Miller QUICK CUT 5000 Owners manual

Page 1
AUTO
ARC)~
January
Effe
1989
ctlve
FORM:OM.143
ii
Seria
JJ5I
527
8269
MODEL:
QUICK
CUTTM
5000
OWNERS.
IMPORTANT:
special installing,
instructions
operation
operate,
understand
647
TC-125
Read
emphasis
operating,
are
of
welding
maintain
or
these
understand
on
or
for
maintaining
use
only
equipment.
this
instructions.
safety
by
unit.
material
persons
Do
Contact
this
entire
trained
allow
your
contents
throughout
equipment.
experienced
untrained
distributor
MANUAL
in
to
the
not
with
before
these
safe
install,
fully
of
the
This
persons
if
this
manual,
unit
you
manual,
do
MILLER
A
Miller
Group
Box
P0
Appleton,
414-734-9821
Tel.
ELECTRIC
Ltd.,
Company
1079
WI
54912
USA
Mfg.
PRINTED
IN
Co.
U.S.A.
Page 2
Page 3
ERRATA
SHEET
After
data
to
the
Add
A~
AMENDMENT
Amend
The
steel
although
an
curve
Table
Section
cutting
within
increase
will
manual
this
appearing
following
CAUTION:
Do
TO
2-1.
Rated
Duty
30
120
2-5.
Output
At
Cycle
Amperes
At
Volts
speed
the
capabilities
the
speeds
in
speed
cause
rapid
was
printed,
In
at
this
the
later
CAUTION
INCORRECT
air
or
only
not
use
SECTION
nitrogen
other
any
2
-
Specifications
Maximum
Open-
~
370
Speed
of
the
DC
(Chart
optimum
of
DC
Cutting
enables
chart
indicated
until
erosion
refinements
manual.
beginning
PLASMA
for
or
gas
INTRODUCTION
Rated
50/60
Amperes
115V
Volts
38
2-1)
the
operator
not
source.
be
achieved
power
speed
the
tip
In
equipment
ot
Sections
GAS
can
plasma
combination
Table
I
gas
2-1.
At
input
Load
HZ
Sin~–hase
At
230V
KVA
SpecifIcations
Output
I
33
to
determine
is
reached.
electrode
7.6
curve
instantaneously.
and
2-4
and
cause
supply.
of
gases.
KW
the
maximum
indicates
Cutting
should
design
3-2,
torch
Air
Cutting
at
speeds
be
occurred.
also
and
power
Plasma
Or
Nitrogen
Flow/Pressure
CFM
L/min.)
(79
50
At
kPa)
(345
cutting
proper
avoided.
speeds
may
above
This
before
source
Gas
PSI
speed
have
the
sheet
Step
Onl~
at
to
begin
proper
2
damage.
Net
52
(24
various
which
lists
exceptions
of
Section
Weight
lbs.
kg)
thickness
cutting
slower
at
a
speeds
Ship
56
(25
shown
5-1.
lbs.
kg)
be
speed
of
dcne.
by
mrld
w~trt
the
Chart
CAUTION: electrode.
Do
not
2-1.
Cutting
EXCEEDING
exceed
Speed
z
z
z
d
LU
0,
0
RECOMMENDED
indicated
90
(2.31
80
(1.5)
30
(0.8)
cutting
Chart
I,
20
I
~
speeds.
2-1.
III
12
(CAGe)
.I0(2.~1
PLATE
CUTTING
CuttIng
3/18
~
ll~
.20(~.I)
THIC~(NESS.
SPEEDS
Speed
1/4
IN.
.30(7.61
(MM)
will
cause
3/8
.i.0(I0.2)
rapid
erosion
SB.lr
of
the
~
tip
and
Page 4
AMENDMENT
TO
SECTION
MAINTENANCE
6-
TROUBLESHOOTING
&
damage
would
unit
(see
6-9.
6-5C.
Amend
C.
To
the
ott,
compressor
Section
Air
Pressure
prevent
pressure/regulator.
Section
WARNING:
a
Each
around
replace
AMENDMENT
time
the
HOT
the
pins,
torch
Do
Turn
or
SURFACES
Allow
shield
clean
TO
OVERLOAD
Switch
torch
the
to
Should
be
completely
6-2.
Table
SHIELD
not
of
Troubleshooting).
CUP
ELECTRIC
touch
f
power
servicing.
cooling
removed
is
cup
with
pins
or
body
pin
SECTION
PROTECTION:
to
air
inoperative.
DETECTOR
SHOCK
live
electrical
source,
cause
can
period
before
from
electrical
assembly,
7-
ELECTRICAL
insufficient
pressure
drop
PIN
can
parts.
remove
severe
servicing.
the
torch,
contact
contact
Air
Pressure
air
pressure,
below
Should
INSPECTION
kill.
input
power
burns.
check
cleaner,
the
nearest
DIAGRAMS
this
a
preset
READY
that
and
Factory
Switch
unit
value,
plug
shield
recheck
is
protected
S5
be
light
from
receptacle
cup
lorfree
Authorized
would
turned
detector
movement,
by
close,
check
on,
before
pins
Service
pressure
the
switchS5located
READY
light
airfilterlregulator
inspecting,
move
lilt
becomes
Station.
maintaining.
If
freely.
necessary
in
would
turn
air
and
thereisdiii
to
Amend
Add
Diagram
Diagram
Add
Diagram
Add
Diagram
AMENDMENT
Amend
25-31 25-35 25-36 25-38 25-39
25-
27-1 27-3
27-13
31-4
Diagram
7-2.
7-3.
7-4.
7-5.
List
Parts
Dia.
Mkgs
iT
Torch Work
7-1.
TO
Circuit
Circuit
Circuit
Circuit
Circuit
SECTION
follows:
as
125181
Diagram
Diagram Diagram
Diagram
Diagram
Part
No.
126
114
121
068
For
For
PARTS
9-
Replaced
Deleted
Deleted Deleted Deleted Deleted
126
125
125181 130 130 130 130032
(see
Driver
Transformer
Filter
High
With
797
285 031
3
this
PC2
Control
(see
Board
Errata
(see
Board
Page
Page
Sheet)
PC3
5
(see
Page
Board
Board
Frequency
LIST
on
Description
Item
not
Item
not
Item
not
Item
not
Item
not
TORCH.
TERMINAL,
FITTING.
available available
available available
available
APT-3000
(added
as
an
as
an
an
as
an
as
as
an
(addeddiamkg)
mkg)
TERMINAL,(addeddiamkg)
TORCH
DETECTIVE
BODY,
INSULATING
SCREW
(consisting
PIN
KIT,
COVER
(consisting
4
this
on
(see
this
on
Page
assembly assembly assembly
assembly assembly
.
(Eff
of)
Errata
Sheet)
5
6
on
on
Sheet)
this
Page
Errata
w/JK634462)
of)
this
Errata
Errata
Sheet)
Sheet)
OU3r~V
First BE
OM-296
SURE
digit
represents
TO
2
Page
PROVIDE
page
MODEL
no
-
digits
AND
following
SERIAL
NUMBER
dash
represent
WHEN
item
ORDERING
no.
REPLACEMENT
PARTS
Page 5
i~i~
~
9
,
PS
~11D~
-.0
IT
063-B
SC125
No.
Diagram
Circuit
ii
~
TMI
PS
~
~
!
~
A
!f!
~
Diagram
Circuit
7-1.
Diagram
Page 6
644
29
SC-i
No.
Diagram
Circuit
PC2
Board
Driver
For
Diagram
Circuit
7-2.
DIagram
0
-o
lQ
Page 7
CN6
-3
-3
CN9-
-3
CN3
-3
CN5-3
CN2-
CN3-
CN4-
CN5-
Diagram
-f
CNI
I
CNI
-3
I
CN8-
Board
CN8-2
I
CN7-
CN7-3
I
CN6-
Diagram
PC3
No.
SA-1
29
636
I
I
I
I
Circuit
CircuIt
7-3.
Diagram
Power
Distribution
3<
4
Ri
C2
Cl
I
CN
3
CN3
L2
C3
L7
>2
CNS
7
5
3
L8
SA-129
Circuit
Diagram
No.
638
Diagram
7-4.
CircuIt
Diagram
Filter
Board
PC4
OM
Y~...
5
~e
Page 8
4
3
ct4I
DIagram
7-5.
CircuIt
Diagram
High
Frequency
Circuit
Board
Diagram
PC5
c~ C6
EI(
29
OTB?
1B2
OM-296
Page
6
Page 9
TABLE
OF
CONTENTS
Section
SECTION
SECTION
SECTION
-
1
SAFETY
1-1.
1-2.
1-3.
1-4.
2-1.
2-2. 2-3. 2-4.
3-1.
3-2. 3-3.
3-4.
Introduction
General
Standards
2-INTRODUCTION
Duty
General
Receiving-Handling
Description
3INSTALLATION
Location Air
Input
Electrical
RULES
Precautions
Welding
Booklet
Index
Cycle
Information
Filter/Regulator
Voltage
Input
And
Installation
Changeover
Connections
Safety
And
Switch
Connections
Page
No.
1
1
4
5
7
7
8
8
8
8
9
9
SECTION
SECTION
SECTION
4-1.
4-2.
4-3.
4-4.
4-5.
4-6.
5-1. 5-2.
5-3.
6-1. 6-2. 6-3. 6-4.
6-5.
6-6.
6-7.
6-8.
4-
OPERATOR
Power
Ready
Metal
Thickness Gas/Air
Trigger
5-
Plasma
Cutting Shutting
6-
Routine
Shield
Torch
Spark
Overload
Safety
Circuit
Switch/Breaker
Light
Switch
Control
Switch
Hold
SEQUENCE
Arc
Problems
Down
MAINTENANCE
Maintenance
Cup.
Gap
Protection
Shutdown
Board
Troubleshooting
CONTROLS
Switch
OF
Cutting
Tip,
Work
Lead
Handling
Power
OPERATION
(PAC)
And
Recommendations
&
TROUBLESHOOTING
Electrode
Inspection
Devices
Precautions
On
Light
Inspection
Connections
Replacement
11 11 11 11 11 11
12
13
13
13
14
15 16
16 16
17
17
SECTION
7-
Diagram
ELECTRICAL
7-1.
Circuit
DIAGRAMS
Diagram
19
Page 10
24262728
Section
SECTION
SECTION
No.
8-
8-1. 8-2.
8-3.
8-4.
8-5.
8-6.
8-7.
9
Figure
Figure
Figure Figure Figure Figure
Figure
PLASMA
General
Definitions
ARC
CUTTING
High-Frequency
Location
General
Guidelines
Power
Installation
PARTS
9-1. 9-2.
9-3.
9-4.
9-5.
9-6. 9-7.
Installation
Sources
Guidelines
LIST
Main
Assembly
Capacitor
Terminal
Front
Panel
Pilot
Unit
Rectifier
Torch,
Assembly
Model
Installation
Assembly
Assembly,
Assembly
Radiation
Procedures
Checklist
.
APT-3000
(PAC)
Of
Plasma
Output
INSTALLATION
Cutting
GUIDELINES
(PAC)
Page
20 20
21 21 21
22
23
29
30
31
LIST
OF
Table
Table Table
CHARTS
2-1. 6-1.
6-2.
AND
TABLES
Specifications
Maintenance
Schedule
Troubleshooting
7
13 18
Page 11
SECTION
1
SAFETY
RULES
1-1.
INTRODUCTION
We
learn
by
sonal
experience,
harmful,
others
Safe
welding
search,
evolved
tion,
wasteful,
teach
practices
development,
reliable
and
servicing
equipment
the safe
son
Some technical
rules.
Read
tempting
Comply
ticular
personal
Failure
ous
based
are
volumes
to
with
equipment
safety
observe
to
or
injury
equipment
These
1-General
ting;
Reference
are
cedures
in
most
The
Health
safe
2-Arc
available
also
than
Standards
complete.
National
Administration,
inspection
ment
installation,
GENERAL
1-2.
DIfferent
and
radiatIon
this
manufacturers
(MSDSs)
ary
A.
Wear
use
shirt
avoid
to
Wear
shields
arc
fluxes
manual,
measures
PreventIon
Burn
protective
in
welding,
collar
entry
helmet
underneath,
(protected
welding
or
experience.
likeachild
unwise.
you.
developed
cutting
are
equipment
practices.
is
improperly
practices
common
on
to
explain.
understand
install,
these
and
death.
be
can
practices
Precautions,
these
operate,
proceduresasapplicable
and
used
these
When
with
used
are
common
Welding
additional
given
Published
Code,
local
standards:
those
Indexinthis
Electrical
requirements
use,
PRECAUTIONS
welding
can
produce
levels.
be
specific
in
addItion
sure
Material
technical
processes,
to
concerning
clothing-gauntlet
hat,
pocket
of
with
flaps,
sparks
safety
appropriate
clear
by
cutting,
cover
(and
Learning
from
describedinthis
and
usedormaintained.
may
their
safety
safe
safety
divided
(and
safety
touching
the
experience
field
experience
safe
installation,
Accidents
not
alwaysbegiven.
sense,
or
others
It
is
wisertofollow
safe
practices
service
instruction
of
others.
practices
becomes
confidence.
into
to
arc
Cutting)
through
a
experience
may
two
welding
(only).
Standards
more
in
this
manual.
manual.
complete
They
ANSI
Occupational
industrial
also
provide
service.
dIfferent
consult
Safety
their
to
codes,
a
electrode
fumes,
flux
data
and
material.
basis
Information
and
Data
gloves
cuffiess
glasses
lenses
This
to
protect
shoes.
is
high
safety-toe
wear
slag.
goggles
and
filter
glass).
chipping)
stove
use
opera
The
require
before
per
of
Re
have
when
rea
at
in
manual.
occur
may
equipment.
to
par
seri
habit,
the
manuals,
cause
a
Sections:
cut
on
safety
pro
listed
are
Z49.1
is
for
local
equip
Safety
alloys,
gases,
electrode
Sheets
precautIon
Button
trousers
with
side
or
plates
eyes
for
for
designed
MUST
a
is
of
In
from
radiant
when
glass
Avoid
Hot should
Medical
and
each
mediate burns.
