The following precautions should be taken when working with metering pumps.
Please read this section carefully prior to installation.
Protective Clothing
ALWAYS wear protective clothing, face shield, safety glasses and gloves when working on or
near your metering pump. Additional precautions should be taken depending on the solution
being pumped. Refer to Safety Data Sheets for the solution being pumped.
Hearing Protection
It is recommended that hearing protection be used if the pump is in an environment where the
time- weighted average sound level (TWA) of 85 decibels is exceeded (as measured on the A
scale- slow response).
Electrical Safety
• Remove power and ensure that it remains off while maintaining pump.
• DO NOT FORGET TO CONNECT THE PUMP TO EARTH/ GROUND.
• Electric protection of the motor (Thermal protection or by means of fuses) is to correspond
to the rated current indicated on the motor data plate.
Liquid Compatibility
Verify if the materials of construction of the wetted components of your pump are
recommended for the solution (chemical) to be pumped.
Pumps Water “Primed”
All pumps are tested with water at the factory. If your process solution is not compatible with
water, ush the Pump Head Assembly with an appropriate solution before introducing the
process solution.
Plumbing and Electrical Connections
Always adhere to your local plumbing and electrical codes.
Line Depressurization
To reduce the risk of chemical contact during disassembly or maintenance, the suction and
discharge lines should be depressurized before servicing.
Over Pressure Protection
To ensure safe operation of the system it is recommended that some type of safety/pressurerelief valve be installed to protect the piping and other system components from damage due
to over- pressure.
Lifting
This manual should be used as a guide only- Follow your company’s recommended lifting
procedures. It is not intended to replace or take precedence over recommendations, policies
and procedures judged as safe due to the local environment than what is contained herein.
Use lifting equipment that is rated for the weight of the equipment to be lifted.
FIGURE 12. Plastic Check Valves for 1-1/4” Plunger .............................................. 41
FIGURE 13. Metallic Check Valves for 1-1/4” Plunger.............................................. 42
FIGURE 14. PVC 4- Function Bleed Valve for 1-1/4” Plunger ........................................ 43
iiiInstruction Manual
Page 5
SECTION 1 - DESCRIPTION
1.1 GENERAL
MILROYAL® G pumps are reciprocating, chemical
dosing pumps capable of producing controlled
ows up to 130 gallons per hour (492 L/H) at
pressures up to 600 psi (41 BAR) (depending on
the model). These pumps feature the robust High
Performance Diaphragm (HPD) liquid end, which
eliminates the need for contour plates, and a
non-lost motion stroke adjustment mechanism
based on the variable eccentric principle. This nonlost motion design substantially reduces pressure
and ow pulsations which in turn increases the
life of system components and results in a more
continuous chemical injection. It is designed
for industrial service and offers an accuracy of
±1% of 100% rated ow between 10% and 100%
of its ow range.
The High Performance Diaphragm (HPD) liquid end
combines all of the best characteristics of traditional
liquid ends into one technologically advanced
design. Its operating characteristics and simplicity
of operation make it the best liquid end to consider
rst for most metering pump applications.
Milton Roy’s HPD liquid end overcomes the
net positive suction head (NPSH) restrictions
associated with conventional disc diaphragm
metering pumps. This is accomplished by a unique
mechanically actuated rell system (MARS) that
eliminates the need for diaphragm support plates
thereby lowering pump NPSH requirements.
The MARS also does away with the need for eld
adjustment of the rell mechanism by automatically
compensating for process liquid modications.
This, combined with removable check valves,
makes the HPD an ideal choice for any process in
which downtime is critical.
The HPD features a preformed, PTFE faced
elastomer diaphragm that is compatible with a
wide range of process liquids and chemicals.
The convoluted design of this composite diaphragm
also offers extended life over conventional at disk
designs.
The HPD liquid end is particularly suitable for
pumping costly, aggressive or hazardous liquids
without leakage.
1.2 PRINCIPLE OF OPERATION (Refer to Figure 5 Through 10)
The pump consists of two major assemblies;
the drive and the liquid end. Pump delivery is a
function of the drive’s stroke rate (strokes/minute),
plunger size and stroke length (% Capacity).
Stroke length can be adjusted while the pump is
running or stopped by turning the stroke adjustment
knob (330).
The drive motor transmits rotary motion to a
worm gear speed reduction unit (343, 50) which
in turn drives the variable eccentric crank (100).
The adjustable crank imparts reciprocating
motion to the plunger/connecting rod assembly
(60, 520, 525). The stroke length is adjusted by
changing the position of the variable eccentric
crank in the connecting rod assembly.
1Instruction Manual
Page 6
SECTION 1 - DESCRIPTION
The mechanical drive system of the pump drives
the plunger back and forth in the High Performance
Diaphragm (HPD) liquid end supplied with the
pump. At the start of a suction stroke, the plunger
moves away from the liquid end, drawing hydraulic
uid with it. As the hydraulic uid is drawn back,
the exible diaphragm (510) follows, lowering the
pressure of the process uid in the liquid end.
This pressure drop causes the ball(s) in the suction
check valve (Figure 10) to be lifted up thereby
allowing process uid to pass through the suction
line into the diaphragm head (1020). At the same
time, the pressure drop in the diaphragm head
causes the ball(s) in the discharge check valve
(Figure 10) to be pulled closed, blocking ow back
through the discharge line.
Note:
It is important that the pressure in the liquid
end remain above the vapor pressure of the
process uid during the suction stroke. If the
uid pressure drops below the vapor pressure,
cavitation will occur, negatively impacting the
performance of the pump. If you suspect the
possibility of cavitation, contact your Milton Roy
Representative for assistance.
At the end of the suction stroke, the process
reverses, beginning the discharge stroke.
Now the plunger moves forward, pushing hydraulic
uid before it. The hydraulic oil must therefore press
against the diaphragm, exing it forward and raising
the pressure of the process uid in the liquid end.
This pressure increase causes the process uid
to ow outward, forcing the discharge ball check
open and the suction ball check to seat, blocking
back ow through the suction line. The process
uid ows out of the diaphragm head and into the
discharge line. This suction/discharge action is
repeated with every stroke of the pump plunger,
and is the direct cause of the pumping action.
As the pump operates, a small quantity of hydraulic
oil is continuously bled through the air bleed system
(970, 960, 980 in Figure 8) in the three- function
hydraulic valve (air bleed/relief/purge- Figure 8).
An additional small quantity of hydraulic oil is
also lost on every stroke through the clearance
between the plunger and displacement chamber
bore. After a while, these normal losses result in
a shortage of hydraulic oil in the displacement
chamber. When this happens, the diaphragm will
be pulled back tight against the back contoured
surface of the displacement chamber, and part of
the diaphragm will press against the Mechanically
Actuated Rell System (MARS) valve (Figure 9).
Now, when the plunger draws back, a vacuum is
created in the displacement chamber. These two
factors (diaphragm pressing against MARS valve &
vacuum in the displacement chamber) must occur
together to trigger the MARS valve.
When both of these conditions are met, the MARS
valve is forced to its rearward position, and the
poppet (760) opens, allowing hydraulic oil from
the reservoir to enter through the refill valve
(740 in Figure 8) and replenish the lost oil. In this
manner, proper hydraulic balance is constantly
maintained in the displacement chamber.
2
Instruction Manual
Page 7
SECTION 1 - DESCRIPTION
1.3 GENERAL SPECIFICATIONS
Maximum Capacity Range20 GPH (76 LPH) to 130 GPH (492 LPH)
Maximum Pressure Range100 PSIG (7 Bar) to 600 PSIG (41 BAR)
Steady State Accuracy±1% of 100% rated ow between 10% and 100% of rated ow
Capacity Adjustment
Temperature Limits
Suction Pressure Limits
LubricationOil bath drive lubrication.
PaintTwo part epoxy, yellow RAL 1018
Hydraulically Actuated Diaphragm with Mechanically Actuated Rell
System (MARS).
PVC, 316 SS, Alloy 20.
