Warning notices must be observed to ensure personal safety as well as that of others, and to
protect the product and the connected eq uip m ent . These w ar ning notices are accompanied
by a clarification of the level of caution to be observed.
Qualified Personnel
This device/system may only be set up and operated in conjunction with this manual.
Qualified personnel are on ly authorized to install and operate this equip m ent in accordance
with established safety practices and standards.
Warning: This product can only function properly and safely if it is correctly transported,
stored, installed, set up, oper at ed, and maintained.
Note: Always use product in accordance with specifications.
Copyright Siemens Milltronics Process
Disclaimer of Liability
Instruments Inc. 2000. All Rights Reserved
This document is available in bound version and in
electronic version. We encourage users to
purchase authorized bound manuals, or t o view
electronic versions as designed and authored by
Siemens Milltronics Process Instruments Inc.
Siemens Milltronics Process Instruments Inc. will
not be responsible for the content s of partial or
whole reproductions of either bound or electronic
versions.
MILLTRONICS®is a registered t rademark of Siemens Milltronics Process Instrume nt s Inc.
Contact SMPI Technical Publications at the following address:
Technical Publications
Siemens Milltronics Process Instruments Inc.
1954 Technology Drive, P.O. Box 4225
Peterborough, Ontario, Ca nad a, K9J 7B1
Email: techpubs@milltronics.com
While we have verified the contents of
this manual for agreement with t he
instrumentation described, variations
remain possible. Thus we cannot
guarantee full agreement. The
contents of this manual are regularly
reviewed and corrections are included
in subsequent editions. We welc ome
all suggestions for improvement.
Technical data subject to change.
For the library of SMPI instruction manuals, visit our Web site: www.milltronics.com
Installation Diagram for the XPS 10 F ...............................................26
PL-551XPS 10/15 F Series TransducerPage 3
Page 4XPS 10/15 F Series TransducerPL-551
About Milltronics’ Transducers
The Echomax XPS F series of transducers operates in association with
Milltronics ultrasonic level monitoring products.
The transducer operates by converting electrical
pulses that are provided by the transceiver into
ultrasonic pulses. When transmitted, these
ultrasonic pulses reflect from the material surface
and echo back to the transducer. The echo is
converted back to an electrical signal, and is
interpreted by the Milltronics tranceiver using
our proven Sonic Intelligence™ algorithms.
About the…
hazardous seal
(XPS 10 F
series only)
transducer
transducer face
The effective acoustical energy is emitted from
the transducer face and radiated outward,
decreasing in amplitude at a rate inversely
proportional to the square of the distance.
Maximum power is radiated axially
(perpendicular) from the transducer face in a
line referred to as the axis of transmission.
Where power is reduced by half (– 3 dB), a
conical boundary defining the sound beam,
centered about the axis of transmission, is
established. The diametric measurement of
the cone in degrees defines the beam
angle. Impedance matching techniques are
used to optimize the transfer of power from the transducer into air and vice
versa.
The XPS F series transducers incorporate an integral temperature sensor
that reports the air temperature at the transducer to the transceiver. The
connection is transparent, in that both the ultrasonic and temperature
components of the transducer use the same leads.
-3db
boundary
axis of
transmission,
perpendicular
to transducer
face
Hazardous Area Applications
The Echomax XPS F series of transducers can be used in hazardous areas.
For the XPS 10 F series transducer, a hazardous seal must be used to suit
hazardous area classification. This seal is
not
supplied by Milltronics.
The XPS 15 F comes equipped with a stainless steel coupling suitable for
use in hazardous locations.
PL-551XPS 10/15 F Series TransducerPage 5
About the…
Page 6XPS 10/15 F Series TransducerPL-551
Specifications
XPS 10 F Series Transducers
Measurement Range:
{
0.3 – 10m (1 – 33ft)
Frequency:
{
43kHz
Beam Angle:
{
12°
Environmental
{
location:
{
altitude:
{
ambient temperature:{-20 to 95°C (-4 to 203°F)
{
pollution degree:
{
indoor/outdoor
{
2000m maximum
{
4
Specifications
Construction
{
exposure:
{
colour:
{ mounting:{ 1” NPT conduit connection
{
options:
{
cable:
{
{
{
{
{
{
®1
Kynar
slate gray
factory flange to suit ANSI standard
submergence shield, where flooding can occur
split flange for field mounting to suit ANSI
The XPS 15 F comes equipped with a stainless steel coupling suitable for
use in hazardous locations.
Page 10XPS 10/15 F Series TransducerPL-551
Mounting
Recommendations
• Special handling precautions must be taken to protect the face of the
transducer from any damage.
• Mount the transducer so that it is above the maximum material level by at
least the blanking value (0.3m for XPS 10 F and 0.45m for XPS 15 F). Refer
to the associated transceiver manual for instructions on setting the blanking
value.
• On liquid applications, the transducer must be mounted so that the axis of
transmission is perpendicular to the liquid surface.
• On solids applications, a Milltronics Easy Aimer should be used to facilitate
aiming of the transducer.
•Do not over-tighten mounting. Hand tightening of the mounting hardware is
sufficient.
