See the following pages for a complete Table of Contents.
Z33
Z34
NOTES, CAUTIONS AND WARNINGS
Installer should pay particular attention to the words: NOTE,
CAUTION, and WARNING.
make the installation easier.
equipment damage.
that personal injury and/or equipment damage may result if
installation procedure is not handled properly.
33 HOT WATER COIL - 40 TON, 1 ROW, AT 10 GPM . . 73
34 HOT WATER COIL - 40 TON, 1 ROW, AT 20 GPM . . 73
35 HOT WATER COIL - 40 TON, 1 ROW, AT 30 GPM . . 74
36 HOT WATER COIL - 40 TON, 1 ROW, AT 40 GPM . . 74
37 HOT WATER COIL - 40 TON, 2 ROW, AT 20 GPM . . 75
38 HOT WATER COIL - 40 TON, 2 ROW, AT 40 GPM . . 75
39 HOT WATER COIL - 40 TON, 2 ROW, AT 60 GPM . . 76
40 HOT WATER COIL - 40 TON, 2 ROW, AT 80 GPM . . 76
17 ELECTRICAL DATA 25 TON BASIC UNIT R-410A . . 26
18 ELECTRICAL DATA 30 TON BASIC UNIT R-410A . . 27
19 ELECTRICAL DATA 40 TON BASIC UNIT R-410A . . 27
20 ELECTRICAL DATA 25 TON W/ELECTRIC HEAT
York Model Z42/Z33/Z34 units are single package cooling
only or cooling with gas, electric, hot water or steam heating
designed for outdoor installation on a rooftop and for non-residential use.
The units are completely assembled on rigid, permanently
attached base rails. All piping, refrigerant charge, and electrical wiring is factory installed and tested. The units require
electric power, gas, steam, or hot water connections and duct
connections. Gas fired units also require installation of a flue
gas outlet hood.
This Furnace is not to be used for temporary heating of buildings or structures under construction.
ALL MODELS
This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other
refrigerant may be used in this system. Gage sets,
hoses, refrigerant containers and recovery systems must be designed to handle R-410A. If you
are unsure, consult the equipment manufacturer.
Failure to use R-410A compatible servicing equipment may result in property damage or injury.
Installer should pay particular attention to the words: NOTE,CAUTION, and WARNING.
make the installation easier.
equipment damage.
personal injury and/or equipment damage may result if installation procedure is not handled properly.
Warnings are given to alert installer that
Notes are intended to clarify or
Cautions are given to prevent
GAS FIRED MODELS
DO NOT store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electrical
switch. Do not use any phone in your building. Immediately
call your gas supplier from a neighbor’s phone. Follow the
gas supplier’s instructions. If you cannot reach your gas sup-
plier, call the fire department.
The furnace and its individual shut-off valve must
be disconnected from the gas supply piping system during any pressure testing of that system at
test pressures in excess of 0.5 psig. Pressures
greater than 0.5 will cause gas valve damage
resulting in a hazardous condition. If gas valve is
subjected to a pressure greater than 0.5 psig, it
must be replaced. The furnace must be isolated
from the gas supply piping system by closing its
individual manual shut-off valve during any pressure testing of that system at test pressures equal
to or less than 0.5 psig.
Installation and servicing of air conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair or service air conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit
and other safety precautions that may apply.
Follow all safety codes, including ANSI Z223.1-Latest Edition: wear safety glasses and work gloves; use quenching
cloth for unbrazing operations; have fire extinguisher avail-
able for all brazing operations.
Before performing service or maintenance operations on unit, turn off main power switch to unit.
Electrical shock could cause personal injury.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property
damage. Refer to this manual. For assistance or
additional information consult a qualified installer,
service agency or the gas supplier.
INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of
damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be
made in writing.
Johnson Controls Unitary Products7
882108-YIM-B-1012
REFERENCE
Additional information is available in the following reference
form:
•246837 - Technical Guide
APPROVALS
Designed certified by CSA, ETL, CETL as follows:
1. For use as a forced air furnace with cooling unit (gas
heat models).