Ear
in
a
others
or
oily
metal
never
first
a
qualified
shift
unless
treatment
should
plugs
confined
work
such
Flammable
sons
intending
B.
Toxic
Severe
fumes,
that
with
dard
with
Lead
and
ing
duce
local
in
the
plied
Metals
toxic
moved
and,
tor.
Work
and,
tor.
Gas Leaked
centration
confined
Leaving
to
prevent
Fume
discomfort,
vapors,
welding
adequate
Z49.1
oxygen.
cadmium
-,
similar
harmful
exhaust
area
as
respirator.
coated
fumes
from
if
necessary,
in
confined
a
if
necessary,
leaks
gas
dangerously.
space.
confined
possible
downstream left
open.
Check
re-entering
from
heat
toxic
The
ultraviolet
Vapors by highly
ucts.
decompose
to
vapors solvent
form
vapors
energy
broken,
greasy
as
be
handled
aid
and
first
medical
of
be
space.
overhead.
hair
preparations
weld
to
Prevention
flying
or
without
treatment.
person
facilities
burns
when
hard
cut.
or
spattered.
A
hat
should
pitted,
clothing.
electrode
eye
aid
flash
worn
A
illnessordeath
or
heat,
(or
ventilationasdescribed
listed
materials,
concentrations
ventilation
well
For
with
should
work
in
a
in
large
valves
to
oxygen
cutting)
in
Standards
zinc
-,
-,
as
mercury-,
when
must
the
operator
beryllium,
or
containing
be
not
surface,
while
wearinganair-supplied
space
while
wearinganair-supplied
confined
quantities
Do
space,
shut
accumulation
have
be
sure
may
heated
only
space
not
been
that
of
whileitis
OFF
it.
chlorinated
of
the
arc
and
gas,
solvents
flame)
(or
other
lung
(radiant)
energy
tnchloroethylene
drawn
DO
into
phosgene.
be
can
metal.
Replace
See
spark
may
stubs
gloves.
First
are
of
the
should
not
be
close
eyes
on
be
be
can
should
working
enrichment
produce.
in
toxic
used,
must
must
materials
unless
area
NEVER
beryllium-bear
(or
fumes.
or
wear
is
well
index.
welded
be
both
being
should
can
change
gas
gas
gases
cylinders
supply
bring
of
accidentally
the
space
be
can
form
to
and
NOT
PHOSGENE,
eye
of
perchioroethylene
WELD
welding
cover
-3A.2.
1
them.
ignite
workpieces
facilities
aid
available
overhead
worn
used
result
or
Prevent
ANSI
cut)
for
im
by
and
skin
when
by
per
from
depletion
them
Stan
ventilate
may
pro
Adequate
each
person
an
air-sup
be
used.
that
emit
coating
is
ventilated
respira
ventilated
respira
be
avoided.
the
at
space
con
into
source
oxygen
in
opened
is
safe
before
decomposed
irritating
or
OM-296
arc
prod
can
where
cut
or
cutting
Page
also
or
re
a
if
or
a
1
Page 12
where
atmosphere
to
atmospheres
trichioroethylene
C.
Fire
Causes
the
by
misuse
rial;
short
circuits.
BE
AWARE
through
and
through
goggled
To
prevent
Keep
and
(in
cause
If
combustibles
work
the
Avoid
fators.
least
at
protect
fire-resistant
Walls
be
not
work shields.
watcher
Fire
guishing
or
ing
a.
or
and
Explosion
of
fire
and
flame,
arc,
of
compressed
ThAT
cracks,
along
wall
operator.
fires
equipment
electrical
short
circuits.
if
practicable,
paint
spray
if
work
35
feet
away
against
covers
touching
welded
should
combustibles
on
be
must
equipment
cutting
appreciable
containing
or
perchioroethylene.
explosion
flying
flying
floor
or
Sparks
and
clean
parts)
in
are
rooms,
cannot
ignition
or
cut).
(or
protected
be
during
construction)
b.
appreciable
feet
c.
openings
within
can
(concealed
35
feet
sparks
combustibles
d.
metal
work
Hot
ensure
been
have
work
After
glowing
An
empty
produce
be
never
cleaned
been
7
listed
This
includes:
solvent
a
bles
solubility)
trogen
OM-296
or
conducted
permit
supervisors
embers,
container
flammable
welded
in
or
carbon
or
Page
partitions
should
taken.
is
done,
and
on
as
Standards
a
thorough
water
washing,
followed
dioxide,
2
heat.
approval
check
that
or
described
radiant
the
even
Prevention
are:
gases
sparks
through
hot
or
sparks,
pipes,
openings,
and
slag
explosion:
and
operable,
of
metallic
do
an
dip
reach
NOT
area
tanks,
moved,
suitable
on
area,
to
be
of
out
with
shields.
Walls,
heat-resistant
by
standing
combustibles
are
combustibles
be
adjacent
flames.
toxic
or
Index.
by
within
ignited
or
may
expose
can
be
obtained
that
that
held
combustibles,
vapors
unless
Cut,
in
steam
by
visible)
to
be
depending
by
purging
using
can
energy
minute
combustibles
slag
and
falling
windows
can
free
particles
weld
freeofcombustibles.
storage
move
of
sparks
opposite
ceilings,
with
suitable
some
(including
35
feet
are
penetrate
amounts
reached
or
heated
mate
cylinders;
can
slag
or
doors,
of
fly
of
combustibles
and
and
time
of
sight
feet.
35
oil,
grease,
that
cut.
or
areas,
and
heat;
snug-fitting,
sides
should
floor
covers
fire
afterweid
building
further
than
sparks
in
floors
orwalls
combustibles
walls,
ceilings,
ignited
before
adequate
is
area
when
container
AWS
caustic
or
on
and
protective
radiant
by
operation
precautions
of
free
that
or
heated,
has
Standard
cleaning
combusti
inerting
sparks,
with
equip-
of
pass
the
can
Move
venti
or
near
or
extin
35
to
roofs,
or
to
can
must
first
A6.O,
(or
ni
ment
working
A
container
(see
of
Hollow
recommended
as
level
preceding
smell
or
castings
may
with
unknown
paragraph).
to
sight
or
weldingorcutting.
Explosive
may
as
gasoline).
0.
Standard
manual,
HANDLING
DERS,
1.
Regulator
regulator
any
with
Never
other
Remove
repair
toms
Leaks-if Excessive
with
Faulty
pin
sure
Repair.
tors
ter,
trained
2.
Cylinders
Avoid third
produce
cident.
ICC
assurance
dled.
Identifying
gas
content.
alter
or
It
is
Empties:
mark
atmospheres.
contain
flammable
Compressed
precautions.
and
those
OF
11
listed
Pressure
relief
from
downstream
one
or
more
connect
than
that
faulty
close
(first
indicate
leaks
gas
Creep-if
downstream
Gauge-if
when
pressurized,
release.
NOT
Do
repair
where
special
personnel.
Cylinders
must
electrical
short
(See
DOT
of
gas
on
to
1-3C.)
marking
damage
electrical
rails,
or
marked
Notify
name,
illegal
Keep
MT;
keep
Gas
COMPRESSED
in
Regulators
valve
overpressure;
equipment.
relief
a
regulator
regulator
cylinder
a
faulty
valve
gauge
attempt
to
manufacturers
be
their
circuit
circuit
safety
content.
them;
supplier
number,
hazardous.
valves
them
promptly.
Prohibited
other
roller.
than
use.
its
Never
intended
in
A6.O.
substitute
determine
containers
They
contents
Do
if
can
explode.
Neverweld
dust,
gas,
EquIpment
Comply
CGA
detailed
Standards
which
in
is
designed
it
devices.
to
regulator
from
Index.
is
Provide
a
valve).
regulator:
externally.
delivery
pressure
closed.
pointer
returns
nor
to
repair.
techniques
handled
walls,
wires,
arcs
must
when
do
separate
valves,
contact
or
that
beoneach
the
Use
not
if
unmarked.
other
or
closed,
a
use
use,
carefully
welding
may
cylinder
only
rely
cylinder
NEVER
Watertilling
just
inerting.
should
NOT
it
is
safe
must
orcut
or
liquid
with
precautions
Standard
GASES
to
intended
not
cylinder
service
The
does
to
stop
Send
designated
or
with
cylinders including
lead
be
weld
to
vented
where
on
depend
be
vapors
P-i,
IN
protect
to
such
protection
containing
was
designed.
immediately
following
continues
not
move
after
pin
faulty
repair
tools
are
to
prevent
devices:
safety
circuits.
serious
to
a
cylinder.
is
properly
color
NEVER
FULLS
or
as
with
to
identify
a
on
caps
contents
a
support
cylinders
on
markings
replace
from
below
cleaned
sense
cut.
or
before
air
(such
in
this
SAFE
CYLIN
the
only
protect
gas
for
symp
rise
to
off
stop
pres
regula
cen
used
by
leaks
can
They
ac
It
is
an
of
name
gas
DEFACE
cylinder.
securely;
return
or
Page 13
Locate
over.
or
secure
cylinders
so
they
cannot
be
knocked
outlet with
a
away
clean
from
people
tintless
cloth.
and
sources
of
ignition.
Wipe
Passageways
where
areas
Transporting
such
port
off
the
slings,
Do
NOT
and
slag,
low
contents
where
Protect
falling
when
moving
Stuck
valve.
cylinder
supplier.
your
Mixing
Never
Cylinder
they
cylinders.
as
a
ground
or
magnets.
expose
flame,
to
such
exposure
cylinders
objects,
cylinders.
Do
valve
gases.
refill
any
fittings
changed.
Hose
3.
Prohibited
signed
tion
rule
inert
ferrules
nary
hoses
No
copper
use.
gases.
or
wireorother
to
fittings.
tubing
tingstosplice
Avoid hose
on,
Coil
or
excess
runs
long
ground
otherwise
hose
work
and
platform
by
may
their
areas.
be
With
or
valves
cylinders
that
etc.
exceed
may
130F.
exists.
particularly
and
weather.
NOT
use
a
that
Never
can
try
not
to
cylinder.
should
Never
specified
for
clamps
fuel
use
gas.
gas,
designed
substitute)
splices.
hose.
to
prevent
keep
it
to
damaged.
to
prevent
struck.
a
crane,
cradle.
to
excessive
cause
valves
hammer
be
mix
never
hose
A
green
as
Use
kinks
from
kinks
Keep
cylinders
use
Do
or
caps,
rupture.
Cool
with
from
Replace
wrench
or
opened
any
gases
be
modified
other
general
for
oxygen,
for
a
binding
standard
only
and
abuse.
run
being
a
secure
lift
cylinders
or
by
heat,
Do
water
bumps,
securely
caps
to
hand.
by
in
a
cylinder.
than
that
identifica
hose
hose
(not
to
connect
brass
Suspend
over,
stepped
tangles.
clear
of
sup
chains,
sparks,
not
al
spray
falls,
a
open
Notify
or
ex
de
black
ordi
f
it
Match that that
NEVER
gas
Tighten
nections,
Tighten.
retighten
regulator
the
regulator
regulator
CONNECT
or
gases
connections.
clean
If
using
Adapters.
between
plier)
two
use
wrenches
LEFT
Regulatoroutlet by
(with
5.
Drain
fore
justing
sive
seat
engaged
Stand
Open
creases
reaches
lowing
to
less
Use
safe
hand
right
grooved
Pressurizing
regulator
opening
screw
compression
to
open
slightly
side
to
cylinder
slowly.
regulator
position:
seal
stem
than
one
pressure
and
efficient,
to
to
a
connection
properly
CGA
Use
a
cylinder
HAND
(or
threads
of
cylinder
in
(clockwise).
on
pressurization.
of
regulator
valve
For
against
turn
charts
regulators.
Check
there-after.
Liquid*
cate
combustible.
or
leak.
leaks
Brush
equivalent
Clean
cylinder.
label
and
inlet
a
cylinder
cylinder
and
regulator
containing
When
smooth
leaks,
fitting
adapter
regulator,
to
tighten
threads.
connections
hose)
oxygen
nut
on
or
Steps:
residual
heat
on
When
gas
manifold
(or
at
high
single-stage
while
so
slowly
gauge
maximum)
oxygen,
possible
to
permit
(available
recommended
first
on
with
pressurization
soap
gallon
per
water
soapy
Before
connecting, marking
cylinder
designed
any
assembling
where
seats
disassemble,
wrench.
(available
if
one
adapter
marked
may
left
shank)
through
fuel
suitable
valve)byturning
Draining
pressure
Leave
prevents
seat
adjusting
regulators.
opening
that
regulator
is
pressurized
leave
cylinder
inert
emergency
from
pressure
of
water).
after
gases,
fuel
your
(capfull
test;
leak.
quick
solution
check
area,
outlet
for
match.
a
particular
other
gas.
threaded
necessary.
clean,
from
your
is
required.
RIGHT
identified
be
threads
hand
gas.
vent
exces
by
allowing
cylinder
pressure
(gauge
valve
open
gas,
open
shutoff.
supplier)
settings
regularly
of
Bubbles
dried
soap
and
con
sup
be ad
screw
valve.
in
in
fol
fully
to
on
ivory
indi
is
Protect
sparks,
Examine
nections.
dicate
Repair
(1-2D3).
ing
4.
Proper
Clean
cylinder
orifices
Except
hose
slag,
hose
Immerse
leaks.
leaky
Connections
damage
for
hydrogen,
from
damage
and
open
regularly
pressured
worn
or
Do
valve
flame.
for
hose
tape.
outlet
seats
crack
by
sharp
leaks,
hose
by
culling
of
impurities
before
valve
momentarily,
edges,
and
wear,
in
water;
area
loose
bubbles
out
that
connecting
by
con
in
and
splic
clog
may
regulator.
pointing
E.
User
ResponsibIlities
Remove
mediately
in
equipment
F.
Close
G.
Rope
cutting
leaky
Leaving
gas
supply
Rope
Staging-Support
staging-support
operation;
*Trademrk
defective
or
repair.
manual.
See
Equipment
at
source
rope
of
Proctor
User
Unattended
should
may
&
Gamble.
equipment
from
Responsibility
drain
gas.
not
be
used
bum.
forwelding
service
statement
OM-296
Page
im
or
3
Page 14
ARC
1-3.
