Millennium Enterprises Z42, Z33, Z34 User Manual

INSTALLATION MANUAL
MILLENNIUM™ ROOFTOP
25, 30 & 40 TON
MODELS: Z42
CONTENTS
NOMENCLATURE. . . . . . . . . . . . . . . . . . . . . . . . . . . 5
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . 7
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
GAS FURNACE OPERATING INSTRUCTIONS. . . 64
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
See the following pages for a complete Table of Contents.
Z33 Z34
NOTES, CAUTIONS AND WARNINGS
Installer should pay particular attention to the words: NOTE, CAUTION, and WARNING.
make the installation easier. equipment damage. that personal injury and/or equipment damage may result if installation procedure is not handled properly.
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
BEGIN TO INSTALL YOUR UNIT.
SA VE THIS MANUAL
Notes are intended to clarify or
Cautions are given to prevent
Warnings are given to alert installer
ISO 9001
Certified Quality
Management System
882108-YIM-B-1012
882108-YIM-B-1012
TABLE OF CONTENTS
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . 7
NOTES, CAUTIONS AND WARNINGS. . . . . . . . . . . . . . . 7
GAS FIRED MODELS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
WHAT TO DO IF YOU SMELL GAS . . . . . . . . . . . . . . . . . . . . . 7
ALL MODELS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
INSPECTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
REFERENCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
LIMITATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
LOCATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
RIGGING AND HANDLING . . . . . . . . . . . . . . . . . . . . . . . 12
CLEARANCES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
AIR HOODS FOR FIXED OUTSIDE AIR
(UNITS WITH MANUAL ECONOMIZER). . . . . . . . . . . . 13
AIR HOODS FOR ECONOMIZER. . . . . . . . . . . . . . . . . . 13
AIR HOODS FOR EXHAUST AIR . . . . . . . . . . . . . . . . . . 13
CONDENSATE DRAIN . . . . . . . . . . . . . . . . . . . . . . . . . . 13
SERVICE ACCESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
COMPRESSORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
THERMOSTAT (CONSTANT VOLUME UNITS) . . . . . . . 14
SPACE SENSOR (VARIABLE AIR VOLUME UNITS). . . 14
POWER AND CONTROL WIRING . . . . . . . . . . . . . . . . . 15
POWER WIRING DETAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
ERV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
GAS CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
VENT AND COMBUSTION AIR. . . . . . . . . . . . . . . . . . . . 17
ELECTRIC HEAT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
HOT WATER HEAT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
PIPING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
STEAM HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
PIPING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
STATIC PRESSURE CONTROL PLASTIC TUBING . . . 20
EXHAUST STATIC PRESSURE . . . . . . . . . . . . . . . . . . . 20
CFM, STATIC PRESSURE, AND POWER - ALTITUDE
AND TEMPERATURE CORRECTIONS . . . . . . . . . . . . 45
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
COMPRESSOR ROTATION . . . . . . . . . . . . . . . . . . . . . . 59
SUPPLY AIR FAN INSTRUCTIONS . . . . . . . . . . . . . . . . 59
CHECK BLOWER BEARING SET SCREWS . . . . . . . . . . . . . 59
CHECKING SUPPLY AIR CFM. . . . . . . . . . . . . . . . . . . . . . . . 59
FAN ROTATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
BELT TENSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
AIR BALANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
CHECKING AIR QUANTITY . . . . . . . . . . . . . . . . . . . . . . . . . . 60
SUPPLY AIR DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . . . . 61
SYSTEM SETPOINTS. . . . . . . . . . . . . . . . . . . . . . . . . . . 61
CONSTANT VOLUME AND VARIABLE AIR VOLUME:. . . . . 61
GAS FURNACE OPERATING
INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
TO LIGHT THE MAIN BURNERS . . . . . . . . . . . . . . . . . . 64
TO SHUT DOWN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
POST-START CHECKLIST (GAS) . . . . . . . . . . . . . . . . . 64
MANIFOLD GAS PRESSURE ADJUSTMENT . . . . . . . . 64
BURNER INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . 65
ADJUSTMENT OF TEMPERATURE RISE. . . . . . . . . . . 65
CHECKING GAS INPUT . . . . . . . . . . . . . . . . . . . . . . . . . 65
NATURAL GAS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
ELECTRIC HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
COOLING OPERATING INSTRUCTIONS . . . . . . . . . . . 66
COMPRESSOR. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
INTERNAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
CONDENSER FANS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
REFRIGERATION SYSTEM . . . . . . . . . . . . . . . . . . . . . . 66
COMPRESSORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
MOTORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
INDOOR BLOWER MOTORS. . . . . . . . . . . . . . . . . . . . . . . . . 66
POWER EXHAUST OR RETURN AIR FAN MOTORS. . . . . . 66
CONDENSER FAN MOTORS. . . . . . . . . . . . . . . . . . . . . . . . . 66
DRAFT MOTOR (GAS FURNACE). . . . . . . . . . . . . . . . . . . . . 66
GAS FURNACE SAFETY FEATURES . . . . . . . . . . . . . . 83
COMBUSTION AIR PROVING . . . . . . . . . . . . . . . . . . . . . . . . 83
ROLLOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
NORMAL MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . 83
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
MOTORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
FAN DRIVES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
OUTDOOR COIL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
GAS BURNER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
TO CLEAN BURNERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
COMBUSTION AIR DISCHARGE. . . . . . . . . . . . . . . . . . . . . . 84
CLEANING FLUE PASSAGES AND HEATING ELEMENTS . 84
SECURE OWNERS APPROVAL . . . . . . . . . . . . . . . . . . 85
2 Johnson Controls Unitary Products