2. For outdoor installation only.
3. For installation on combustible material and may be
installed directly on combustible flooring or Class A,
Class B or Class C roof covering materials.
4. For use with natural gas (convertible to LP with kit).
Not suitable for use with conventional venting systems.
INSTALLATION
PRECEDING INSTALLATION
If a factory option convenience outlet is installed, the weatherproof outlet cover must be field installed. The cover shall be
located in the unit control box. To install the cover, remove
the shipping label covering the convenience outlet, follow the
instructions on the back of the weatherproof cover box, and
attach the cover to the unit using the (4) screws provided.
After installation, gas fired units must be adjusted to obtain a
temperature rise within the range specified on the unit rating
plate.
If components are to be added to a unit to meet local codes,
they are to be installed at the contractor's and/or the customer's expense.
Size of unit for proposed installation should be based on heat
loss / heat gain calculation made according to the methods of
the Air Conditioning Contractors of America (ACCA).
LOCATION
Use the following guidelines to select a suitable location for
these units:
TABLE 1: COOLING & ELECTRICAL APPLICATION
UNIT POWER
SUPPLY
575-3-60540630
208/230-3-60187252
460-3-60432504
VOLTAGE VARIATIONS
MIN. VOLTSMAX VOLTS
TABLE 2: COOLING & ELEC. APP. LIMITATIONS
MODEL
LIMITATIONS
Z42Z33Z34
208/230-3-60 and 380/415-3-50 units with factory
installed Powered Convenience Outlet Option are
wired for 230v and 415v power supply respectively.
Change tap on transformer for 208-3-60 or 380-3-50
operation. See unit wiring diagram.
LIMITATIONS
The installation of this unit must conform to local building
codes, or in the absence of local codes, with ANSI Z223.1
Natural Fuel Gas Code and /or CAN/CGA B149 installation
codes.
In U.S.A.:
1. National Electrical Code ANSI/NFPA No. 70-Latest Edition.
2. National Fuel Gas Code Z223.1-Latest Edition.
3. Gas-Fired Central Furnace Standard ANSI Z21.47-Latest Edition.
4. Local gas utility requirements.
Refer to Table 1 for Cooling and Electrical Application Data
and to Table 2 for Gas Heat Application Data.
Supply Air CFM
(min./max)
Entering Wet Bulb
Temp (F°) (min./max)
Ambient Temp40/12540/12540/125
Min. Air Temperature on Gas Fired Heat Exchangers (°F)
Aluminized252525
Stainless000
6,00012,500
57/7557/7557/75
6,000-
15,000
8,000-
20,000
1. Unit is designed for outdoor installation only.
2. Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit
on either north or east side of building.
3. Suitable for roof mount on curb.
4. Roof structures must be able to support the weight of the
unit and its accessories. Unit must be installed on a solid
level roof curb or appropriate angle iron frame.
5. Maintain level tolerance to 3/4 inches across width and 2
inches along length.
If a unit is to be installed on a roof curb other than a
York roof curb, gasketing must be applied to all surfaces that come in contact with the unit underside.
If a unit is to be installed on an angle iron frame it is
recommended that it be sized to allow the bottom
rail to overhang to facilitate installation of condensate drains (see Fig. 4).
RIGGING:
27”
CABLES
(1) RIG WITH SIX CABLES AND THREE SPREADER
BARS AT LEAST 98” ACROSS THE WIDTH OF THE UNIT.
(2) CENTER OF GRAVITY INCLUDES ECONOMIZER
AND POWER EXHAUST.
ALL PANELS MUST BE SECURED IN
PLACE WHEN THE UNIT IS LIFTED.
NOTE: If the Millennium is VAV with ERV, add the
weight of an exhaust VFD - it will be in the unit.
.
REAR
B
92”
FIGURE 3 -CENTER OF GRAVITY
1.
