Milltronics COMPUFLO III Instruction Manual

COMPUFLO III
FLOWMETER
INTEGRATOR
Instruction Manual
PL-368
March 1993
33453680 PRR 1.1
TITLE PAGE #
Gener al Inf ormation
About the CompuF lo III 1 – 1 About th is Manual
General 1 – 2 Conventions 1 – 2
Specifications
CompuFlo III 2 – 1 Options 2 – 2
Installation
CompuFlo III 3 – 1 Interconnection 3 – 1
Hazardous Locations 3 – 1
Start Up
Hardware Set Up 4 – 1 Pre Start Up Checks 4 – 3 Initial Start Up 4 – 3
Programming
Calibration
General 5 – 1 Keypad 5 – 1 Parameter Entry 5 – 2
Direct Parame ter Access 5 – 2 Automat ic Parameter Access 5 – 2 Altering Parameter Values 5 – 3 Last Parameter Recall 5 – 3
Parameter Reset 5 – 3 Programming Sequence 5 – 3 Quick Start Procedure 5 – 3
General 6 – 1 Initial Calibration References 6 – 1 Zero 6 – 2 Span 6 – 2 Calibration Accuracy 6 – 2 Calibration Alternatives 6 – 3
Auto Zero 6 – 3
Lockout Mode 6 – 3
On-Line Span Calibration 6 – 3
Alternate Test References 6 – 4
ECAL Calibration 6 – 4
PL-368 i
Parameters
General 7 – 1 Parameters 7 – 1
Programming Chart 8 – 1
Operation
Initial Operation 9 – 1 Normal Operation
Start Up 9 – 2 Zero Calibration Check 9 – 2 Span Calibration Check 9 – 2 Reset Total 9 – 2 Run 9 – 2
Communication
General 10 – 1
Remote Com munication 10 – 2 Host Communication 10 – 2 Serial Printer Communication 10 – 2
Protocol 10 – 3
Data Field Descriptions 10 – 3 Message Requests 10 – 4 Message Responses 10 – 4
Appendices
Figures
Alphabetical Par ameter Listing 11 – 1 Maintenance and Spare Parts 11 – 2 Error Messages 11 – 3 Trouble Shooting 11 – 4 Quick Start 11 – 5
Start U p 11 – 5 Calibration 11 – 6 Operation 11 – 7 Performance Enhancement 11 – 7
FIG. 1 Outline and Mounting 12 – 1 FIG. 2 Layout 12 – 2 FIG .3 CompuFlo III / Flowmeter Interconnection 12 – 3 FIG. 4 Po wer, Auto Zero, & Rate Output Wiring 12 – 4 FIG. 5 Relay Wiring 12 – 5 FIG. 6 Communication Wiring 12 – 6
PL-368 ii
GENERAL INFORMATION
ABOUT THE COMPUFLO
The Milltro nics CompuFlo III is a microprocessor based integrator designed specifically for b u lk dry solids in-line weighing applications.
The CompuFlo III integrates a signal proportional to material flowrate (such as from a Milltronics flowmeter) over time to provide material totalization.
The Com puFlo III provides: » Rate and Total displays
» an analog mA output proportional to rate » a relay contact f or remote total izer or PLC operation » 2 alarm/ control relays based on rate and/or On-line Calibration » 2 communication ports for computer , PLC, or serial printer c onnection
The CompuFlo I II has three modes of operation; program, calib rate and run.
MULTI SPAN NO: 1R2:RATE HI R1:SPEED LO
1263957
TOTAL
T
150%100%50%0%-50%
The operator programs the CompuFlo III via the keypad to provide displays and outputs in the desired units of measure. The Comp uFlo III displays the name, range of acceptable values, (and additional information/instruction) of the parameter (programming feature) accessed.
In the calibrate mode, the system Zero (no flow) and Span (100% flowrate) calibration is established. A test reference (test weight) is used to simulate the force of material impacting the flowmeter sensing plate during the Span calibration. A mater ial test is normally performed to verify the calibration accuracy. If necessary, the material test results may be used to correct any deviation in calibration accuracy.
Calibration accuracy may be checked at any time. The results of th is check are automatically compared to the system calibration and the deviation is displayed. The operator may choose to continue operation with the previous calibration or the results of the calibration check.