LIST OF FIGURES

Fig. # Pg. #
882108-YIM-B-1012
Fig. # Pg. #
1 COMPONENT LOCATION . . . . . . . . . . . . . . . . . . . . . . . 6
2 TYPICAL RIGGING . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . . 11
4 RECOMMENDED DRAIN PIPING . . . . . . . . . . . . . . . . 14
5 TYPICAL THERMOSTAT WIRING . . . . . . . . . . . . . . . 14
6 TYPICAL GAS PIPING CONNECTION . . . . . . . . . . . . 16
7 VENT AND COMBUSTION AIR HOODS . . . . . . . . . . . 17
8 CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9 HOT WATER PIPING CROSS-SECTION . . . . . . . . . . 19
10 STEAM PIPING CROSS-SECTION . . . . . . . . . . . . . . . 19
11 BOTTOM SUPPLY AND RETURN . . . . . . . . . . . . . . . 21
12 END RETURN, BOTTOM SUPPLY . . . . . . . . . . . . . . . 22
13 BOTTOM RETURN, FRONT & REAR SUPPLY . . . . . 23
14 END RETURN, FRONT & REAR SUPPLY . . . . . . . . . 24
15 FIELD INSTALLED DISCONNECT . . . . . . . . . . . . . . . 43
16 40 TON CONDENSER DETAIL . . . . . . . . . . . . . . . . . . 43
17 PARTIAL ROOF CURB MODEL 1RC0455P . . . . . . . . 44
18 ALTITUDE/TEMPERATURE CONVERSION
FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
19 FAN PERFORMANCE - 25 TON . . . . . . . . . . . . . . . . . 48
20 FAN PERFORMANCE - 30 TON . . . . . . . . . . . . . . . . . 50
21 FAN PERFORMANCE - 40 TON . . . . . . . . . . . . . . . . . 52
22 POWER EXHAUST - ONE FORWARD CURVE FAN
- 25 TONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
23 POWER EXHAUST - TWO FORWARD CURVED FANS
- 30 & 40 TONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
24 BELT TENSION ADJUSTMENT . . . . . . . . . . . . . . . . . 59
25 TYPICAL GAS VALVES . . . . . . . . . . . . . . . . . . . . . . . . 65
26 TYPICAL FLAME APPEARANCE . . . . . . . . . . . . . . . . 66
27 HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 10 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
28 HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 20 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
29 HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 30 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
30 HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 40 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
31 HOT WATER COIL - 25 & 30 TON, 2 ROW,
AT 60 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
32 HOT WATER COIL - 25 & 30 TON, 2 ROW,
AT 80 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
33 HOT WATER COIL - 40 TON, 1 ROW, AT 10 GPM . . 73 34 HOT WATER COIL - 40 TON, 1 ROW, AT 20 GPM . . 73 35 HOT WATER COIL - 40 TON, 1 ROW, AT 30 GPM . . 74 36 HOT WATER COIL - 40 TON, 1 ROW, AT 40 GPM . . 74 37 HOT WATER COIL - 40 TON, 2 ROW, AT 20 GPM . . 75 38 HOT WATER COIL - 40 TON, 2 ROW, AT 40 GPM . . 75 39 HOT WATER COIL - 40 TON, 2 ROW, AT 60 GPM . . 76 40 HOT WATER COIL - 40 TON, 2 ROW, AT 80 GPM . . 76
41 STEAM COIL - 25 & 30 TON (1 ROW) . . . . . . . . . . . . 77
42 STEAM COIL - 40 TON (1 ROW) . . . . . . . . . . . . . . . . 77
43 TYPICAL CONTROL WIRING . . . . . . . . . . . . . . . . . . . 78
44 LEGEND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
45 TYPICAL 25 TON POWER WIRING . . . . . . . . . . . . . . 80
46 TYPICAL STANDARD GAS HEAT WIRING . . . . . . . . 81
47 TYPICAL MODULATING GAS HEAT WIRING . . . . . . 82
48 TYPICAL FLUE BAFFLE . . . . . . . . . . . . . . . . . . . . . . . 85
49 25 TON CHARGING CURVE . . . . . . . . . . . . . . . . . . . . 86
50 30 TON CHARGING CURVE . . . . . . . . . . . . . . . . . . . . 87
51 40 TON CHARGING CURVE . . . . . . . . . . . . . . . . . . . . 88
52 PRESSURE DROP DRY EVAPORATOR COIL VS
SUPPLY AIR CFM - 25 TON . . . . . . . . . . . . . . . . . . . . 89
53 PRESSURE DROP DRY EVAPORATOR COIL VS
SUPPLY AIR CFM - 30 TON . . . . . . . . . . . . . . . . . . . . 90
54 PRESSURE DROP DRY EVAPORATOR COIL VS
SUPPLY AIR CFM - 40 TON . . . . . . . . . . . . . . . . . . . . 91
55 R-410A QUICK REFERENCE GUIDE . . . . . . . . . . . . . 92
Johnson Controls Unitary Products 3
882108-YIM-B-1012
LIST OF TABLES
Tbl. # Pg. #
1 COOLING & ELECTRICAL APPLICATION . . . . . . . . . 8
2 COOLING & ELEC. APP. LIMITATIONS . . . . . . . . . . . 8
3 STANDARD GAS HEATING CAPACITIES . . . . . . . . . 9
4 TEMPERATURE RISE . . . . . . . . . . . . . . . . . . . . . . . . . 9
5 MINIMUM HEATING CFM . . . . . . . . . . . . . . . . . . . . . . 9
6 MODULATING GAS HEATING CAPACITIES . . . . . . . 9
7 MODULATING HEAT . . . . . . . . . . . . . . . . . . . . . . . . . 10
8 UNIT WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9 SUPPLY FAN MOTOR VFD WEIGHTS . . . . . . . . . . . 11
10 EXHAUST FAN MOTOR VFD WEIGHTS . . . . . . . . . 11
11 UNIT CORNERWEIGHT . . . . . . . . . . . . . . . . . . . . . . 12
12 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . 12
13 CONTROL WIRE SIZES . . . . . . . . . . . . . . . . . . . . . . 14
14 PIPE SIZES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
15 GENERAL PHYSICAL DATA . . . . . . . . . . . . . . . . . . . 25
16 REFRIGERANT FACTORY CHARGE R-410A . . . . . 26
17 ELECTRICAL DATA 25 TON BASIC UNIT R-410A . . 26 18 ELECTRICAL DATA 30 TON BASIC UNIT R-410A . . 27 19 ELECTRICAL DATA 40 TON BASIC UNIT R-410A . . 27 20 ELECTRICAL DATA 25 TON W/ELECTRIC HEAT
R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
21 ELECTRICAL DATA 30 TON W/ELECTRIC HEAT
R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
22 ELECTRICAL DATA 40 TON W/ELECTRIC HEAT
R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
23 ELECTRICAL DATA 25 TON W/POWER EXHAUST
R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
24 ELECTRICAL DATA 30 TON W/POWER EXHAUST
R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
25 ELECTRICAL DATA 40 TON W/POWER EXHAUST
R-410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
26 ELECTRICAL DATA 25 TON W/ELECTRIC HEAT
AND POWER EXHAUST R-410A . . . . . . . . . . . . . . . .34
27 ELECTRICAL DATA 30 TON W/ELECTRIC HEAT
AND POWER EXHAUST R-410A . . . . . . . . . . . . . . . .37
28 ELECTRICAL DATA 40 TON W/ELECTRIC HEAT AND
POWER EXHAUST R-410A . . . . . . . . . . . . . . . . . . . .40
29 ALTITUDE CORRECTION FACTORS . . . . . . . . . . . . 45
Tbl. # Pg. #
30 FAN PERFORMANCE - 25 TON . . . . . . . . . . . . . . . . . 47
31 FAN PERFORMANCE - 30 TON . . . . . . . . . . . . . . . . . 49
32 FAN PERFORMANCE - 40 TON . . . . . . . . . . . . . . . . . 51
33 COMPONENT STATIC RESISTANCE. . . . . . . . . . . . . 53
34 SUPPLY FAN MOTOR AND DRIVE DATA . . . . . . . . . 54
35 EXHAUST FAN DRIVE DATA . . . . . . . . . . . . . . . . . . . 54
36 POWER EXHAUST - ONE FORWARD CURVED
FAN 25 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
37 POWER EXHAUST - TWO FORWARD CURVED
FANS - 30 & 40 TON . . . . . . . . . . . . . . . . . . . . . . . . . . 57
38 BELT ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . 60
39 BLOWER SPEED RATE OF CHANGE . . . . . . . . . . . . 61
40 25 TON DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . . . 62
41 30 TON DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . . . 62
42 40 TON DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . . . 63
43 DRIVE ADJUSTMENT FOR POWER EXHAUST
- 25 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
44 DRIVE ADJUSTMENT FOR POWER EXHAUST
- 30 & 40 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
45 GAS RATE - CUBIC FEET PER HOUR . . . . . . . . . . . . 66
46 STEAM COIL (1 ROW, 40 TON) . . . . . . . . . . . . . . . . . 67
47 STATIC RESISTANCE STEAM COIL (25 & 30 TON) . 67
48 STEAM COIL (1 ROW, 25 & 30 TON) . . . . . . . . . . . . . 67
49 STATIC RESISTANCE STEAM COIL (40 TON) . . . . . 67
50 HOT WATER COIL (1 ROW 25 & 30 TON) . . . . . . . . . 67
51 HOT WATER COIL (1 ROW, 40 TON) . . . . . . . . . . . . . 68
52 WATER PRESSURE DROP (1 ROW, 25 & 30 TON) . 68
53 WATER PRESSURE DROP (1 ROW, 40 TONS) . . . . 68
54 HOT WATER COIL (2 ROW, 25 & 30 TON) . . . . . . . . 68
55 WATER PRESSURE DROP (2 ROW, 25 & 30 TON) . 69
56 WATER PRESSURE DROP (2 ROW, 40 TON) . . . . . . 69
57 STATIC RESISTANCE HOT WATER COIL
(25 & 30 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
58 STATIC RESISTANCE HOT WATER COIL
(40 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
59 INDOOR BLOWER BEARING LUBRICATION
SCHEDULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
4 Johnson Controls Unitary Products

