this treatment does not eliminate the trouble, the cartridge assembly should be replaced.
A. Disassembly (refer to gure 13)
1. The check valve cartridge assemblies use an SAE straight thread with an O-ring seal to
facilitate port alignment with the connecting pipes. To remove the cartridge from the liquid
end, rst loosen the lock nut (435) one or two threads, then unscrew the cartridge (444,
445).
2. Remove and discard the O-ring (441) and split ring (439).
3. Carefully clean any parts to be reused. If any
chemicals are used in the cleaning process, ensure that they are compatible with the process liquid.
17Instruction Manual
Page 22
SECTION 4 - MAINTENANCE
B. Reassembly (refer to gure 13)
1. To install the cartridge, position the lock nut (435) toward the shoulder of the cartridge so
that the recess on the face of the lock nut is
adjacent to the O-ring (441).
2. Make certain the split ring (439) is coiled in
a counterclockwise helix(this is opposite the direction normally employed by suppliers of these rings). Fit this split ring in the lock nut
recess. Push it rmly down in the recess as
completely as possible.
3. Install a new O-ring (435) against the split
ring.
Note:
To assure a tight, leak free seal, new O-rings
and split rings should be used each time the
check valves are disassembled.
4. Screw the cartridge assembly (444, 445) into the
liquid end until the O-ring band is approximately level with the top of the spot face in the liquid
end, then screw it one (1) additional turn plus a
partial turn as required to align the pipe thread port with connecting pipe.
1-3/4, 2-1/2, and 3”Plungers: Plastic Single- Ball Check Valves: see Figure 11
A. Disassembly
1. Unscrew the union nut (435). The union end (445) is held in place by the union nut and will
now separate easily from check valve ball guide
(424).
2. Unscrew the ball guide (424) from the liquid
end.
3. Screw the union nut partially (one or two turns)
onto the end of the ball guide containing the
seat. Be sure the union nut is loosely installed to allow for a gap for the seat (420) to drop into
as it is removed from the ball guide.
4. Sit the ball guide/union nut onto a at surface
with the union nut down. Looking into the top of the ball guide, you will see four large holes surrounding one small hole. Insert a thin, blunt instrument such as a hex head screwdriver into the small center hole until it rests on the top of
the ball (422).
5. Tap screwdriver gently with a hammer until ball and seat are released from the ball guide.
SUCTION AND DISCHARGE
CHECK VALVE CARTRIDGES
ARE NOT IDENTICAL. BE SURE THAT THE CORRECT
CARTRIDGE IS BEING SCREWED INTO THE PROPER PORT.
(DISCHARGE CARTRIDGES HAVE HEXAGONAL CAP ON THE
TOP; SUCTION CARTRIDGES DO NOT.) IF CHECK VALVE
CARTRIDGES ARE INSTALLED INTO THE WRONG PORT, ONE
OF THE FOLLOWING WILL OCCUR: (A) IMMEDIATE SEVERE
DAMAGE TO PUMP MECHANISM, (B) NO PUMPING, (C)
REVERSE PUMPING ACTION (FRONT DISCHARGE LINE INTO
SUCTION LINE).
5. After completing pipe connection, tighten lock nut securely against spot face so that O-ring is trapped in chamfer of liquid end thread. Make sure that the split ring is completely contained in its recess and not extending to the outside.
18
Instruction Manual
IF YOU ARE DISASSEMBLING
UNIT FOR INSPECTION ONLY,
BE SURE TO USE A BLUNT INSTRUMENT AND TAP GENTLY TO
AVOID DAMAGING THE BALL. IF THE BALL AND/OR SEAT ARE
DAMAGED DURING DISASSEMBLY, THEY WILL NEED TO BE
REPLACED. TO AVOID DAMAGE, IF AVAILABLE, IT IS
ADVISABLE TO USE GENTLE AIR PRESSURE (APPLIED AT
END OPPOSITE THE SEAT-420) FOR BALL AND SEAT
REMOVAL.
6. Carefully remove the two O-rings (419) from the
ball guide and seat.
Page 23
SECTION 4 - MAINTENANCE
7. Inspect the balls carefully. If they are smooth,
round and free of deposits or pits, they are
suitable for continued use. Examine the check
valve seats. The area of the seat in contact with the ball (the un-chamfered side) must be in near perfect condition for continued use. Any visible imperfection on the seating surface (pits, erosion, cracks) necessitates replacement of the seat. If both the balls and the seats are in good condition, then the length of time between parts replacement may be increased. If the balls and seats are severely damaged, then the length of time between parts replacement
should be shortened. Carefully clean any
parts to be reused. If any chemicals are used in the cleaning process, ensure that they are compatible with the process liquid.
B. Reassembly
1. Drop the ball into the curved inner chamber end
of the ball guide.
2. Sit the ball guide on a at surface so that the side
with the ball faces upwards. Position seat on the ball guide, trapping the ball inside. When the seat is pressed into the ball guide, the beveled edge of the seat must be facing outward. The bevel should not face the inside of the check valve (refer to Figure 11). Use a at surface such as a board to press the seat into the ball guide
with rm, even pressure.