All programming and calibration information is stored in non-volatile memor y. If desired, the security parameter may be set to ensur e the CompuFlo III programming and calibration is not inadvertent ly altered in the run mode.
The run mode is the normal operating mode, providing dynamic measurement displays, analog mA output, and a variety of other features.
PL-368 1 – 1
ABOUT THIS MANUAL
GENERAL
This instruction manual conta ins informat ion essential to successful CompuFlo III operation. SPECIFICATIONS, includes CompuFlo III environmental, phys ical, and operational characteristics. INSTALLATION, indicates the typical mounting and interconnection procedure. START UP, prepares the Compu Flo III for programming. PROGRAM MING, details activities required to ta ilor t he CompuFlo III to the par ticular application. CALIBRATION, includes the CompuFlo III input signal to output feature corr elation procedure. PARAMETERS, describes the function, factory setting, and range of possible settings,
of each parameter. PROGRAM MING CH A RT, provides a space to record programmed parameter values for futur e reference. OPERATION, describes initial and normal CompuFlo III operation. COMMUNICATION, provides CompuFlo III serial communication information. APPENDICES, contains Quick Start , Alphabetical Parameter L ist, Maintenance and Spare Parts,
Error Messages and Trouble Shooting information. FIGURES, includes a complete set of installation and interconnection drawings.
CONVENTIONS
Throughout this instruction manual the following symbols and presentation practices have been utilized: [1234567ABCDEFG] alpha numeric characters enclosed within these brackets repr esents information
displayed by the CompuFlo III display.
[T/h] units of measure were arbitrarily chosen from the imperial set. The actual units
displayed or other wise applicable will be dependent upon o perator programming.
indicates the following CompuFlo III keypad button is to be pressed.
"RUN" or alpha numeric characters enclosed within quotation marks or this symbol
ENTER
represent a key on the CompuFlo III keypad.
Italics
are used to identify the defined word(s) or phrase within a definition statement.
Informat ion of a hig her order of importance, is indented from
both left and right margins and in bold print.
PL-368 1 – 2
SPECIFICATIONS
COMPUFLO III
Power: » 100/115/200/230 V AC ±10%, jumper
selectable, 50/60 Hz, 65 VA
Fuse: » FU 1 » 3/ 4 Amp MDL SLO-BLO or equivalent
» FU 2 » 1/ 4 Amp MDL SLO-BLO or equivalent
Operating » -20 to 50°C (-5 to 122°F) Temperature:
Accuracy: » 0.1% of span, typical Resolution: » 0.02% of span, typical Inputs: » Load cell: » -20 to +45 mV DC per load cell
» 2 load cells max. » LVDT: » 0 to 0.75 Vrms, 3 kHz » Multispan: » 4 contact inputs for up to 8 spans » Keypad: » 20 key sealed membrane with tactile feedback » On-Line: » 4-20 mA proportional to weight
(Calibration) » Auto Zero » contact input for enable » Printer: » contact input for print request
Outputs: » Load cell: » 10 V DC, 250 mA max.
(excitation) » LVDT: » 2.0 Vrms, 3 kHz, 50 mArms max.
(excitat ion) » Analog: » 4-20 mA,(0-25 mA scaleable), isolated, proportional to rate » 0.1% resolution
» 750 max. load » Remote » SPST sealed relay
Totalizer:
» 1 form "A" contact rated 2A at 250 V AC, 100 VA max.
» 25 msec. minimum contact closure duration
» 15 closur es per second max
PL-368 2 – 1
» Alarm: » 2 multipurpose relays for Rate or On-line Calibration
assignment
» 1 Form "C" SPDT contact per relay, rated 5A at 230 V AC
» Communication: » 1 relay, 4PDT used for communication loop dropout,
rated 1A at 230 V AC
» Display: » illuminated 256 x 128 dot matr ix
Communication: » 2 serial ports
» RS232C and ± 20 mA current loop
Enclosure: » NEMA 4 style, steel construction with polycarbonate window
» 330 mm W x 406 mm H x 102 mm D
(13" W x 16" H x 4" D)
Shipping Weight: » 11.0 Kg (24.3 lbs), no opti o n s
OPTIONS
Cable: » Single load cell, 150m (500 ft) max. 20 AWG, 4 wire shielded,
Belden 8404 or equivalent
» Single load cell, 300m (1 000 ft) max. 20 AWG, 6 wire shielded,
Belden 8426 or equivalent
» Dual load cell, 150 m (500 ft) max. 20 AWG, 6 wire shielded,
Belden 8426 or equivalent
» Dual load cell, 300 m (1000 ft) max. 20 AWG, 8 wire shielded,
Belden 8418 or equivalent
» LVDT, 150 m (500 ft) max. 20 AWG, 4 wire shielded,
Belden 8404 or equivalent Barrier Strips: » For hazardous location flowmeters Enclosure Heater: » Recommended for operating temperatur es below -10 ° C
(14°F) or excessive humidity Relay: » Food Grade remote totalizer relay CVCC: » For bipolar current loop/RS-232C conversion BIC-II: » For 6 port bipolar current loop/RS-232C or RS-422 conversion.