• Secure installation by connecting a safety chain from the transducer to a
structural member.
• Consider the optional temperature sensor when mounting the transducer.
Solids Applications
Note:
For the XPS 10 F series transducer, a hazardous seal must be used
to suit hazardous area classification. This seal is
Milltronics. For more information, refer to page 26.
(XPS 10 F shown)
Easy Aimer
(typical model)
safety chain
transducer
not
supplied by
Mounting
PL-551XPS 10/15 F Series TransducerPage 11
Liquid Applications
Notes:
• In, the examples that follow, an XPS 10 F Series transducer is shown
using a hazardous seal. This seal is
• An XPS 15 F transducer can also be used in these applications, but,
because it comes equipped with a stainless steel coupling, no
hazardous seal is required.
not
supplied by Milltronics.
Mounting
Flexible Conduit
safety
chain
Flexible conduit transducer should not be
subjected to wind, vibration or jarring.
Submersible
(XPS 10 F shown)
hazardous seal
(XPS 10 F only)
transducer
(XPS 10 F shown)
flexible
conduit
channel
Bracket
steel
(XPS 10 F shown)
rigid metal
conduit
safety
chain
Submersible transducer, used in
applications where flooding is possible.
hazardous seal
(XPS 10 F only)
submergence
shield
Page 12XPS 10/15 F Series TransducerPL-551
Blind Flange
Flange, gasket, hazardous seal and hardware supplied by customer.
(XPS 10 F shown)
Refer to page 19
nipple welded
to bind flange
hazardous seal
(XPS 10 F only)
Flanged
(XPS 10 F shown)
hazardous seal
(XPS 10 F only)
factory flanged
transducer
bolt
gasket
customer flanged,
flat face only
nut
Flange, gasket, and hardware supplied by customer.
Refer to page 19
Note: Tighten the flange bolts evenly in order to ensure a good seal between
the mating flanges.
Caution: Over-tightening can cause performance degradation
.
Mounting
PL-551XPS 10/15 F Series TransducerPage 13
Mounting
Page 14XPS 10/15 F Series TransducerPL-551
Interconnection
k
Note:
Installation should only be performed by qualified personnel and in
accordance with local governing regulations.
Recommendations
• When using an XPS 15 F transducer, configure the electronic transceiver for
an XCT-12. These two transducers use the same settings.
• Do not route cable openly.
• For optimum isolation against electrical noise, run cable separately in a
grounded metal conduit.
• Seal all thread connections to prevent ingress of moisture.
• Do not run cable near high voltage or current runs, contactors and SCR
control drives.
Note:
In the interconnection examples that follow:
• an XPS 10 F Series transducer is shown. An XPS 15 F transducer can
also be used, but no hazardous seal is required.
• assume that the transducer is located in a Hazardous location (Class I,
Div. 1, Group A,B,C,D or Class II, Div. 1, Group E,F,G.) and the
transceiver in a Non-Hazardous (Safe) Location.
Direct Connection
Hazardous Location
(Class I, Div. 1, Group
A,B,C,D or Class II, Div.
1, Group E,F,G)
metal conduit
PL-551XPS 10/15 F Series TransducerPage 15
(XPS 10 F shown)
Non-Hazardous Location
(Safe)
bl
drain / shield
Note:
When connecting to an EnviroRanger ERS 500, the
white, black, and shield wires are all connected
separately. Do not tie the white and shield wires together.
wht
Interconnection
2-Wire Extension
(XPS 10 F shown)
Hazardous Location
(Class I, Div. 1, Group
A,B,C,D or Class II, Div.
1, Group E,F,G)
metal conduit
Coaxial Cable
Hazardous Location
(Class I, Div. 1, Group
A,B,C,D or Class II, Div.
1, Group E,F,G)
Non-Hazardous Location
(Safe)
junction box
drain / shield
blk
wht
extend cable using 18 AWG
shielded / twisted pair
Note:
When connecting to an EnviroRanger ERS 500, the
white, black, and shield wires are all connected
separately. Do not tie the white and shield wires together.
(XPS 10 F shown)
Non-Hazardous Location
(Safe)
metal conduit
extend cable using RG – 62 A/U
coax for optimum noise immunity
Note:
When connecting to an EnviroRanger ERS 500, do NOT
use coaxial cable.
Interconnection
Page 16XPS 10/15 F Series TransducerPL-551
Applications
Notes:
• The transducer is to be used only in the manner outlined in this
instruction manual.
• Normally, the transducer requires no cleaning or maintenance.
However, if performance changes are observed, immediately shut
down the level measurement system and perform a thorough
inspection, especially on the transducer.
• An XPS 10 F Series transducer is shown in these examples. An XPS
15 F transducer can also be used, but no hazardous seal is required.
Liquid Applications
Stilling Well / OCM
blind flange
air vent
TS-3 *
Applications
transducer
standpipe
bracing
standpipe inlet
primary element
stilling well inlet
Refer to page 19.
* the use of a TS-3 temperature sensor provides better temperature tracking in
applications where the temperature can change quickly.