IF THE SEAT IS IMPROPERLY
POSITIONED (WITH BALL
AGAINST BEVELED SURFACE), THE BALL WILL NOT CREATE
A TIGHT SEAL AND POOR PUMPING PERFORMANCE WILL
RESULT.
3. Fit new O-rings into grooves in the ball guide
and seat.
Note:
To assure a tight, leak free seal, new O-rings should be used each time the check valves are disassembled.
4. Position the union end (445) onto the correct
end of the ball guide. Refer to Figure 11 as the correct end is determined by whether the valve is intended for the suction or discharge port of
the liquid end. Slip the union nut (435) over the
union end and screw tightly (hand tight only) onto the ball guide.
THE ORDER OF ASSEMBLY OF
THE SUCTION AND DISCHARGE
CHECK VALVES IS DIFFERENT. REFER TO FIGURE 11 FOR
PROPER ASSEMBLY ORDER. IF CHECK VALVE CARTRIDGES
ARE INSTALLED INCORRECTLY, ONE OF THE FOLLOWING
WILL OCCUR: (A) IMMEDIATE SEVERE DAMAGE TO PUMP
MECHANISM, (B) NO PUMPING, (C) REVERSE PUMPING
ACTION (FROM DISCHARGE LINE INTO SUCTION LINE).
5. Screw the valve assembly into the liquid end body(hand tight only). DO NOT
OVERTIGHTEN!
1-1/4” Plunger, Plastic Double Ball Check Valves 1-3/4”, 2-1/2”, 3” Plungers, Plastic &
Metallic Double Ball Check Valves
A. Disassembly (Refer to Figure 10).
Double ball check valves differ from the plastic single ball check in that the ball seat is now integral to the ball guide. The seats cannot easily be inspected for damage or wear. If you suspect that the check valve may be damaged or worn, replace the entire check valve assembly as per instructions below.
1. If metallic valve, unscrew the coupling (445) from the ball guide (424). If plastic, unscrew the union nut (435, gure 11) and remove union end (445, gure 11) from the ball guide (424).
2. Unscrew the ball guide (424) from the liquid
end.
3. Remove and discard the O-rings (419).
4. Remove ball stop (420) and balls (421, 422).
19Instruction Manual
Page 24
SECTION 4 - MAINTENANCE
Inspect the balls carefully. If they are smooth, round and free of deposits or pits, they are
suitable for continued use. Examine the ball seat areas in the valve body (424). A magnifying
glass is recommended for this inspection. The seat must be in near perfect condition for continued use. Any visible imperfection on the seating surface (pits, erosion, cracks) renders the seat unusable thereby requiring replacement
of the valve body (424). If both the balls and the
seats are in good condition, then the length of time between parts replacement may be increased. If the balls and seats are severely damaged, then the length of time between parts
replacement should be shortened. Carefully
clean any parts to be reused. If any chemicals are used in the cleaning process, ensure that they are compatible with the process liquid.
B. Reassembly (Refer to Figure 10):
1. Drop the balls (422, 421) into the valve body (424). Drop ball stop (420) into place making
sure that side with O-ring groove is facing up.
Install new O-rings (419) on both ends of valve
body.
(445) onto the check valve assembly, trapping a new O-ring (419) between the coupling and
the check valve assembly. If plastic check
valve, position the union end (445) onto the
correct end of the ball guide. Slip the union
nut (435) over the union end and screw tightly
(hand tight only) onto the ball guide. DO NOT OVERTIGHTEN!
4.3.5 Oil Strainer Replacement Refer to Figure 8.
Over time, the oil strainer (670) which screws into the rell valve body (660) can become fouled or
clogged. It should therefore be replaced yearly and is included with the check valve parts in the
RPM Kit. If the strainer becomes clogged more
frequently than once a year (which is extremely unlikely), it can be ordered separately.
Since the oil must rst be drained from the pump
casing, it is a good idea to schedule strainer replacement with oil replacement.
1. Drain oil as described in the above “Oil Replacement” section of this manual.
2. Unscrew the strainer (670) from the rell valve body (660).
Note:
To assure a tight, leak free seal, new O-rings should be used each time the check valves are disassembled.
2. Screw the correct end of the check valve
assembly into the liquid end (hand tight only) trapping a new O-ring between the liquid end and the check valve assembly. DO NOT
OVERTIGHTEN!
THE END OF THE CHECK VALVE
THAT IS SCREWED INTO THE
PUMP HEAD IS DIFFERENT FOR THE SUCTION AND
DISCHARGE CHECK VALVES. REFER TO FIGURE 10 FOR
PROPER ASSEMBLY ORDER. IF CHECK VALVE CARTRIDGES
ARE INSTALLED INCORRECTLY, ONE OF THE FOLLOWING
WILL OCCUR: (A) IMMEDIATE SEVERE DAMAGE TO PUMP
MECHANISM, (B) NO PUMPING, (C) REVERSE PUMPING
ACTION (FROM DISCHARGE LINE INTO SUCTION LINE).