Micrometer (Standard): Lockable micrometer is adjustable from
0% to 100% while pump is running or stopped
Electronic (Optional): Electronic stroke length adjustment from
4-20ma input.
Ambient Limit:
Note: Limited by standard lubricants. Modications are available through
Applications Engineering.
Plastic Liquid Ends: 20ºF to 140ºF
Metallic Liquid Ends: 20ºF to 190ºF
Minimum Internal Pressure: 3 psia (11.5 psi maximum vacuum)
Maximum Suction Pressure: 100 psig at 80ºF and below.
130ºF Maximum
0ºF Minimum
Liquid Temperature Limits:
3Instruction Manual
Page 8
SECTION 1 - DESCRIPTION
1.4 PRODUCT CODE
MILROYAL® G pumps are available in a variety of different congurations. The complete product code
is composed of the pump “model number” + “product code”. For a breakdown of the options included
in a specic pump, compare the pump model number and product code found on the pump nameplate
with the model/product code breakdown shown in Figure 1. A sample nameplate is shown in Figure 2.
MODEL NUMBER
MGH
456
Digit 4 & 5: Plunger SizeDigit 6: Liquid End Material
Note: Degassing options are available. Consult
MRC factory or representative for details
SN
Figure 1. Model/Product Code
4
Instruction Manual
Page 9
SECTION 2 - INSTALLATION
2.1 UNPACKING
Pumps are shipped Free on Board (FOB) factory
or representative warehouse and the title passes to
the customer when the carrier signs for receipt of
the pump. In the event that damages occur during
shipment, it is the responsibility of the customer to
notify the carrier immediately and to le a damage
claim.
Carefully examine the shipping crate upon receipt
from the carrier to be sure there is no obvious
damage to the contents. Open the crate carefully so
accessory items fastened to the inside of the crate
will not be damaged or lost. Examine all material
inside the crate and check against packing list to
be sure that all items are accounted for and intact.
2.2 SAFETY PRECAUTIONS
When installing, operating, and maintaining the
MILROYAL® G pump, keep safety considerations
foremost. Use proper tools, protective clothing, and
eye protection when working on the equipment
and install the equipment with a view toward
ensuring safe operation. Follow the instructions
in this manual and take additional safety
measures appropriate to the liquid being pumped.
Be extremely careful in the presence of hazardous
substances (e.g., Corrosives, toxins, solvents,
acids, caustics, ammables etc.).
2.3 STORAGE
2.3.1 Temporary Storage (Less than 6 Months)
It is preferable to store the material under a shelter
in its original package to protect it from adverse
weather conditions. In condensing atmospheres,
follow the long term storage procedure.
2.3.2 Long Term Storage
(Longer than 6 Months) Primary Considerations
The primary consideration in storage of pump
equipment is to prevent corrosion of external and
internal components. This corrosion is caused
by natural circulation of air as temperature of the
surroundings change from day to night, day to day,
and from season to season. It is not practical to
prevent this circulation which carries water vapor
and other corrosive gasses, so it is necessary to
protect internal and external surfaces from their
effects to the extent possible.
When the instructions given in this section are
completed, the equipment is to be stored sheltered/
protected from direct exposure to weather.
The prepared equipment should be covered with a
plastic sheet or a tarpaulin, but in a manner which
will allow air circulation and prevent capture of
moisture. Equipment should be stored 12” or more
above the ground.
If equipment is to be shipped directly from
Milton Roy into long term storage, contact
Milton Roy to arrange for factory preparation.
2.3.3 Pump Drive
1. Flood the pump drive housing with a high grade
lubricating oil/rust preventative such as Mobile
Oil Corporation product “Mobilarma 524”.
Fill the housing completely to minimize air space
and water vapor condensation. After storage,
drain this material and rell the equipment to the
correct oil level with the recommended lubricant
for equipment commissioning.
2. Remove drive motor and brush all unpainted
metal surfaces with multipurpose grease
(NLGI grade 2 or 3). Store motor unattached.
5Instruction Manual
Page 10
SECTION 2 - INSTALLATION
2.3.4 Electrical Equipment
1. Motors should be prepared in the manner
prescribed by their manufacturer. If information
is not available, dismount and store motors as
indicated in step 3 below.
2. Dismount electrical equipment (including
motors) from the pump.
3. For all electrical equipment, place packets of
Vapor Phase Corrosion Inhibitor (VPCI) inside of
the enclosure, then place the entire enclosure,
with additional packets, inside a plastic bag.
Seal the bag tightly closed. Contact Milton Roy
Service Department for recommended VPCI
materials.
2.4 MOUNTING
Support the pump rmly in a level position on a
solid, vibration- free foundation, preferably with
the base above oor level to protect the pump
from wash downs and to provide easier access
for service. Be sure to allow enough space around
the pump for easy access during maintenance
operations, pump adjustments, and/or oil lling or
draining procedures.
MILROYAL® G pumps are provided with mounting
holes to accommodate anchor bolts. Refer to
Figure 3 for mounting hole dimensions.
Some MILROYAL® G pumps are shipped with
motors dismounted. After anchoring pump in
position, install motor, referring to Figure 5.
To avoid damage to pump drive during
operation, make sure spring (360) provided with
pump is installed in worm shaft prior to motor
installation. Pumps installed outdoors should be
protected by a shelter.
2.5 CONVENTION PROCEDURE
A MILROYAL® G pump can, in some cases, be
converted from one liquid end plunger size or
material of construction to another. For more
information on converting between different liquid
end models, please contact the Milton Roy factory
or your local authorized representative.
2.6 PIPING CONNECTIONS
2.6.1 NPSH Considerations
The MILROYAL® G HPD liquid end is far superior
to conventional diaphragm liquid ends for suction
lift and many other NPSH- critical applications.
In these demanding applications, the patented
diaphragm and rell mechanism give this liquid
end truly exceptional performance.
For NPSH apply a 3 psia limitation (instead of
9 psia) in evaluating applications for this liquid end.
Size piping to accommodate peak instantaneous
flow. Because of the reciprocating motion of
the pump diaphragm, pump delivery follows an
approximate sine curve with a peak instantaneous
ow equal to pi (3.14) times the average ow.
Therefore, piping must be designed for a ow
3.14 times the pump capacity; this means that a
pump rated for 100 gallons per hour (379 L/hr.)
requires piping sufcient for 3.14 x 100 gph, or
314 gph (1188 L/hr.).
To minimize viscous ow losses when handling
viscous liquids, it may be necessary to use suction
piping up to four times larger than the size of
the suction connection on the pump. If in doubt,
contact your nearest Milton Roy representative to
determine the necessary pipe size.
6
Instruction Manual
Page 11
SECTION 2 - INSTALLATION
2.6.2 General Piping Considerations
1. Use extreme care in piping to plastic liquid
end pumps with rigid pipe such as PVC. If any
stresses or vibration are unavoidable, exible
connections are recommended.
2. Use piping materials that will resist corrosion by
the liquid being pumped. Use care in selecting
materials to avoid galvanic corrosion at pump
liquid end connections.
3. Use piping heavy enough to withstand maximum
pressures.
4. Remove burrs, sharp edges, and debris from
inside piping. Blow out all pipelines before
making nal connections to pump.
5. Because vapor in the liquid end will cause
inaccurate pump delivery, piping should be
sloped down to pump suction check valve to
prevent vapor pockets.
6. When pumping suspended solids (such as
slurries), install plugged crosses at all 90° line
turns to permit line cleaning without dismantling
piping.
7. See Figure 4 for a typical recommended pump
installation scheme.
2.6.3 Suction Piping Considerations
1. It is preferable to have the suction of the pump
ooded by locating the liquid end below the
lowest level of the liquid in the supply tank.
Installing the supply vessel on the suction line
in close proximity to the pump will help ensure
a ooded suction line.
2. Avoid negative suction pressure conditions
(suction lift), as such conditions adversely
affect metering accuracy. A lift of 20 Ft. of water
column straight out of a supply tank is the
maximum suction lift permissible.