Comply
Arc
Welding,
careless
high
bright
frared
pressed
WELDING
with
operator
currents
hot.
and
energy
gases
unnecessary
accidents. dards
A.
Comply
The
can
damage
from
Skin
shielded
BURNED;
1.
Wear
arc)
essary,
leather sistant
ton.
Bare
Button
to
ets
2.
Protect
electric
Welding
12
no.
face
Protect
Cracked
worn;
Cracked,
Precautions
referencedinindex.
Protection
Burn
with
welding
light-colored
burns
arcs
COMPLY
Protective
long-sleeve
in
addition
use
jacket
leggings.
skin
protection.
collar
prevent
Eye
eyes
arc
helmet
ordenser
before
filter
or
radiation
broken,
IMMEDIATELY.
ken,
pitted,
Flash
goggles
helmet
the
helmet
the
struck.
eyes
cause area
Protection
3.
Enclosed
rate
round
ble
screens
ticularly
OM-296
to
not
Looking
(particularly
retinal
a
field
in
the
welding
room
or
operation
floor
at
Page
precautions
properly
invites
at
significant
Sparks
radiates,
be
may
risks
and
precautions
is
intense
arc
penetrate
eyes,
surfaces,
resemble
are
acute
more
WITH
Clothing
clothing
to
gloves,
additional
or
sleeves,
Avoid
Wear
to
protect
of
entry
Head
Protection
from
or
must
plate
broken
can
exposure
protection.
shield
be
arc.
with
helmet
pass
loose
or
without
striking
Replace
or
spattered.
with side
some
give
lowered
be
at
an
arc
a
high
that
burn
of
vision.
of
Nearby
area.
enclosed
with
or
panels.
level.
4
in
done,
trouble.
1
1-1,
isasafe
The
-2,
voltages.
fumes
fly,
weidments
used.
protects
are
in
and
rise,
wise
himself
described
1-2.
visibly
lightweight
and
burn
sunburn,
severe
painful.
PRECAUTIONS.
(particularly
and
hat,
shoes
protective
flame-proof
outer
garments
substantial
dark,
chest
neck
sparks.
to
arc.
containing
used
when
clear
a
cover
or
shield
through
filter
plates
clear
cover
shields
to
MUST
protection
over
face
momentanly
intensity
may
Personnel
bay
low-reflective,
Allow
gas-shielded
leave
production
is
best.
free
this
and
process,
equipment
The
arc
ultraviolet
are
hot,
operator
and
others
and
here
bright.
clothing,
the
skin
those
DONT
for
gas-shielded
-2A).
(1
clothing
apron,
of
untreated
button
NEVER
filter
a
plate
welding.
plate.
should
must
burns.
be
cause
plate
be
worn
the
to
eyes
before
with
unprotected
a
permanent
welding,
In
open
non-combusti
circulation,
section.
but
carries is
very
and
com
avoids
from
in
stan
radiation
reflect
eyes.
from
gas-
GET
As
nec
such
and
fire-re
cot
clothing.
pock
look
at
shade
Place
over
NOT
replaced
when
bro
under
should
an
arc
can
arc)
dark
a
sepa
areas,
sur
in
as
an
be
is
the
weld.
Viewing
will
who
Others
a
flash
Before
bay
B.
Comply
be
working
goggles.
starting
doors
are
Toxic
Fume
with
looking
Generatorengine
air.
Carbon
C.
FIre
and
Comply
with
Equipments
ing
equipment.
Loose
cause
Never
sel.
ture
D.
Comply
E.
Exposed ing
ment
conductor.
TOUCH
cable
lire.
a
strike
It
creates
lead
or
Compressed
with
Shock
circuit,
can
Prevention
or
fatally
DO
wet
a
Provide
directly
in
area.
to
weld,
closed.
PreventIon
precautions
exhaust
monoxide
ExplosIon
precautions
rated
capacity.
It
may
connections
an
arc
on
brittle
a
to
such
a
Gas
precautions
conductorsorother
in
ungrounded,
shock
NOT
surface
face
at
See
that
make
1
in
must
kill.
can
Prevention
1
in
overheat
may
a
cylinder
that
area
rupture
EquIpment
in
1
a
person
STAND,
when
shields
the
all
sure
-2B.
be
-2C.
Do
not
cables
overheat
or
can
under
-2D.
bare
electrically-HOT
whose
SIT,
welding,
weld.
persons
that
vented
overload
other
cause
rough
metal
body
LIE,
for
all
are
screen
to
the
cause
or
pressure
violent
a
handling.
in
becomes
LEAN
without
persons
wearing
flaps
outside
weld
arc
a
flash
the
weld
equip
ON,
suitable
or
fire.
and
ves
rup
a
OR
protection.
To
protect
Wear
body
adequate
duckboard,
dry
can
tween
metal
able
through
A
voltage
ducting
ing
objects
trical
against
dry
insulating
clothing
insulation
be
not
avoided.
body
reduces
dangerous
will
object
include,
work
tools,
workpieces,
metal
object
1.
Grounding
welding
National
grounded
When
welding
culatorto
quate
according
Cutting.
installing,
power
the
to
carry
body.
shock:
gloves
dry.
against
rubber
or
Sweat,
an
electrically
the
electrical
and
exist
between
in
work
benches,
Never
etc.
unless
the
Equipment
the
equipment
Electrical
to
connect
source,
building
ground.
ground
work
Never
electrical
when
mat
sea
resistance,
possibly
circuit.
not
are
welding
touch
welding
be
must
Code,
ANSI
the
frames
control,
currents
body
in
damp
dampness
water,
part
lethal
electrode
Examples
limited
the
power
to,
power
electrode
grounded
the
Z49.1
Safety
of
work
table,
Conductors
safely.
protection.
without
area
shock.
currents
moisture
or
or
Stay
or
sweat
grounded
could
to
any
of
conduct
buildings,
source
source
cases,
and
Is
according
work
must
In
Welding
each
unit
such
water
must
be
Equipment
made
Keep
on
be
en
flow
con
elec
any
off.
to
be
as
cir
ade
a
Page 15
electrically
tally.
carrying Three-phase
equipment
available,
wires
ment ment
tion
Before conductors
frames
If
a
equipment ground
plug
ceptacle,
ground
prong
Never
plug
2.
Fully
NOT
3.
Fully
join
4.
Frequently
IMMEDIATELY
or
damaged
from
taped
Keep
from
5.
Terminals should tion.
6.
HOT
Do
NOT
before
connect
of
ground
will
become
that
can
welding,
connections.
at
line
cord
lead
to
is
added
prong
connect
plug,
remove
with
broken
a
Electrode
insulated
holders
use
Connectors
insulated
welding
Cables
inspect
cable.
bared
to
give
cable
dry,
hot
metal
Terminals
and
have
Electrode
a.
Equipment
GROUND
gas
connection.
3-phase
lead
shock,
are
cable
insulation
insulating
Welding
metal
welding mally
control
so
equipped
trically
ON
touch
in
ject
the
welding
by
stray
flammable
or
installing. single-phase
line.
to
electrically
possibly
check
touching
with
a
ground
connection
grounded
connection
for
ground only.
Holders
lead
If
to
ground
ground
electrode
with
protruding
lock-type
lengths.
cables
REPLACE
Cables
resistance
freeofoil
and
sparks.
Other
other
exposed
with
power
arc
welding
(GTAW)
are
equipped
of
HOT
when
welding
electrode
contact
with
power
current
to
may
electrical
liquid
Check
If
phase
only
equipment
Do
NOT
third
(live)
HOT-a
fatally.
ground
a
connectors
to
bare
lead
to
a
switchbox,
switchbox.
to
a
must
line
cord
grounded
prong
prong.
holders
for
wear,
with
those
avoid
with
damaged
equivalent
and
grease,
Exposed
parts
covers
output
sources
secured
on/off
(GMAW),
and
similar
with
devices
welding
electrode
power
switch
gun
wire
or
the
electrode
source
shock,
conduit,
such
possibly
orto
a
oilorfuel.
as
pipe
requirements
3-phase
connect
wire,
dangerous
continuity.
metal
is
provided
grounded
be
connected
comes
mating
from
a
should
screws.
should
cracks
excessively
possibly-lethal
to
original
Parts
of
control
for
use
gas
power
wire
source
any
off.
is
power
to
only
equip
or
equip
condi
Be
of
equipment
with
connect
if
a
three-prong
mating
to
with
three-
a
receptacle.
or
plug,
be
and
areas
electrical
before
use
used.
be
used
damage.
shock
may
cable.
protected
opera
(contactor)
with
the
tungsten
processes
that
permit
output.
When
becomes
switch
is
closed.
Never
conducting
circuit
unless
sure
worn
units
elec
fa
two
the
re
Do
gas
arc
nor
on-
ob
be
of
is
to
is
a
b.
Equipment
contactor)
Welding
metal
esses
output
ment
power electrode
f.
of
7.
Safety
Safety
should
Before
shut
red-tag
power.
source,
Do
ing.
against
Leaving
devices
not
installation,
OFF
switches)
Disconnect
not
open
in
an
If,
shock
equipment
disconnect
Power
welding
F.
port
Magnetic
disconnect
power
Protection
Devices
fields
operation.
equipment
before
going
operations.
1-4.
STANDARDS
more
information,
their
latest
1.
ANSI
Standard
CUTTING
Society,
2.
NIOSH,SAFETYAND
AND
GAS
from
ernment
3.
OSHA,
29CFR
of
Documents,
Washington,
4.
ANSI
Standard
OCCUPATION
FACE
can
National
New
York,
5.
ANSI
Standard
SAFETY-TOE
American
Broadway,
without
power
arc
may
on-off
the
electrode
switch
unless
Devices
such
be
disconnected
sources
welding
not
be
control
is
turned
as
interlocks
inspection,
to
bums,
power
source.
and
prevent
all
cables
volts
circuit
it
flash
or
unattended.
to
equipment.
switch
Wearers
power
pull
power
emergency,
(Pacemakers)
from
Persons
(pacemaker)
near
arc
revisions
currents
high
wearing
should
welding,
BOOKLET
refer
Z49.1,
obtainable
N.W.
WELDING
LeJeune
Superintendent
obtainable
U.S.
D.C.
AND
Standards
NY
10018.
Z41.1.
FOOTWEAR
National
New
York,
Office,
20402.
Z87.1,
Printing
SAFETY
1910,
PROTECTION
output
used
(SMAW)
equipped
devices.
is
or
remove
or
change
must
with
electrically
ON.
welding
shunted
or
service,
line
accidental
from
line-cord
be
disconnected,
from
switch
Always
be
must
of
Electronic
can
electronic
consult
gouging,
INDEX
to
the
following
SAFETY
from
as
comply
Rd,
HEALTH
AND
CUTTING
of
Documents,
Washington,
HEALTH
from
the
Government
SAFE
EDUCATIONAL
obtainable
Institute,
STANDARD
obtainable
Standards
NY
10018.
on/off
with
and
welding
With
HOT
Never
power
circuit
out.
of
fuses
turning
welding
control
shielded
similar
proc
power
such
equip
when
touch
source
breakers
equipment,
lock
(or
ON
power
plugs.
while
polarity
weld
guard
arcing.
OFF
shut
available
affect
with
LIfe
pacemaker
life
their
or
spot
standards
near
support
doctor
welding
applicable:
IN
WELDING
American
Miami,
IN
Welding
FL
33126.
WELDING
obtainable
U.S.
D.C.
20402.
STANDARDS,
Superintendent
Printing
PRACTICES
from
1430
Institute,
Office,
EYE
the
Ameri
Broadway,
FOR
MENS
from
(no
is
or
of
Sup
or
Gov
FOR
AND
1430
OM-296
Page
5
Page 16
ANSI
6.
USE obtainable
Institute,
AWS
7.
CONTAINERS
TIBLES
ciety,
NFPA
8.
TEMS
PROCESSES
Protection
MA
NFPA
9.
CODE
Association,
02269.
NFPA
PROCESSES
Protection
MA
CGA
11.
PRESSED
Standard
CUTTING
OF
1430
Standard
obtainable
N.W.
550
Standard
FOR
02269.
Standard
obtainable
Standard
02269.
Pamphlet
the
FIRE
American
Z49.2,
from
Broadway,
WELDING
A6.0,
WHICH
from
LeJeune
OXYGEN-FUEL
51,
WELDING,
obtainable
Association,
70,
from
Batterymarch
51B,
obtainable
Association,
SAFE
P-i,
GASES
IN
PREVENTION
National
York,
AND
HELD
Miami,
Park,
PROCESSES
NY
FL
National
Park,
ELECTRICAL
Fire
Quincy,
National
Park,
WELDING
New
HAVE
American
the
Rd,
CUTTING,
from
Batterymarch
NATIONAL
National
the
CUTTING
from
Batterymarch
HANDLING
CYLINDERS
IN
Standards
10018.
CUTTING
COMBUS
Welding
33126.
SYS
GAS
ALLIED
Quincy,
Protection
WELDING
Quincy,
COM
OF
obtainable
THE
So
Fire
Fire
MA
from ferson
22202.
CSA
WELDING
nadian 178
M9W
NWSA
13. PHY
Association,
19103.
American
14.
RECOMMENDED
PREPARATION OF
H
ELD from LeJeune
15.
ANSI
TORY
can
New
Compressed
Davis
Standard
AND
Standards
Rexdale
1R3.
booklet,
obtainable
Welding
CONTAINERS
HAZARDOUS
American
Rd,
Standard
PROTECTION,
National
NY
York,
Gas
Highway,
W117.2,
CUTTING
Association,
Boulevard,
WELDING
the
from
Arch
1900
Society
SAFE
FOR
AND
Welding
Miami,
Standards
FL
Z88.2,
10018.
Association,
Suite
501,
CODE
Rexdale,
National
Street,
WELDING
FOR
obtainable
Standards
Ontario,
SAFETY
Philadelphia,
Standard
PRACTICES
PIPING
SUBSTANCES,
Society,
33126.
PRACTICE
obtainable
Institute,
1235
Arlington,
SAFETY
from
Canada
BIBLiOGRA
Welding
AND
FOR
from
1430
Supply
AWSF4.1,
FOR
CUTTING
ThAT
obtainable
550
RESPIRA
Broadway,
Jef
VA
IN
Ca
Sales,
PA
ThE
HAVE
N.W.