3. If metallic check valve, screw the coupling
20
Instruction Manual
3. Clean any debris from the strainer cavity in the
valve body.
4. Screw a new strainer into the rell valve body.
5. Rell pump casing with recommended oil as described in the “Oil Replacement” section.
Page 25
SECTION 4 - MAINTENANCE
4.4 CORRECTIVE MAINTENANCE
4.4.1 3- Function Hydraulic Valve
The 3- function hydraulic valve assembly (see Figure 8) operates in ltered hydraulic oil
and should require maintenance only if unusual circumstances occur, such as if corrosive media
contaminates the uid.
Assembly and disassembly is straightforward. Follow instructions in the “Start- Up of Pump
Containing No Oil in Casing and Displacement Chamber” section of the manual. Field servicing
should be limited to inspection and cleaning only. Repairs of this critical component should only be carried out by an authorized Milton Roy repair facility.
4.4.2 “MARS” Valve Assembly
The Mechanically Activated Rell System (MARS)
valve assembly (see Figures 8 & 9) requires no
periodic maintenance. Clean hydraulic oil is critical
for proper operation. Field servicing should be limited to inspection and cleaning only. Repairs of this critical component should only be carried out by an authorized Milton Roy repair facility.
The valve is designed to be easily removed through the front of the pump without having to remove the displacement chamber. The following steps describe the procedure for removal of the valve from the displacement chamber (refer to Figure 9):
A. Disassembly
1. Remove liquid end according to instructions in the “Removing the Liquid End” portion of
the “Diaphragm Replacement” section of the manual.
2. Insert a small tip screw driver into one of the two small holes in the valve button (780) and gently pry out plastic cap (790).
4. Slide OFF activation button (780) and spring (800).
5. Remove large retaining ring (810) using the
appropriate retaining ring pliers (Waldes Truarc
Internal Type, Waldes Truarc part# 0300).
6. Reinstall small retaining ring (820) in groove in valve stem (770).
7. To avoid damage to valve stem, grip retaining
ring with pliers and pull remaining valve assembly out of displacement chamber.
8. Discard O-rings (830,840) and retaining rings (810, 820).
NOTE:
When reinstalling, make certain that new O-rings and retaining rings are installed on MARS assembly.
B. Reassembly
1. Install new O-rings (830, 840) on valve body (750) and apply a light layer of O-ring grease
to O-rings.
2. Push assembly into place until it reaches stop
in displacement chamber.
3. Reinstall large bowed retaining ring (810). Using a hammer and at tipped screwdriver,
gently tap the ring to insure that it is securely seated in the retaining groove machined into the displacement chamber.
4. Reinstall spring (800) and activation button (780).
5. While pressing button (780), reinstall small retaining ring (820). Gently tap on the ring to
insure that it is securely seated in the retaining ring groove machined into the valve stem
(770).
6. Press plastic cap piece (790) into activation button (780).
3. While pressing down on button (780), remove the retaining ring (820) using the appropriate retaining ring pliers (Waldes Truarc External Type, Waldes Truarc part# M-1520).
7. Valve is now ready for service.
21Instruction Manual
Page 26
SECTION 4 - MAINTENANCE
4.4.3RellValveAssembly(see Figure 8).
The only required periodic maintenance for the refill valve assembly is the suggested annual replacement of the oil strainer (see above “Oil
Strainer Replacement” section). Clean hydraulic
oil is critical for proper operation. Field servicing of the valve assembly is limited to inspection and cleaning only. Repairs of this critical component should only be carried out by an authorized Milton Roy repair facility.
The valve is designed to be easily removed through the bottom of the pump without having to remove the displacement chamber. The following steps describe the procedure for removal of the valve from the displacement chamber (Figure 8):
A. Disassembly
1. Drain oil from the pump housing as described in the above “Oil Replacement” section.
2. Unscrew the valve body (660) from the displacement chamber (600).
3. Clean any debris from the valve cavity in the
displacement chamber.
4. Discard O-rings (720, 730).
Note:
When reinstalling the valve assembly, be sure to install new O-rings (720, 730).
B. Reassembly
4.4.4 Diaphragm Replacement
MILROYAL® G liquid ends are designed to provide reliable service under normal operating circumstances and should not require replacement
of the diaphragm. However, in the unlikely event
of a failure, the diaphragm can be replaced by the following the procedure:
A. Removal of Diaphragm (Figures 7 & 8):
BEFORE BEGINNING DISASSEMBLY
PROCEDURES, RELIEVE ALL
PRESSURE FROM SYSTEM, ISOLATE THE LIQUID END FROM ALL
SOURCES OF PROCESS LIQUID WITH APPROPRIATE VALVING, AND
PURGE LIQUID END OF ALL PROCESS LIQUID.
1. Disconnect both the suction inlet and discharge
outlet from the piping system.
2. Locate drain pan under diaphragm head to collect oil. Approximately 1 pint of oil will drain
from the displacement chamber after removal of the diaphragm.