NOMENCLATURE

R
A = 1,3,5,7
OPTIONS
ADDITIONAL
CONFIGURATION
Cu/Cu Condenser Coil
Cu/Cu Evaporator Coil
123 4
14
D
13
A
12
C
CONTROL
Exhaust VFD (Customer)
(see note 3)
* Premium Cabinet (6 doors)
* Standard Cabinet (4 doors)
* Drain Pan - powder coat
* Drain Pan - stainless steel
D = SYNTHESYS CONTROL
E = SYNTHESYS CONTROL,
DISC., 110V OUTLET
110V OUTLET
F = SYNTHESYS, DISC.
J = SIMPLICITY CONTROL,
H = SIMPLICITY CONTROL
I = SIMPLICITY CONTROL, DISC
®
®
®
DISC, 110V OUTLET
DISC, NO 110V OUTLET
K = SIMPLICITY CONTROL W/SIMPLICITY LINC
DISC, NO 110V OUTLET
L = SIMPLICITY CONTROL W/SIMPLICITY LINC
M = SIMPLICITY CONTROL W/SIMPLICITY LINC
N = YCCS CONTROL
ECONOMIZER
P = YCCS CONTROL W/DISC., 110V OUTLET
Q = YCCS ZONING CONTROL
R = YCCS ZONING CONTROL W/DISC.,
110V OUTLET
S = YCCS-VAV CONTROL
T = YCCS-VAV CONTROL W/DISC.,
110V OUTLET
C, = DRY BULB ENTH Low leak type
B, = SINGLE ENTH Low leak type
D = MANUAL Low leak (Not w/PE)
A = DUAL ENTH Low leak type
H = DRY BULB Std type
F = DUAL ENTH Std type
G = SINGLE ENTH Std type
E = NONE
(See note 5)
EXHAUST
B = 1, 3 K = 2, 6 T = A, 4
A = BARO J = 2, 5 S = A, 3
C = 1, 4 L = 2, 7 U = A, 5
D = 1, 5 M = 2, 8 V = A, 6
E = 1, 6 N = NONE W = A, 7
882108-YIM-B-1012
3 = 13,000 CFM ERV
9 = Non Std Config
I = 2, 4 R = 2, 0 2 = 8,000 CFM ERV
H = 2, 3 Q = 2, 9 Z = A, 0
F = 1, 7 O = 1, 9 X = A, 8
G = 1, 8 P = 1, 0 Y = A, 9
7 = 10 HP HI-EFF
MOTOR
Motor
Power Exhaust
1 = MODULATING DAMPERS A = VFD MODULATING
2 = NON-MOD. (ON/OFF)
0 = 5 HP HI-EFF (25T Only)
8 = 15 HP HI-EFF (Except 25 Ton)
-EFF
6 = 7.5 HP HI
11
A
10
A
9
1
8
B
7
4
6
3
5
N
4
A
3
3
2
3
1
Z
FILTERS
A = STAND.
B = 65%
VOLTAGE
2 = 208/230-60
3 = 380-60
PACKAGE
Z = York Brand R-410A
C = 95%
D = 2" HI-EFF
1. 108KW not available with 208/230V.
NOTES:
(See note 4)
(30T/40T)
4 = 460-60
ID BLOWER
5 = 575-60
7 = 380/415-50
BASIC UNIT
GENERATION
2 = 25 TON
minimum efficiency regulations mandated
in Canadian Energy Efficiency Regulations.
only; VFD will be customer supplied and
2. Standard efficiency motor meets Canadian
A = A, F, I L = D, G, J W = D, E, J
field installed. If VFD Exh is also
3. (VFD-CUSTOMER) = Wired for VFD
E = A, E, H P = B, G, J 2 = B, E, J
D = A, G, J O = B, G, I Z = B, E, I
C = A, F, J N = B, F, J Y = B, E, H
B = A, G, I M = B, F, I X = D, F, H
CONFIGURATION
3 = 30 TON
4 = 40 TON
A = 1,2 1 - BOTTOM RETURN
B = 1,4 2 - BOTTOM SUPPLY
specified, it will also be cust supplied.
G = A, E, J R = C, F, J 4 = C, E, H
F = A, E, I Q = C, F, I 3 = B, F, H
(5)
3 - END RETURN
C = 1,5
Contact engineering for
air foil applications.
available in end return configuration.
6. Air foil fan available on cooling only.
4. VAV ID Blower requires hot gas bypass .
5. Power exhaust and barometric relief not
9 = D, G, H
K = D, G, I V = D, E, I
J = D, F, J U = D, E, H 8 = C, F, H
I = D, F, I T = C, G, J 7 = C, E, J
H = A, F, H S = C, G, I 6 = C, E, I
D = 3,2 4 - REAR SUPPLY
Air Volume
a = CV
F = 3,5
E = 3,4 5 - FRONT SUPPLY
FRONT SUPPLY - COOLING ONLY
HOT WATER, STEAM & ELECTRIC HEAT -
BOTTOM SUPPLY ONLY
GAS HEAT - BOTTOM OR REAR SUPPLY ONLY
b = VAV (VFD-FACTORY INSTALLED)
Config
Z = 2,3,9,8
2 = 2,4,9,8
7 = 1,4,9,8
Y = 1,3,9,8
9 = Non-Std
R = 2,3,9,7
T = 2,4,9,7
Q = 1,3,9,7
L = 2,4,5,8
S = 1,4,9,7
K = 1,4,5,8
REFRIGERATION
D = 2,4,5,7
I = 1,3,5,8
B = 2,3,5,7
(3)
Fan (See note 6)
c = BYPASS FACTORY VFD
d = VAV (VFD-CUSTOMER)
J = 2,3,5,8
C = 1,4,5,7
g = AIR FOIL FAN [always Class II]
e = FORWARD CURVE FAN Class I
f = FORWARD CURVE FAN Class II
Condenser Coil Head Press. Ctrl.
Class I blower is limited to 15HP in 25/30Ton
Class I blower is limited to 20HP in 40Ton
Class II blowers are not HP limited
Blower Mount
HEAT SOURCE
W = HOT WATER COIL
C = COOLING ONLY
E = ELECTRIC HEAT
T = NATURAL GAS, MODULATING HEAT, SS *
N = NATURAL GAS
S = NATURAL GAS, SS HEAT EXCHANGER
D = NATURAL GAS, MODULATING HEAT*
HEAT EXCHANGE
(See note 4)
Piping
Evaporator Coil
2 = TECHNICOAT 8 = NO
1 = STANDARD 7 = YES
3 = STANDARD 4 = HOT GAS BYPASS
5 = STANDARD
9 = STD W/TECHNICOAT
(See note 2)
ID MOTOR
j = 2 inch deflection spring
h = Neoprene
i = 1 inch deflection spring
5 = 10 HI-EFF
6 = 15 HI-EFF
HEAT CAPACITY
3 = 267 MBH
5 = 533 MBH
8 = 800 MBH (40T ONLY)
X = STEAM COIL
4 = 40 KW
8 = 25 HI-EFF (Except 25T)
0 = 7.5 HI-EFF (25T Only)
7 = 20 HI-EFF
(1)
0 (ZERO) NO HEAT
1 = 108 KW
1 = 1 ROW
8 = 80 KW
1 = 1 ROW
2 = 2 ROW
Johnson Controls Unitary Products 5
882108-YIM-B-1012
EVAPORATOR COIL
AND DRAIN PAN ACCESS
REAR
LEFT END
FILTER DRIERS
FILTER ACCESS
POWER EXHAUST ACCESS
HEAT SECTION
POWER & CONTROL WIRING
COMPRESSOR ACCESS
HEAT SECTION
FRONT
EVAPORATOR COIL
AND DRAIN PAN ACCESS
OPTIONAL POWER OUTLET (115V)
RIGHT
END
FILTER ACCESS
REAR
SUPPLY BLOWER & MOTOR

FIGURE 1 - COMPONENT LOCATION

6 Johnson Controls Unitary Products

GENERAL

York Model Z42/Z33/Z34 units are single package cooling
only or cooling with gas, electric, hot water or steam heating designed for outdoor installation on a rooftop and for non-res­idential use.
The units are completely assembled on rigid, permanently
attached base rails. All piping, refrigerant charge, and electri­cal wiring is factory installed and tested. The units require electric power, gas, steam, or hot water connections and duct connections. Gas fired units also require installation of a flue gas outlet hood.
Reference R-410A Quick Reference Guide, Figure 55 for R-410A Refrigerant information.

SAFETY CONSIDERATIONS

NOTES, CAUTIONS AND WARNINGS

882108-YIM-B-1012
This Furnace is not to be used for temporary heat­ing of buildings or structures under construction.

ALL MODELS

This system uses R-410A Refrigerant which oper­ates at higher pressures than R-22. No other refrigerant may be used in this system. Gage sets, hoses, refrigerant containers and recovery sys­tems must be designed to handle R-410A. If you are unsure, consult the equipment manufacturer. Failure to use R-410A compatible servicing equip­ment may result in property damage or injury.
Installer should pay particular attention to the words: NOTE, CAUTION, and WARNING. make the installation easier. equipment damage. personal injury and/or equipment damage may result if instal­lation procedure is not handled properly.
Warnings are given to alert installer that
Notes are intended to clarify or
Cautions are given to prevent

GAS FIRED MODELS

DO NOT store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance. Do not touch any electrical switch. Do not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you cannot reach your gas sup-
plier, call the fire department.
The furnace and its individual shut-off valve must be disconnected from the gas supply piping sys­tem during any pressure testing of that system at test pressures in excess of 0.5 psig. Pressures greater than 0.5 will cause gas valve damage resulting in a hazardous condition. If gas valve is subjected to a pressure greater than 0.5 psig, it must be replaced. The furnace must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pres­sure testing of that system at test pressures equal to or less than 0.5 psig.
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should install, repair or service air conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe pre­cautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes, including ANSI Z223.1-Latest Edi­tion: wear safety glasses and work gloves; use quenching cloth for unbrazing operations; have fire extinguisher avail-
able for all brazing operations.
Before performing service or maintenance opera­tions on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
Improper installation, adjustment, alteration, ser­vice or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.

INSPECTION

As soon as a unit is received, it should be inspected for possi­ble damage during transit. If damage is evident, the extent of damage should be noted on the carrier’s freight bill. A sepa­rate request for inspection by the carrier’s agent should be made in writing.
Johnson Controls Unitary Products 7
882108-YIM-B-1012

REFERENCE

Additional information is available in the following reference form:
246837 - Technical Guide

APPROVALS

Designed certified by CSA, ETL, CETL as follows:
1. For use as a forced air furnace with cooling unit (gas heat models).
2. For outdoor installation only.
3. For installation on combustible material and may be installed directly on combustible flooring or Class A, Class B or Class C roof covering materials.
4. For use with natural gas (convertible to LP with kit).
Not suitable for use with conventional venting systems.

INSTALLATION

PRECEDING INSTALLATION

If a factory option convenience outlet is installed, the weath­erproof outlet cover must be field installed. The cover shall be located in the unit control box. To install the cover, remove the shipping label covering the convenience outlet, follow the instructions on the back of the weatherproof cover box, and
attach the cover to the unit using the (4) screws provided.
After installation, gas fired units must be adjusted to obtain a temperature rise within the range specified on the unit rating plate.
If components are to be added to a unit to meet local codes, they are to be installed at the contractor's and/or the cus­tomer's expense.
Size of unit for proposed installation should be based on heat loss / heat gain calculation made according to the methods of the Air Conditioning Contractors of America (ACCA).