PL-368 2 – 2
INSTALLATION
CompuFlo III
The CompuFlo III should be mounted in an area that is within the specified temper ature range, and that is suitable for NEMA 4 style enclosures. The front cover should be accessible for keypad operation, display viewing, and have sufficient room to swing open.
It is advisable to keep the CompuFlo III away from high voltage or current runs, contact ors, S CR control drives and RF interference.
For proper totalizer relay operation, the CompuFlo III must be mounted within 30° from vertical. Do not mount the CompuFlo III in direct sunl ight without the use of a sun shield.
INTERCONNECTION
Remov e the enclosure bottom plate prior t o drilling or punching cable/conduit entrance(s ), to ensure metal filings do not come in contact with the CompuFlo III electronics.
Load cell or LVDT, rate output, On-Line Calibration input, communication, and low voltage contact wiring may be run in a common conduit separated from power and high voltage contact wiring. Refer to Figures.
The power ground (TB1-50) is internally connected to SHLD connections (TB1-13,26, TB2-5), and to the mother board bottom mounting lugs. COM connections (TB1-15,29,32,36,37, a nd TB2-8) are connected to power ground via jumper J2 (below TB1, between the mounting lugs). If the COM connections must be isolated from power ground, remove J2.
Refer to FIGURES All wiring must be perf ormed in accordance with all governing regulations.
HAZARDOUS LOCATIONS
The CompuFlo III cannot be mounted in an area classed as hazardous. Where the associated flowmeter is mounted in a hazardous area, barrier strips must be used to isola te the CompuFlo III from the hazardous area for intrinsic safety. Encapsulated LVDT transducing elements are also available. Contact Milltronics or your local representative for hazardous application information.
PL-368 3 – 1
START UP
HARDWARE SET UP
UNIT I.D.
The CompuFlo III identification code factory setting is 00, as set by SW1 contacts 1 - 4.
When more than one CompuFlo III is connected to a host computer or PLC, the identification code of each CompuFlo III must be set to a differ ent value.
UNIT SW 1
I. D. 1 2 3 4
00 O O O O 01 C O O O 02 O C O O 03 C C O O 04 O O C O 05 C O C O 06 O C C O 07 C C C O
SW1
UNIT I. D. #
1248
METRIC
0000
IMPERIAL
UNIT SW 1
I. D. 1 2 3 4
08 O O O C 09 C O O C 10 O C O C 11 C C O C 12 O O C C 13 C O C C 14 O C C C 15 C C C C
LOCKOUT
MAIN TOTAL RESET
TEST
NORMAL
O = switch contact open C = switch contact closed
UNITS OF MEASURE
Two sets of Units are available; Imperial and Metric. Leave SW1 contact 5 (SW1-5) in the open position for Imperial, or closed for Metric units. R efer to PARAMETERS / P0 - RATE UNITS for the Rate Unit options available.
SW1-5 must be set to the desired position b ef ore i nitial pro grammi ng is performed. To alter the Units of Measure of a programmed CompuFlo III, set SW1-5 as desired,
then perform a Reset. Refer to Parameters / P99 Reset.
LOCKOUT
Leave SW1 contact 6 (SW1-6) in the open position for normal applications. Close SW1-6 for Lockout Mode operation, after all programming and calibration is complete. Refer to Calibration / Calibration Alternatives.
TOTALIZER RESET
Leave SW1 contact 7 (SW1-7) in the open position for normal operation. When this contact is closed, the Main Total Display cannot be reset.