3. Remove the diaphragm head bolts (1025) which
hold the head to the displacement chamber and
remove diaphragm head (1020). Oil will begin to leak out. In most cases, the white teon-faced
diaphragm will remain in the displacement chamber.
4. Remove the diaphragm. Oil will now drain out
of the front of the displacement chamber.
1. Install new O-rings (720, 730) and coat rings
with O-ring grease.
2. Screw valve assembly back into displacement
chamber until it reaches mechanical stop.
3. Make sure the strainer (670) is installed and strainer plug (650) is tight. Valve is now ready for service. Rell pump casing with recommended oil as described in the “Oil Replacement”
section.
22
Instruction Manual
Page 27
SECTION 4 - MAINTENANCE
B. Installation of New Diaphragm (Figures 7 & 8):
1. Make sure the contoured diaphragm support
surface and O-ring groove machined into displacement chamber are clean. To prevent leakage from occurring, be careful not to scratch the O-ring groove when cleaning.
2. Install the diaphragm into the displacement
chamber with the black rubber side against the contoured surface of the displacement chamber. Make sure the diaphragm sealing
bead ts securely in the diaphragm groove of the displacement chamber. The white teon-face of
the diaphragm should be facing outward and visible.
3. Align the two holes in the diaphragm head with the locating pins (610) in the displacement chamber and reinstall diaphragm head (1020).
4. Reinstall head bolts (1025), at washer (1040), lock washers (1035), and nuts (1030).
5. Tighten bolts rmly in a crisscross pattern.
4.4.5 Removal of Pump Liquid End
(Figures 7 & 8)
MILROYAL® G liquid ends are designed to provide reliable service under normal operating circumstances and should not require removal
of the liquid end. However, if the need arises, the
following describes the procedure.
BEFORE BEGINNING DISASSEMBLY
PROCEDURES, RELIEVE ALL
PRESSURE FROM SYSTEM, ISOLATE THE LIQUID END FROM ALL
SOURCES OF PROCESS LIQUID WITH APPROPRIATE VALVING, AND
PURGE LIQUID END OF ALL PROCESS LIQUID.
A. Disassembly:
1. Disconnect both the suction inlet and discharge
outlet from the piping system.
2. Drain oil as described in the above “Oil Replacement” section of this manual.
3. Remove 3- Function Valve assembly as described in the “Start- Up of Pump Containing No Oil in Casing and Displacement Chamber”.
4. Remove six displacement chamber bolts (570) and lock washers (560) which secure liquid end
to pump drive housing.
5. Locate a container under liquid end to catch
approximately 1 pint of oil that will escape during
next step.
6. Gently pull liquid end OFF drive housing being careful to avoid damage to plunger (520, gure 5) during removal. Drain oil into waste container.
7. Discard displacement chamber gasket (590).
8. Place the liquid end, diaphragm head up, on
a bench or other clean, at, convenient work
area.
B. Reassembly:
1. Make sure gasket surface on pump housing
and displacement chamber are clean and free of markings which could serve as leak paths.
2. Install new displacement chamber gasket (590)
in correct orientation on liquid end.
3. With vent cap (620) at 12 O’clock, gently slide
liquid end over plunger.
4. Reinstall six displacement chamber bolts (570) and lock washers (560) and tighten securely.
5. Follow procedure for filling pump housing and liquid end with oil described in “Start- Up
of Pump Containing No Oil in Casing and Displacement Chamber”.
23Instruction Manual
Page 28
SECTION 5 - TROUBLESHOOTING
5.1 SYMPTOMS & REMEDIES
• Low process liquid level in tank. Add liquid.
• Worn or dirty check valves. Clean or replace.
• Blocked discharge line. Clear line.
• Frozen liquid: Thaw liquid throughout pumping system.
Pump will not operate
Insufcient delivery
Erratic delivery
• Blown fuse. Replace fuse.
• Open thermal overload device in motor starter. Reset device.
• Broken wire. Locate and repair.
• Low voltage: Investigate and correct (wiring may be too light).
• Pump not primed. Allow suction line and pump head to ll with liquid before pumping against pressure. Refer to “Filling Pumping System” in Section 3.
• Capacity adjustment set at zero. Readjust capacity.
• Relief valve relieving.
• Blocked discharge line. Clear line.
• Relief valve set too low. Adjust valve to 15% over operating pressure.
• Air in hydraulic system. Operate purge button.
• Clogged rell line: Remove oil strainer and clean or replace.
• Incorrect capacity adjustment: Readjust capacity setting.
• Incorrect pump speed. Match line voltage and frequency to pump motor data plate.
• Starved suction. Increase piping size or suction head.
• Leaky suction piping. Repair piping.
• High suction lift (Insufcient NPSH). Most common with long suction lines, small
diameter suction lines, acid pumping, polymer (viscous) liquids, or drawing from
a source lower than pump. Consult your local representative or the Milton Roy
Factory Aftermarket Department.
• Liquid near boiling. Cool liquid or increase suction head.
• Leaky safety valve in discharge line. Repair or replace safety valve.
• High liquid viscosity. Reduce viscosity (e.g., heat or dilute liquid).
