Milltronics XPS-10, XPS-15 Instruction Manual

XPS-10/15 F SERIESTRANSDUCER
Instruction Manual PL-551 January 2001
33455510 Rev.2.2
Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected eq uip m ent . These w ar ning notices are accompanied by a clarification of the level of caution to be observed.
Qualified Personnel
This device/system may only be set up and operated in conjunction with this manual. Qualified personnel are on ly authorized to install and operate this equip m ent in accordance with established safety practices and standards.
Warning: This product can only function properly and safely if it is correctly transported,
stored, installed, set up, oper at ed, and maintained.
Note: Always use product in accordance with specifications.
Copyright Siemens Milltronics Process
Disclaimer of Liability
Instruments Inc. 2000. All Rights Reserved
This document is available in bound version and in electronic version. We encourage users to purchase authorized bound manuals, or t o view electronic versions as designed and authored by Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. will not be responsible for the content s of partial or whole reproductions of either bound or electronic versions.
MILLTRONICS®is a registered t rademark of Siemens Milltronics Process Instrume nt s Inc.
Contact SMPI Technical Publications at the following address:
Technical Publications Siemens Milltronics Process Instruments Inc. 1954 Technology Drive, P.O. Box 4225 Peterborough, Ontario, Ca nad a, K9J 7B1 Email: techpubs@milltronics.com
While we have verified the contents of this manual for agreement with t he instrumentation described, variations remain possible. Thus we cannot guarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. We welc ome all suggestions for improvement.
Technical data subject to change.
For the library of SMPI instruction manuals, visit our Web site: www.milltronics.com
© Siemens Milltronics Process Instruments Inc. 2001
Table of Contents
About Milltronics’ Transducers ...........................................................5
Hazardous Area Applications.................................................... 5
Specifications ........................................................................................ 7
XPS 10 F Series Transducers ..................................................7
XPS 15 F Series Transducers ..................................................8
Outline and Dimensions .......................................................................9
XPS 10 F Series Transducers ..................................................9
XPS-15 F Series Transducers ................................................10
Mounting ..............................................................................................11
Recommendations .................................................................. 11
Solids Applications..................................................................11
Liquid Applications .................................................................. 12
Interconnection ...................................................................................15
Recommendations .................................................................. 15
Applications.........................................................................................17
Liquid Applications .................................................................. 17
Solids Applications..................................................................22
Installation Diagram for the XPS 10 F ...............................................26
PL-551 XPS 10/15 F Series Transducer Page 3
Page 4 XPS 10/15 F Series Transducer PL-551
About Milltronics’ Transducers
The Echomax XPS F series of transducers operates in association with Milltronics ultrasonic level monitoring products.
The transducer operates by converting electrical pulses that are provided by the transceiver into ultrasonic pulses. When transmitted, these ultrasonic pulses reflect from the material surface and echo back to the transducer. The echo is converted back to an electrical signal, and is interpreted by the Milltronics tranceiver using our proven Sonic Intelligence™ algorithms.
About the…
hazardous seal (XPS 10 F series only)
transducer
transducer face
The effective acoustical energy is emitted from the transducer face and radiated outward, decreasing in amplitude at a rate inversely proportional to the square of the distance.
Maximum power is radiated axially (perpendicular) from the transducer face in a line referred to as the axis of transmission. Where power is reduced by half (– 3 dB), a conical boundary defining the sound beam, centered about the axis of transmission, is established. The diametric measurement of the cone in degrees defines the beam angle. Impedance matching techniques are used to optimize the transfer of power from the transducer into air and vice versa.
The XPS F series transducers incorporate an integral temperature sensor that reports the air temperature at the transducer to the transceiver. The connection is transparent, in that both the ultrasonic and temperature components of the transducer use the same leads.
-3db boundary
axis of transmission, perpendicular to transducer face
Hazardous Area Applications
The Echomax XPS F series of transducers can be used in hazardous areas.
For the XPS 10 F series transducer, a hazardous seal must be used to suit hazardous area classification. This seal is
not
supplied by Milltronics.
The XPS 15 F comes equipped with a stainless steel coupling suitable for use in hazardous locations.
PL-551 XPS 10/15 F Series Transducer Page 5
About the…
Page 6 XPS 10/15 F Series Transducer PL-551
Specifications
XPS 10 F Series Transducers
Measurement Range:
{
0.3 – 10m (1 – 33ft)
Frequency:
{
43kHz
Beam Angle:
{
12°
Environmental
{
location:
{
altitude:
{
ambient temperature:{-20 to 95°C (-4 to 203°F)
{
pollution degree:
{
indoor/outdoor
{
2000m maximum
{
4
Specifications
Construction
{
exposure:
{
colour:
{ mounting: { 1” NPT conduit connection
{
options:
{
cable:
{
{
{
{
{
{
®1
Kynar
slate gray
factory flange to suit ANSI standard submergence shield, where flooding can occur split flange for field mounting to suit ANSI
2-wire shielded / twisted, 0.5 mm2 (20 AWG) PVC jacket
Supply Source
{
Transducer shall only be supplied by a Milltronics certified controller.