3. MILROYAL® G pumps are intended to be
operated with process liquid supplied at or
above atmospheric pressure. Although these
pumps can move liquids supplied at less
than atmospheric pressure, in these negative
pressure applications it is important that all
connections be absolutely drip free and vacuum
tight.
4. When pumping a liquid near its boiling point,
provide enough suction head to prevent the
liquid from “ashing” into vapor when it enters
the pump liquid end on the suction stroke.
5. If possible use metal or plastic tubing for the
suction line because such tubing has a smooth
inner surface and can be formed into long,
sweeping bends to minimize frictional flow
losses.
6. A strainer should be used in the suction line to
prevent foreign particles from entering the liquid
end. This and any other measures to prevent
debris from entering and fouling the ball-checks
will give increased maintenance-free service.
Check strainer frequently to prevent blockage
which could lead to cavitation.
7. Keep suction piping as short and straight as
possible.
8. Piping size should be one or two sizes larger
than the liquid end suction tting to prevent
pump starvation.
9. If long suction lines are unavoidable, install a
stand pipe or suction accumulator dampener
near the pump in the suction line.
10. Suction piping must be absolutely airtight to
ensure accurate pumping. After installation,
test suction piping for leaks with air and soap
solution.
7Instruction Manual
Page 12
SECTION 2 - INSTALLATION
2.6.4 Discharge Piping Considerations
1. Install pipe large enough to prevent excessive
pressure losses on the discharge stroke of the
pump. Maximum pressure at the discharge
tting on the liquid end must be kept at or below
the rated pressure (Max. allowable working
pressure shown on the pump nameplate).
2. The pump will not deliver a controlled ow unless
the discharge line pressure is 35 psi greater than
the suction line pressure. There are a number of
ways to create an articial pressure, such as by
installing a back pressure valve. (Please contact
Milton Roy for recommendations to increase
back pressure in slurry applications.)
3. When pumping water-treatment chemicals
directly into boiler drums, use one liquid
end assembly for each boiler drum.
Discharging into a manifold having the slightest
pressure difference between its several
discharge connections can diminish metering
accuracy as the outlet with the lowest pressure
will receive more liquid than the outer outlets.
2.6.6 Pulsation Dampeners
An accumulator, surge chamber, surge suppressor,
or pulsation dampener should be used with the
back pressure valve in the discharge line to
absorb the ow peaks between the pump and
the back pressure valve. Without the pulsation
dampener the valve mechanism will snap open
and closed with the surge from each pump stroke.
The pulsation dampener will allow the back
pressure valve to oscillate about a partly-closed
position, thus minimizing wear on the valve.
Discharge line pulsation dampeners offer the
further advantage of limiting the ow and pressure
variations characteristic of this kind of pump.
Installing a properly sized pulsation dampener
will improve pump performance and may reduce
system costs dramatically by permitting the
substitution of smaller piping. Please contact
Milton Roy for further information on pulsation
dampeners.
2.6.5 Back Pressure Valves
A Milton Roy Back Pressure Valve should be
installed in the discharge line near the pump to
ensure sufficient discharge head pressure for
proper pump metering action. Normally, the valve
should be located near the pump. However, back
pressure valves for large pumps with long and
extremely small discharge lines may have to
be installed near the point of discharge into the
process (to minimize siphoning tendencies).
8
Instruction Manual
Page 13
SECTION 2 - INSTALLATION
2.6.7 Pressure Relief Valve (PRV)
Maximum safety and reliability may be ensured by
protecting liquid ends and piping with an external
pressure relief valve installed in the system
discharge line. Although the pump is protected
against excessive pressure by an internal relief
valve, to prevent a blocked discharge line from
causing damage to the piping or process equipment,
install a Milton Roy pressure relief valve in the pump
discharge line. This valve is designed and sized to
handle system ow rates and pressures safely
while resisting corrosion by the process liquid.
Install the safety valve in the discharge line
between the pump and the nearest shut- OFF
valve. (This will prevent potential system damage
from accidental valve closure.) Pipe the pressure
relief valve outlet back to the suction tank or to
drain, but in either case ensure that the pipe end
is continuously visible so pressure relief valve
leakage may be detected. Milton Roy pressure
relief valve must be installed in accordance with its
user manual top of supply tank in order to function
properly.
2.6.8 Check Valves
A check valve should be installed at the point
where the discharge line enters a boiler or other
high-pressure vessel. This will prevent back ow
through the discharge piping and will isolate the
pump discharge from system pressures (a safety
consideration).
2.6.9 Shut- OFF Valves
In order to isolate the pump during maintenance,
provide shut- OFF valves in both suction and
discharge lines next to the pump. Locate discharge
line shut- OFF valve downstream from the inlet
connection of the safety valve. Figure 4 shows
recommended valve locations.
2.7 ELECTRICAL CONNECTIONS
Ensure that the electrical supply matches the pump
motor nameplate characteristics. Before operating
the pump, check the direction of rotation of the
motor to be sure it matches the direction of the
arrow stamped on the motor (rotation should be
clockwise when viewed from the top of the motor).
If motor rotation is incorrect, refer to the motor
data plate or motor manufacturer’s instructions
for reversing.
OPERATION WITH THE WRONG
MOTOR ROTATION WILL DAMAGE
THE PUMP AND MOTOR AND VOID THE WARRANTY.
DO NOT FORGET TO CONNECT
THE PUMP TO AN EARTH
GROUND!
Electric protection of the motor (fuses, overload
meters or relays) should correspond to the rated
current indicated on the motor data plate.
9Instruction Manual
Page 14
SECTION 3 - OPERATION
3.1 INITIAL START- UP
Check that all mounting bolts are tight, piping is
installed properly, and the discharge line is open.
Check oil drain plug for tightness. Remove the
orange oil ll cap and ll the pump casing until
level is between the top two marks on the oil cap
dipstick. (approximately 3-1/2 quarts). DO NOT
OVERFILL ABOVE TOP DASH!
Note:
The oil furnished with the pump is grade AGMA
No. 5 EP with a viscosity of 1000 SSU at 100°F
(218.4 cSt at 40°C). For operation in ambient
temperatures below 50°F (10°C), substitute
AGMA No. 2 EP with a viscosity of 400 SSU
at 100°F (86.4 cSt at 40°C). Manufacturers’
equivalent oils are shown below.
DO NOT START UP PUMP DRIVE
MOTOR BEFORE FILLING GEAR
BOX WITH OIL OR SERIOUS DAMAGE WILL OCCUR.
Chevron N.L. Gear Compound
220
ABOVE 50°F:
BELOW 50°F:
Food Grade
Alteration
Exxon Spartan E.P. 220
Mobil Mobilgear 630
Texaco Meropa 220
Chevron N.L. Gear Compound 68
Exxon Spartan E.P. 68
Mobil Mobilgear 626
Texaco Meropa 68
Shell Omaha 68
Nevastane EP220
3.1.1 Start- Up for New Pump
For pumps received from the factory, the
displacement chamber (600) is already lled with
oil. Simply remove the orange oil ll cap from the
pump casing and ll the casing with the specied
oil to a level between the top two dashes on the
dipstick. DO NOT OVERFILL ABOVE TOP DASH!
Pump is now ready for operation. Operation of
the air purge button may be required to remove
air that may have come out of solution from the
oil during shipment and storage. Refer to “USE
OF AIR PURGE BUTTON” section for operation
instructions. The integral pump relief valve is
factory adjusted according to customer specied
setting. For instructions on adjustment of the pump
relief valve please refer to the next section.
BEFORE SWITCHING ON POWER
TO THE PUMP, TURN THE
CAPACITY ADJUSTMENT KNOB TO ZERO. CHECK THAT ALL
SHUT- OFF VALVES IN THE SUCTION AND DISCHARGE LINES
ARE OPEN BEFORE INCREASING THE CAPACITY
ADJUSTMENT FROM ZERO.