• Worn or dirty check valve seats. Clean or replace.
• Leaky relief valve. Repair or replace valve (consult factory).
• Leaky suction piping. Repair piping.
• Leaky safety valve. Repair or replace safety valve.
• Liquid near boiling. Cool liquid or increase suction head.
• Worn or dirty check valves. Clean or replace.
• Blocked suction line. Clean strainer.
• High suction lift (Insufcient NPSH). Most common with long suction lines, small
diameter suction lines, acid pumping, polymer (viscous) liquids, or drawing from
a source lower than pump. Consult your local representative or the Milton Roy
Factor Aftermarket Department.
24
Instruction Manual
Page 29
SECTION 5 - TROUBLESHOOTING
Excessive Delivery
Motor and pump body hot
Pump still pumps even at zero capacity setting
Gear noise.
Loud knock with each stroke
Noisy operation in liquid end
• Low discharge line pressure. Increase line pressure
(e.g., install a back pressure valve).
• Normal operating temperature of both motor and pump body is frequently uncomfortable to the touch. However, neither should exceed 200°F (93°C).
• Power supply does not match electrical requirement of motor. Insure proper
matching of power supply and motor.
• Pump is being operated at greater than rated performance. Reduce pressure or
stroke speed. If this is not practical, contact service facility.
• Pump improperly lubricated. Drain oil and rell with proper amount of
recommended lubricant.
• Misadjusted micrometer knob. Readjust capacity setting.
• Insufcient discharge pressure. Correct condition
(e.g., install a back pressure valve).
• Excessive backlash. Consult service facility.
• Worn bearings. Consult service facility.
• Wrong or insufcient lubricant. Replace or replenish lubricant.
• Excessive gear set wear. Consult service facility.
• Worn bearings. Consult service facility.
• Incorrect motor rotation. Should be clockwise as viewed from top of motor.
• Worm shaft spring (360) missing.
• Noise in check valves. Ball checks move up and down with some force. A distinct “clicking” noise is normal, especially in metal piping systems.
25Instruction Manual
Page 30
SECTION 6 - PART NUMBERS
6.1 BASIC PARTS LIST- PUMP DRIVE (Refer to Figure 5 & 6)
Item No. Description Qty. Req.
10 Housing 1
19 O-ring 1
20 Drain Plug 1
30 Gear Thrust Flange Bearing 1
40 Bearing Cup 1
50 Gear (144/173 spm) 1
50 Gear (72/86 spm) 1
50 Gear (43/36 spm) 1
50 Gear (180 spm) 1
60 Connecting Rod 1
100 Sliding Crank 1
110 Eccentric 1
120 Shoe 1
130 Retaining Ring 1
140 Ball Bearing 1
150 Retaining Ring 1
160 O-ring 1
171 Stroke Adjustment Screw Assembly 1
175 Stroke Scale 1
190 O-ring 1
200 Side Cover 1
205 Cover Screw (M8 x 16mm) 4
310 Nylon Stroke Locking Ball 1
320 Stroke Locking Knob 1
322 O-ring 1
330 Stroke Adjustment Knob 1
335 Knob Sticker 1
340(note 1) Worm Assembly (173 spm, 56C) 1
Worm Assembly (173 spm, 145TC) 1
Worm Assembly (173 spm, 182TC) 1
Worm Assembly (180 spm, IEC80, F165) 1
343(note 1)
Worm Assembly (144 spm, IEC80, F165) 1
Worm Assembly (86spm, 56C) 1
Worm Assembly (86 spm, 145TC) 1
Worm Assembly (86 spm, 182TC) 1
Worm Assembly (72 spm, IEC 80, F165) 1
26
Instruction Manual
Page 31
SECTION 6 - PART NUMBERS
Item No. Description Qty. Req.
Worm Assembly (43 spm,56C) 1
343(note 1)
346(note 1)
360(note 1)
370 Oil Fill/Breather Cap 1
376 Motor Adaptor plate (182TC) 1
376 Motor Adaptor plate (IEC80, F165) 1
377 Adaptor plate screws; M10 x 25mm 4
400 Motor screws (182TC);1/2-13 x ¾ 4
400 Motor screws (56C, 145TC); 3/8-16 x 1 4
410 Washer- 56C, 145TC (3/8) 4
450 Base 1
460 Base Screws (M8 x 35mm) 4
465 Lock Washers (8mm) 4
470 Nut (M8) 4
520 Plunger (1-1/4”) 1
520 Plunger (1-3/4”) 1
520 Plunger (2-1/2”) 1
520 Plunger (3”) 1
525 Plunger Pin (1-1/4” plunger) 1
525 Plunger Pin (1-3/4” plunger) 1
525 Plunger Pin (2-1/2”, 3” plungers) 1
560 Lock Washer (8mm) 6
570 Displacement Chamber Screw (M8x30mm) 6
Worm Assembly (43 spm, 145TC) 1
Worm Assembly (43 spm, 182TC) 1
Worm Assembly (36 spm, IEC80, F165) 1
Worm/Motor Coupling (56C) 1
Worm/Motor Coupling (145TC) 1
Worm/Motor Coupling (182TC) 1
Worm/Motor Coupling (IEC80, F165) 1
Spring (182TC) 1
Spring (145TC) 1
Spring (56C) 1
Spring (IEC80) 1
Note 1: Worm Assembly (343) includes worm, coupling (346), spring (360), and bearing cone (340).