Amen
OM-296
Page
6
Page 17
Rated
At
Duty
30
At
Output
Cycle
Amperes
Volts
DC
Maximum
Open-
Circuit
voltage
370
Volts
DC
SECTION
Table
input
Rated
Load
Hz
50/60
Amperes
200V 230V
38
2
INTRODUCTION
2-1.
SpecificatIons
At
Output
Single-Phase
At
KVA
33
7.6
KW
Plasma
Gas
Air
CFM
(79
4
6
~
At
(345
~
Llmin.)
PSI
50
kPa)
In.
8-1/8
(206
Net
52
(24
Weight
lbs.
kg)
Ship
56
(25
lbs.
kg)
DUTY
2-1.
This
power
cycle. period
at
age rated
rated
ing
a
given
to
that
the
at
load
minutes,
cooling.
CYCLE
source
duty
the
output
power
40
percent
power
four
and
cycle
without
source
minutes
the
torch
is
source
duty
unit
causing
rated
are
percentage
and
torch
overheating
and
torch.
it
cycle,
Out
should
can
often.
idle
Figure
40
at
percent
of
a
can
Since
be
During
to
permit
2-1.
duty
ten
minute
be
operated
this
unit
operated
remain
proper
Overall
is
at
Dimensions
CAUTION:
4A
2-2.
A.
RATINGS
torch.
GENERAL
General
Information
bels,
tags,
equipment
(440
Do
not
exceed
INFORMATION
presented
and
plates
design,
18-1/2
(470
17-3/8
In.
mm)
EXCEEDING
will
damage
indicated
in
this
manual
provided
installation,
operation,
on
THE
In.
DUTY
power
duty
cycles.
SAFETY
and
on
this
unit
maintenance,
TC-125
CYCLE
source
various
pertains
OM-296
647
and
Page
la
to
7
Page 18
and
troubleshooting
and
followed
ment.
The
nameplate
for
labeling
appear
B.
Safety
installation,
bleshooting
procedures
others.
of
operated,
accordance such
as,
1
tion
Safety
throughout
pear
words
levels
ent
WARNING
maintenance
and
carefully
loss
or
CAUTION
maintenance
carefully damage
A
third
which
tions ficient
the
for
of
front
the
at
appropnate
of this
which
Therefore,
maintained
with
not
limited
Rules.
but
-
Safety
instructions
WARNING
of
hazard.
statements
followed
life.
of
statements
followed
this
to
signal
equipment.
word,
need
operation
which
should
and
safe
this
unit
panel
section
operation,
equipment
ensure
personal
this
equipment
only
this
manual
those
to,
specifically
this
manual
CAUTION
and
include
be
effective
international
uses
controls.
in
maintenance,
requires
safety
qualified
by
and
all
listed
pertaining
highlighted
which
installation,
read,
use
The
is
applicable
at
proceduresorpractices
in
could
result
include
serious
installation,
proceduresorpractices
could
IMPORTANT
special
this
of
resultinminor
emphasis
equipment.
personal
highlights
obtain
to
understood,
of
this
equip
symbols
symbols
text.
practices
to
be
installed,
persons
of
this
unit
to
by
identify
operation,
which
personal
operation,
which
injury
instruc
most
also
trou
and
safety
in
codes
Sec
ap
signal
differ
if
not
injury
if
not
or
ef
RECEIVING-HANDLING
2-3.
Before
age claims
Assistance
from
ers
When
ways
This
quiring
unpacking
that
have
may
loss
or
filing
distributor
Transportation
requesting
provide
DESCRIPTION
2-4.
unit
negative)
isadirect
Plasma
single-phase
metals
Arc
This
APT-3000
APT-3000M
Rated
duty
Plasma
high
electrically
fice)
through
perature
constrictionofthe
emerges
The
metal,
the
through
Cutting
unit
(PAC)
is
designed
curved-nozzle
straight-nozzle
output
cycle.
is
temperature
conductive.
of
the
range.
in
formed
and
torch.
constricts
arc
the
tip
which
heat
cut.
is
which
equipment,
occurred
damage
or
settling
and/or
Department.
information
Model
1/4
30
where
Since
form
airstream
Description
current,
Arc
Cutting
electrical
in.
(6.35
process.
be
to
amperes
and
ionized
The
torch
it
airisforced
tip,
of
a
by
check
during
wIth
the
about
straight
mm)
used
torch.
torch
at
been
electrode
tip
The
arc.
is
heated
cannot
highly
and
arc
forces
carton
shipment.
the
deliverIng
claims
may
equipment
this
Serial
polarity
(PAC)
so
power
The
input.
thick
using
with
supplied
An
optional
is
also
volts
heated
hasasmall
that
to
the is
compressed
to
expand
through
compressed
the
plasma
the
molten
for
any
File
any
carrier.
obtained
be
manufactur
equipment,
Number.
(electrode
source
will
unit
Plasma
model
model
available.
40
dc,
percent
an
extremely
air
becomes
located
inside
opening
flows
plasma
tem
duetothe
orifice
airstream.
melts
metal
from
al
re
cut
(ori
WARNING:
A~
IMPORTANT:
power
frequency
before
lines
LOCATION
3-1.
WARNING:
a
from
surfaces;
overheating
nal
stricted derside
OM-296
Page
ELECTRIC
Do
Turn
not
plug
Read
touch
power
from
entire
equipment
installing
this
(Figure
FIRE
placing
unit
RESTRICTED
and
parts.
Do
Maintain
locate
not
least
at
on
space
freeofobstructions.
8
live
electrical
source,
receptacle
Section
location
and
unit.
2-1)
OR
EXPLOSION
on
or
possible
unit
over
10
inches
sides
SECTION
SHOCK
can
parts.
and
remove
before
8
regarding
installation
combustible
over
AIR
FLOW
damage
combustible
mm)
(254
unit,
and
of
kill.
moving
can
causes
to
surfaces.
of
keep
3INSTALLATION
input
unit.
high-
guide
result
inter
unre
un
take
Warranty
is
Figure
source.
when
2-1
service
moisture,
3-2.
AND
CONNECTIONS
IMPORTANT:
clean,
dry
pressure
1.
Remove bracket
regulator Figure
Do
not
place
passages
void
is
used.
and
life
is
subjected
overall
efficiency
vapors,
gives
unit
corrosive
FILTER/REGULATOR
Be
sure
air
supply
flow
screws
(see
rate
two
from
mounting
3-1
Figure
power
type
of
high
extreme
device
of
this
levels
source.
filtering
of
unit
heat.
filtering
of
this
if
any
dimensions
to
INSTALLATION
And
that
Table
3-1
this
Figure
unit
is
2-1.
supplied
Specifications
(Figure
specifications).
filter/regulator
of
rear
bracket
unit,
onto
and
install
rear
3-2).
over
the
reduced
are
of
dust,
mounting
of
unit
in
device
power
dirt,
3-2)
by
filter/
(see
a
Page 19
2.
Remove
insert
mounting
IMPORTANT:
direction. in
direction
with
install
3.
Secure
installing
4.
Coat
of
end
1/2
tor
(see
Coat
5.
remaining
unit
Figure
Connect
6. air
of
INPUT
3-3.
(Figure
3-2)
ELECTRIC
a
VOLTAGE
power
changing
missing.
This
power
230
200
or
retaining
of
top
nrig
air
litter/regulator
bracket.
Check
Position
indicated
plugged
filter/regulatorto
and
threads
supplied
(12.7mm)
Figure
threads
end
located
filter/regulator
filter/regulator
filter
on
toward
port
tightening
with
teflon
12
fitting
3-1).
with
teflon
of
hose
directly
below
3-2).
from
hose
line
filter/regulator
VOLTAGE
not
touch
off
Do
Turn
plug
switch
Do
not
operate
source
volts,
single-phase,
(see
SHOCK
can
damage
live
power
from
receptacle
positions.
is
designed
unit
from
body
rear
mounting
retaining
and
tape,
(305
mm)
Out
to
port
and
tape,
air
to
input
compressor
Figure
CHANGEOVER
can
unIt.
electrical
source,
with
access
to
50/60
lifter/regulator,
through
proper
that
so
(see
of
Figure
unit.
bracket
bottom
will
3-1),
by
of
flow flow
or
re
nng.
install
and
tighten
hose
on
cord
to
with
tighten
of
rear
(see
In
port
long
of
airfilter/regula
install
input
fitting
power
3-1).
SWITCH
INCORRECT
kill;
parts.
before
be
operated
Hz,
remove
inspecting
cover
ac
power
open
from
input
or
or
sup-
a
This
switch
To
Turn
plug
Open
Place
200
put
Close
ELECTRICAL
ft.
15
unit
change
from
or
voltage.
3-2)
(4.6
on
ply.
over
ages.
lows:
1.
2.
3.
4.
3-4.
(Figure
A
provided grounded
gle-phase
The
National
tion)
provides
of
ity
supply
power
can
source.
be
operated
therefore,
with
ply
ply
additional
IMPORTANT:
must volts
tion.
to
opening
these
and
receptacle
be
operation
The
the
supply
capable
power
line
inadequate
is
equipped
allow
to
the
power
source,
receptacle.
rear
panel
Input
Voltage
230
volts
and
secure
withaNEMA
cord
m)
this
unit.
and
protected
200/230
the
volts
Electrical
standards
conductors
This
unit
at
rated
cord
standards.
comply
and
state
The
supply
of
carrying
33
or
a
source
Circuit. fusesorcircuit
or
Poor
improper
with
an
operation
switch
access
position,
and
cover
Changeover
rear
panel
CONNECTIONS
Connect
(fuses
ac
receptacle.
Code
amperage
based
has
a
load
supplied
plug
Be
sure.
with
codes.
to
(Article
40
position
INPUT
local
wiring
a
ampere
must
be
unit
performance
breakers
supply.
Input
from
remove
(see
match
access
6-50
circuit
or
on
percent
four
that
NEC
38
ampere
load
the
only
Voltage
different
proceed
input
Figure
switch
available
the
cover.
plug
to
plug
breakers)
630B.,
carrying
duty
duty
minutes
this
with
building
standards
the
power
for
230
load
or
result
can
Change
volt
line
fol
as
power
3-2).
in
attached
a
either
properly
sin
1987
capabil
cycle
cycle
of
out
unit
ten;
com
the
of
sup
any
source
load
volts
200
opera
connected
frequently
from
in
is
an
Connect
Fitting
Ret&rilng
1/2
in.
(12.7
Air
To
input
Power
Source
Air
Figure
Pressure
Gauge
3-1.
Arrow
Direction
~
Air
Filter/Regulator
indicates
Of
Air
On
mm)
Hose
Fitting
Out
(to
Port)
Flow
Components
Information
Mounting
Bracket
Locking
Screw
Filter!
Air
Regulator
Adlustment
Knob
In
Port
OM-296
TC-126
Page
828
9
Page 20
Rear
(Shown
Panel
in
Access
Open
Cover
Position)
Power
Input
Cord
Air
input
Fitting
Out
Port
Figure
3-2.
Rear
Panel
View
With
Component
Locking
Air
Locations
Screw
Location
FIIter/Reguiator
Air
Pressure
Gauge
TB.125
648
Plasma
Torch
Input
Cutting
Thickness
Power
SECTION
GaelAIr
Fuse
Fl
Control
4-
Switch
OPERATOR
Metai
Switch
CONTROLS
Light
Power
Light
On
OM-296
Page
Work
10
Clamp
Figure
4-1.
Operator
Controls
TC-125
647
Page 21
POWER
4-1.
LIGHT
(Figure
POWER
POWER
Placing
energizes
er
is
breaker
POWER
4A
the
motor
come
is
placed
in
receiving
in
ON
CAUTION:
SWITCH/BREAKER
problem
Do
See
READY
4-2.
READY
When
devices
down
monitored,
READY switch/breaker
safety
4-3.
METAL
painted
PAINTED
frequency
METAL
provides
and
light
devices
METAL
metal.
position,
for
switch
only
SWITCH/BREAKER
4-1)
switch/breaker
on
OFF
source.
whenever
ON
position
power.
position
fan
and
power
input
light,
RESElliNG
cause
can
reset
not
Table
LIGHT
tripped
6-2.
(FIgure
light
within
does
is
(see
SWITCH
switch
When
arc
is
high
unit
not
placed
Section
provides
the
starting
placed
frequency
00
in
POWER
The
POWER
and
indicate
POWER
turns
without
damage
POWER
the
off
the
TRIPPED
to
Placing
motor.
Troubleshooting
4-1)
all
comes
control
is
ready
come
in
6-6).
(Figure
a
METAL
unit
providesapilot
in
on,
circuitry
when
on
ON
position,
4-1)
means
switch
during
BARE
arc
starting
of
operation.
for
cutting.
position,
POWER
ON
ON
ON
position
light
switch/break
the
that
power
unit
switch/
source,
POWER
correcting
this
unit.
switch/breaker.
Section
in
cutting
is
placed
arc
safety
have
POWER
check
bare
When
the
and
not
shut
been
If
in
high
unit
the
in
The
ing
cutting.
BARE
possible
4-4.
The
control
power brated
setting
position
life
THICKNESS
THICKNESS
cutting
clockwise
source.
in
gauge
by
adjustment
longest
4-5.
The
Placing
6.
gizes
latorto
GAS/AIR
cutting
4-6.
The torch the
tion,
the
switch
or
switch
switch the switch
short
tion
possible
GAS/AIR
GAS/Al
filter/regulator
the
be
torch.
TRIGGER
TRIGGER
switch
TRIGGER
the
torch
cutting
is
is
must
of
should
cutting
for
long
METAL
whenever
from
capacity
thickness
four
gauges
of
the
SWITCH
R
switch
GAS/AIR
solenoid
properly
switch
self-hold
hold
switch
circuit
pressed
placed
be
held
the
cutting
be
operations
cutting
life
in
HOLD
hold
switch
possible
torch
the
CONTROL
control
provides
of
increases
scale
surrounding
when
THICKNESS
the
from
(FIgure
provides
without
will
in
placed
energizing
switch
thereby
50
to
set
CUT
the
SWITCH
switch
long
switch
be
can
continue
again.