10
Instruction Manual
Page 15
SECTION 3 - OPERATION
3.1.2 Start- Up of Pump Containing No Oil
in Casing and Displacement Chamber
The following instructions assume that both the
pump casing and liquid end (displacement chamber)
contain no oil. This condition typically exists when
the pump is subjected to annual maintenance
during which oil may be drained from the pump
casing and oil may escape from the displacement
chamber during diaphragm replacement.
New pumps received from the factory will have
an empty pump casing and a lled displacement
chamber (liquid end). Please refer to the previous
section for start- up of new pumps. After pump
casing is lled to correct oil level (between top two
dashes on oil cap dipstick), perform the following
operations before placing the pump into service.
Numbers refer to item numbers shown in assembly
drawings (Figures 7-9) located in the back of this
manual.
1. Remove hydraulic 3- function valve (refer to
Figure 8):
a. Remove relief valve cap piece (850).
b. Make sure relief valve locknut (900) is tight
to maintain previous relief valve setting upon
start- up.
c. Remove purge button and relief valve
adjustment assembly by removing large
adjustment nut (910).
d. Using needle-nose pliers, remove spring
(950).
e. Using same pliers, remove relief valve poppet
by gently gripping the top of the valve body
(960).
2. Make sure pump capacity adjustment is set to
100%.
3. Fill the opening in the displacement chamber
(600) through the port uncovered by removal
of the 3- function valve in step 1 with the same
oil used to ll the pump casing. Fill the chamber
slowly, allowing air bubbles to escape, until
the oil level reaches the level of the drain tube
(640).
4. Reinstall 3- function valve:
a. Gently gripping the top of the relief valve
poppet (960) with needle-nose pliers, drop
the poppet assembly down into the empty
relief valve port.
b. Drop spring (950) back into relief valve port.
c. Make sure washer (935) is in place above
the O-ring (940) on purge stem (930) and
reinstall purge and relief valve adjustment
assembly by screwing large adjustment nut
(910) back into place. Make sure adjustment
nut (910) is tight.
d. Reinstall relief valve cap piece (850).
5. The pump is now properly lled with oil and ready
for service. If the relief valve locking nut (900)
remained tight during the above procedure, the
relief valve setting should remain unchanged.
If not, refer to next section for instructions on
how to set relief valve.
BEFORE SWITCHING ON POWER
TO THE PUMP, TURN THE CAPACITY
ADJUSTMENT KNOB TO ZERO. CHECK THAT ALL SHUT- OFF VALVES
IN THE SUCTION AND DISCHARGE LINES ARE OPEN BEFORE
INCREASING THE CAPACITY ADJUSTMENT FROM ZERO.
6. Make sure that all air has been bled from the
suction piping and pump head. This can be
accomplished by opening all suction line valves
as well as the system drain (Prime/Air Purge)
valve shown in Figure 4 and allowing uid to ow
into drain until all air has been purged. If drain
valve not present, with the pump capacity set
to 100%, operate the pump under no discharge
pressure until the entire pumping system has
been lled.
11Instruction Manual
Page 16
SECTION 3 - OPERATION
3.2 RELIEF VALVE ADJUSTMENT
All MILROYAL® G liquid ends have a built in relief
valve which allows hydraulic uid to return to the
pump casing if excessive pressure builds up in the
discharge line. This effectively stops the pump from
pumping, since the forward stroke of the piston
will not displace the hydraulic uid and force the
diaphragm to ex. During operation of the pump, a
relief condition caused by over pressurization can
easily be seen by looking through the sight glass
(630, Figure 7) for excessive oil ow from the drain
tube (640, Figure 8).
Note:
Under normal operation, a few drops of oil
should escape from the drain tube during each
pump stroke due to normal oil ow through the
air bleed ball (970, gure 8). If a stream of oil
from the drain tube is evident on each pump
stroke, the system pressure has exceeded the
pump relief valve setting and the pump is in a
relief condition.
The MILROYAL® G liquid end relief valve may be
adjusted to operating conditions by the following
procedure. Adjust the relief valve after rst installing
the pump and after any maintenance procedures.
THE PRESSURE RELIEF VALVE IS
FACTORY SET TO OPEN AT A
PRESSURE 15% OVER THE CUSTOMER SPECIFIED OPERATING
PRESSURE OR AT 15% ABOVE THE MAXIMUM PRESSURE
RATING OF THE PUMP IF NO OPERATING PRESSURE IS
SPECIFIED BY THE CUSTOMER. WHEN ADJUSTING THE VALVE
SETTING, NEVER SET THE VALVE AT A PRESSURE GREATER
THAN 15% OVER THE PUMP MAXIMUM PRESSURE RATING.
3.2.1 Relief Valve Adjustment (With an Adjustable System Back pressure Valve).
Refer to Figures 7 & 8.
The following procedure assumes that a back
pressure valve and pressure gauge are installed
in the discharge line. If these components are not
installed, refer to next section.
1. Make sure all system shut- OFF valves are
open and that the back pressure valve is backed
out to allow for ow against zero discharge
pressure.
2. Start pump and set capacity at 100%. If a drain
valve is present in the discharge line, pump
process liquid to drain or other safe point to
establish proper pumping action. Close drain.
3. Slowly increase system pressure until:
a. Signicant ow is observed from the drain
tube (640, gure 8) as viewed through the
sight glass (630, gure 7) or
b. The system pressure reaches 15% over the
desired system pressure.
4. For condition (a) in step 4, if relief condition
occurs at less than 15% above desired pump
operating pressure, the relief valve setting
must be increased. Remove valve cover
(850) and increase relief valve setting by
turning the adjustment screw (890) clockwise
until only a few drops of oil escape on each
pump stroke (normal leakage past air bleed
ball-980). Increase system pressure to 15%
above desired operating pressure to verify that
pump is now in relief condition. If it is not, reduce
relief valve setting by turning adjustment screw
(890) counterclockwise until relief is observed
in sight glass drain tube at a pressure equal to
15% greater than desired operating pressure.
Lock-in relief valve setting by tightening locking
nut (900) while holding adjustment screw (890)
stationary. The relief valve is now properly
adjusted. Reinstall valve cover (850).
5. For condition (b) in step 4, the setting of the
relief valve should be reduced. Remove valve
cover (850) and turn adjustment screw (890)
counterclockwise until relief is observed in
sight glass drain tube at a pressure equal to
15% greater than desired operating pressure.
Lock-in relief valve setting by tightening locking
nut (900) while holding adjustment screw (890)
stationary. The relief valve is now properly
adjusted. Reinstall valve cover (850).
12
Instruction Manual
Page 17
SECTION 3 - OPERATION
3.2.2 Relief Valve Adjustment (Without an
Adjustable System Back Pressure Valve).
If no adjustable back pressure valve is present
in the discharge line, use the following simplied
procedure to check and/or set the relief valve
setting.
1. If pump is in a relief condition at normal
operating pressure, the relief valve setting
should be increased. Remove valve cover (850)
and increase relief valve setting by turning the
adjustment screw (890) clockwise until only a
few drops of oil escape on each pump stroke
(normal leakage past air bleed ball) (970).
Turn adjustment screw an additional ½ turn to
provide an adequate buffer zone. Lock-in relief
valve setting by tightening locking nut (900)
while holding adjustment screw (890) stationary.
The relief valve is now properly adjusted.
Reinstall valve cover (850).
2. If pump is not in a relief condition at normal
operating pressure, and the operator wishes
to reset the valve setting to approximately 15%
above operating pressure(recommended),
use the following procedure. Remove valve
cover (850) and decrease the relief valve
setting by turning the adjustment screw (890)
counterclockwise until a stream of oil ows
from the drain tube (640) on each pump stroke.
Now slowly turn adjustment screw clockwise
until only a few drops of oil escape on each
pump stroke (normal leakage past air bleed
ball). Turn screw an additional ½ turn to provide
an adequate buffer zone. Lock-in relief valve
setting by tightening locking nut (900) while
holding adjustment screw (890) stationary.
The relief valve is now properly adjusted.
Reinstall valve cover (850).