LOCATION

Use the following guidelines to select a suitable location for these units:
TABLE 1: COOLING & ELECTRICAL APPLICATION
UNIT POWER
SUPPLY
575-3-60 540 630
208/230-3-60 187 252
460-3-60 432 504
VOLTAGE VARIATIONS
MIN. VOLTS MAX VOLTS
TABLE 2: COOLING & ELEC. APP. LIMITATIONS
MODEL

LIMITATIONS

Z42 Z33 Z34
208/230-3-60 and 380/415-3-50 units with factory installed Powered Convenience Outlet Option are wired for 230v and 415v power supply respectively. Change tap on transformer for 208-3-60 or 380-3-50 operation. See unit wiring diagram.
LIMITATIONS
The installation of this unit must conform to local building codes, or in the absence of local codes, with ANSI Z223.1 Natural Fuel Gas Code and /or CAN/CGA B149 installation codes.
In U.S.A.:
1. National Electrical Code ANSI/NFPA No. 70-Latest Edi­tion.
2. National Fuel Gas Code Z223.1-Latest Edition.
3. Gas-Fired Central Furnace Standard ANSI Z21.47-Lat­est Edition.
4. Local gas utility requirements.
Refer to Table 1 for Cooling and Electrical Application Data and to Table 2 for Gas Heat Application Data.
Supply Air CFM
(min./max)
Entering Wet Bulb
Temp (F°) (min./max)
Ambient Temp 40/125 40/125 40/125
Min. Air Temperature on Gas Fired Heat Exchangers (°F)
Aluminized 25 25 25
Stainless 000
6,000­12,500
57/75 57/75 57/75
6,000-
15,000
8,000-
20,000
1. Unit is designed for outdoor installation only.
2. Condenser coils must have an unlimited supply of air. Where a choice of location is possible, position the unit on either north or east side of building.
3. Suitable for roof mount on curb.
4. Roof structures must be able to support the weight of the unit and its accessories. Unit must be installed on a solid level roof curb or appropriate angle iron frame.
5. Maintain level tolerance to 3/4 inches across width and 2 inches along length.
8 Johnson Controls Unitary Products
TABLE 3: STANDARD GAS HEATING CAPACITIES
GAS HEAT
OPTION
AVAILABLE ON
MODELS
INPUT CAPACITY (MBH)
1ST STAGE TOTAL 1ST STAGE TOTAL
1
N3 Z42/Z33/Z34 267 267 213 247 247 N5 Z42/Z33/Z34 267 533 426 247 495 N8 Z34 ONLY 267
1.
Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.
2.
Blower motor heat not included.
3.
Based on a heat content of 1075 Btu/Ft.
4.
Unit Control Board with 3 heating outputs only. For all other Unit Control Boards the 1st Stage is 533 MBH.
4
3
800 638 247 742
TABLE 4: TEMPERATURE RISE
O
UTPUT
CAPACITY
(MBH)
2
G
AS RATE, CU. FT./HR.
TABLE 5: MINIMUM HEATING CFM
882108-YIM-B-1012
3
TON
123
MODULES
25 5-35 25-55 ­30 5-35 20-50 ­40 5-30 10-45 25-55
TABLE 6: MODULATING GAS HEATING CAPACITIES
GAS HEAT OPTION
2
D3
2
D5
2
D8
1.
Output Capacity at Full Fire.
2.
Modulating Gas Heat available on CV models only.
AVAILABLE ON
MODELS
Z42/Z33/Z34 69 267 6 213 64 247 Z42/Z33/Z34 69 533 12 426 64 495
Z34 ONLY 69 800 17 638 64 744
INPUT CAPACITY (MBH)
INIMUM MAXIMUM MINIMUM MAXIMUM
M
TON
1
1
MODULES
23
25 6,000 7,183 ­30 6,000 7,901 ­40 8,000 8,779 13,169
1.
Calculated minimum CFM for maximum heat rise is 5,644 for 25/30T and 6,584 for 40T, 1 module.
AS RATE, CU. FT./HR.
STEPS
O
UTPUT CAPACITY
(MBH)
1
G
Johnson Controls Unitary Products 9
882108-YIM-B-1012
TABLE 7: MODULATING HEAT
STAGES OF GAS CONTROL (% OF FULL HEAT OUTPUT)
AS HEAT OPTION AVAILABLE ON MODELS STEP INPUT OUTPUT % OF TOTAL OUTPUT
G
1 69,333 55,466 26%
D3
(Turn down ratio
3.8 to 1)
D5
(Turn down ratio
7.7 to 1)
D8
(Turn down ratio
11.5 to 1)
Z42, Z33, Z34
Z42, Z33, Z34
Z34 Only
2 106,666 85,333 40% 3 165,332 132,266 62% 4 202,665 162,132 76% 5 229,332 183,466 86% 6 266,666 213,333 100% 1 69,333 55,466 13% 2 106,666 85,333 20% 3 165,332 132,266 31% 4 202,665 162,132 38% 5 229,332 183,466 43% 6 266,666 213,333 50% 7 325,331 260,265 61% 8 362,664 290,132 68%
9 389,331 311,465 73% 10 426,664 341,331 80% 11 495,997 396,798 93% 12 533,330 426,664 100%
1 69,333 55,466 9%
2 106,666 85,333 13%
3 165,332 132,266 21%
4 202,665 162,132 25%
5 229,332 183,466 29%
6 266,666 213,333 33%
7 325,331 260,265 41%
8 362,664 290,132 45%
9 389,331 311,465 49% 10 426,664 341,331 53% 11 495,997 396,798 62% 12 533,330 426,664 67% 13 586,663 469,330 73% 14 655,996 524,797 82% 15 693,329 554,663 87% 16 762,662 610,130 95% 17 799,995 639,996 100%
SPREADER BARS
(3 PLACES)
If a unit is to be installed on a roof curb other than a York roof curb, gasketing must be applied to all sur­faces that come in contact with the unit underside.
If a unit is to be installed on an angle iron frame it is recommended that it be sized to allow the bottom rail to overhang to facilitate installation of conden­sate drains (see Fig. 4).
RIGGING:
27”
CABLES
(1) RIG WITH SIX CABLES AND THREE SPREADER BARS AT LEAST 98” ACROSS THE WIDTH OF THE UNIT.
(2) CENTER OF GRAVITY INCLUDES ECONOMIZER AND POWER EXHAUST.
ALL PANELS MUST BE SECURED IN PLACE WHEN THE UNIT IS LIFTED.
32”

FIGURE 2 - TYPICAL RIGGING

10 Johnson Controls Unitary Products
882108-YIM-B-1012
TABLE 8: UNIT WEIGHTS
COMPONENT 25 TON 30 TON 40 TON
Basic Unit 4410 4565 4845
Gas Heat
267 MBH 180 180 180 533 MBH 320 320 320 800 MBH - - 450
Electric Heat
40KW 40 40 40 80KW 105 105 105
108KW 110 110 110
Hot Water Heat
1 Row Coil 70 70 70 2 Row Coil 85 85 85
Steam Heat
1 Row Coil 85 85 85
Blower
Forward Curve Fan (Std Fan) 0 0 0
FC IGV 155 155 175
Air Foil Fan 135 135 155
AF IGV 155 155 180
Motor - Supply Fan
7.5hp 110 - ­10hp 145 145 145 15hp 200 200 200 20hp 240 240 240 25hp - 300 300
Supply Fan Motor VFD See Table 9
Refrigeration
T-Coat Evap. 32 30 40 T-Coat cond. 32 30 40
Hot Gas Bypass 10 10 10
Low Ambient Head Pressure Control
208-230/380/460 5 5 5
575 25 25 25
Filters
6" Rigid 70 70 70
Exhaust
Exhaust Type
Barometric 45 65 65
Modulated 140 275 275
Exhaust Motor
5hp 80 80 80
7.5hp 110 110 110 10hp 145 145 145 15hp 200 200 200
Exhaust Motor VFD See Table 10
Economizer
Std. Econ. 235 235 235
Econ. w/ERV 50 50 50
Disconnect 15 15 15 110V outlet 55 55 55
Optilogic 20 20 20
Roof Curb
Partial Curb 415 415 415
1.
If ERV and Supply Fan VAV are selected, add the weight of an Exhaust VFD, Table 9.
1
Control
TABLE 9: SUPPLY FAN MOTOR VFD WEIGHTS
Supply Fan Motor VFD 230V 460V 575V
W/O Bypass
7.5hp 60 25 30 10hp 60 25 30 15hp 75 50 60 20hp 75 50 60 25hp 115 50 60
W/Bypass
7.5hp 155 90 120 10hp 155 90 120 15hp 185 140 155 20hp 185 140 155 25hp 255 140 155
TABLE 10: EXHAUST FAN MOTOR VFD WEIGHTS
Exhaust Fan Motor 230V 460V 575V
W/O Bypass
5hp 15 10 20
7.5hp 50 15 20 10hp 50 15 20 15hp 65 40 50
NOTE: If the Millennium is VAV with ERV, add the weight of an exhaust VFD - it will be in the unit.
.
REAR
B
92”

FIGURE 3 - CENTER OF GRAVITY

1.
Refer to Tables 11 and 12 for A, B, C, D and X and Y data respectively.
CENTER OF GRAVITY
Y
A
C
240”
RIGHT END CONDENSER COILS
D
X
FRONT
1
Johnson Controls Unitary Products 11
882108-YIM-B-1012
All panels must be secured in place when the unit is lifted.
The condenser coils should be protected from damage by the rigging cables with plywood or other suitable material.