NORMAL
closed
operation.
in
and
operations.
should
electrode
(FIgure
power
mild
cutting
torch
a
in
allowing
PSI
position
provides
cutting
is
placed
released
to
When
while
the
placed
be
to
and
means
a
source.
cutting
steel.
aluminum.
control
electrode
4.1)
means
the
SET
bars).
(3.4
provides
(Figure
operations.
in
while
operate
the
position,
cutting
The
NORMAL
in
placed
the
get
tip.
4-1)
Rotating
capacity
control
Increase
will
provide
for
adjusting
cutting
position
Placing
4-1)
capability
HOLD
cutting,
until
TRIGGER
released
TRIGGER
position
HOLD
the
longest
selecting
the
of
the
is
cali
gauge
Proper
the
and
tip.
the
circuit.
ener
filter/regu
the
to
of
When
posi
torch
hold
torch
at
hold
posi
a
WARNING:
hazardous;
from
placing
surfaces.
Only
qualified
equipment
ers
safety
not
Do
Use
torch(es)
CUTTING
tanks,
fire,
properly
ELECTRIC
FLOW
can
in
Keep
and
or
poisonous
containers
Cut
AND
damage
not
Do
Keep
place.
children
cleaned
all
PLASMA
FIRE
OR
unIt
persons
according
practices.
locate
unit
specified
away.
CONTAINERS,
pIpes,
only
SHOCK
EXPOSURE
Internal
touch
live
covers,
panels,
SECTION
ARC
EXPLOSION
or
on
are
codes
to
combustible
over
in
result
can
fumes.
after
prepared.
can
kill;
TO
parts.
electrical
CUTTING
combustible
near
to
operate
and
Owners
such
as
In
explosions,
they
IMPROPER
ENVIRONMENT
parts.
guards
5-
SEQUENCE
can
can
employ
surfaces. Manual.
barrels,
have
securely
be
result
this
been
OF
OPERATION
tion.
sulation.
power
from
stricted
keep
take
Warranty
with
FUMES your
vice.
Wear
dry
Do
not
Turn
plug
torch
Ma/nt
aTh
space
underside
Do
not
air
passages
portion
any
health.
Keep
your
Ventilate
insulating
cables
use
power
from
receptacle
or
replacing
tip
least10inches
at
al/sides
on
free
place
any
if
void
is
of
GASES
head
or
area,
gloves
torch
or
source,
obstructions.
of
filtering
of
this
power
power
outer
can
of
out
use
approved
with
and
before
any
(254
of
power
device
source
enclosure
seriously
fumes.
any
body
damaged
remove
cleaning
torch
parts.
mm)
source,
over
source.
is
removed.
breathing
OM-296
protec
in
input
slag
of
unre
in
operated
harm
de
11
Page
Page 22
5-1.
a
1.
2.
OM-296
Read
manufacturers
and als
used.
When
fable
designed
sparks.
Cutting
cause
workpiece.
recommended
FLYING
cause
not
Do
mable
Protect
and
Allow
dling.
Watch
nearby.
RAYS
ARC
can
damage
Wear
Wear
Cover
Protect
PILOT
Keep
switch CUTTING
FLOOR
Do
floor.
trim.
burn
Remove,
CUTTING
computer(s)
nents.
Disconnect
vehicle.
on
a
Place
to
Be
sure
connections
To
be
computer(s)
Section
formation.
PLASMA
WARNING:
at
tion
proceeding.
and
Install
the
Place
12
Page
Material
possible
aluminum
hydrogen
Contact
SPARKS
fire
where
cut
material.
yourself
metal. work
and
fire,
can
hearing.
safety
face
a
skin.
ears.
ARC
can
torch
is
pressed.
WORKPIECE
cause
can
not
place
METAL
cover,
CURRENT
work
avoid
long
torch
to
100
percent
from
1
Read
beginning
connect
GAS/AIR
Safety
instructions
cut
over
minimize
to
plate
detonation
equipment
practices
AND
burns.
flying
others
equipment
and
keep
burn
goggles
shield.
cause
tip
away
concrete
workpiece
SPARKS
or
protect
other
both
battery
as
clamp
electrical
to
power
work
clamp
free
the
Safety
of
unit
according
switch
vehicle.
entire
-
CUTTING
Data
a
on
for
HOT
sparks
eyes
with
burns.
from
directly
will
can
electronic
cables
close
paths.
scurce
of
Rules
(PAC)
follow
in
the
Sheets
any
table
water
fumes,
a
gases,
water
beneath
manufacturer
cutting
a
correct
aluminum.
METAL
can
from
flying
cool
to
fire
extinguisher
skin;
filter
personnel
CONCRETE
ON
to
explode.
on
mark
glass
damage
before
the
to
cut
as
clean
are
disconnect
risk,
basic
safety
Section
Section
to
position.
(MSDSs)
materi
or
fable
strike
sparks
before
NOISE
shade.
concrete
glass
or
vehicle
compo
cutting
as
well
as
and
safety
informa
5
before
work
and
may
the
can
flam
when
trim.
possi
lead
tight.
the
in
3.
Place
3.
tion.
4.
Turn
50
gauge
ommended
vide
of
according
a.
b.
c.
5.
Place
Section
Rotate
6. tion
7.
Place
READY
ready
Place
8.
position
tions).
9.
Wear
safety
ANSI
10.
Connect
workpiece.
11.
Place
in
tip
12.
Press
seconds
Once
cutting
tom
14.
Pause be
will
torch.
the
IMPORTANT:
material
gauge
torch
on
will
wear
slight
gap
will
be
blown
back
ing
Wear
a
eration.
POWER
POWER
The
air
on
supply,
PSI
on
(3.4
rear
bars)
unit.
of
output
minimum
a
PSI
Loosen lator
Turn wisetoincrease clockwise
Tighten
the
of
bars).
(10.2
to
Figure
locking
adjustment
filter/regulator
decrease
to
locking
METAL
switch
4-3).
THICKNESS
Section
(see
GAS/AIR
light
operation.
TRIGGER
(see
insulating
dry
goggles
Z49.1.
work
of
tip
over
just
torch
of
arc
starts,
Adjust
through
speed
of
cut.
briefly
Cut,
flow
for
If
another
will
arc
to
start
material,
parts,
increase
or
angle
a
way
onto
face
shield
4-4).
will
come
Section
with
clamp
torch
at
metal
switch.
pref
drag
torch
material
is
being
at
then
approximately
cut
start
immediately.
unit
This
cut
a
away
there
as
accordingly.
to
from
torch
if
any
switch/breaker
light
adjust
PSI
Make
as
knob.
proper
the
(5.4
will
observing
bars)
follows:
in
center
ON
and
while
from
80
screw
adjustment
pressure
pressure
screw.
in
control
in
on
indicating
switch
hold
for
4-6
filter
to
clean,
metal
of
the
switch
gloves
correct
edge
edge.
will
There
before
slowly
tip
speed
away
when
used
of
cut
to
is
started
can
from
be
material
torch
10
also
the
little
release
will
Always
materialsothat
torch
will
further
tip
piercing
ON
in
on.
come
air
filter/regulator
pressure
regulation,
supply
and
pressure
of
setting
should
maximum
a
adjustment
filter/regu
knob
counter
or
setting.
desired
long
arc
so
from
allow
seconds
before
be
or
becomes
tip.
is
position
desired
to
CUT
position.
the
that
in
the
NORMAL
cutting
clothing,
shade
tobecut
be
approximately
starts.
according
metal
bare
with
smoothly
that
sparks
torch
tip.
sparks
switch.
used
metal
no
go
metal
bridge
Postflow
to
low
postf
to
pierce
edge.
additional
thicker,
pierce
molten
Molten
to
reduce
be
part
metal
of
opera
out
cool
On
using
posi
to
rec
pro
clock
(see
posi
The
unit
is
wear
to
at
hole
2
across
di
are
Proper
to
air
ends,
the
light
wear
the
metal
b/ow
life.
tip
the
op
a
Page 23
5-2.
TIONS
1.
2.
CUTTING
If
sparks
The
a.
travel.
The
b.
c.
Tip
If
arc
The
a.
b.
to
c.
come
torch
workpiece
or
Section
(see
goes
torch
place
Work
clean,
Check
PROBLEMS
out
is
being
electrode
6-2).
while
out
was
torch
on
disconnected;
clamp
bare
READY
AND
of
cut
top
moved
cut
being
worn;
replace
cutting:
lifted
too
workpiece
metal
at
workpiece.
see
light;
RECOMMENDA
cut
or
too
is
too
tip
from
while
connect
Section
is
clean:
not
slow
fast;
thick.
andelectrode
workpiece;
cutting.
work
4-2.
torch
clamp
3.
4.
5-3.
1.
2.
3.
4.
If
arc
goes
The
a.
torch
b.
Tip
(see
See
Table
remedies.
SHUTTING
Stop
cutting.
Allow
unit
Place
the
tion.
Turn
on/off
torch
travel.
electrode
or
Section
to
POWER
supply.
while
cutling:
is
being
worn;
moved
6-2).
6-2.
Troubleshooting
DOWN
idle
1
to
switch/breaker.in
too
replace
2
minutes.
slowly;
and
tip
for
increase
electrode
additional
OFF
posi
ROUTINE
6-1.
IMPORTANT:
this
maintained
when
precautionary
4~
unit
necessary.
WARNING:
NIFICANT
of
Input
Do
Turn
plug
ing,
Internal
less
power.
minutes.
Measure
legibility.
in
labels.
not
from
maintaining,
within
touching
MOVING
Keep
SURFACES
HOT
Allow
A.
This
relies
tons
quires
Motor
Fan
source
power
forced
on
manufactured
maintenance.
no
SECTION
MAINTENANCE
months
six
Every
All
precautionary
See
readable
Parts
a
clearly
ELECTRIC
DC
VOLTAGE
power.
live
touch
f
of
power
source,
receptacle,
or
voltage
60
seconds
Lesser
voltages
voltageoninput
parts.
PARTS
away
cooling
is
draft
can
from
period
equipped
adequate
lifetime
with
6-
inspect
state
for
List
SHOCK
exIsts
electrical
remove
WAIT
and
servicing.
will
decrease
after
remain
may
cause
cause
before
with
parts.
an
moving
can
cooling.
sealed
MAINTENANCE
labels
the
labels
must
and
replaced
number
part
can
kIll;
after
removal
parts.
input
before
removal
to
50
inspect
volts
of
up
capacitors
serious
severe
Injury.
burns.
servicing.
fan
exhaust
bearings
SIG
power
input
to
before
and
mo
and
on
be
two
re
of
or
&
TROUBLESHOOTING
B.
Torch
a
Cable
WARNING:
tion
at
beginnIng
proceeding.
three
Every
breaks
if
torch connectionsateach
C.
Internal
a
months
in
insulation.
insulation
CleanIng
WARNING: tion
at
beginning
breaks
proceeding.
six
Every
vacuum
a
dirty
months
source.
power
suction
conditions
Table
are
6-1.
Frequency*
Week
Every
or
as
required
Month
Every
3
6
hours
Months
Months
of
if
usage
service
week.
Every
Every
Frequency
40
enance
And
Leads
Read
of
inspect
Repair
are
inspection.
Read
of
vacuum
Remove
dust
cleaning
present,
MaIntenance
Inspect
trode
(see
in
Units
ments:
Check
internal
Check
Section
Check
block,
parts
exceeds
labels,
cables,
Section
(see
is
based
Increase
and
follow
entIre
cable,
or
replace
present.
follow
entIre
and
the
outer
clean
Maintenance
shield
Section
heavy
parts.
6-1
B).
labels
Section
on
frequency
hours
40
safety
cable,
Clean
and
leads,
Section
leads,
safety
from
6-1
Section
dirt
enclosure,
operation.
the
unit
monthly.
Schedule
tip,
cup,
6-2).
service
leads, torch;
leads,
6-1).
(see
environ
torch
IMPORTAN
Clean
6-iC).
units
operated
of
maint
week.
per
OM-296
Informa
before
torch
tighten
Informa
before
inside
use
If
dusty
elec
clean
(see
internal
Page
of
or
13
Page 24
SHIELD
6-2.
TION
Figure
a
6-2)
WARNING:
power
maintaining,
HOT
EXCESSIVE
can
or
been
IMPORTANT:
necessary,
use
only
To
replace
Turn
1.
plug
Remove
2.
3.
Using
shield
Remove
4.
5.
inspect
cent
CUP,
REPLACEMENT
not
Do
Turn
Allow
touch
power
from
plug
SURFACES
cooling
damage
Inspect
whenever
shield
significantly
If
tip
replace
genuine
off
from
a
cup
oversize,
replacement
torch
parts,
power
receptacle.
shield
cup.
clean,
dry
(see
tip
using
in
hole
tip.
replace
TIP,
ELECTRIC
live
electrical
source,
receptacle
or
servicing.
can
period
TIP
torch.
cup,
cutting
reduced.
electrode
or
the
at
both
proceed
source,
cloth,
Figure
6-1).
supplied
If
hole
tip
ELECTRODE
(Figure
SHOCK
and
before
cause
before
ELECTRODE
and
tip,
speed
replacement
same
parts.
follows:
as
and
remove
wipe
wrench.
is
tip
(see
deformed
Figure
in
INSPEC
kill.
can
parts.
remove
inspect
severe
burns.
servicing.
electrode
thickness
or
becomes
Be
time.
input
contact
surface
or
6-1).
And
input
ing,
WEAR
weekly
to
sure
power
on
50
per
6.
Inspect
depth
move
7.
Reinstall
Reinstall
8.
ceptacle,
Figure
end
electrode
of
and
replace
tip
input
and
6-1.
electrode
of
exceeds
electrode
shield
and
power
resume
(LII
0ll00.059
ShIeld
Cup,
InspectIon
Figure
(see
0.039
using
cup.
200/230
into
plug
operation.
mm)
ln.(I.5
Tip,
If
(1.0
volts
Surface
Cup
Oversized
erosion
mm),
wrench.
ac
Hole
Worn
rip
6-1).
supplied
Contact
Shield
Ullllm
Electrode
S.OO93
Electrode
re
re
Plasma
Torch
Cutting
~2Iectrode
Figure
6-2.