3.3 USE OF AIR PURGE BUTTON Refer to Figure 7 & 8:
As with any hydraulically actuated diaphragm
pump, dissolved air will come out of solution
during normal operation which can negatively
impact pump performance if not removed
from the pump displacement chamber.
The MILROYAL® G hydraulic 3- function valve is
equipped with two mechanisms for removal of this
gas: a continuous air bleed and an air purge button.
The continuous air bleed portion of the valve is
composed of a sealed ball (970) which allows for a
controlled leakage of a few drops of oil, and any small
accumulations of evolved gas, on each pump stroke.
Larger quantities of air can be quickly removed by
pressing the spring-loaded purge button (860), until
it reaches its mechanical stop, for a few seconds.
Upon doing so, the operator will observe a stream
of oil and air escaping from the drain tube (640).
The need for use of the purge button to remove
a large quantity of air can be caused by several
factors:
1. Blocked suction line: A partially or fully blocked
suction line can create a vacuum pressure
condition in the hydraulic system which pulls
significant quantities of dissolved gas from
solution.
2. Oil Change: The recommended annual
changing of the oil in the pump drive can lead to
the presence of air pockets in the displacement
chamber (600).
3. Diaphragm Replacement: Results in signicant
loss of oil from the displacement chamber.
4. Pump Start- up After Long Idle Period: If the
pump has sat idle for a signicant time, gas
may come out of solution from the oil and collect
into pockets which can negatively impact pump
ow. Depression of the purge button will quickly
evacuate these pockets and restore the pump
to desired performance.
13Instruction Manual
Page 18
SECTION 3 - OPERATION
The operator should only activate the purge button
if some type of pump upset occurs such as the
above 4 examples. When activating the purge, only
press button for 2-3 seconds or until a stream of oil
owing from the drain tube (640) is seen through
the sight glass (630). Immediately after activation
of the purge button, a temporary reduction in ow
will occur as the rell system replenishes oil lost
during the purge. However, the pump should return
to normal operation within 1 to 2 minutes after
activation of the purge button. If after that time, the
pump ow rate is still less than it should be, repeat
the purge operation and wait another 2 minutes.
If ow has still not resumed to expected levels,
consult the troubleshooting section of this manual.
3.4 MANUAL CAPACITY CONTROL
To adjust pump capacity on standard pumps
equipped with manual stroke adjustment, first
loosen the stroke locking screw located in
the pump side cover. Pump capacity is then
adjusted by turning the micrometer-type stroke
adjustment knob clockwise to decrease capacity or
counterclockwise to increase capacity as required.
The adjustment scale is marked in percent (%)
of full stroke, with calibration lines on the knob at
1% intervals. After adjusting the knob to the desired
capacity setting, hand tighten the stroke locking
screw to maintain the capacity setting.
3.5 FILLING PUMPING SYSTEM
For proper pump operation, it is especially important
that pump suction and discharge lines be free of
entrained air. To ensure this condition, operate the
pump without any discharge pressure and ll the
entire pumping system with liquid before starting
pressure tests. A simple method to assure priming
of the pump is to install a tee and a shut- OFF valve
at the discharge connection of the pump.
If the pump is idle for long periods, temperature
changes in the process liquid may produce air in
the system. To discharge the air, install a valve in
the discharge line which will allow the process liquid
to be pumped to a drain when starting the pump.
3.6 CAPACITY CALIBRATION
After the rst 12 hours of operation, the pump
should be tested and calibrated to nd the exact
pump capacity under specic operating conditions
and capacity settings for the specic uid being
pumped. Typically, calibrating the pump at 100,
50, and 10 percent capacity settings is enough to
establish a pump performance curve throughout
the adjustment range.
The pump can be calibrated by measuring the
decrease in liquid level pumped from a calibrated
vessel. This method is recommended for hazardous
liquids because it eliminates operator contact
with the liquid. Milton Roy test-tube Calibration
Columns are available for convenient and accurate
calibration of any pump. The pump can also be
calibrated by collecting and measuring pumped
liquid at the pump discharge port in which case it
will be necessary to create discharge head at the
liquid takeoff point so that the pump will operate
properly. (See Section 2 for recommended ways
to do this.)
14
THIS METHOD IS NOT
GENERALLY RECOMMENDED
AS IT MAY EXPOSE OPERATING PERSONNEL TO HAZARDOUS
LIQUIDS.
Instruction Manual
Page 19
SECTION 4 - MAINTENANCE
4.1 RECOMMENDED SPARE PARTS
To avoid delays in repairs, a Routine Preventative
Maintenance Kit should be ordered for each pump.
The RPM kit contains an oil strainer and check
valve parts. Part orders must include the following
information:
1. Quantity required.
2. Part Number.
3. Part Description.
4. Pump serial number (found on pump
nameplate).
5. Pump model number (found on pump
nameplate).
6. Pump product code (found on pump
nameplate).
Always include the serial number, model number,
and product code in all correspondence regarding
this unit.
4.2 SHIPPING PUMPS FOR REPAIR
Pumps can not be accepted for repair without a
Return Material Authorization. Pumps should be
clearly labeled to indicate the liquid being pumped.
Process liquid should be ushed from the pump
liquid end and oil should be drained from the pump
housing and displacement chamber. To drain oil
from the displacement chamber, unscrew the rell
valve body (660, gure 8) from the displacement
chamber. Allow oil to drain into a waste container.
Remove diaphragm (510) and tilt up the back of
the pump until oil ceases to drain from the front of
the pump.
Note:
Federal law prohibits handling of equipment
that is not accompanied by an OSHA Safety
Data Sheet (SDS). A completed SDS must be
packed in the shipping crate with any pump
shipped for repair. These safety precautions will
aid the troubleshooting and repair procedure
and preclude serious injury to repair personnel
from hazardous residue in pump liquid end.
A Safety Data Sheet must accompany all
returns.
All inquiries or parts orders should be addressed to
your local Milton Roy representative or distributor.
4.3 ROUTINE PREVENTATIVE
MAINTENANCE
BEFORE ANY MAINTENANCE,
RELIEVE ALL PRESSURE
FROM SYSTEM, ISOLATE LIQUID END FROM ALL SOURCES
OF PROCESS LIQUID WITH APPROPRIATE VALVING, AND
PURGE LIQUID END OF ALL PROCESS LIQUID.
4.3.1 Oil Replacement
I n i t i a l l y , c h a n g e o i l i n p u m p c a s i n g a f t e r t h e r s t
250 hours of operation. Then change oil after
every 4000 hours of operation or every six months
whichever comes first. Oil can be drained by
removing the drain plug (20, gure 6). When oil
has nished draining, make sure that the area
around the drain hole is clean. Screw drain plug
back in securely. Fill the pump housing with
the recommended oil until the level is between
the top two marks on the dipstick. DO NOT OVERFILL(above top mark)! Replace the oil
ll cap and screw rmly in place. Dispose of oil
according to any federal, state or local codes which
may apply.
Note:
It is not necessary to purge the liquid end
displacement chamber of oil during annual oil
replacement.
15Instruction Manual
Page 20
SECTION 4 - MAINTENANCE
4.3.2 Check Valves
Milton Roy recommends that check valve balls,
seats, gaskets, and O-rings be replaced on an
annual basis. If highly corrosive material (acids,
slurries etc.) is being pumped, some applications
may require more frequent replacement.
Milton Roy recommends an annual tune up using
a Routine Preventive Maintenance (RPM) Kit.
RPM kits contain replacements for those parts
which are subject to wear; specically the ball
checks, check valve seats, gaskets/seals, and the
strainer. Replacing these parts annually with an
RPM kit can reduce the possibility of unexpected
downtime and will help to extend pump life.
To determine if check valves need maintenance,
disassemble the check valves following the
instructions in the following “Check Valve
Replacement” section. In valves that permit
disassembly, inspect the ball check and seat for
chemical or physical damage. The ball should be
perfectly round and free of pits, marks, or scratches.