RIGGING AND HANDLING

This unit is not designed to be handled with a fork-truck.
Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching cable slings to the lifting lugs provided in the unit base rails. Spreaders MUST be used across the top of the unit. Refer to Figure 2.
An adhesive backed cover is provided over the outside of the combustion air inlet opening on gas
Rig with six cables and spread with three 98-inch spreaders across width of unit.
fired units to prevent moisture from entering the unit which could cause damage to electrical com­ponents. Allow this closure label to remain in place until the combustion air hood is to be installed (Refer to Figures 7).
Refer to Tables 8 and 11 for unit weight.
Center of gravity includes economizer, exhaust or return air fan (Refer to Table 12).
TABLE 11: UNIT CORNERWEIGHT
UNIT
DESCRIPTION
Basic Unit 870 949 1352 1239 930 972 1360 1303 969 969 1454 1454
Basic Unit With
Economizer
Basic Unit With
Economizer and
Gas or Electric Heat
Basic Unit With
Economizer and
Gas or Electric Heat
and Power Exhaust
NOTES: Basic Unit = cooling only, 10hp FC fan.
+ Econ = +235lb + Heat = single stage gas, 180 lb + Power Exhaust = modulating 7.5hp
ABCDAB CDABCD
1018 1111 1313 1203 1076 1124 1328 1272 1058 1058 1482 1482
994 1084 1418 1300 1073 1073 1403 1403 1102 1055 1503 1570
1220 1275 1318 1262 1275 1275 1410 1410 1335 1278 1485 1551
TABLE 12: UNIT CENTER OF GRAVITY
MODEL
Basic Unit 99” 48” 100” 47” 96” 46"
Basic Unit /w
Econ.
Basic Unit /w
Econ. & Gas or
Elect. Heat,
Steam or Hot
Water Heat
Basic Unit /w
Econ. & Gas or
Elect. Heat, &
Power Exhaust
25 TON 30 TON 40 TON
XYXYXY
110” 48” 110” 47” 100” 46"
104” 48” 104” 46” 99” 45"
118” 47” 114” 46” 111” 45"
25 TON 30 TON 40 TON

CLEARANCES

All units require certain clearances for proper operation and service. Installer must make provisions for adequate combus­tion and ventilation air in accordance with section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149 installation codes-Latest Edition and/or applicable provisions of the local building codes. required for combustible construction, servicing, and proper unit operation.
Refer to Figure 8 for clearances
(COOLING OPERA TION) Do not permit overhang­ing structures or shrubs to obstruct condenser air discharge outlet, combustion air inlet or vent out­lets.
12 Johnson Controls Unitary Products
882108-YIM-B-1012
When the unit is equipped with power exhaust fans or return air fan the return duct should have a 90 elbow before opening to the building space to abate noise.
(GAS HEATING OPERATION) Excessive exposure to contaminated combustion
air will result in safety and performance related problems. To maintain combustion air quality, the recommended source of combustion air is the out­door air supply.
The outdoor air supplied for combustion should be free from contaminants due to chemical exposure that may be present from the following sources:
Commercial buildings
Indoor pools
Laundry rooms
Hobby or craft rooms
Chemical storage areas The following substances should be avoided to
maintain outdoor combustion air quality:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool cleaners
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
The supply and return air duct systems should be designed for the CFM and static pressure requirements of the job. They should NOT be sized to match the dimensions of the duct connections on the unit.
If the unit is equipped with hot water or steam heat then the supply air direction will be down only.

AIR HOODS FOR FIXED OUTSIDE AIR (UNITS WITH MANUAL ECONOMIZER)

These hoods are factory installed. The dampers may be adjusted by loosening the thumb screw, turning the lever to the desired position, and retightening the thumb screw.

AIR HOODS FOR ECONOMIZER

There are (3) economizer outside air intake hoods provided with the unit. The hood on the end of the unit is factory mounted. The (2) front and rear hoods are made operational per the following instructions.
Remove the screws holding the economizer hood shipping covers in place. Discard covers.
Rotate the hoods out (each hood is hinged in the lower cor­ner). Secure the hoods with screws along the top and sides.
Apply a bead of RTV sealer along the edge of both hoods and each pivot joint to prevent water leakage.
Seal any unused screw holes with RTV or by replacing the screw.

AIR HOODS FOR EXHAUST AIR

When furnished, these hoods and dampers are factory

DUCTWORK

Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of
America (ACCA). A closed return duct system should be used. This will not pre-
clude use of economizers or outdoor fresh air intake. The supply and return air duct connections at the unit should be made with flexible joints to minimize noise.
Johnson Controls Unitary Products 13
installed.

CONDENSATE DRAIN

There is one condensate drain connection. Trap the connec­tion per Figure 4. The trap and drain lines should be pro­tected from freezing.
Plumbing must conform to local codes. Use a sealing com­pound on male pipe threads. Install condensate drain lines from the 1-1/2 inch NPT female connections on the unit to an open drain.
882108-YIM-B-1012
D R A I N C O N N E C T I O N
F A C T O R Y I N S T A L L E D
H

FILTERS

U N I T B A S E
Y
R O O F C U R B
O R
P E R I M E T E R
S U P P O R T
S T R U C T U R E
F I E L D S U P P L I E D
Throwaway or rigid filters are supplied with each unit. Filters must always be installed ahead of evaporator coil and must be kept clean or replaced with same size and type. Dirty fil­ters will reduce the capacity of the unit and will result in frosted coils or safety shutdown. Required filter sizes are shown in Table 15. The unit should not be operated without filters properly installed.

THERMOSTAT (CONSTANT VOLUME UNITS)

Y - M I N I M U M 2 " H - 1 / 2 " P L U S T O T A L S T A T I C P R E S S U R E - M I N I M U M
FIGURE 4 - RECOMMENDED DRAIN PIPING SERVICE ACCESS
Access to all serviceable components is provided by the fol­lowing hinged doors:
Furnace compartment
Supply Air Fan compartment Evaporator Coil compart­ment (three doors)
Filter compartment economizer compartment (two doors)
Power Exhaust compartment (two doors)
Main control panels (one door)
Refer to Figure 1 for location of these access panels.
Make sure that all screws and panel latches are replaced and properly positioned on the unit to maintain an air-tight seal.
T 7 3 0 0 T H E R M O S T A T S U B B A S E
R C G Y 1 Y 2 Y 3 Y 4 W 1 W 2 A 1 C T T
R E M O T E
2 T H O 4 7 0 2 2 2 4
S E N S O R
R
Y 1
G
Y 2
Y 3
Y 4
W 1
W 2
A 1
C
L 1
A
P O W E R S U P P L Y
P O W E R W I R I N G
L 2 L 3
T B 1
B
E Q U I P . G N D .
C

FIGURE 5 - TYPICAL THERMOSTAT WIRING

The thermostat, if used, should be located on an inside wall approximately 56 inches above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with sensor for general installation procedure (See Figure 5). Refer to Table 13 for control wire sizing and maximum length.
TABLE 13: CONTROL WIRE SIZES
WIRE SIZE MAXIMUM LENGTH
20 AWG 100 Feet

COMPRESSORS

18 AWG 150 Feet
Units are shipped with compressor mountings factory­adjusted and ready for operation.
DO NOT loosen compressor mounting bolts.
14 Johnson Controls Unitary Products

SPACE SENSOR (VARIABLE AIR VOLUME UNITS)

The space sensor, if used, should be located on an inside wall approximately 56 inch above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with sensor for general installation procedure.
882108-YIM-B-1012

POWER AND CONTROL WIRING

Field wiring to the unit must conform to provisions of National Electrical Code (NEC) ANSI / NFPA 70-Latest Edition and / or local ordinances. The unit must be electrically grounded in accordance with the NEC and / or local codes. Voltage toler­ances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 1.
The internal wiring harnesses furnished with this unit are an
integral part of the design certified unit. Field alteration to comply with electrical codes should not be required. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram and the same minimum gauge as the replaced wire.
Power supply to the unit must be NEC Class 1 and must comply with all applicable codes. A disconnect switch must be provided (factory option available). The switch must be separate from all other circuits. Wire entry at knockout open­ings requires conduit fittings to comply with NEC and/or Local Codes. Refer to Figures 11, 12, 13, and 14 for installation location of openings.
If installing a field mounted disconnect on the unit, refer to Figure 15 for the recommended mounting location. Unitstrut™ or equivalent rails should be mounted as shown to provide structure for mounting. The location of the rails should be adjusted to fit the disconnect within the dimensions shown. Conduit run from the disconnect to the power entry location in the baserail should be routed so that it does not interfere with the doors of the unit access panels.
Refer to Figure 5 for typical field wiring and to the appropriate unit wiring diagram mounted inside control doors for control circuit and power wiring information.