PL-551XPS 10/15 F Series TransducerPage 17
stilling well
Submergence
In applications where flooding is possible, the transducer can be fitted with a
submergence shield*. The shield acts as a bell to create an air pocket in
front of the transducer face. The associated transceiver* interprets this as a
flooding condition, and reacts accordingly.
Applications
Note:
Refer to transceiver manual for programming requirements.
hazardous seal
(XPS 10 F only)
transducer
submergence shield*
(Refer to Milltronics
instruction manual
PL-530 for assembly
details)
air pocket
* on applicable models
Page 18XPS 10/15 F Series TransducerPL-551
Standpipes
In many applications, access must be made via a standpipe. In such cases,
Milltronics can provide factory bonded flanged transducers or a split flange
kit that will readily mate to the flanged standpipe. Another option is to hang
the transducer from a blind flange.
The standpipe length should be as short and the diameter as large as
possible. As a rule of thumb, the -3 dB cone of the sound beam should not
intersect the standpipe wall in applications opening into a vessel or larger
area. Otherwise, additional blanking will be required to compensate for the
interference zone created by the opening.
Note: When using a stilling well, make sure there is no build-up, weld s,
cou plings, or ot her debris o n the in side of the well wall. T his can affec t
reliability of measurement.
flanged
transducer
Applications
no
intersection
vessel
no additi on al bl ank ing requ iredno additi on al bl ank ing requ ired
nipple
welded into
blind fl ange
transducer
can read
level inside
or below
standpipe
transducer
standpipe
end cut on a
45° angle
typically
vessel
no
vessel
nipple
welded into
blind fl ange
transducer
sound be am
intersects
reflecti on at
interference
zone created
by opening
no additi on al bl ank ing requ ired
near blank ing extens io n of 150 m m (6”)
PL-551XPS 10/15 F Series TransducerPage 19
Volume
‘Alternate’
‘Preferred’
‘Bad’
Maintain full level
for full calibration.
Applications
Above this level
erroneous readings
will result as level
has entered
blanking zone.
(shaded area)
Empty level for
‘alternate locations.
Below this level,
echo would reflect
away from the
transducer.
may require target to
obtain empty reading
rise
discharge
beam
angle
tank
manufacturer’s
full level
span:
corresponds to tank
manufacturer’s
empty level.
tank
manufacturer’s
empty level
1. Beam should not detect bin bottom. If this occurs, use range extension
parameters (on transceivers where available) to omit false echoes. A 6° beam
angle (XPS 15 F) represents a rise:run of about 20:1 (10:1 for the 12° beam
angle of the XPS 10 F). In most tanks, the transducer should be centered as
much as possible (without interference from inlet) for optimum reading range.
2. Sound beam must be perpendicular to liquid surface. If standpipe is used,
refer to page 19.
3. Echo has missed improperly levelled transducer.
4. When performing an empty or full calibration, the tank must contain its
normal vapour and be at its normal temperature.
5. When used in hazardous areas, the XPS 10 F series transducer (shown)
must use a hazardous seal. This seal is
not
supplied by Milltronics. The
XPS 15 F Series transducer comes equipped with a stainless steel coupling
suitable for use in hazardous locations.
Page 20XPS 10/15 F Series TransducerPL-551
Water / Wastewater
Differential Level
Pump Control
Applications
Sewage Lift
PL-551XPS 10/15 F Series TransducerPage 21
Solids Applications
r
Typical
1. Transducer angled to avoid seams in bin wall and aimed at discharge in
order to read bin when empty.
Applications
2. Avoid intersecting bin wall seams, structural members and wall irregularities.
1
bin wall seams
2
filling profile
emptying profile
3. Transducer too close to material inlet. Falling material will intersect sound
beam and cause erroneous readings or loss of echo.
Easy Aime
3
Page 22XPS 10/15 F Series TransducerPL-551
4. On fluid like solids, aim transducer perpendicular to material surface.
r
minimal angle
of repose
4
discharge
5. On dual discharge bins, aim each transducer at the discharge point.
Applications
transduce
5
PL-551XPS 10/15 F Series TransducerPage 23
Special
r
Storage Bin with Agitator
1. Transducer should be kept away from infeed.
Applications
2. Where agitators are in use, use the Agitator Discrimination parameter on
transceivers where available.
3. Transducer should be aimed away from wall projections.
4. When used in hazardous areas, the XPS 10 F series transducer (shown)
must use a hazardous seal. This seal is
XPS 15 F Series transducer comes equipped with a stainless steel coupling
suitable for use in hazardous locations.
agitato
not
supplied by Milltronics. The
infeed
Page 24XPS 10/15 F Series TransducerPL-551
Dryer - Wood Chips
1. Transducer should be mounted perpendicular to slope of wood chips.
2. When used in hazardous areas, the XPS 10 F series transducer (shown)
must use a hazardous seal. This seal is
XPS 15 F Series transducer comes equipped with a stainless steel coupling
suitable for use in hazardous locations.
drag conveyor
not
supplied by Milltronics. The
infeed
Applications
typical low
level
typical high
level
PL-551XPS 10/15 F Series TransducerPage 25
Installation Diagram for the XPS 10 F
Page 26XPS 10/15 F Series TransducerPL-551
*7ml19981DU01*