The seat should retain a smooth edge where the
ball contacts for proper sealing. If the seat edge
is worn or damaged, or has any pits, marks, or
scratches, it should be replaced. If the ball and/
or seat is excessively damaged, the replacement
schedule should be shortened accordingly.
If the ball and seat are both in good condition, the
replacement schedule can be lengthened.
BEFORE CARRYING OUT ANY
SERVICING OPERATION ON THE
METERING UNIT OR PIPES, DISCONNECT ELECTRICAL
POWER FROM THE PUMP, AND TAKE THE NECESSARY STEPS
TO ENSURE THAT THE HARMFUL LIQUID THEY CONTAIN
CANNOT ESCAPE OR COME INTO CONTACT WITH
PERSONNEL. SUITABLE PROTECTIVE EQUIPMENT MUST BE
PROVIDED. CHECK THAT THERE IS NO SYSTEM FLUID
PRESSURE BEFORE PROCEEDING WITH DISMANTLING OF
LIQUID END COMPONENTS.
4.3.3 Cleaning Fouled Check Valves
Check valve assemblies are designed to be self
cleaning and should seldom need servicing.
Fouled check valves can usually be cleaned by
pumping a solution of mild detergent and warm
water (if compatible with liquid being pumped) for
15 minutes, followed by ushing with water.
4.3.4 Check Valve Replacement
Before beginning work on the valve assemblies,
make sure the shut- OFF valves are closed and
that pressure has been bled from the system. When
replacing the valves, take care to systematically
change their O-rings and/or gaskets. Take care to
properly assemble the valve assemblies. In valves
that permit replacement of ball and seat, the ball
must be placed on the sharp edge of the seats.
For each plunger size, check valves are supplied
in three different congurations: plastic- single
ball, plastic-double ball, and metallic- double ball.
Be sure to refer to the appropriate instructional set
below pertaining to your plunger size and valve
type.
BE SURE TO FOLLOW
INSTRUCTIONS CAREFULLY
AND REFER TO THE APPROPRIATE FIGURE WHEN
REASSEMBLING CHECK VALVES. IF CHECK VALVE
CARTRIDGES ARE INSTALLED INCORRECTLY, ONE OF THE
FOLLOWING WILL OCCUR: (A) IMMEDIATE SEVERE DAMAGE
TO PUMP MECHANISM, (B) NO PUMPING, (C) REVERSE
PUMPING ACTION (FROM DISCHARGE LINE INTO SUCTION
LINE).
16
Instruction Manual
Page 21
SECTION 4 - MAINTENANCE
1-1/4” Plunger;Plastic Single Ball Check
Valves: see Figure 12
1. Unscrew the valve body (445).
2. Remove the cartridge assembly (425): includes
cartridge (ball, seat, ball guide), O-ring, and
washer.
3. Clean the valve housing and mating port in the
liquid end.
4. Press a new clear plastic washer into valve
body.
5. Install new cartridge valve assembly in
orientation shown in gure 12.
• Make sure that seat end of cartridge (white)
is always facing down.
• On discharge side, drop cartridge assembly
into threaded port in head. The O-ring should
be stretched around outside of cartridge on
same end as ball seat. Screw valve body into
discharge side of diaphragm head until valve
is hand tight. Do not overtighten.
• On suction side, drop cartridge assembly
into check valve body. The O-ring should
be stretched around outside of cartridge on
opposite end of ball seat. Screw suction valve
housing with cartridge valve into suction side
of head. Do not overtighten.
1-1/4” Plunger; Metallic Double Ball Check
Valves: see Figure 13
The metallic check valves used on the 1-1/4”
plunger size pumps are precision assembled at
the factory. Do not attempt to disassemble these
cartridges. If they become inoperative, ush them
with solvent, wash them with warm detergent and
blow them out with compressed air to remove any
foreign matter. If this treatment does not eliminate
the trouble, the cartridge assembly should be
replaced.
A. Disassembly (refer to gure 13)
1. The check valve cartridge assemblies use
an SAE straight thread with an O-ring seal to
facilitate port alignment with the connecting
pipes. To remove the cartridge from the liquid
end, rst loosen the lock nut (435) one or two
threads, then unscrew the cartridge (444,
445).
2. Remove and discard the O-ring (441) and split
ring (439).
3. Carefully clean any parts to be reused. If any
chemicals are used in the cleaning process,
ensure that they are compatible with the process
liquid.
17Instruction Manual
Page 22
SECTION 4 - MAINTENANCE
B. Reassembly (refer to gure 13)
1. To install the cartridge, position the lock nut
(435) toward the shoulder of the cartridge so
that the recess on the face of the lock nut is
adjacent to the O-ring (441).
2. Make certain the split ring (439) is coiled in
a counterclockwise helix(this is opposite the
direction normally employed by suppliers of
these rings). Fit this split ring in the lock nut
recess. Push it rmly down in the recess as
completely as possible.
3. Install a new O-ring (435) against the split
ring.
Note:
To assure a tight, leak free seal, new O-rings
and split rings should be used each time the
check valves are disassembled.
4. Screw the cartridge assembly (444, 445) into the
liquid end until the O-ring band is approximately
level with the top of the spot face in the liquid
end, then screw it one (1) additional turn plus a
partial turn as required to align the pipe thread
port with connecting pipe.
1-3/4, 2-1/2, and 3”Plungers: Plastic Single- Ball
Check Valves: see Figure 11
A. Disassembly
1. Unscrew the union nut (435). The union end
(445) is held in place by the union nut and will
now separate easily from check valve ball guide
(424).
2. Unscrew the ball guide (424) from the liquid
end.
3. Screw the union nut partially (one or two turns)
onto the end of the ball guide containing the
seat. Be sure the union nut is loosely installed
to allow for a gap for the seat (420) to drop into
as it is removed from the ball guide.
4. Sit the ball guide/union nut onto a at surface
with the union nut down. Looking into the top
of the ball guide, you will see four large holes
surrounding one small hole. Insert a thin, blunt
instrument such as a hex head screwdriver into
the small center hole until it rests on the top of
the ball (422).
5. Tap screwdriver gently with a hammer until ball
and seat are released from the ball guide.
SUCTION AND DISCHARGE
CHECK VALVE CARTRIDGES
ARE NOT IDENTICAL. BE SURE THAT THE CORRECT
CARTRIDGE IS BEING SCREWED INTO THE PROPER PORT.
(DISCHARGE CARTRIDGES HAVE HEXAGONAL CAP ON THE
TOP; SUCTION CARTRIDGES DO NOT.) IF CHECK VALVE
CARTRIDGES ARE INSTALLED INTO THE WRONG PORT, ONE
OF THE FOLLOWING WILL OCCUR: (A) IMMEDIATE SEVERE
DAMAGE TO PUMP MECHANISM, (B) NO PUMPING, (C)
REVERSE PUMPING ACTION (FRONT DISCHARGE LINE INTO
SUCTION LINE).
5. After completing pipe connection, tighten lock
nut securely against spot face so that O-ring is
trapped in chamfer of liquid end thread. Make
sure that the split ring is completely contained in
its recess and not extending to the outside.
18
Instruction Manual
IF YOU ARE DISASSEMBLING
UNIT FOR INSPECTION ONLY,
BE SURE TO USE A BLUNT INSTRUMENT AND TAP GENTLY TO
AVOID DAMAGING THE BALL. IF THE BALL AND/OR SEAT ARE
DAMAGED DURING DISASSEMBLY, THEY WILL NEED TO BE
REPLACED. TO AVOID DAMAGE, IF AVAILABLE, IT IS
ADVISABLE TO USE GENTLE AIR PRESSURE (APPLIED AT
END OPPOSITE THE SEAT-420) FOR BALL AND SEAT
REMOVAL.
6. Carefully remove the two O-rings (419) from the
ball guide and seat.
Page 23
SECTION 4 - MAINTENANCE
7. Inspect the balls carefully. If they are smooth,
round and free of deposits or pits, they are
suitable for continued use. Examine the check
valve seats. The area of the seat in contact
with the ball (the un-chamfered side) must be
in near perfect condition for continued use.