POWER WIRING DETAIL

Units are factory wired for the voltage shown on the unit nameplate. The main power block requires copper wires. Refer to Electrical Data Tables 17 through 28 to size power wiring, fuses and disconnect switch. All field supplied wiring, fuses and disconnects must comply with applicable NEC codes.
Power wiring is brought into the unit through the side of the baserail or the bottom of the unit/control box inside the curb. The baserail has a 2-1/2” diameter hole for field wiring and a 3-5/8” hole is provided for a through-the-curb connection. A removable patch plate covers both the openings.
Waterproof connections MUST be used to ensure that water cannot penetrate the roof or roof curb.
ERV
The ERV [Energy Recovery Ventilation] is a separate air han­dler that attaches to the exhaust end of the 25-40T Millen­nium packaged rooftop unit. The ERV is shipped separately and assembled to the Millennium at the jobsite. An 'ERV' Mil­lennium is shipped with an end configuration and electric hookups designed to mate with the ERV. This option is avail­able only with the Simplicity® control, and no other power exhaust option can be supplied if an ERV is selected.
Use care to avoid damage when drilling holes for the disconnect mounting.
NOTE: Since not all local codes allow mounting a discon-
nect on the unit, please confirm compliance with local code before mounting a disconnect on the unit.
Electrical wiring must be sized properly to carry the load. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.
When connecting electrical power and control wir­ing to the unit, waterproof connectors MUST BE USED so that water or moisture cannot be drawn into the unit during normal operation. The above waterproofing conditions will also apply when installing a field-supplied disconnect switch.
Johnson Controls Unitary Products 15
The ERV incorporates a rotating heat exchange wheel and a pair of exhaust blowers. It exhausts return air through the wheel, capturing the thermal energy of the exiting hot or cold air as it passes. As the wheel rotates, the incoming airstream, pulled through by the supply fan, regains that energy.
The Millennium ERV has a terminal block and mating con­nectors to simplify hooking up the two systems. The controls of both units are factory set to interact properly . Power for the ERV blower motors and controls is provided through the Mil­lennium unit. The Millennium /ERV dataplate information includes the ERV electrical load.
The Millennium Simplicity® control has parameters for the ERV; refer to the parameter list. When economizer and ERV options are selected on the same unit, the Simplicity® control and the ERV have specific connections and internal rules for that operation.
Also refer to the ERV Installation Instructions packaged with the ERV.
882108-YIM-B-1012

GAS HEATING

On VAV units with gas fired furnace, ALL INDIVID­UAL ROOM DAMPER BOXES MUST BE CON­TROLLED FULL OPEN DURING HEATING OPERATION TO ENSURE PROPER AIRFLOW OVER THE FURNACE. A control contact powered by the “VAV OPEN” terminals on the Simplicity® control is provided for the damper box interlock. this contact is normally open, and is closed during heating operation.

GAS PIPING

Proper sizing of gas piping depends on the cubic feet per hour of gas flow required, specific gravity of the gas and the length of run. National Fuel Gas Code Z223.1-Latest Edition should be followed in all cases unless superseded by local codes or gas company requirements. Refer to Table 14.
The heating value of the gas may differ with locality. The value should be checked with the local gas utility.

FIGURE 6 - TYPICAL GAS PIPING CONNECTION

Gas piping recommendations:
1. A drip leg and a ground joint union must be installed in the gas piping.
2. When required by local codes, a manual shut-off valve will have to be installed outside of the unit.
3. Use wrought iron or steel pipe for all gas lines. Pipe dope should be applied sparingly to male threads only.
TABLE 14: PIPE SIZES
LENGTH IN
FEET
10 1,050 1,600 3,050 20 730 1,100 2,100 30 590 890 1,650 40 - 760 1,450 50 - - 1,270 60 - - 1,150 70 - - 1,050 80 - - 990
1.
Maximum capacity of pipe in cubic feet of gas per hour (based upon a pressure drop of 0.3 inch water column and 0.6 specific gravity gas.
NOTE: There may be a local gas utility requirement specify-
ing a minimum diameter for gas piping. All units require a 1-1/4 inch pipe connection at the entrance fitting. Line should not be sized smaller than the entrance fitting size.
NOMINAL IRON PIPE, SIZE
1-1/4 IN.
1
1-1/2 IN.
1
2 IN.
1

GAS CONNECTION

The gas supply line should be routed within the space and penetrate the roof at the gas inlet connection of the unit. Refer to Figures 11 through 14 to locate the access opening. Typical supply piping arrangements are shown in Figure 6.
Natural gas may contain some propane. Propane, is an excellent solvent and will quickly dissolve white lead or most standard commercial pipe seal­ing compounds. Therefore, special shellac base pipe dope compounds such as Gaskolac or Stalas­tic, and compounds such as Rectorseal #5, Clyde’s or John Crane must be applied for wrought iron or steel pipe.
4. All piping should be cleaned of dirt and scale by ham­mering on the outside of the pipe and blowing out the loose particles. Before initial start-up, be sure that all of the gas lines external to the unit have been purged of air.
5. The gas supply should be a separate line and installed in accordance with all safety codes as prescribed under Limitations. After the gas connections have been com­pleted, open the main shutoff valve admitting normal gas pressure to the mains. Check all joints for leaks with soap solution or other material suitable for the purpose. NEVER USE A FLAME.
6. The furnace and its individual manual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pres­sures in excess of 0.5 psig.
16 Johnson Controls Unitary Products
Disconnect gas piping from unit when leak testing at pressures greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in a hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced.
882108-YIM-B-1012

VENT AND COMBUSTION AIR

NOTE: All the hoods and hardware are shipped within the
evaporator section. Each hood must be properly attached to the furnace doors to assure proper operation and compliance with CSA/ETL safety cer­tification. (Refer to Figure 7.)
The products of combustion are discharged horizontally through hooded openings in the gas heat access doors.
7. A 1/8 inch N.P.T. plugged tapping, accessible for test gage connection, must be installed immediately upstream of the gas supply connection to the furnace.
EXHAUST VENT OUTLET
COMBUSTION AIR INLET
VENT FLUE ASSEMBLY
REMOVE SHIPPING LABELS PRIOR TO VENT INSTALLATION
HEAT SECTION DOOR
FIGURE 7 - VENT AND COMBUSTION AIR
HOODS
(Figure 7)
1. Remove the shipping covers that are attached to the heat section door covering the flue outlets.
2. Locate the flue which is shipped in the evaporator sec­tion.
3. Place the flue over the flue outlet and attach with screws provided.
4. Refer to the Gas Furnace Operation Instruction in the Start-up Section of this manual for further instructions.
10'
RIGHT
END
60"
60"
REAR
60"
FRONT
LEFT
END
60"
* Front is the side with access to the Electrical/Gas Controls
LEFT RIGHT
REAR
FRONT
TOP
60" 60" 60" 60" 10'
NOTE: DO NOT use the unit roof to support any type of structure bracing.

FIGURE 8 - CLEARANCES

Johnson Controls Unitary Products 17
882108-YIM-B-1012

ELECTRIC HEAT

Units with electric heat are fully wired and operational when shipped. Constant volume units are designed for two equal steps of capacity for 80 and three for 108 kWH heat; 40 kW heat is one step only . Heat outputs on VA V units are all turned on together at full heat capacity.

HOT WATER HEAT

The YORK Millennium units (25, 30, and 40 Ton sizes) can be furnished with a YORK hot water coil as the heat source. One or two row coil units will be factory installed in the heating section.
NOTE: The hot water control valve will not be provided. The
installer will need to provide a hot water control valve, to connect the hot water piping and power wiring at the job site for the hot water heat section to be operational.
There are no provisions in the coil or control sequence to prevent freezing of condensate. The control valve, piping and field installed wiring con­nections are particularly vulnerable because they are installed in the vestibule outside of the condi­tioned air stream. The installing party will be responsible for properly insulating and installing power and control wiring, to the actuator and pip­ing.
In one row hot water coil systems DO NOT exceed a 40 gallons per minute flow rate.
In two row hot water coil systems DO NOT exceed an 80 gallons per minute flow rate.
Condensate will freeze on the control valve and piping if they are not properly insulated. Insulating the control valve and piping is the responsibility of the installing party.
DO NOT use hot water coils as steam coils under any circumstances.
All piping, control valves, and wiring that is field installed must be properly insulated and conform to all local and national codes.
NOTE: For all hot water coils the entering water tempera-
ture should not exceed 200°F.
The hot water coil is located downstream of the supply air fan and just above the supply air opening in the bottom of the unit.
Refer to Tables 50 through 58 and Figures 27 through 40 for flow rate and capacity.

PIPING CONNECTIONS

The hot water piping must enter the unit through the floor of the heat section compartment. The access doors to the com­partment are gasketed so the compartment can be sealed. However, as added protection for water leakage into the space, the piping access holes should be sealed with a heat resistant mastic Figure 9 shows the location of the compart­ment and piping connections.
Piping access holes should be sealed with a heat resistant mastic to prevent damage to equipment.
18 Johnson Controls Unitary Products
882108-YIM-B-1012
DO NOT use tin based solder. Brazing with tin based solder could cause equipment damage or possible injury to tenants of the structure that is being conditioned.
( 1 O R 2 R O W )
C O N D E N S I N G
S E C T I O N
8 8 . 7 5 "
O U T S I D E O F
B A S E R A I L
1 5 . 8 "
1 1 . 8 8 "
H E A T S E C T I O N
C O M P A R T M E N T
2 . 2 5 "
H O T W A T E R
C O I L
2 6 "
I N L E T ( 2 " )
C
L
O U T L E T ( 2 " )
8 . 3 8 "
2 . 5 5 "
FIGURE 9 - HOT WATER PIPING CROSS-SEC-
TION

STEAM HEAT

The YORK Millennium units (25, 30 and 40 Ton sizes) can be
furnished with a YORK single row steam coil. YORK steam coils are a factory installed option.
T O P V I E W
C O N D E N S I N G
S E C T I O N
O U T S I D E O F
B A S E R A I L
1 5 . 8 "
S T E A M
C O I L
2 6 "
O U T L E T ( 1 1 / 2 " )
I N L E T ( 2 " )
8 "
8 . 3 8 "
All piping and control valves, and wiring that is
field installed must be properly insulated and con­form to all local and national codes.
There are no provisions in the coil or control sequence to prevent freezing of condensate. The control valve, piping and field installed wiring con­nections are particularly vulnerable because they are installed in the vestibule outside of the condi­tioned air stream. The installing party will be responsible for properly insulating and installing power and control wiring, to the actuator and pip­ing.
DO NOT use steam coils as hot water coils under any circumstances.
In steam coil systems, the steam pressure shall not exceed 15 PSI.