Note 2: For part numbers not listed, consult local Milton Roy representative or Milton Roy Aftermarket
Department (215-441-0800).
27Instruction Manual
Page 32
SECTION 6 - PART NUMBERS
6.2. BASIC PARTS LIST- LIQUID END (Refer to Figure 7-9)
6.2.1 MARS VALVE (see Figure 9)
Item No. Description Qty. Req.
775(Note 1) Valve Assembly 1
750(Note 2) Valve Body 1
760(Note 2) Poppet 1
770(Note 2) Valve Stem 1
780 Button (1-1/4” plunger) 1
780 Button (1-3/4, 2-1/2, 3” plungers) 1
790 Plug (1-1/4” plunger) 1
790 Plug (1-3/4, 2-1/2, 3” plungers) 1
800 Spring 1
810 Valve Body Retaining Ring 1
820 Valve Stem Retaining Ring 1
830 O-Ring 1
840 O-Ring 1
Note 1: Include items 750, 760, 770, 810, 820, 830, 840.
Note 2: Not sold separately. Must purchase item 775 (MARS Valve Assembly).
6.2.2 REFILL VALVE (see Figure 8)
Item No. Description Qty. Req.
740(Note 1) Rell Valve Assembly 1
650 Oil Strainer Plug, ¼” NPT 1
660(Note 2) Valve Body 1
670 Oil Strainer 1
680(Note 2) Ball 1
690(Note 2) Spring 1
730 O-Ring 1
700(Note 2) Washer 1
710(Note 2) Retaining Ring 1
720 O-Ring 1
Note 1: Includes items 650,660,670,680,690, 700,710,720,730.
Note 2: Not sold separately. Must purchase item 740 (Rell Valve Assembly).
28
Instruction Manual
Page 33
6.2.3 3- FUNCTION VALVE (see Figure 8)
SECTION 6 - PART NUMBERS
Item No. Description
850 Valve Cap 1
860 Purge Button 1
870 Pin 1
880 Purge Button Spring 1
890 Relief Valve Adjustment Screw 1
900 Relief Valve Locking Nut 1
910 Relief Valve Adjustment Nut 1
920 O-Ring 2
930 Purge Stem 1
935 Washer 1
940 O-Ring 1
950 Relief Valve Spring (1-1/4, 1-3/4” plungers)
PVC Liquid End (purple) 1
Metallic Liquid End (orange) 1
950 Relief Valve Spring (2-1/2, 3” plungers),purple 1
1015(note 1) Poppet Assembly 1
960(note 2) Air Bleed Valve Body 1
970(note 2) Ball 1
980(note 2) O-Ring 1
990(note 2) Air Bleed Ball Seat 1
1000(note 2) Spring 1
1005(note 2) Air Bleed Body Seat 1
Qty.
Req.
Note 1: Includes items 960, 970, 980, 990, 1000, 1005.
Note 2: Not sold separately. Must purchase item 1015 (Poppet Assembly).
6.2.4 CHECK VALVE PARTS (see Figures 10-13)
The Pump Model Number is used to identify the check valve parts.
The 4 & 5 digits identify the plunger size, digit 6 identies the liquid end material.
MGH -
Digits
• Code 20 is a 1-1/4”(32mm) Plunger
• Code 28 is a 1-3/4”(45mm) Plunger
• Code 40 is a 2-1/2”(63mm) Plunger
• Code 48 is a 3”(75mm) Plunger
• Code 1 is 316SS, Code 2 is PVC, Code 5 is Alloy 20
4 5 6
Codes for Digits 4 & 5
Codes for Digit 6
29Instruction Manual
Page 34
SECTION 6 - PART NUMBERS
6.2.5 PVC Liquid End (see Figures 10-13)
1-1/4” plunger: Single Ball Check Valve
(see Figure 12)
Item No. Description Qty. Req.
71 Check Valve Assembly Tubing Conn: includes 2
425 Cartridge Valve Assembly 2
435 Tubing Connector 2
445 Valve Body-Tube 2
71 Check Valve Assembly NPT Conn. includes 2
425 Cartridge Valve Assembly 2
445 Valve Body- NPT 2
4 Function PVC Bleed Valve (see Figure 14)
Item No. Description Qty. Req.
446 ¼” NPT Discharge Bleed Valve Assembly 1
446 ½” Tube Conn. Discharge Bleed Valve Assembly 1
1-1/4” plunger: Double Ball Check Valve
(see Figure 10)
Item No. Description Qty. Req.