Any visible imperfection on the seating surface
(pits, erosion, cracks) necessitates replacement
of the seat. If both the balls and the seats are in
good condition, then the length of time between
parts replacement may be increased. If the
balls and seats are severely damaged, then
the length of time between parts replacement
should be shortened. Carefully clean any
parts to be reused. If any chemicals are used
in the cleaning process, ensure that they are
compatible with the process liquid.
B. Reassembly
1. Drop the ball into the curved inner chamber end
of the ball guide.
2. Sit the ball guide on a at surface so that the side
with the ball faces upwards. Position seat on the
ball guide, trapping the ball inside. When the
seat is pressed into the ball guide, the beveled
edge of the seat must be facing outward.
The bevel should not face the inside of the check
valve (refer to Figure 11). Use a at surface such
as a board to press the seat into the ball guide
with rm, even pressure.
IF THE SEAT IS IMPROPERLY
POSITIONED (WITH BALL
AGAINST BEVELED SURFACE), THE BALL WILL NOT CREATE
A TIGHT SEAL AND POOR PUMPING PERFORMANCE WILL
RESULT.
3. Fit new O-rings into grooves in the ball guide
and seat.
Note:
To assure a tight, leak free seal, new O-rings
should be used each time the check valves are
disassembled.
4. Position the union end (445) onto the correct
end of the ball guide. Refer to Figure 11 as the
correct end is determined by whether the valve
is intended for the suction or discharge port of
the liquid end. Slip the union nut (435) over the
union end and screw tightly (hand tight only)
onto the ball guide.
THE ORDER OF ASSEMBLY OF
THE SUCTION AND DISCHARGE
CHECK VALVES IS DIFFERENT. REFER TO FIGURE 11 FOR
PROPER ASSEMBLY ORDER. IF CHECK VALVE CARTRIDGES
ARE INSTALLED INCORRECTLY, ONE OF THE FOLLOWING
WILL OCCUR: (A) IMMEDIATE SEVERE DAMAGE TO PUMP
MECHANISM, (B) NO PUMPING, (C) REVERSE PUMPING
ACTION (FROM DISCHARGE LINE INTO SUCTION LINE).
5. Screw the valve assembly into the liquid
end body(hand tight only). DO NOT
Double ball check valves differ from the plastic
single ball check in that the ball seat is now
integral to the ball guide. The seats cannot easily
be inspected for damage or wear. If you suspect
that the check valve may be damaged or worn,
replace the entire check valve assembly as per
instructions below.
1. If metallic valve, unscrew the coupling (445)
from the ball guide (424). If plastic, unscrew the
union nut (435, gure 11) and remove union end
(445, gure 11) from the ball guide (424).
2. Unscrew the ball guide (424) from the liquid
end.
3. Remove and discard the O-rings (419).
4. Remove ball stop (420) and balls (421, 422).
19Instruction Manual
Page 24
SECTION 4 - MAINTENANCE
Inspect the balls carefully. If they are smooth,
round and free of deposits or pits, they are
suitable for continued use. Examine the ball
seat areas in the valve body (424). A magnifying
glass is recommended for this inspection.
The seat must be in near perfect condition for
continued use. Any visible imperfection on the
seating surface (pits, erosion, cracks) renders
the seat unusable thereby requiring replacement
of the valve body (424). If both the balls and the
seats are in good condition, then the length
of time between parts replacement may be
increased. If the balls and seats are severely
damaged, then the length of time between parts
replacement should be shortened. Carefully
clean any parts to be reused. If any chemicals
are used in the cleaning process, ensure that
they are compatible with the process liquid.
B. Reassembly (Refer to Figure 10):
1. Drop the balls (422, 421) into the valve body
(424). Drop ball stop (420) into place making
sure that side with O-ring groove is facing up.
Install new O-rings (419) on both ends of valve
body.
(445) onto the check valve assembly, trapping
a new O-ring (419) between the coupling and
the check valve assembly. If plastic check
valve, position the union end (445) onto the
correct end of the ball guide. Slip the union
nut (435) over the union end and screw tightly
(hand tight only) onto the ball guide. DO NOT
OVERTIGHTEN!
4.3.5 Oil Strainer Replacement Refer to Figure 8.
Over time, the oil strainer (670) which screws into
the rell valve body (660) can become fouled or
clogged. It should therefore be replaced yearly
and is included with the check valve parts in the
RPM Kit. If the strainer becomes clogged more
frequently than once a year (which is extremely
unlikely), it can be ordered separately.
Since the oil must rst be drained from the pump
casing, it is a good idea to schedule strainer
replacement with oil replacement.
1. Drain oil as described in the above “Oil
Replacement” section of this manual.
2. Unscrew the strainer (670) from the rell valve
body (660).
Note:
To assure a tight, leak free seal, new O-rings
should be used each time the check valves are
disassembled.
2. Screw the correct end of the check valve
assembly into the liquid end (hand tight only)
trapping a new O-ring between the liquid
end and the check valve assembly. DO NOT
OVERTIGHTEN!
THE END OF THE CHECK VALVE
THAT IS SCREWED INTO THE
PUMP HEAD IS DIFFERENT FOR THE SUCTION AND
DISCHARGE CHECK VALVES. REFER TO FIGURE 10 FOR
PROPER ASSEMBLY ORDER. IF CHECK VALVE CARTRIDGES
ARE INSTALLED INCORRECTLY, ONE OF THE FOLLOWING
WILL OCCUR: (A) IMMEDIATE SEVERE DAMAGE TO PUMP
MECHANISM, (B) NO PUMPING, (C) REVERSE PUMPING
ACTION (FROM DISCHARGE LINE INTO SUCTION LINE).
3. If metallic check valve, screw the coupling
20
Instruction Manual
3. Clean any debris from the strainer cavity in the
valve body.
4. Screw a new strainer into the rell valve body.
5. Rell pump casing with recommended oil as
described in the “Oil Replacement” section.
Page 25
SECTION 4 - MAINTENANCE
4.4 CORRECTIVE MAINTENANCE
4.4.1 3- Function Hydraulic Valve
The 3- function hydraulic valve assembly
(see Figure 8) operates in ltered hydraulic oil
and should require maintenance only if unusual
circumstances occur, such as if corrosive media
contaminates the uid.
Assembly and disassembly is straightforward.
Follow instructions in the “Start- Up of Pump
Containing No Oil in Casing and Displacement
Chamber” section of the manual. Field servicing
should be limited to inspection and cleaning only.
Repairs of this critical component should only be
carried out by an authorized Milton Roy repair
facility.
4.4.2 “MARS” Valve Assembly
The Mechanically Activated Rell System (MARS)
valve assembly (see Figures 8 & 9) requires no
periodic maintenance. Clean hydraulic oil is critical
for proper operation. Field servicing should be
limited to inspection and cleaning only. Repairs of
this critical component should only be carried out
by an authorized Milton Roy repair facility.
The valve is designed to be easily removed through
the front of the pump without having to remove
the displacement chamber. The following steps
describe the procedure for removal of the valve
from the displacement chamber (refer to Figure 9):
A. Disassembly
1. Remove liquid end according to instructions
in the “Removing the Liquid End” portion of
the “Diaphragm Replacement” section of the
manual.
2. Insert a small tip screw driver into one of the two
small holes in the valve button (780) and gently
pry out plastic cap (790).
4. Slide OFF activation button (780) and spring
(800).
5. Remove large retaining ring (810) using the
appropriate retaining ring pliers (Waldes Truarc
Internal Type, Waldes Truarc part# 0300).
6. Reinstall small retaining ring (820) in groove in
valve stem (770).
7. To avoid damage to valve stem, grip retaining
ring with pliers and pull remaining valve
assembly out of displacement chamber.
8. Discard O-rings (830,840) and retaining rings
(810, 820).
NOTE:
When reinstalling, make certain that new
O-rings and retaining rings are installed on
MARS assembly.