PIPING CONNECTIONS

Refer to Tables 46 through 49 and Figures 41 and 42 for flow rate and capacity.
The steam piping must enter the unit through the floor of the heat section compartment. The access doors to the compart­ment are gasketed so the compartment can be sealed. How­ever, as added protection for condensate leakage into the space, the piping access holes should be sealed with a heat resistant mastic. The following figure illustrates the location of the compartment and piping connections.
2 . 5 5 "
C
L
8 8 . 7 5 "
Piping access holes should be sealed with a heat resistant mastic to prevent damage to equipment.
H E A T S E C T I O N
C O M P A R T M E N T
9 "

FIGURE 10 - STEAM PIPING CROSS-SECTION

NOTE: The steam control valve, power and control wiring to
the actuator of the valve is the responsibility of the installing party.
Johnson Controls Unitary Products 19
DO NOT use tin based solder. Brazing with tin based solder could cause equipment damage or possible injury to tenants of the structure that is being conditioned.
882108-YIM-B-1012

STATIC PRESSURE CONTROL PLASTIC TUBING

On units with variable frequency drives (VFD’s) or inlet guide vanes (IGV's) on the supply blower and/or power exhaust fans, pressure sensing tubing must be field supplied and installed. All tubing must be installed from the transducers (located in the unit) to the location in the building (or ductwork) where a constant pressure is desired. The tubing must also be installed from the transducers to a low-side ref­erence to the atmosphere.
The supply air duct pressure sensor (DPS) is located in the control box directly below the Millennium Simplicity® control. Plastic tubing (1/4”) must be run from the high pressure tap of the transducer to a static pressure tap (field supplied) in the supply duct located at a point where constant pressure is desired. Tubing must also be run between the low pressure tap of the transducer to atmospheric pressure. Changing the adjustment is done to the duct pressure setpoint in the con­trol.

EXHAUST STATIC PRESSURE

If a modulating-damper or variable frequency drive power exhaust is installed, there will be a building pressure sensor (BPS) in the control box directly below the Millennium Sim- plicity® control. This ± .25 0-5VDC transducer sends a build­ing pressure signal to the control. A sensing tube must be installed from a representative location in the building to the HI port of the transducer. Tubing must also be run between the low pressure tap of the transducer to atmospheric pres­sure.
Changing the adjustment is done to the building pressure set­point in the control.
Do not run plastic tubes in the supply or return air ducts as air movement could cause erroneous sensing. If tubes penetrate bottom of unit be sure openings are sealed against air and water leak­age.
20 Johnson Controls Unitary Products
64"
RETURN AIR
SUPPLY AIR
92"
REAR
DETAIL
FRONT
SEE
B
SEE
DETAIL
C
882108-YIM-B-1012
RIGHT END
72.25”
99.5”
131.5”
LEFT END
4-5/8”
1-1/2" FPT
DETAIL A
(DRAIN CONNECTION)
LEFT END
80.93"
4.5"
BASE RAIL
83"
REAR
4.5"
SEE
71.61"
26"
DETAIL
A
38.59"
6.46"
127.5"
FRONT
C
4.5"
BASE RAIL
DETAIL B
(ELECTRICAL CONNECTION)
FOR COOLING ONLY AND ALL HEATING APPLICATIONS
L
2.31”
Ø 2-1/2”
OPEN
3.625"
240"
3-5/8"
6.45"
15.89"
RIGHT END
2-1/2”
DIA. HOLES
12"
MIN
C
L
28”
1-1/4” NPT
(GAS CONNECTION
THROUGH CURB)
88.7 "
7”
DETAIL C
TO GAS VALVE
MANIFOLD
11”

FIGURE 11 - BOTTOM SUPPLY AND RETURN

Johnson Controls Unitary Products 21
882108-YIM-B-1012
LEFT END
RETURN AIR
SUPPLY AIR
7-7/8”
64"
LEFT END
76-3/8”
92"
8
0.93"
REAR
REAR
24.9”
SEE
DETAIL
A
"
6.25”
FRONT
4.5"
71.61"
SEE
DETAIL
B
6.46"
SEE
DETAIL
C
3.625"
26"
FRONT
240"
NOTE: FACTORY INSTALLED POWER EXHAUST CANNOT BE ORDERED WITH END RETURN.
RIGHT END
72.25”
99.5”
131.5”
RIGHT END
OPEN
12"
MIN
15.89"
C
L
88.7"
4-5/8”
BASE RAIL
1-1/2" FPT
BASE RAIL
DETAIL A
(DRAIN CONNECTION)
(ELECTRICAL CONNECTION)
FOR COOLING ONLY AND ALL HEATING APPLICATIONS

FIGURE 12 - END RETURN, BOTTOM SUPPLY

2-1/2"
DETAIL B
2.31”
3-5/8"
6.45"
2-1/2”
DIA. HOLES
28”
1-1/4” NPT
7”
DETAIL C
(GAS CONNECTION
THROUGH CURB)
TO GAS VALVE
MANIFOLD
11”
22 Johnson Controls Unitary Products
FRONT SUPPLY: FOR COOLING ONLY APPLICATIONS REAR SUPPLY: FOR COOLING ONLY OR GAS HEAT APPLICATIONS
882108-YIM-B-1012
FRONT
64"
RETURN AIR
SUPPLY AIR
REAR
92"
LEFT END
80.93"
4.5"
REAR
RIGHT END
26"
55"
72.25”
99.5”
FRONT
SEE
DETAIL
B
8.15"
SEE
DETAIL
C
131.5”
RIGHT
END
REAR
OPEN
SEE
DETAIL
A
6.46"
3.625"
12"
MIN
38.59"
FRONT
4.5"
2.31”
BASE RAIL
2-1/2"
DETAIL B
(ELECTRICAL CONNECTION)
FOR COOLING ONLY AND ALL HEATING APPLICATIONS
240"
2-1/2”
DIA. HOLES
3-5/8"
6.45"
28”
1-1/4” NPT
DETAIL C
(GAS CONNECTION
THROUGH CURB)
TO GAS VALVE
MANIFOLD
7”
11”
LEFT END
4-5/8”
BASE RAIL
1-1/2" FPT
DETAIL A
(DRAIN CONNECTION)
83"

FIGURE 13 - BOTTOM RETURN, FRONT & REAR SUPPLY

Johnson Controls Unitary Products 23
882108-YIM-B-1012
FRONT SUPPLY: FOR COOLING ONLY APPLICATIONS REAR SUPPLY: FOR COOLING ONLY OR GAS HEAT APPLICATIONS
RETURN AIR
SUPPLY AIR
REAR
REAR
26
26"
FRONT
"
55"
64”
7-7/8”
76-3/8”
92”
LEFT END
8 0 . 9 3 "
LEFT END
24.9”
6.25”
REAR
SEE
DETAIL
A
SEE
DETAIL
B
FRONT
6 . 4 6 "
26"
55"
8.15"
DETAIL
3 . 6 2 5 "
FRONT
2 4 0 "
SEE
C
131.5”
OPEN
72.25”
99.5”
RIGHT END
1 2 "
M I N
2-1/2”
DIA. HOLES
RIGHT END
TO GAS VALVE
MANIFOLD
3-5/8"
4-5/8”
BASE RAIL
1-1/2" FPT
DETAIL A
(DRAIN CONNECTION)
6.45"
BASE RAIL
2.31”
2-1/2"
DETAIL B
(ELECTRICAL CONNECTION)
FOR COOLING ONLY AND ALL HEATING APPLICATIONS
28”
1-1/4” NPT
(GAS CONNECTION
THROUGH CURB)
7”
11”
DETAIL C