425 Check Valve Assembly Assemblies include the following items 1
419 O-Ring, viton 2
420 Ball Stop 1
421 Ball, ceramic, 3/8” 1
422 Ball, ceramic, 14mm 1
424 Ball Guide 1
445 Union End, PVC, ½” NPT Female 1
435 Union Nut, PVC Shown in Figure 11 1
1-3/4”, 2-1/2,” plungers: Double ball check valve
(Figure 10)
Item No. Description Qty. Req.
425 Check Valve Assembly Assemblies include the following items 1
419 O-Ring, viton 2
420 Ball Stop 1
421 Ball, ceramic, 14mm 1
422 Ball, ceramic, 7/8” 1
424 Ball Guide 1
435 Union Nut, PVC Shown in Figure 11 1
445 Union End, PVC, ½” NPT Female 1
30
Instruction Manual
Page 35
SECTION 6 - PART NUMBERS
1-3/4, 2-1/2, 3” plungers: Single Ball Check Valves, (Figure 11).
Item No. Description Qty. Req.
425
419 Seal, PTFE Encapsulated Rubber 2
420 Seat, PVDF 1
422 Ball; 5/8” Ceramic 1
423 Seat, Seal, Ball-Replacement Kit 1
424 Ball Guide/Body, PVDF 1
435 Union Nut, PVC 1
445 Union End, PVC, ½” NPT Female 1
6.2.6 Metallic Liquid End (see Figure 10)
316SS & Alloy 20 Liquid End, 1-1/4” Plunger: Double Ball Check Valve (Figure 13)
Item No. Description Qty. Req.
425 Suction Valve Assembly 316SS 2
425 Suction Valve Assembly Alloy 20 2
426 Discharge Valve Assembly 316SS 2
426 Discharge Valve Assembly Alloy 20 2
Check Valve assemblies include seal (419), seat (420), balls (421), ball guide (424)
435 Lock Nut 2
439 Back- up Ring 2
441 O-Ring, Viton 2
Check Valve Assembly Assemblies include two seals (419), seat (420), ball (422), ball guide (424)
1
316SS Liquid End, 1-3/4, 2-1/2” plungers: Double Ball Check Valves
Item No. Description Qty. Req.
425 Check Valve Assembly 1
Check Valve assemblies include two seals (419), seat (420), balls (421, 422), ball guide (424)
419 O-Ring, viton 2
420 Ball Stop 1
421 Ball, 14mm 1
422 Ball, 22mm 1
424 Ball Guide/Body 1
445 Coupling, ½” BSP Female 1
445 Coupling, ½” NPT Female 1
31Instruction Manual
Page 36
SECTION 6 - PART NUMBERS
Alloy 20 Liquid End, 1-3/4, 2-1/2, 3” plungers: Double Ball Check Valves (Figure 10)
Item No. Description Qty. Req.
425 Check Valve Assembly 1
Check Valve assemblies include two seals (419), seat (420), balls (421, 422), ball guide (424)
419 O-Ring, viton 2
420 Ball Stop 1
421 Ball, 14mm 1
422 Ball, 22mm 1
424 Ball Guide/Body 1
445 Coupling, ½” BSP Female 1
445 Coupling, ½” NPT Female 1
316SS Liquid End, 3” plungers: Single Ball Check Valves
Item No. Description Qty. Req.
425 Check Valve Assembly 1
Check Valve assemblies include two O-rings (419), seat (420), ball stop (420), seat (421), ball (422), body (424)
419 O-Ring, 2
420 Ball Stop 1
421 Seat 1
422 Ball, 22mm 2
424 Body 1
32
Instruction Manual
Page 37
SECTION 6 - PART NUMBERS
6.3 REMAINING LIQUID END PARTS (see Figure 8)
Item No. Description Qty. Req.