Weight
2
{
0.8kg (1.8lb)
Separation
{
365m (1200ft) from transducer
Approvals
{
FM Class 1 Div 1, Group A, B, C and D
{
FM Class 2 Div 1, Group E, F, and G
{ see nameplate or consult Milltronics for other current approvals
1
Kynar® is registered trade mark of ELF Atochem.
2
approximate shipping weight of transducer with standard cable length
PL-551 XPS 10/15 F Series Transducer Page 7
XPS 15 F Series Transducers
Measurement Range:
{
0.45 – 15m (1.5 – 50ft)
Frequency:
{ 43kHz
Beam Angle:
{
Environmental
{
location:
{
altitude:
{
ambient temperature:{-20 to 95°C (-4 to 203°F)
{
Specifications
pollution degree:
Construction
{
exposure:
{
colour:
{
mounting:
{
options:
{
cable:
{
indoor/outdoor
{
2000m maximum
{
4
{
Kynar
{
slate gray
{
1” NPT conduit connection
{
factory flange to suit ANSI standard
{
submergence shield, where flooding can occur
{
split flange for field mounting to suit ANSI
{
2-wire shielded / twisted, 0.5 mm2 (20 AWG) PVC jacket
®3
Supply Source
{
Transducer shall only be supplied by a Milltronics certified controller.
Weight
4
{
2.0 kg (4.4lb)
Separation
{
365m (1200ft) from transducer
Approvals
{
FM Class 1 Div 1, Group A, B, C and D
{
FM Class 2 Div 1, Group E, F, and G
{
see nameplate or consult Milltronics for other current approvals
3
Kynar® is registered trade mark of ELF Atochem
4
approximate shipping weight of transducer with standard cable length
Page 8 XPS 10/15 F Series Transducer PL-551
Outline and Dimensions
XPS 10 F Series Transducers
Standard Flange (optional)
122mm
(4.8”)
86mm
(3.4”)
122mm
(4.8”)
radiating face
to suit ANSI
standards
Split Flange (optional) Submergence Shield (optional)
128mm
(5.0”)
nominal
to suit ANSI
standards
152mm
(6.0”)
Outline & Dimensions
124mm
(4.9”)
Refer to submergence shield instructions
(Milltronics’ manual number PL-530)
Note:
For the XPS 10 F series transducer, a hazardous seal must be used to suit hazardous area classification. This seal is
not
supplied by Milltronics.
For more information, refer to page 26.
PL-551 XPS 10/15 F Series Transducer Page 9
XPS-15 F Series Transducers
Standard Flange (optional)
1” NPT
304
stainless
steel
Split Flange (optional) Submergence Shield (optional)
Outline & Dimensions
120mm
(4.7”)
185mm
(7.3”)
radiating face
191mm
(7.5”)
nominal
185mm
(7.3”)
to suit ANSI
standards
253mm
(10.0”)
to suit ANSI
standards
158mm
(6.2”)
Refer to submergence shield instructions
(Milltronics’ manual number PL-530)
Note:
The XPS 15 F comes equipped with a stainless steel coupling suitable for use in hazardous locations.
Page 10 XPS 10/15 F Series Transducer PL-551
Mounting
Recommendations
Special handling precautions must be taken to protect the face of the transducer from any damage.
Mount the transducer so that it is above the maximum material level by at least the blanking value (0.3m for XPS 10 F and 0.45m for XPS 15 F). Refer
to the associated transceiver manual for instructions on setting the blanking value.
On liquid applications, the transducer must be mounted so that the axis of transmission is perpendicular to the liquid surface.
On solids applications, a Milltronics Easy Aimer should be used to facilitate aiming of the transducer.
Do not over-tighten mounting. Hand tightening of the mounting hardware is sufficient.
Secure installation by connecting a safety chain from the transducer to a structural member.
Consider the optional temperature sensor when mounting the transducer.
Solids Applications
Note: For the XPS 10 F series transducer, a hazardous seal must be used to suit hazardous area classification. This seal is Milltronics. For more information, refer to page 26.
(XPS 10 F shown)
Easy Aimer (typical model)
safety chain
transducer
not
supplied by
Mounting
PL-551 XPS 10/15 F Series Transducer Page 11
Liquid Applications
Notes:
In, the examples that follow, an XPS 10 F Series transducer is shown using a hazardous seal. This seal is
An XPS 15 F transducer can also be used in these applications, but, because it comes equipped with a stainless steel coupling, no hazardous seal is required.
not
supplied by Milltronics.