Tip
Torch
And
Wrench
Parts
Torch
Air/Torch
Connector
()
Replacement
Leads
And
Arc/
Pilot
Detector
I
Lead
ShIeld
Cup
3
4
Detector
Lead
2
OM-296
Page
14
Page 25
TORCH
6-3.
CONNECTIONS
WARNING:
a
NIFICANT
of
plug
ing,
less
power.
minutes.
Measure
touching
WORK
(Figure
ELECTRIC
DC
Input
power.
Do
Turn
touch
not
off
power
from
receptacle,
maintaining,
Internal
within
Lesser
voltage
60
voltage
parts.
any
SURFACES
Allow
cooling
LEAD
6-3)
VOLTAGE
live
electrical
source,
and
or
servicing.
will
decrease
seconds
voltages
on
input
cause
can
period
INSPECTION
SHOCK
exists
remove
WAIT
after
remain
may
before
can
kill;
after
removal
parts.
input
be
fore
inspect
50
to
volts
removal
of
up
capacitors
severe
burns.
servicing.
SIG
power
input
two
to
before
4.
Disconnect shield
cup
5.
Disconnect
iT.
strip
6.
Disconnectwork
7.
Remove
B.
Relnstallatlon
1.
Route
2.
nect
Route
or
lief,
a.
b.
torch
new
work
to
new
and
connect
Connect
nector.
Connect terminal
arc/shield
pilot
detector
torch
leadfromwork
cable
Of
work
lead
(+)
output
torch
torch
pilot
1
on
lead
switch
leads
Torch
through
terminal.
cable
cable
cable
arc/shield
cup
2
from
leads
And
leads
leads
to
air/torch
cup
detector
terminal
3
and4from
(+)
from
Work
strain
lead1and
strip
outputterminal.
unit.
Lead
relief,
through
follows:
as
(-)
output
detector
terminal
and
con
strain
con
1
lead
re
to
If
it
work
A.
1.
2.
3.
should
lead
Removal
Turn
from
plug
Open
Loosen from
become
clamp,
Of
power
receptacle.
lower
front
cable
air/torch
Torch
necessary
Torch
source,
panel
clamp,
(-)
output
proceed
access
connector.
Switch
to
replace
follows:
as
Work
remove
door.
disconnect
Air/Torch
Connector
Lead
()
torch
input
torch
Terminals
Terminal
Terminal
power
cable
3
2:
ShIeld
1:
or
And
Pilot
3.
4.
5.
4:
Torch
Detector
Cup
Arc/Shield
Connect
c.
IT.
on
d.
Connect
ii.
on
Connect
e.
on
Secure
Close
Reinstall
torch
and
input
ceptacle,
5witch
Lead
Lead
Detector
Cup
shield
torch
torch
cable
secure
power
resume
Connections
Connection
Lead
detector
cup
switch
switch
leads
lower
front
plug
operation.
Connection
PB1
into
lead
lead
lead
in
panel
200/230
Torch
2
3
4
strain
access
Terminal
to
terminal
to
terminal
to
terminal
relief.
volts
door.
ac
Strip
2
3
4
re
iT
Plasma
Torch
Cutting
And
Cable
Work
And
Clamp
Lead
Figure
6-3.
Lower
Front
Panel
VIew
With
Relief
Access
Work
Terminal
Door
Output
Open
OM-296
18-t25
Page
646
15
Page 26
SPARK
6-4.
WARNING:
AA
NIFICANT
of
Do
plug
ing,
Internal
less
power.
minutes.
Measure
touching
MOVING
HOT
Allow
Troubleshooting
fied
This
behind
tory,
spark
come
lows:
1.
2.
3.
4.
5.
6.
7.
8.
is
unit
the
and
gap
necessary
Turn
from
plug
Remove
Loosen
Place
C.
point Apply
gauge
Tighten
Reinstall
Reinstall
ceptacle,
~
Figure
OM-296
Page
GAP
Input
not
Turn
from
(Figure
ELECTRIC
DC
power.
touch
off
power
receptacle,
VOLTAGE
live
source,
6-4)
SHOCK
exists
electrical
remove
WAITbefore
maintaining,orservicing.
will
on
can
moving
can
period
be
to
a
spark
spark
is
not
the
and
decrease
after
mayre
input
cause
parts.
cause
before
performed
gap
gap
recommended.
mm).
(1.2
spark
gap,
remove
voltage
within60seconds
Lesser
voltages
voltage
parts.
any
PARTS
away
a
cooling
with
panel.
from
The
Keep
SURFACES
persons.
provided
front
readjustment
is
to
adjust
0.047
source,
setting
power
receptacle.
half
left
screw
feeler
slight
held
is
screw
left
input
and
16
of
A.
gauge
pressure
firmly
A.
half
of
power
resume
6-4.
Spark
wrapper
of
in
wrapper
from
proper
against
gap.
onto
into
plug
200/230
operation.
Gap
Adjustment
can
after
parts.
input
50
to
removal
main
forup
capacitors
serious
severe
servicing,
only
assembly
at
was
If
it
should
proceed
input
unit.
thickness
B
point
unit,
volts
SIG-
kill;
removal
power
inspect-
volts
of
input
to
two
before
Injury.
burns.
by
quaIl-
located
the
fac-
Normal
be fol-
as
power
between
feeler
so
ac
re-
TA124
812
OVERLOAD
6-5.
WARNING:
~.
Do
Turn
power
maintaining,
INCORRECT
Use
or
Fuse
from
would tive.
To follows:
1.
2.
3.
4.
5. Install
6.
7.
type,
Fl
protects
overload.
be
off,
replace
Turn
from
plug
Depress
wise.
Pull
out
free.
Insert
Depress
cover
Reinstall
fuse
new
fuse
ceptacle,
SAFETY
6-6.
A.
Shield
Should
stalledonthe
unit
READY
and
properly
check
by
loosening
light.
ating
source
Service
B.
Tip
TO
prevent
pletely
check
off,
Section
AIr
C.
To
prevent
pressure, pressure
Should
Cup
shield
would
light
shield
If
READY
properly.
Station
Leakage
injury
electrode
light
inoperative.
and
6-2,
Pressure
damage
this
switch
air
pressure
PROTECTION
ELECTRIC
touch
not
off
power
from
plug
or
FUSE
replacement
only
rating
control
the
Should
unit
the
and
Fl
correct
,
power
source,
receptacle.
rotate
with
fuse
fuse
with
and
is
secure.
input
and
cover
into
fuse
rotate
power
resume
SHUTDOWN
Detector
cup
torch,the
be
completely
turned
be
installed
light
If
contact
cup
shield
READY
according
detector
turns
immediately.
Detector
from
coming
turn
would
Should
replace
if
necessary.
unit
the
Switch
to
is
protectedbynormally
located
S5
drop
SHOCK
electrical
live
source,
receptacle
servicing.
can
damage
Parts
(see
circuitofthe
Fl
would
fuse
fuse
holder
fuse
plug
open,
the
problem,
and
holder
when
holder
holder
into
the
be
cover
operation.
DEVICES
CIrcuit
be
removed
READY
light
inoperative.
check
circuit
remains
nearest
CircuIt
contact
torch
in
that
to
observing
detector
shock
READY
electrode
a
preset
off,
cup
off,
light
electric
in
off,
tip
the
below
(Figure
4-1)
can
kilt.
parts.
and
before
fuse
remove
unit.
of
input
inspecting,
same
size,
List).
source
power
READY
completely
and
proceed
remove
cover
fuse
cover
200/230
Section
input
couriterclock
holder
cover.
back
clockwise
not
or
would
shield
proper
on,
properly
turn
6-2.
the
circuit
turnoff
cup
Factory
caused
with
each
unit
would
light
according
to
insufficient
tight
inopera
power
cover
into
unit.
un
volts
ac
and
off,
Should
is
the
clean
Weekly
operation
READY
is
oper
power
Authorized
by
other,
be
com
be
turned
closed
as
is
re
in-
tip
to
air
pressure/regulator.
value,
S5
would
Page 27
open,
be
completely
turned
(see
D.
This
READY
pletely
run.
minutes
6-7.
oft,
Table
Thermal
unit
or
inoperative.
Should
shutdown,
CIRCUIT
A~
4A
READY
light
inoperative.
check
air
6-2.
Troubleshooting).
ProtectIon
is
protected
located
open,
would
light
READY
the
a
cooling
will
be
required.
BOARD
WARNING: NIFICANT of
input
power.
Do
Turn
plug
ing,
Internal
less
power.
minutes.
Measure
touching
MOVING
Keep
Allow
CAUTION:
(ESD)
BEFORE
Transport
shielding
Perform
touch
not
off
from
receptacle,
maintaining,
within60seconds
Lesser
any
PARTS
away
SURFACES
a
can
on
handling
carriers
would
turnoff,
Should
filter/regulator
by
normally
in
power
thermal
turn
The
off,
fan
shutdown
and
motor
light
period
HANDLING
ELECTRIC
DC
VOLTAGE
live
power
voltage
source,
or
servicing.
will
voltages
voltage
supply
the
FM
be
turned
of
SHOCK
exists
electrical
remove
WAiTbefore
decrease
after
may
on
input
parts.
can
cause
from
moving
can
cause
cooling
period
ELECTROSTATIC
damage
properly
circuit
or
work
only
before
circuit
grounded
circuit
boards.
boards
packages.
at
static-safe
a
unit
would
READY
air
closed
would
unit
would
would
light
compressor
thermostats
circuit.
occur,
continue
due
Should
be
to
a
approximately
PRECAUTIONS
can
kIll;
after
removal
parts.
input
power
inspect
50
to
volts
removal
remain
capacitors
serious
for
up
Injury.
of
to
before
parts.
severe
burns.
servicing.
DISCHARGE
boards.
wrist
in
proper
static-
work
be
the
com
to
ther
five
SIG
or
input
two
strap
area.
INCORRECT
plugs
Be
aligned.
EXCESSIVE
board.
Use
ment
plugs
6-8.
TROUBLESHOOTING
WARNING:
AA
NIFICANT of
input
Do
Turn
plug
ing,
Internal
less
power.
minutes.
Measure
touching
MOVING
Keep
HOT
Allow
Troubleshooting
fied
It
is
assumed
to
Section
ing
with
function
working
The
remedies
this
circuit dures. these ized
tion,
instructions.
properly
following
for
power
source.
diagram
If
procedures,
Service
strictly
INSTALLATION
plugs
cIrcuIt
are
can
sure
damage
that
PRESSURE
minimal
only
when
disconnectingorconnecting
removingorinstalling
pressure
(Table
ELECTRIC
DC
VOLTAGE
power.
touch
not
from
maintaining,
within60seconds
Lesser
live
electrical
power
receptacle,
voltage
source,
and
or
servicing.
will
voltages
voltageoninput
parts.
any
PARTS
away
SURFACES
a
cooling
persons.
that
of
3
of
until
table
some
while
trouble
Station.
follow
this
is
contact
can
from
moving
can
period
be
to
unit
was
manual,
controls,
trouble
designedtodiagnose
of
troubles
this
table
performing
is
remedied
not
the
In
cases
manufacturers
or
board.
properly
can
misaligned
installed
break
and
gentle
board.
6-2)
SHOCK
exIsts
can
after
parts.
remove
WAIT
decrease
after
remain
may
input
before
to
removal
50
capacitors
cause
serious
parts.
cause
performed
properly
before
severe
servicing.
only
installed
operator
power
source
developed.
and
that
in
conjunction
may
develop
troubleshooting
after
nearest
of
equipment
performing
Factory
procedures
and
cIrcuit
move
board
SIG
kill;
removal
power
inspect
volts
of
input
to
up
before
injury.
burns.
by
quali
accord
is
familiar
was
provide
with
proce
Author
malfunc
or
two
in
and
OM-296
Page
17
Page 28
Table
6-2.
Troubleshooting
TROUBLE
Unit
completely
POWER
ative;
and
PL1 PL2
both
POWER
fan
off;
run.
not
Does
FM
runs;
PL1
light
light
No
high
READY
POWER
on.
moper-
ON
READY
oft.
ON
motor
cut;
light
light
FM
does
motor
POWER
READY
both
on.
frequency.
PL2
light
ON
light
light
ON
off;
POWER
Line
switch/breaker
disconnect
position.
Line
fuse
or
Power
cord
receptacle.
Work
clamp
switch
Torch
switch
Torch
Fl
Fuse
Shield
contact
open.
cup
surface
not
switch
circuit
not
plug
connected.
not
PBI
PB1
tight
dirty.
CAUSE
in
breaker
secure
lead
connections.
lead
connections.
shield
or
CB1
tnpped.
OFF
open.
in
power
cup
Contact
.
line
Place
position.
Check
breaker.
Secure
Connect
and
workpiece.
Check,
connections
Check,
connections
Check
6-5.
Check,
Section
(see
Factory
disconnect
replace
power
work
clean,
(see
clean,
(see
replace
clean,
6-2).
Authonzed
cord
clamp
tighten
Section
tighten
Section
tighten
REMEDY
switch
line
fuse
plug.
to
clean,
Fl
according
shield
Service
in
or
bare
torch
6-3).
torch
6-3).
the
reset
switch
switch
to
cup
Station.
ON
circuit
metal
lead
lead
Section
torch
on
at
Fan POWER
both
does
READY
on.
ON
not
run;
light
light
PU
Shield
Electrode
Thermostats
(thermal
Insufficient
Specifications
Incorrect
Dirty
Fan
detector
cup
touching
shutdown).
air
pressure
pressure
air
filter/regulator.
motor
lead
connections.
inside
(see
torch.
open
Table
tip
and/or
requirements).
adjustment.
Check,
lead
Check
6-2).
Allow
minutes
2-1.
Repair
Adjust
Section
Clean
manufacturers
unit).
Replace
and
clean,
connections
tighten
a
cooling
(see
or
replace
filter/regulator
tighten
(see
penod
Section
air
5-1).
filter/regulator
instructions
FM.
shield
Section
electrode
of
approximately
6-6).
compressor.
(see
according
detector
cup
6-3).