510 Diaphragm, 1-1/4” 1
510 Diaphragm, 1-3/4, 2-1/2, 3” plungers 1
530 Plunger Sleeve, 1-1/4” plunger 1
530 Plunger Sleeve, 1-3/4” plunger 1
540 O-Ring (1-1/4”, 1-3/4” plungers only) 1
550 Screw, M6 x 18mm (1-1/4, 1-3/4” plungers only) 6
560 Lock Washer 6
570 Screw, M8 x 30mm 6
580 O-Ring 1
590 Gasket 1
600 Displacement Chamber (1-1/4” plunger) 1
600 Displacement Chamber (1-3/4,2-1/2,3” plungers) 1
610 Locating Pin 2
620 Breather Cap 1
630 Sight Glass 2
640 Hose Barb Union 1
650 Displacement Chamber Plug, ¼” NPT 1
1020 Diaphragm Head, PVC, 1-1/4” plunger 1
1020 Diaphragm Head, PVC, 1-3/4,2-1/2,3” plungers 1
1020 Diaphragm Head, 316SS, 1-1/4” plunger 1
1020 Diaphragm Head, 316SS, 1-3/4,2-1/2,3” plungers 1
1020 Diaphragm Head, Alloy 20, 1-1/4” plunger 1
1020 Diaphragm Head, Alloy 20, 1-3/4,2-1/2,3” plungers 1
1025 Head Bolt, Stainless steel
For 1-1/4” plunger sizes: M6 x 55mm 8
For 1-3/4”, 2-1/2” ,3” plunger sizes M12 x 90mm 6
1030 Nut, M12, Stainless Steel (1-3/4,2-1/2,3” plungers) 6
1035 Lock Washer, S.S., M12 (1-3/4,2-1/2,3” plungers) 6
1040 Washer, S.S., M12 (1-3/4,2-1/2,3” plungers) 6
1050 Head Plate (1-1/4”, PVC only); stainless steel 1
33Instruction Manual
Page 38
Model No. MGH281 Product Code 10CDM2SE11NN22 S/N1234567891 Flow Rate X.X GPH @ XX PSI XXX PSI MA WP Tag No. 12345678 XXXXX12345678
Milton Roy Company Made in USA
Liquid End C
9”
(228.6 mm)
L
0.354” (9 mm) Dia. Mounting Holes
Motor
C
L
41/2”
(114.3 mm)
Figure 2. Sample Nameplate
Pressure Relief Valve
Figure 3. Mounting Hole Dimensions
Suction
Accumulator
Dampener
Figure 4. Typical Recommended Pump Installation Scheme
34 Instruction Manual
Page 39
EC80
MOTOR
390
400
56C
182TC
MOTOR
MOTOR
376
410
377
376
417
343
40
346
360
340
370
400
60
520
525
460
465
Figure 5. Drive Parts- Side View
470
450
35Instruction Manual
Page 40
175
310
160
330
335
171
200
322
320
190
110
10
150
140
205
560
570
130
50
SEE LIQUID END
19
30
20
100
Figure 6. Drive Parts- Top View
36 Instruction Manual
120
Page 41
1020
PLASTIC ONLY
1050
PLATE IS USED ON 1-1/4” PLUNGER ONLY. LARGER PLUNGER SIZES USE WASHERS
TORQUE TO
1025
40 IN-LB FOR METALIC 20 IN-LB FOR PLASTIC
View for 1-1/4” PLUNGER Size.
SEE DRIVE HOUSING
1040
610630
630
560
10351030
570
View for 1-3/4”, 2-1/2” and 3 Plunger Sizes.
TORQUE TO 125 IN-LB FOR PLASTIC HEAD
1025
250 IN-LB FOR METAL HEAD
Figure 7. Liquid End- Top View
37Instruction Manual
Page 42
870
970
980
990
1015
1000
1010
550
TORQUE TO 125 IN-LB
900
1005
530
650
620
950
540
640
880
935
860
850
3- FUNCTION HYDRAULIC VALVE
930
890
920
900
910
920
940
SEE CHECK VALVE
510
1020
720
MARS VALVE SEE FIGURE
600
590
580
730
740
700710
690
680
670660
650
REFILL VALVE
NEXT SHEET
Figure 8. Liquid End- Section A-A
38 Instruction Manual
Page 43
MARS VALVE
Mechanically Activated Rell System (MARS) Valve assembly.
Except for O-rings, the valve may only be purchased as an assembly.
810
780
760
830
775
750
770
840
800
Figure 9. MARS VALVE
The MARS Valve is located between the plunger and the diaphragm.
820
790
39Instruction Manual
Page 44
445
419
420
422
424
421
419
445
DISCHARGE
420
419
422
424
419
SUCTION
PVC and Metallic Double Ball Check Valve Parts- 1-1/4” thru 2-1/2” Plunger Sizes
419
422
420
424
421
Metallic Double Ball Check Valve Parts- 3” Plunger Only
Figure 10.
445
435
419
424
424
422
420
419
DISCHARGE SUCTION
420
419
422
419
435
445
PVC Single Ball Check Valve Parts
Figure 11.
40 Instruction Manual
Page 45
435
445
425
425
071
445
435
445
425
DISCHARGE
SHOWN WITH TUBE CONNECTIONS
071
DISCHARGE
SUCTION
425
445
SUCTION
SHOWN WITH NPT CONNECTIONS
Figure 12. Plastic Check Valves, 1-1/4” Plunger Size
41Instruction Manual
Page 46
435
METALLIC CHECK VALVES
437
419
445
426
424
439
441
441
439
435
421
421
421
444
420
421
424
420
425
Figure 13. Metallic Check Valves, 1-1/4” Plunger Size
42 Instruction Manual
Page 47
PVC LIQUID END FOUR FUNCTION BLEED VALVE 1.25” PLUNGER
FOUR FUNCTION BLEED VALVE NPT CONNNECTION SHOWN
446
Cartridge Valve Assembly
Cartridge Valve Assembly
425
425
447
SPACER(0.040”)
448
SPACER(0.020”)
Suction Valve Assembly
071
NPT CONNNECTION SHOWN
Figure 14. Four Function Bleed Valve
43Instruction Manual
Page 48
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people and our family of brands— including Club Car®, Ingersoll Rand®, Thermo King® and Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency. We are committed to a world of sustainable progress and enduring results.
Info@miltonroy.com www.miltonroy.com
MILROYAL® is a registered trademark of Milton Roy, LLC.
© 2019 Milton Roy, LLC.
Loading...