TEST MODE
Leave SW1 contact 8 (SW1-8) in the open position for normal operation. The closed position is reserved for Milltronics service personnel.
PL-368 4 – 1
ALTERNATE
TB2 BAUD
000
4
X
4
2
PRINTER
REMOTE
TERMINAL
SERIAL
TEST /
ADJUST
SW2
3
0
1
X
ENGLISH
SPARE
PORT 2 BAUD RATE
The CompuFlo III TB2 com munication port baud rate is independent of the PORT 1 baud rate, and is set by SW2 contacts 1 and 2. Set the baud as required by the device connected. The factory setting is 300 baud.
Baud SW2
Rat e 1 2
300 O O
O = switch contact open
1200 C O 2400 O C
C = switch contact closed
9600 C C
NORMAL
LANGUAGE
Leave SW2 contact 3 (SW2-3) in the open position for English, or closed for alternate language, CompuFlo III displays.
REMOTE DISPLAY
Leave SW2 contact 6 (SW2-6) open for normal operation. If a remote mounted terminal is used, SW2-6 of the remote terminal (only) must be closed.
PORT 2 COMMUNICATION MODE
Leave SW2 contact 7 (SW2-7) open for normal operation, or closed if a serial printer is connected to PORT 2.
TEST/ADJUST MODE
Leave SW2 contact 8 (SW2-8) in the ope n position for normal operation. In th e closed position, a test menu is displayed.
When the keypad test is selected, a pictorial representat ion of the keypad is displayed. As each keypad button is depressed, the display indicates successful operation.
When the display contrast adjustment is selected, pressing "4" increases, and pressing "8" decreases the display contrast.
PL-368 4 – 2
PRE START UP CHECKS
After the Compu Flo III has been properly installed and interconnected, the following checks should be performed prior to connecting power:
»all cable connections are correct and secure. »the proper voltage has been selected (J1 on the mother board). »SW1 and SW2 have been set as required. »the POWER switch is in the OFF position.
Connect power to TB1 -51,52 and ground to TB1-50 of the CompuFlo III. Ensure all connections are secure.
Do not operate the CompuFlo III with the
ground (earth) wire disconnected.
INITIAL START UP
Se t the Co mpuFl o III POWER switch to the ON position. The CompuFlo III will enter the following initialization routine:
COMPUSCALE/FLO III (REV DATE) (EPROM 2 REV) TEST : (MESSAGES)
PL-368 4 – 3
When the display initializa tion routine is complete, the display revert s to the last operati ng mode accessed. If the CompuFlo III is not programmed, the paramet er entry display is accessed.
The CompuFlo III display is divided into the following fields:
MULTISPAN
FEATURE
ECAL
VALUE
RELAY
CALIB CYCLE
UNITS
AUX 1
AUX 2
-50%
150%100%RAT E0%
RATE BAR GRAPH
FIELD DESCRIPTION
MULTISPAN current span calibration selected. If Multispan 0 is selected, the field is blank. RELAY current relay status (run mode). If re lays are not used, or in non-alarm, the field is blank. FEATURE para meter number (parameter entry), calibration type (calibrate mod e), Rate or Total (run mod e) ECAL indicates ECAL (simulated rate signal) is on. If ECAL is off, the field is blank. CYCLE full cycles remaining before calibration completion (calibrate mode). CALIB calibrate mode indicator. When displayed, tota lizers are on HOLD (unless otherwise specified). VALUE the current va lue associated with the featur e selected. UNITS the units of measure associated with the value displayed AUX 1 parameter name (parameter entry), auxiliary message (cali b rate mode), not used (run mode). AUX 2 parameter value range (paramet er entry) , addit ional information or error message (any mode). BAR GRA PH represents current rate, displayed as percent of span (run mode).
PL-368 4 – 4
PROGRAMMING
GENERAL
Information specific to a particular application is entered into the Com puFlo III memory, via the keypad, prior to the calibration procedure.