Section
(see
4
Step
(supplied
in
to
with
five
OM-296
Page
18
Page 29
z
0
-l
C,
ii
U)
36
-.1
56
mrii
C,-IC,
I
a
C)
TIP
I~TECTOR
~-IIELD
.
PILOT
ARC
I
o~
.
>~
>~
CN2-3
cN2-I
U)
9
SWITCH
TORCH
O-~--O
IT
~
)
-3
CNI-4>>~
PC
CR1
063-A
C-125
No.
Diagram
Jul
.09
aoJi
1CIH
1C14
1IJ~
F~fH!~J~4f
A9
~
TIe
A8
-H
1.2
-
-~--~
r
I
I
I
_J
TB2L
TBIL
4
V
PC5
CR2
I
V
CNI
I
<<I
<<3
34
CR1
ZI
137
Lt~JJ
03
CA
C3 C2
50~
TI
5
361
li-i
F~1~
101
I
~jCI3~TJ
/2
I
H1J
0A
cs1c4~c~T

/6
___
A
4
.1
CT2
~
CR1
PC2
__
~
o~c
54
____
PRESSURE
SWITCH
RECT.
IN
,
2
2
~
2
~
2
~
<(CN2-2
~<CN2-l
>~__~__JL._~i_
>>__
CN2-I
C142-3
PC3
2/
____
i
~
~
2
TRANS.
IN
~
Z
22
i:I~
CNJJ>
CN3-I
CN8-2
<
<<O~-3
<<CN~-l
~
>
>
CNI8-5~
CR18-I
-
I
CII
TLPNS
Ui_i
T~1J
I
2
<<CN4-2
-<(CR4-I
I
/05
>
CNI8-3~
>--~<<CN4-3
>
I
CNI9-2
CNI9-I
CNI9-3
PCI
si\J52\JAJ4JLJ.
60~~j.4~5v.63~J0
<<CUlL-i
>>
CUE-i
<<CNI2-3
<<CNI2-I
~-<(CNI6-I
27
>
>
>>
(246-I
CR4-I
CN4-3
z
?
2
?
L__V._VV
Circuit
~
SQE~jD
AIR
Diagram
CircuIt
7-1.
Diagram
48
~~23OV.
-Tn
Page 30
SECTION
GENERAL
8-1.
The
following
installation
(PAC)
The
importance
emphasized
high-frequency
have
shown
tion
was
authorized
suitable
take
instructions
these
interference
plasma
ice
Department
technical
ing
Many
processes
open-circuit
to
trode
maximum
cutting
several
takes
to
spark
the
pilot,
current sent
at
In
order
practice
the
output
using
by
frequency
will
be
DEFINITIONS
8-2.
A.
High-Frequency
(PAC)
In
the
plasma
be
may
of
arc
an
energyfromthe
torch
well
B.
Cutting
circuit
electrode,
C.
Output
Output
cutting
Electrode
D.
information
the
of
equipment
of
since
plasma
that,
fault.
at
FCC
services
steps
that
arc
cutting
personnel
information.
voltages
work
open-circuit
(FAG)
jump
power
thousand
the
creating
follow
can
low
power
to
provide
to
superimpose
of
a
plasma
high-frequency
voltage
discussed
used
Sources
arc
for
initiating
Power
outage,
electrode
insulated
CIrcuIt
consists
arc,
pilot
Terminals
terminals
current
and
Terminal
PLASMA
8-
is
necessary
high-frequency
described
correct
a
case
in
most
In
to
clear
could
might
(PAC)
applications
without
in
installation
histories
arc
cutting
cases,
event
occurs,
the
serve
as
be
caused
equipment.
will
assist
sufficient
making
situation.
voltage
volts
between
path
is
of
hazards
source
gap
initial
an
without
frequencies.
these
higher
a
high
arc
cutting
techniques.
be
this
AssIsted
a
source
section.
(PAC)
cutting
can
in
cutting
reinitiating
high-frequency
a
good
connecting
of
and
are
pilot
cable.
attachments
work
terminals.
terminals
arc.
ARC
make
to
plasma
instruction
this
interference
of
arc
cannot
(PAC)
an
inadequate
interference
that
a
by
of
to
jump
(OCV)
not
to
cause
the
ionization,
voltages,
is
user
guide
the
The
processes
direct
sufficient
torch
required
In
such
in
high-frequency
Factory
user
from
contact.
of
a
plasma
an
electrode
that
would
that
is
it
open-circuit
(PAC)
power
resulting
of
interference
Plasma
process,
cutting
quality,
high
arc
and,
arc.
source
low
connected
which
Arc
mustflowto
impedance,
provide
CUTTING
a
proper
cutting
manual.
be
over
to
equipment
installa
with
to
cases,
minimizing
Serv
supply
by
require
elec
The
arc
this.
the
be
pre
source
It
arc
on
electrical
common
voltage
high-
Cutting
frequency
in
the
case
the
to
(PAC)
E.
The
lead
F.
The
workpiece
G.
A
to
rent
H.
The
directions
I.
Bonding
to
less and
J.
Depending
these
tion,
earth
K.
A
INSTALLATION
Pilot
arc
pilot
is
connected.
Work
work
Cutting
device
control
to
used
Cutting
cutting
cutting
Bonding
refers
of
any
cause
Figure
Grounding
terms
or
bonding,
.The
Receiver
receiver
Terminal
terminal
Terminal
terminal
is
connected.
Torch
in
position
and
arc,
Zone
zone
from
to
objects
current
8-4).
the
on
is
commonly
terms
is
any
electromagnetic
munications
L.
Conduction
Conduction
ergy
M.
HIgh
High
frequency
tinuous
N.
High-Frequency
purposes.
is
the
electrical
an
Frequency
or
pulsed,
(PAC)
High-frequency
to
fers
requiring
0.
Interference
Interference
of
high-frequency
P.
Radiation
any
of
the
high
frequency.
is
the
is
the
is
terminal
the
plasma
of
the
to
direct
the
is
space
midpoint
arc
(see
Figure
connecting
be
to
flow
between
(Earthing)
practices
of
parts
be
may
energy
used
device
transmission
conductor
radio
is
assisted
used
Assisted
frequency
to
plasma
plasma
unwanted
energy.
GUIDELINES
terminal
arc
electrode,
within
between
to
which
to
cutting
flow
of
50
which
(PAC)
to
plasma
8-6).
metallic
at
within
usedtoindicate
of
objects
same
potential
them
(see
jurisdictions,
the
apparatus
interchangeabiy.
normally
converting
start
arc
used
it
of
high-frequency
or
conducting
energy,
a
plasma
Plasma
arc
culling
cutting
(PAC)
problematic
transfer
(15
power
Figure
receiving
to
useful
either
arc.
(PAC)
processes
reception
pilot
cutting
process
cur
gas.
in
all
m)
source
together
regard
of
one
connec
the
to
com
en
medium.
con
Cutting
re
The
trode
OM-296
electrode
lead
or
20
Page
terminal
cutting
is
torch
terminaltowhich
connected.
is
elec
Radiation
through
is
space.
transmission
of
high-frequency
energy
Page 31
HIGH-FREQUENCY
8-3.
RADIATION
Installations
power
diation.
at
disruption
in
major
A.
Direct the
Such
receiving
sensitive
causes
Direct
radiation
power
considered
B.
Direct
attachment
Any
source
is
capable
high-frequency
cutting
tant
C.
Line
Most
quency
by
radiation
diation
D.
circuitisthe have
to
Conduction
power
reradiation
from
Reradiatlon
Radiation
energy
is
grounded
mediate
radiated.
ence.
vicinity,
This
high
using
source
will
radiation,
device,
of
communications
electronic
of
high-frequency
Radiation
is
that
be
Radiation
direct
the
to
of
acting
source.
to
Radiation
energy.
major
only
lines
are
which
from
these
when
small
torch
the
from
metal
cutting
objects
conducted
beatroublesome
can
frequency
produce
if
signal
can
cause
controls
From
radiation
radiation
From
output
as
Since
source
proper
Radiation
capable
cause
may
power
compared
work
circuit
unshielded
or
as
some
strength
an
or
can
radiation
Power
emanating
from
from
The
Cutting
terminals
antenna
an
direct
of
radiation,
attached.
torch
of
conducting
interference
lines.
to
cables
can
some
an
integral
part
high-frequency
is
sufficient
inconvenience
cause
systems.
malfunction
The
follows:
as
are
four
Source
power
the
directly
power
line
source.
from
is
not
Circuit
of
power
radiation
From
radiating
from
it
is
impor
The
Power
the
high-fre
directly
up
in
of
interfer
such
by
by
Normally,
that
caused
leads.
or
be
picked
wiring
distance,
source
of
ra
or
Plasma
Cutting
Power
8-5.
A.
Position
gether
ble.
or
ra
B.
(PAC)
When
operation, securely
good
un
im
re
ing.
manufacturer,
Plasma
Arc
(PAC)
Source
Figure
tion
Pickup
~
Keep
wires
8-1.
Requirements
in
GENERAL
Torch
the
torch
as
close
High-Frequency
Power
contact
Except
Arc
Power
Sources
plasma
service
fastened,
around
changes
the
Cutting
Source
\
unshielded
all
of
out
The
Vicinity
INSTALLATION
Cables
Work
work
floor
to
Assisted
arc
cutting
doors
and
adequately
the
source
power
(PAC)
Place
leadsonfloor
on
boards,
3/4
in.
I
to
and
the
ungrounded
weldIng
To
Minimize
Of
PROCEDURES
Or
Leads
cables
or
orground
Plasma
(PAC)
covers
entire
perimeter
adjustments
should
and
keep
(19-25
mm)
,
zone.
Cutting
leads
plane
power
must
bonded
of
allowedbythe
be
not
or
them
apart.
Ground
S.0084
Reradla
Zone
close
as
as
Cutting
source
be
closed,
to
ensure
modified.
to
possi
in
is
open
LOCATION
8-4.
Locate
as
ground
tion
should
amount
phone,
tors)
tallic which
quency
cellaneous
in
some
ciency,
Figure
possible.
connection
of
be
of
communications,
located
conductors
will
energy
grounded,
other
8-1).
source
power
iocated
miscellaneous
pick
Also
power
within
up,
consider
when
source.
in
the
in
the
conduct,
an
transmitted
the
in
wiring
metallic
rigid
material
having
grounded
closetothe
as
the
selecting
Ideally,
area
wiring
and
other
cutting
cutting
or
by
cutting
conduit,
an
50
at
nearness
site
a
the
where
there
(lighting,
unshielded
zone.
Ungrounded,
zone
can
reradiate
the
cutting
should
zone
copper
equivalent
(15
m)
cutting
of
a
forthe
power
is
a
power,
act
as
antennas
circuit.
be
enclosed
braid,
shielding
intervals
process
suitable
installa
source
limited
tele
conduc
me
re
high-f
All
mis
eff
(see
Electrical
Input
Supply
8-2.
This
with
General
(Earthing)
ground
No.
toawater
or
(3
m)
Figure
C.
Grounding
is
It
recommended
or
i
grounded.
workpiece
ground
within
rod
10
Cables
12
of
Rules
Or
Leads
that
the
must
be
AWG
or
pipe
workpiece.
Torch
Workpiece
workpiece
made
by
smaller
which
wire
enters
grounding
OM-296
be
to
S-0085
Work
firmly
driven
a
earth
Page
21
Page 32
D.
Metal
Installation
within
a
suitably
building
quency
sources
can
radiation.
in
Grounded
Buildings
of
a
plasma
bonded
effective
be
an
Wherever
such
places.
Copper
arc
and
cutting
grounded
means
possible,
(PAC)
(earthed)
of
reducing
power
high-fre
install
source
metal
power
metallic
rigid
rial
havinganequivalent
wound,
of
the
ing
be
grounded
tance
tween
conduit,
flexible,
miscellaneous
at
electrical conduit
sections
Copper
metallic
50
connections
copper
ft.
(15
Strap
braid,
shielding
conduit
wiring
intervals.
m)
(see
Figure
Coupling
in
must
is
the
or
some
capability
not
suitable).
cutting
Good
be
maintained
8-4).
other
(spirally
Shield
zone
low
mate
must
resis
be
FIgure
However,
metal
that
(earthed). good building.
any
the
(as pieces).
should
vals.
grounded
of
not
E.
ting
when
building,
building
This
electrical
During
having
type
reinforcing
welding
by
be
bolted
All
windows
copper
than
more
ShIeldIng
Zone
Ungrounded,
antennas
act
can
reradiate
cutting
pipes telephone,
within
OM-296
as
the
circuit.
be
must
communications,
the
cutting
22
Page
Bonding
8-3.
Grounding
Of
Panels
the
precautions
can
ground
metalinthe
and
each
metal
or
screen
1/4
Of
MIscellaneous
metallic
high-frequency
This
grounded,
zone
Metal
power
is
be
construction
structural
piece
source
properly
accomplished
rods
around
of
buildings,
welded
doorways
or
in.
(6.4
conductors
which
will
means
that
and
must
must
metaltoall
togetheratfrequent
galvanized
mm)
energy
be
Metal
Panels
Of
Metal
Bonding
Building
is
installed
be
taken
bonded
by
the
of
a
structure,
steel
is
bonded
adjacent
should
mesh.
Wiring
in
pick
transmitted
ungrounded
that
other
enclosed
Panels
within
be
to
grounded
placing
several
periphery
new
building
be
sure
that
together
other
adlacent
metal
panels
covered
be
hardware
in
cutting
conduct,
and/or
by
lighting,
power,
conductors
in
grounded,
sooig
sure
of
the
inter
with
cloth
Cut
zone
the
water
a
of
all
Figure
F.
The
connected
this
supply
8-4.
Power
plasma
manual,
conductors
completely equivalent
the
power
cord.
shielding,
power
source.
entrance
Shielding
throughout
electrical
good
the
ing
Line
Input
Power
Suppivi
Line
Fuse
And
Switch
Receptacle
Figure
8-6.
PLASMA
1.
8-5.
GUIDELINES
ARC
Locate
connected
possible.
2.
Shield
connection
source
ments
Bonding
Method
Service
arc
to
If
cutting
the
line
the
unit
(PAC)
input
is
equipped
serving
up
The
solid
extend
location
should
source.