Mounting
Flexible Conduit
safety
chain
Flexible conduit transducer should not be
subjected to wind, vibration or jarring.
Submersible
(XPS 10 F shown)
hazardous seal
(XPS 10 F only)
transducer
(XPS 10 F shown)
flexible conduit
channel
Bracket
steel
(XPS 10 F shown)
rigid metal conduit
safety
chain
Submersible transducer, used in
applications where flooding is possible.
hazardous seal (XPS 10 F only)
submergence shield
Page 12 XPS 10/15 F Series Transducer PL-551
Blind Flange
Flange, gasket, hazardous seal and hardware supplied by customer.
(XPS 10 F shown)
Refer to page 19
nipple welded to bind flange
hazardous seal (XPS 10 F only)
Flanged
(XPS 10 F shown)
hazardous seal (XPS 10 F only)
factory flanged transducer
bolt
gasket
customer flanged, flat face only
nut
Flange, gasket, and hardware supplied by customer.
Refer to page 19
Note: Tighten the flange bolts evenly in order to ensure a good seal between the mating flanges.
Caution: Over-tightening can cause performance degradation
.
Mounting
PL-551 XPS 10/15 F Series Transducer Page 13
Mounting
Page 14 XPS 10/15 F Series Transducer PL-551
Interconnection
k
Note:
Installation should only be performed by qualified personnel and in accordance with local governing regulations.
Recommendations
When using an XPS 15 F transducer, configure the electronic transceiver for an XCT-12. These two transducers use the same settings.
Do not route cable openly.
For optimum isolation against electrical noise, run cable separately in a
grounded metal conduit.
Seal all thread connections to prevent ingress of moisture.
Do not run cable near high voltage or current runs, contactors and SCR
control drives.
Note:
In the interconnection examples that follow:
an XPS 10 F Series transducer is shown. An XPS 15 F transducer can also be used, but no hazardous seal is required.
assume that the transducer is located in a Hazardous location (Class I, Div. 1, Group A,B,C,D or Class II, Div. 1, Group E,F,G.) and the transceiver in a Non-Hazardous (Safe) Location.
Direct Connection
Hazardous Location
(Class I, Div. 1, Group
A,B,C,D or Class II, Div.
1, Group E,F,G)
metal conduit
PL-551 XPS 10/15 F Series Transducer Page 15
(XPS 10 F shown)
Non-Hazardous Location
(Safe)
bl
drain / shield
Note:
When connecting to an EnviroRanger ERS 500, the white, black, and shield wires are all connected separately. Do not tie the white and shield wires together.
wht
Interconnection
2-Wire Extension
(XPS 10 F shown)
Hazardous Location
(Class I, Div. 1, Group
A,B,C,D or Class II, Div.
1, Group E,F,G)
metal conduit
Coaxial Cable
Hazardous Location
(Class I, Div. 1, Group
A,B,C,D or Class II, Div.
1, Group E,F,G)
Non-Hazardous Location
(Safe)
junction box
drain / shield
blk
wht
extend cable using 18 AWG
shielded / twisted pair
Note:
When connecting to an EnviroRanger ERS 500, the white, black, and shield wires are all connected separately. Do not tie the white and shield wires together.
(XPS 10 F shown)
Non-Hazardous Location
(Safe)
metal conduit
extend cable using RG – 62 A/U
coax for optimum noise immunity
Note:
When connecting to an EnviroRanger ERS 500, do NOT use coaxial cable.
Interconnection
Page 16 XPS 10/15 F Series Transducer PL-551
Applications
Notes:
The transducer is to be used only in the manner outlined in this instruction manual.
Normally, the transducer requires no cleaning or maintenance. However, if performance changes are observed, immediately shut down the level measurement system and perform a thorough inspection, especially on the transducer.
An XPS 10 F Series transducer is shown in these examples. An XPS 15 F transducer can also be used, but no hazardous seal is required.
Liquid Applications
Stilling Well / OCM
blind flange
air vent
TS-3 *
Applications
transducer
standpipe
bracing
standpipe inlet
primary element
stilling well inlet
Refer to page 19.
* the use of a TS-3 temperature sensor provides better temperature tracking in
applications where the temperature can change quickly.
PL-551 XPS 10/15 F Series Transducer Page 17
stilling well
Submergence
In applications where flooding is possible, the transducer can be fitted with a submergence shield*. The shield acts as a bell to create an air pocket in front of the transducer face. The associated transceiver* interprets this as a flooding condition, and reacts accordingly.