KEYPAD
Button Operation Function
0
9
parameter entry numeric entries
4
8
RUN
PAR
ZERO
SPAN
ALT
DISP
RESET TOTAL
parameter entry increase: analog mA output (P17 and P18 only), ECAL value (P22 only)
parameter entry decrease: analog mA output (P17 and P18 only), ECAL value (P22 only)
parameter entry decimal point
parameter entry negative entry or display prev ious parameter
any mode enter the run mode, return to previously selected display
any mode access parameter for entry or viewing
any mode access zero calibration, view current zero count
any mode access span calibration, view current span count
any mode enter the run mode, select rate or total display
any mode reset displayed totalizer value to zero (refer to Start Up\Hardware
Set Up\Total izer Reset)
CLEAR
parameter entry clear entry calibrate mode abort calibration
ENTER
parameter entry display parameter value, or store altered parameter value,
or display next parameter calibrate mode activate zero or span calibration, or accept calibration results any mode with total displayed, switch to alternate total (ma in or sub)
PL-368 5 – 1
PARAMETER ENTRY
Application information must be entered into the appropriate CompuFlo III memory locations . These locations are identified by a Paramet er Number (P#). The information entered is referred to as a Parameter Value (Value ). To enter informat ion, the operator accesses the desired parameter number, v iews the parameter value displayed, and then accepts or alters the current parameter value.
Common Parameter Entry Display Fields
FEATURE
VALUE
UNITS
AUX 1
AUX 2
-50%
150%100%RATE0%
RATE BAR GRAPH
DIRECT PARAMETER ACCESS
To directly access any parameter, followed by the parameter number.
PAR
Only valid parameter numbers will be accepted. Refer to PARAMETERS for the list of valid parameter numbers.
eg. [PARAMETER ] is displayed in the F EAT URE field, if PARAMETER 0 is desired [PARAMETER 0 ] is displayed in the F EAT UR E field,
PAR
0
[RATE UNITS ] is displayed in the AUX 1 field.
To view the current paramet er value and auxiliary messages for the displayed parameter,
ENTER
[PARAMETER 0 ] is displayed in the FEAT UR E field [ 1 ] is displayed in the VAL UE field (unless previously altered) [RATE UNITS ] is displayed in the AUX 1 field
[1:T/h;2: LT/h;3: lb/ h;4: lb/m in ] is displayed in the AUX 2 field (with SW1-5 open)
AUTOMATIC PARAMETER ACCESS
Upon accessing any parameter value, pressing "ENTER" will autom atically access the next parameter in the programming sequence. Pressing "-" will automat ically access the previous parameter.
eg. with the VA LUE field of PARA METER 0 displayed...
ENTER
[PARAMETER 1 ] is displayed in the FEAT UR E field [ 0.0000 ] is displayed in the VAL UE field (unless previously altered) [RATE ] is displayed in the AUX 1 field [ENTER VALUE ] is displayed in the AUX 2 field
all fields associated with PARAMETER 0 are displayed
PL-368 5 – 2
ALTERING PARAMETER VALUES
Once the desired parameter number is accessed, the parameter value may be accept ed or altered as required.
eg. if the VALUE f ield of PARAMETER 0 is 1 (T/h), however 2 (LT/h) is desired
2
ENTER
[ 2 ] is displayed in the VALUE fi eld the new value (2) is now stored in memory
LAST PARAMETER RECALL
From the Calibrate or Run mode, the last parameter accessed in the Program mode, may be recalled.
the last parameter accessed is displayed.
ENTER
PAR
PARAMETER RESET
To reset all parameters to factory settings, refer to PARAMETE RS/P99 M aster Reset.
PROGRAMMING SEQUENCE
Typically, the CompuFlo III is programmed as follows:
a) Referring to PARAMETERS, copy the selected parameter v alues to the spaces provided on the PROGRAMMING CHART fold out.
b) Perform a MASTER RESET (P99). c) Access each parameter ( in sequence from P 0) and enter the parameter values
from the PROG RAMM ING CHA RT. d) Perform a Zero and Span calibration (refer to CALIBRATION) e) Perform Span Adjust (P8) or Factoring (P9) procedures, as req uired.
Remember to copy any parameter value alterations onto
the PROGRAMMING CHART for future refer ence.
QUICK START PROCEDURE
The Quick Start Procedure describes the minimum star t up, programming, and calibration requirements of the CompuFlo III, to obta in successful RUN mode operation for most applications.
If desired, refer to APPENDICES /Quick Start. Parameters which are not included in the procedure may be program med after the RU N mode is entered.
PL-368 5 – 3
Loading...
+ 42 hidden pages