5Oft.(15m)
Ground
(PAC)
CUTTING
the
workpiece,
input
of
Section
in
solid,
to
metallic
is
,o
Conduit
Power
FOR
power
plasma
by
8-5F).
enclosed
shielding,
should
length
contact
power
Is
~
InstallationOfPlasma
equipment
to
the
line
as
specified
(see
power
power
supply
with
the
power
metallic
point
conduit,
entire
in
building
be
electrically
should
be
provided
Plasma
eta
c
______
Source
INSTALLATION
(PAC)
so
POWER
that
can
leads
arc
manufactures
Conduit
source
as
a
power
source
conduit,
of
connection
distance
connected
between
Arc
Power
________
Arc
ground
be
kept
to
up
cutting
Sections
should
instructed
cord,
should
or
equivalent
from
to
power
continuous
so
the
shield
Cutting
Source
Cutting
SOURCES
lead,
short
as
point
(PAC)
power
require
be
the
be
or
with
that
(PAC)
S
-002
OF
when
in
in
1
as
of
Page 33
3.
Be
point
within
not
equivalent
lead
tory.
suitable.
4.
Keep
gether
5.
Adjust
given
Secure
6.
ing.
Visualize
7.
(15
power
and
a.
b.
c.
8.
10
cold
that
sure
least
at
that
the
cutting
used,
covered
Spirally
torch
spark
in
this
radius
m)
source
Figure
Have
all
munication in
grounded
cutting
Ground
wires,
Be
sure
phone
driven
(3
m)
water
the
conduit
50
(15
conduit
zone.
be
sure
shielding
cable,
wound,
work
to
close
as
setting
gap
manual.
service
cutting
centered
and
8-6),
unshielded
wires
shieldsorrelocated
zone.
all
large
or
support
there
that
within
wires
ground
less
or
pipes
from
as
system
from
m)
system
If
that
efficiency.
or
flexible
cablesorleads
access
zone
cutting
proceed
power,
within
metallic
wires
are
rods
the
ground
is
one
metallic
rigid,
shielding
Copper
equivalent,
metallic
ground
to
doors
as
a
sphere
on
a
point
torch
as
cutting
within
external
no
cutting
which
ground
for
continuous
is
power
complete
conduit used
sleeving,
is
conduit
as
as
plane
minimum
before
with
between
Figure
(see
follows:
lighting,
objects,
enter
zone
outside
long
cutting
power
zone.
the
connection,
workpiece.
to
a
source,
run
is
has
satisfac
is
not
close
to
possible.
setting
operat
50
a
the 8-1
com
placed
guy
zone.
ortele
ground
or
Power
Be
Arc
sure
Plasma
9.
tight.
If
the
be
ing,
8-7.
INSTALLATION
items
stallation.
may
terference
1.
Is
equipment
8-5D,
2.
ac
Sections
3.
Are
torch
properly
4.
ground
tions
5.
Is
equipment
tions
Point
Center
Figure
that
sure
source
that
not
power
Complete
with
authorized
and
8-5E,
input
power
8-5B,
installed
connections
8-5C,
8-6.1,
8-6.5
~-
8-6.
all
ground
is
building
GUIDELINES
be
necessary
necessary
properly
8-6.1)?
connections
8-6.2,
work
cables
(see
8-6.4,
properly
8-6.6)?
CuttIng
connections
operated
is
or
FCC
services.
located
8-6.3)?
or
Sections
properly
8-6.10,
set
up
Zone
clean
are
within
properly
practical
itemstoeliminate
(see
properly
leads
adjusted
a
CHECKLIST
Sections
and
8-5A
made
8-6.11)?
metal
build
grounded.
each
made
equipment
8-6.4)?
(see
(see
S.0022
in in
8-4,
(see
Sec
Sec
OM-296
Page
23
Page 34
SECTION
0
N
I-
I
I-
0
9-
PARTS
LIST
.c,)
E
C)
(n
4
C)
1~
a)
C.,
C.,
LI.
\
0)
C)
L.
LI.
\
OM-296
Page
24
Page 35
Item
No.
Dia.
Mkqs.
Part
No.
Description
Quantity
Figure
1
2 3
4
5
6
7 8
9
10
11
12
13
14
15
16
17
18 19 20
21
22
23
24
25 26
27
28 29 30
31 32
33 34
35
36
37
38
39
40
DCV1
T2
AS1
S4
S5
FM
TI
Zi
125134 125135
+125
125133
125130
125111 125106
125110
125109
125105
125115
125108
125276
125107
125128
125092
+125
125021 125293 125118 125137 125119 125120 125132
125131
125093 125091
125122
125083
125124 124729
125125
125136
125084 125127 125126 125114
125129
125123
125121
+125
125045 125042
125043
125044 125145
125030
Main
SCREW
NUT
CASE
GROMMET
SUPPORT CIRCUIT
DC
CIRCUIT
CIRCUIT
TRANSFORMER,
TERMINAL,
CIRCUIT
LABEL,
CIRCUIT
HOSE, VALVE,
117
PANEL, LABEL,
SCREW COVER SCREW
SWITCH, BUSHING,
FITTING
FITTING,
PRESSURE
FAN
BRACKET,
TRANSFORMER,
BASE
LABEL,
CAPACITOR
SCREW
STABILIZER
LEG,
TERMINAL
FRONT
HOSE
PILOT RECTIFIER BRACKET
116
REGULATOR/FILTER
REGULATOR/FILTER
HOSE,
BRACKET,
GAUGE,
TORCH,
Assembly
CARD
POWER
CARD CARD
CARD
warning
CARD
88
rear
warning
toggle
pipe
MOTOR,
warning
rubber
PANEL
CLAMP
UNIT
model
ASSEMBLY
SOURCE,
ASSEMBLY ASSEMBLY
control
15
amp
2
ASSEMBLY
electric
ASSEMBLY
volts
way
2
dc
primary
SPDT
strain-relief
-
brass
SWITCH,
volts
-
fan
mtg
motor
power
general
ASSEMBLY
ASSEMBLY,
ASSEMBLY
(Figure
ASSEMLBY
mtg
air
9-5)
-
PST
60
APT-3000
2
amp
15
volts
pole
shock
changeover
15
amp
tee
3100
ac
-
main
can
250
rpm
kill
etc
200-230
volts
precautionary
(Figure
output
(Figure
ASSEMBLY
9-2)
(Figure
(Figure
9-6)
(consisting
9-3)
9-4)
filter/regulator
(Figure
9-7)
2
2
2
1
20
1
1 1
1 1 1 1
2
1 1 1
1
volts
ac
1
2
1
13
1 1
1 1
1
1 1 1 1
1
10
1
4
1
1
1 1 1
1
of)
1
1 1 1 1 1
+When BE
ordering
SURE
TO
a
component
PROVIDE
originally
MODEL
AND
displaying
SERIAL
NUMBER
a
precautionary
WHEN
the
label,
ORDERING
label
should
REPLACEMENT
also
be
ordered.
PARTS.
OM-296
Page
25
Page 36
2
1
5
item
Figure
1 2
3
4
5 6 7 8
BE
SURE
OM-296
Page
Dia.
Mkgs.
RI
C1,13
R2
TO
26
PROVIDE
Part
125
125 167
125
125170 125171
172
125 125
173
125168
MODEL
Figure
CapacItor
BRACKET,
RESISTOR
BUS
BUS
CAPACITOR,
RESiSTOR,
BRACKET,
INSULATOR
SERIAL
9-2.
CapacItor
Description
Assembly
-
capacitor
mtg
electrolytic
-
component
NUMBER
20
cement
mtg
(Fig
1800
watt
WHEN
Assembly
Item
uf
8.2K
ORDERING
31)
volts
ac
REPLACEMENT
Quantity
1
1 1 1
2
1
1 1
PARTS.
Page 37
2
8
9
10
11
12
Item
No.
Figure
1
2
3
4
5
6 7 8 9
10
11
12
13
14
15 16 17
SURE
BE
Dia.
Mkgs.
R13
~R12
C14
C15,16,17
PROVIDE
TO
Part
No.
125
125 125 125 125 125 125 125 125 125 125186
125 125183 125182
125184
125185
MODEL
9-3.
Assembly,
15
mtg
pipe
cement cement
15
6
175
FIgure
Terminal
TERMINAL, BRACKET, FITTING, RESISTOR, RESISTOR,
TERMINAL,
TERMINAL,
CAPACITOR,
CAPACITOR,
RESISTOR,46OvoItsO.6watt
FASTON
187
181
FASTON
TERMINAL,
TERMINAL,
TERMINAL,
30
STOPPER
BINDER
INSULATOR
SUPPORT
AND
SERIAL
TermInal
Descnption
4
amp
-
component
-
brass
40
20
2
amp
4
amp
pole
600
amp
metanzed
ceramic
NUMBER
Assembly,
Output
(Fig
pole
9/16-18
watt watt
UNF
6.8K
8.2K
pole
film
0.047
0.01uf400
receptacle
volts
ac
WHEN
ORDERING
9-1
ohm ohm
uf
volts
1
pole
Output
Item
volts
ac
35)
dc
REPLACEMENT
PARTS.
OM-296
Quantity
1
1 1 1
1
1 1 I
3
1 1 1 1 1
1
1 1
27
Page
Page 38
11I1113I311I413331
6
iT
16
3
2
9
1
7
8
Item
FIgure
9-4
1
2 3
4
5 6
7
8
9
10
11
12
13
14
15 16
17
18
Re~mmended
SURE
BE
OM-296
Page
Dia.
Mkgs.
Fl
R15
S1,2,3
CB1
PL1
LED1
PROVIDE
TO
28
Spare
Part
125
*125
106
125
125 140
125141
125
125 125283
125148 125 125284 125 125280
125281 125282
097922
Parts.
MODEL
172
275
Front
FUSE,
HOLDER,
NAMEPLATE
PANEL,
INSULATOR
RESISTOR,
143
SWITCH,
CIRCUIT
112
NUT SHAFT
DOOR,access-front
144
LAMP,
SCREW
LAMP,
NUT
WASHER
RiNG
KNOB
FIgure
Panel
5
amp
fuse
front
toggle
PROTECTOR,
indicator
indicator
SERIAL
9-4.
Front
Descnption
Assembly
volts
250
volts
carbon
SPST3
220
15
NUMBER
0.3
vofts
mamp
Panel
(FIg
ac
ac
watt
amp
2P.50
ac,
dc,
WHEN
Assembly
9-1
Item
5K
30
volts
amp
red
lens
green
-,
ORDERING
36)
lens
dc
volts
ac
REPLACEMENT
Quantity
.
.
.
.
PARTS.
Page 39
2
.3
.4
Item
No.
FIgure
2 3
4
5
6
7
8
9
BE
SURE
Mkgs.
R10,11
Dia.
05
C18
CR1
13
R9
RB
TO
PROVIDE
Part
No.
125
125 125 125 125
125161
125103
MODEL
164
165
162
085
163
Unft
PIlot
DIODE,
high
CAPACITOR,
RELAY,
enclosed
TERMINAL,
RESISTOR,
COUPLING
BRACKET
RESISTOR, RESISTOR,
AND
SERIAL
Figure
(Fig
-
speed
film
15
WW
COIL
cement
cement
NUMBER
9-5.
Descnption
Item
9-1
2.5
20uf400
24
volts
2P
amp
60
watt
5
watt
20
Pilot
38)
amp
dc
12
watt.
WHEN
volts
SPST
3.3K
Unit
600
dc
ORDERING
volts
5
REPLACEMENT
Quantity
1
1
I 1 2
1
1
1 1
PARTS.
OM-296
Page
29
Page 40
5
4
.7
8
1
18
13
3
5
17
Item
Figure
1
2
3
4
5
6 7 8 9
10
11
12
.
13
14
15
16
17
18
Dia.
Mkgs.
C2-10
C11,12
R5 R7
D3,4
CT2
TMI
SR2
R6
SRi
R3,4
Part
No.
125
125 125
125
125
125154 125 125
125157
125158 125
125
FIgure
149
150
RectIfier
RESISTOR,
RESISTOR,
CAPACITOR,
Assembly
BUSBAR
089
DIODE,
CURRENT
high
TRANSFORMER
BUSBAR
TRANSISTOR
086
DIODE
CAPACITOR,
MODULE,
BINDER
155
SUPPORT,mtg-capacitor
156
RESISTOR,
SUPPORT
HEATSINK
THERMOSTAT,
DIODE
087 151
RESISTOR,WW53watt3.3
MODULE,
9-6.
Description
cement
WW
53
ceramic
-
speed
MODULE,
50
film
0.047
cement
NC
75
RectIfier
9-1
(Ag
40
watt
10
watt
0.01Ut400
12
amp
amp
uf~1000
10
watt
amp,8U0
Assembly
Item
1200
volts
vofts
10
ohm
vo1ts~
ohm
16
39)
volts
volts
dc.~
.
.
ac
volts
.:~
Quantity
1
1
9
2
2
1
2
1
1
2
1 1 I 1
1
1
1
2
BE
OM-296
SURE
Page
TO
30
PROVIDE
MODEL
SERIAL
NUMBER
WHEN
ORDERiN~G
R~PLACEMENT
-.
PARTS.
.
Page 41
14-~
2 3
4
.6
7
8
Rem
Figure
1
2
3
4
5
6
7 8 9
10
11
12 13 14
9-7
Dia.
Mkgs.
Part
125
125071
125070
125
069
294
079
030
1~
10
Figure
Torch,
CUP
TORCH
INSULATING SWITCH TORCH
SHRINKABLE
HEAT
HOSE
PILOT
TORCH
POWER
TORCH
WRENCH
SHEATH
AND
Model
BODY
COVER
SWITCH
DETECTIVE
SWITCH
CABLE
HANDLE
9-7.
Torch,
Description
APT-3000
TUBE
LEAD
ASSEMBLY
TUBE
Model
LEAD
.9
APT-3000
Quantity
1
1 1 1
1
1 1 1 1 1
1
1
1
1
BE
SURE
TO
PROVIDE
MODEL
AND
SERIAL
NUMBER
WHEN
ORDERING
REPLACEMENT
PARTS.
OM-296
Page
31
Page 42
Loading...