B. Reassembly
1. Install new O-rings (830, 840) on valve body
(750) and apply a light layer of O-ring grease
to O-rings.
2. Push assembly into place until it reaches stop
in displacement chamber.
3. Reinstall large bowed retaining ring (810).
Using a hammer and at tipped screwdriver,
gently tap the ring to insure that it is securely
seated in the retaining groove machined into
the displacement chamber.
4. Reinstall spring (800) and activation button
(780).
5. While pressing button (780), reinstall small
retaining ring (820). Gently tap on the ring to
insure that it is securely seated in the retaining
ring groove machined into the valve stem
(770).
6. Press plastic cap piece (790) into activation
button (780).
3. While pressing down on button (780), remove
the retaining ring (820) using the appropriate
retaining ring pliers (Waldes Truarc External
Type, Waldes Truarc part# M-1520).
7. Valve is now ready for service.
21Instruction Manual
Page 26
SECTION 4 - MAINTENANCE
4.4.3RellValveAssembly(see Figure 8).
The only required periodic maintenance for the
refill valve assembly is the suggested annual
replacement of the oil strainer (see above “Oil
Strainer Replacement” section). Clean hydraulic
oil is critical for proper operation. Field servicing
of the valve assembly is limited to inspection and
cleaning only. Repairs of this critical component
should only be carried out by an authorized
Milton Roy repair facility.
The valve is designed to be easily removed through
the bottom of the pump without having to remove
the displacement chamber. The following steps
describe the procedure for removal of the valve
from the displacement chamber (Figure 8):
A. Disassembly
1. Drain oil from the pump housing as described
in the above “Oil Replacement” section.
2. Unscrew the valve body (660) from the
displacement chamber (600).
3. Clean any debris from the valve cavity in the
displacement chamber.
4. Discard O-rings (720, 730).
Note:
When reinstalling the valve assembly, be sure
to install new O-rings (720, 730).
B. Reassembly
4.4.4 Diaphragm Replacement
MILROYAL® G liquid ends are designed to
provide reliable service under normal operating
circumstances and should not require replacement
of the diaphragm. However, in the unlikely event
of a failure, the diaphragm can be replaced by the
following the procedure:
A. Removal of Diaphragm (Figures 7 & 8):
BEFORE BEGINNING DISASSEMBLY
PROCEDURES, RELIEVE ALL
PRESSURE FROM SYSTEM, ISOLATE THE LIQUID END FROM ALL
SOURCES OF PROCESS LIQUID WITH APPROPRIATE VALVING, AND
PURGE LIQUID END OF ALL PROCESS LIQUID.
1. Disconnect both the suction inlet and discharge
outlet from the piping system.
2. Locate drain pan under diaphragm head to
collect oil. Approximately 1 pint of oil will drain
from the displacement chamber after removal
of the diaphragm.
3. Remove the diaphragm head bolts (1025) which
hold the head to the displacement chamber and
remove diaphragm head (1020). Oil will begin to
leak out. In most cases, the white teon-faced
diaphragm will remain in the displacement
chamber.
4. Remove the diaphragm. Oil will now drain out
of the front of the displacement chamber.
1. Install new O-rings (720, 730) and coat rings
with O-ring grease.
2. Screw valve assembly back into displacement
chamber until it reaches mechanical stop.
3. Make sure the strainer (670) is installed and
strainer plug (650) is tight. Valve is now ready for
service. Rell pump casing with recommended
oil as described in the “Oil Replacement”
section.
22
Instruction Manual
Page 27
SECTION 4 - MAINTENANCE
B. Installation of New Diaphragm (Figures 7 & 8):
1. Make sure the contoured diaphragm support
surface and O-ring groove machined into
displacement chamber are clean. To prevent
leakage from occurring, be careful not to scratch
the O-ring groove when cleaning.
2. Install the diaphragm into the displacement
chamber with the black rubber side against
the contoured surface of the displacement
chamber. Make sure the diaphragm sealing
bead ts securely in the diaphragm groove of the
displacement chamber. The white teon-face of
the diaphragm should be facing outward and
visible.
3. Align the two holes in the diaphragm head with the
locating pins (610) in the displacement chamber
and reinstall diaphragm head (1020).
4. Reinstall head bolts (1025), at washer (1040),
lock washers (1035), and nuts (1030).
5. Tighten bolts rmly in a crisscross pattern.
4.4.5 Removal of Pump Liquid End
(Figures 7 & 8)
MILROYAL® G liquid ends are designed to
provide reliable service under normal operating
circumstances and should not require removal
of the liquid end. However, if the need arises, the
following describes the procedure.
BEFORE BEGINNING DISASSEMBLY
PROCEDURES, RELIEVE ALL
PRESSURE FROM SYSTEM, ISOLATE THE LIQUID END FROM ALL
SOURCES OF PROCESS LIQUID WITH APPROPRIATE VALVING, AND
PURGE LIQUID END OF ALL PROCESS LIQUID.
A. Disassembly:
1. Disconnect both the suction inlet and discharge
outlet from the piping system.
2. Drain oil as described in the above “Oil
Replacement” section of this manual.
3. Remove 3- Function Valve assembly as
described in the “Start- Up of Pump Containing
No Oil in Casing and Displacement Chamber”.
4. Remove six displacement chamber bolts (570)
and lock washers (560) which secure liquid end
to pump drive housing.
5. Locate a container under liquid end to catch
approximately 1 pint of oil that will escape during
next step.
6. Gently pull liquid end OFF drive housing
being careful to avoid damage to plunger
(520, gure 5) during removal. Drain oil into
waste container.
7. Discard displacement chamber gasket (590).
8. Place the liquid end, diaphragm head up, on
a bench or other clean, at, convenient work
area.
B. Reassembly:
1. Make sure gasket surface on pump housing
and displacement chamber are clean and free
of markings which could serve as leak paths.
2. Install new displacement chamber gasket (590)
in correct orientation on liquid end.
3. With vent cap (620) at 12 O’clock, gently slide
liquid end over plunger.
4. Reinstall six displacement chamber bolts (570)
and lock washers (560) and tighten securely.
5. Follow procedure for filling pump housing
and liquid end with oil described in “Start- Up
of Pump Containing No Oil in Casing and
Displacement Chamber”.
23Instruction Manual
Page 28
SECTION 5 - TROUBLESHOOTING
5.1 SYMPTOMS & REMEDIES
• Low process liquid level in tank. Add liquid.
• Worn or dirty check valves. Clean or replace.
• Blocked discharge line. Clear line.
• Frozen liquid: Thaw liquid throughout pumping system.
Pump will not
operate
Insufcient delivery
Erratic delivery
• Blown fuse. Replace fuse.
• Open thermal overload device in motor starter. Reset device.
• Broken wire. Locate and repair.
• Low voltage: Investigate and correct (wiring may be too light).
• Pump not primed. Allow suction line and pump head to ll with liquid before
pumping against pressure. Refer to “Filling Pumping System” in Section 3.
• Capacity adjustment set at zero. Readjust capacity.
• Relief valve relieving.
• Blocked discharge line. Clear line.
• Relief valve set too low. Adjust valve to 15% over operating pressure.
• Air in hydraulic system. Operate purge button.
• Clogged rell line: Remove oil strainer and clean or replace.
PVC LIQUID END FOUR FUNCTION BLEED VALVE 1.25” PLUNGER
FOUR FUNCTION BLEED VALVE
NPT CONNNECTION SHOWN
446
Cartridge Valve Assembly
Cartridge Valve Assembly
425
425
447
SPACER(0.040”)
448
SPACER(0.020”)
Suction Valve Assembly
071
NPT CONNNECTION SHOWN
Figure 14. Four Function Bleed Valve
43Instruction Manual
Page 48
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments. Our people
and our family of brands— including Club Car®, Ingersoll Rand®, Thermo King® and Trane®—work together to enhance the quality
and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and
efficiency. We are committed to a world of sustainable progress and enduring results.
Info@miltonroy.com
www.miltonroy.com
MILROYAL® is a registered trademark of Milton Roy, LLC.