Applications
Note:
Refer to transceiver manual for programming requirements.
hazardous seal (XPS 10 F only)
transducer
submergence shield*
(Refer to Milltronics instruction manual PL-530 for assembly details)
air pocket
* on applicable models
Page 18 XPS 10/15 F Series Transducer PL-551
Standpipes
In many applications, access must be made via a standpipe. In such cases, Milltronics can provide factory bonded flanged transducers or a split flange kit that will readily mate to the flanged standpipe. Another option is to hang the transducer from a blind flange.
The standpipe length should be as short and the diameter as large as possible. As a rule of thumb, the -3 dB cone of the sound beam should not intersect the standpipe wall in applications opening into a vessel or larger area. Otherwise, additional blanking will be required to compensate for the interference zone created by the opening.
Note: When using a stilling well, make sure there is no build-up, weld s, cou plings, or ot her debris o n the in side of the well wall. T his can affec t reliability of measurement.
flanged transducer
Applications
no intersection
vessel
no additi on al bl ank ing requ ired no additi on al bl ank ing requ ired
nipple welded into blind fl ange
transducer can read level inside or below standpipe
transducer
standpipe end cut on a 45° angle typically
vessel
no vessel
nipple welded into blind fl ange
transducer
sound be am intersects
reflecti on at interference zone created by opening
no additi on al bl ank ing requ ired
near blank ing extens io n of 150 m m (6”)
PL-551 XPS 10/15 F Series Transducer Page 19
Volume
‘Alternate’
‘Preferred’
‘Bad’
Maintain full level for full calibration.
Applications
Above this level erroneous readings will result as level has entered blanking zone. (shaded area)
Empty level for ‘alternate locations. Below this level, echo would reflect away from the transducer.
may require target to obtain empty reading
rise
discharge
beam angle
tank manufacturer’s full level
span: corresponds to tank manufacturer’s empty level.
tank manufacturer’s empty level
1. Beam should not detect bin bottom. If this occurs, use range extension parameters (on transceivers where available) to omit false echoes. A 6° beam angle (XPS 15 F) represents a rise:run of about 20:1 (10:1 for the 12° beam angle of the XPS 10 F). In most tanks, the transducer should be centered as much as possible (without interference from inlet) for optimum reading range.
2. Sound beam must be perpendicular to liquid surface. If standpipe is used, refer to page 19.
3. Echo has missed improperly levelled transducer.
4. When performing an empty or full calibration, the tank must contain its normal vapour and be at its normal temperature.
5. When used in hazardous areas, the XPS 10 F series transducer (shown) must use a hazardous seal. This seal is
not
supplied by Milltronics. The XPS 15 F Series transducer comes equipped with a stainless steel coupling suitable for use in hazardous locations.
Page 20 XPS 10/15 F Series Transducer PL-551
Water / Wastewater
Differential Level
Pump Control
Applications
Sewage Lift
PL-551 XPS 10/15 F Series Transducer Page 21
Solids Applications
r
Typical
1. Transducer angled to avoid seams in bin wall and aimed at discharge in order to read bin when empty.
Applications
2. Avoid intersecting bin wall seams, structural members and wall irregularities.
1
bin wall seams
2
filling profile
emptying profile
3. Transducer too close to material inlet. Falling material will intersect sound beam and cause erroneous readings or loss of echo.
Easy Aime
3
Page 22 XPS 10/15 F Series Transducer PL-551
4. On fluid like solids, aim transducer perpendicular to material surface.
r
minimal angle of repose
4
discharge
5. On dual discharge bins, aim each transducer at the discharge point.
Applications
transduce
5
PL-551 XPS 10/15 F Series Transducer Page 23
Special
r
Storage Bin with Agitator
1. Transducer should be kept away from infeed.
Applications
2. Where agitators are in use, use the Agitator Discrimination parameter on transceivers where available.
3. Transducer should be aimed away from wall projections.
4. When used in hazardous areas, the XPS 10 F series transducer (shown) must use a hazardous seal. This seal is XPS 15 F Series transducer comes equipped with a stainless steel coupling suitable for use in hazardous locations.
agitato
not
supplied by Milltronics. The
infeed
Page 24 XPS 10/15 F Series Transducer PL-551
Dryer - Wood Chips
1. Transducer should be mounted perpendicular to slope of wood chips.
2. When used in hazardous areas, the XPS 10 F series transducer (shown) must use a hazardous seal. This seal is XPS 15 F Series transducer comes equipped with a stainless steel coupling suitable for use in hazardous locations.
drag conveyor
not
supplied by Milltronics. The
infeed
Applications
typical low level
typical high level
PL-551 XPS 10/15 F Series Transducer Page 25
Installation Diagram for the XPS 10 F
Page 26 XPS 10/15 F Series Transducer PL-551