FIGURE 14 - END RETURN, FRONT & REAR SUPPLY

24 Johnson Controls Unitary Products
TABLE 15: GENERAL PHYSICAL DATA
UNIT SIZE 25 TON 30 TON 40 TON
NIT EER / IPLV
U
(S
TANDARD CAPACITY EVAPORATOR)
10.5 / 12.3
C
OMPRESSOR DATA
NUMBER/SIZE 4 x 5.7Ton 4 x 7 Ton 4 x 8.6 Ton
YPE Scroll Scroll Scroll
T
NIT CAPACITY STEPS 25%, 50%, 75%, 100% 25%, 50%, 75%, 100% 25%, 50%, 75%, 100%
U
NDOOR FAN AND DRIVE
I
NUMBER / TYPE 1 / FC 1 / FC 1 / FC
IAMETER X WIDTH (INCHES) 22 x20 22 x 20 25 x 22
D
CFM R
ANGE 7.5 - 20 10 - 25 10 - 25
HP R
ANGE (FULL LOAD) 6,000 - 12,500 6,000 - 15,000 8,000 - 18,000
ANGE 0.2” - 4.0” 0.2" - 4.0” 0.2" - 4.0"
ESP R
XHAUST FAN
E
NUMBER/SIZE/TYPE 1/FC 2/FC 2/FC
ANGE (SINGLE MOTOR) 5 - 10 7.5 - 15 7.5 - 15
HP R
CFM 3,000 - 9,000 4,000 - 15,000 4,000 - 18,000
VAPORATOR COIL
E
SIZE (SQ. FT.) 26.0 26.0 30.4
OWS/FPI 3 / 16 4 / 16 4 / 16
R
ONDENSER COIL
C
SIZE (SQ. FT.) 65 78 104
OWS/FPI 2/16 2 /16 2 /16
R
ONDENSER FANS
C
QUANTITY / DIAMETER (INCHES) 4 / 24 4 / 24 4 / 30
OMINAL CFM 6,800 7,200 9,600
N
OTOR HP 1.0 1.5 1.5
M
K
W RANGE 40 - 108 40 - 108 40 - 108
KW / CAPACITY STEPS (CV/VAV) 111
40
KW / CAPACITY STEPS (CV/VAV) 2 / 1 2 / 1 2 / 1
80
108
KW / CAPACITY STEPS (CV/VAV)
LECTRIC HEAT
E
3 / 1
2
NATURAL GAS HEAT
UNIT SIZE 25 TON 30 TON 40 TON 267 MBH C 533 MBH C 800 MBH C
APACITY STEPS (CV/VAV) 1 / 1 1 / 1 1 / 1 APACITY STEPS (CV/VAV) 2 / 1 2 / 1 2 / 1 APACITY STEPS (CV/VAV) --
267 MBH “MODULATING” CAPACITY STEPS (CV ONLY) 6 / 1 6 / 1 6 / 1 533 MBH “M 800 MBH “M
ODULATING” CAPACITY STEPS (CV ONLY) 12 / 2 12 / 2 12 / 2 ODULATING” CAPACITY STEPS (CV ONLY) - - 17 / 3
OT WATER COIL
H
SIZE (INCHES) 22.5” x 65” 22.5" X 65” 22.5" X 65”
APACITY 25 T on 30 Ton 40 Ton
C
TEAM COIL
S
SIZE (INCHES) 21" X 65"
YPE Steam Coil
T
UMBER / SIZE 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25
N
ACE AREA (SQ. FT.) 30.4 30.4 30.4
F
UMBER / SIZE 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25
N
ACE AREA (SQ. FT.) 30.4 30.4 30.4
F
ILTERS 65% RIGID W/ 2” TA PREFILTERS
F
ILTERS 2" TA
F
ILTERS 2" PLEATED, 30%
F
NUMBER / SIZE 4 / 16 x 25 & 6 / 20 x 25 4 /16 x 25 & 6 / 20 x 25 4 / 16 x 25 & 6 / 20 x 25
ACE AREA (SQ. FT.) 30.4 30.4 30.4
F
ILTERS 95% RIGID W/ 2” TA PREFILTERS
F
NUMBER / SIZE 4 ea. 16 x 25 / 6 ea. 20 x 25 4 ea. 16 x 25 / 6 ea. 20 x 25 4 ea. 16 x 25 / 6 ea. 20 x 25
ACE AREA (SQ. FT.) 30.4 30.4 30.4
F
1.
Cooling Only Unit Efficiency/ Gas Electric Unit Efficiency is 10.0
2.
Unit Control Board with 3 heating outputs only, all other Unit Control Boards 2 / 1.
10.1
1
3 / 1
/ 11.0
2
882108-YIM-B-1012
10.5 / 11.2
2
3 / 1
2
3 / 1
Johnson Controls Unitary Products 25
882108-YIM-B-1012
TABLE 16: REFRIGERANT FACTORY CHARGE R-410A
UNIT (TONS) MODEL
SYSTEM #1 SYSTEM #2 SYSTEM #3 SYSTEM #4
25 wo/HGBP 13lb 8oz 12lb 8oz 12lb 8oz 12lb 8oz 25 w/HGBP 14lb 12lb 8oz 12lb 8oz 12lb 8oz 30 wo/HGBP 16lb 16lb 8oz 14lb 18lb 4oz 30 w/HGBP 16lb 8oz 17lb 14lb 8oz 18lb 12oz 40 wo/HGBP 17lb 10oz 17lb 10oz 19lb 13oz 19lb 13oz 40 w/HGBP 18lb 2oz 18lb 2oz 20lb 5oz 20lb 5oz
TABLE 17: ELECTRICAL DATA 25 TON BASIC UNIT R-410A
Voltage
208-3-60 4 22.4 149 35 4 4.5
230-3-60 4 22.4 149 35 4 4.3
460-3-60 4 10.6 75 16.5 4 2.15
575-3-60 4 7.7 54 12 4 1.7
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC.
Compressors (each) OD Fan Motors
Qty RLA LRA MCC Qty FLA HP FLA
Supply Blower
7.5 24.2 138 150 10 30.8 146 175 15 46.2 165 200 20 59.4 182 225
7.5 22 134 150 10 28 142 150 15 42 159 200 20 54 174 225
7.5 11 65 70 10 14 69 80 15 21 77 90 20 27 85 110
7.5 9 49 50 10 11 51 60 15 17 59 70 20 22 65 80
Motor
CHARGE
MCA
(Amps)
1
Max Fuse2/
Breaker
Size
(Amps)
3
26 Johnson Controls Unitary Products
TABLE 18: ELECTRICAL DATA 30 TON BASIC UNIT R-410A
Voltage
Compressors (each) OD Fan Motors
Qty RLA LRA MCC Qty FLA HP FLA
208-3-60 4 25.0 164 39 4 5.8
230-3-60 4 25.0 164 39 4 5.8
460-3-60 4 12.0 100 19 4 2.9
575-3-60 4 9.0 78 14 4 2.2
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC.
Supply Blower
10 30.8 162 175 15 46.2 181 225 25 74.8 217 250 20 59.4 197 250 10 28 158 175 15 42 176 200 25 68 208 250 20 54 191 225 10 14 77 90 15 21 86 100 20 27 93 110 25 34 102 125 10 11 59 60 15 17 66 80 20 22 72 90 25 27 79 100
Motor
MCA
(Amps)
1
Max Fuse2/
Breaker
Size
(Amps)
882108-YIM-B-1012
3
TABLE 19: ELECTRICAL DATA 40 TON BASIC UNIT R-410A
Voltage
Compressors (each) OD Fan Motors
Qty RLA LRA MCC Qty FLA HP FLA
208-3-60 4 30.1 255 47 4 5.8
230-3-60 4 30.1 255 47 4 5.8
460-3-60 4 16.7 114 26 4 2.9
575-3-60 4 12.2 80 19 4 2.2
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC.
Supply Blower
10 30.8 182 200 15 46.2 201 225 20 59.4 218 250 25 74.8 237 300 10 28 179 200 15 42 196 225 20 54 211 250 25 68 229 250 10 14 97 110 15 21 105 125 20 27 112 125 25 34 121 150 10 11 72 80 15 17 79 90 20 22 85 100 25 27 91 110
Motor
MCA
(Amps)
1
Max Fuse2/
Breaker
Size
(Amps)
3
Johnson Controls Unitary Products 27
882108-YIM-B-1012
TABLE 20: ELECTRICAL DATA 25 TON W/ELECTRIC HEAT R-410A
Compressors
Voltage
(each)
Qty RLA LRA MCC FLA HP FLA Option KW Applied Stages Amps
208-3-60 4 22.4 149 35 4.5
230-3-60 4 22.4 149 35 4.3
460-3-60 4 10.6 75 16.5 2.15
575-3-60 4 7.7 54 12 1.7
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC.
OD Fan Motors
(each)
Supply Blower
Motor
Electric Heat Option
7.5 24.2 10 30.8 146 175 15 46.2 165 200
E4 40 30 1 83
20 59.4 182 225
7.5 24.2 10 30.8 205 225 15 46.2 225 250
E8 80 60 2 167
20 59.4 241 300
7.5 22 10 28 150 150 15 42 168 200
E4 40 36.8 1 92
20 54 183 225
7.5 22 10 28 220 250 15 42 237 250
E8 80 73.6 2 184
20 54 252 300
7.5 11 10 14 75 80 15 21 84 90
E4 40 36.8 1 46
20 27 91 110
7.5 11 10 14 110 125 15 21 119 125
E8 80 73.6 2 92
20 27 126 150
7.5 11 10 14 142 175 15 21 151 175
E1 108 99.4 3 125
20 27 158 175
7.5 9 10 11 64 70 15 17 72 80
E4 40 36.8 1 40
20 22 78 80
7.5 9 10 11 94 110 15 17 102 110
E8 80 73.6 2 80
20 22 108 125
7.5 9 10 11 122 150 15 17 130 150
E1 108 99.4 3 108
20 22 136 150
Max Fuse2/
1
MCA
(Amps)
138 150
197 225
143 150
212 250
71 80
106 125
138 150
62 70
92 110
120 150
Breaker
Size
(Amps)
3
28 Johnson Controls Unitary Products
Loading...
+ 64 hidden pages