Refer to Tables 11 and 12 for A, B, C, D and X and Y
data respectively.
CENTER OF
GRAVITY
Y
A
C
240”
RIGHT END
CONDENSER
COILS
D
X
FRONT
1
Johnson Controls Unitary Products11
882108-YIM-B-1012
All panels must be secured in place when the unit
is lifted.
The condenser coils should be protected from
damage by the rigging cables with plywood or
other suitable material.
RIGGING AND HANDLING
This unit is not designed to be handled with a fork-truck.
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig
the unit by attaching cable slings to the lifting lugs provided in
the unit base rails. Spreaders MUST be used across the top
of the unit. Refer to Figure 2.
An adhesive backed cover is provided over the
outside of the combustion air inlet opening on gas
•Rig with six cables and spread with three 98-inch
spreaders across width of unit.
fired units to prevent moisture from entering the
unit which could cause damage to electrical components. Allow this closure label to remain in place
until the combustion air hood is to be installed
(Refer to Figures 7).
•Refer to Tables 8 and 11 for unit weight.
•Center of gravity includes economizer, exhaust or return
air fan (Refer to Table 12).
+ Econ = +235lb
+ Heat = single stage gas, 180 lb
+ Power Exhaust = modulating 7.5hp
ABCDAB CDABCD
101811111313120310761124132812721058105814821482
99410841418130010731073140314031102105515031570
122012751318126212751275141014101335127814851551
TABLE 12: UNIT CENTER OF GRAVITY
MODEL
Basic Unit99”48”100”47”96”46"
Basic Unit /w
Econ.
Basic Unit /w
Econ. & Gas or
Elect. Heat,
Steam or Hot
Water Heat
Basic Unit /w
Econ. & Gas or
Elect. Heat, &
Power Exhaust
25 TON30 TON40 TON
XYXYXY
110”48”110”47”100”46"
104”48”104”46”99”45"
118”47”114”46”111”45"
25 TON30 TON40 TON
CLEARANCES
All units require certain clearances for proper operation and
service. Installer must make provisions for adequate combustion and ventilation air in accordance with section 5.3, Air for
Combustion and Ventilation of the National Fuel Gas Code
ANSI Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149
installation codes-Latest Edition and/or applicable provisions
of the local building codes.
required for combustible construction, servicing, and proper
unit operation.
Refer to Figure 8 for clearances
(COOLING OPERA TION) Do not permit overhanging structures or shrubs to obstruct condenser air
discharge outlet, combustion air inlet or vent outlets.
12Johnson Controls Unitary Products
882108-YIM-B-1012
When the unit is equipped with power exhaust fans or return
air fan the return duct should have a 90 elbow before opening
to the building space to abate noise.
(GAS HEATING OPERATION)
Excessive exposure to contaminated combustion
air will result in safety and performance related
problems. To maintain combustion air quality, the
recommended source of combustion air is the outdoor air supply.
The outdoor air supplied for combustion should be
free from contaminants due to chemical exposure
that may be present from the following sources:
•Commercial buildings
•Indoor pools
•Laundry rooms
•Hobby or craft rooms
•Chemical storage areas
The following substances should be avoided to
maintain outdoor combustion air quality:
•Permanent wave solutions
•Chlorinated waxes and cleaners
•Chlorine based swimming pool cleaners
•Water softening chemicals
•De-icing salts or chemicals
•Carbon tetrachloride
•Halogen type refrigerants
•Cleaning solvents (such as perchloroethylene)
•Printing inks, paint removers, varnishes, etc.
•Hydrochloric acid
•Cements and glues
•Antistatic fabric softeners for clothes dryers
•Masonry acid washing materials
The supply and return air duct systems should be designed
for the CFM and static pressure requirements of the job. They
should NOT be sized to match the dimensions of the duct
connections on the unit.
If the unit is equipped with hot water or steam heat then the
supply air direction will be down only.
AIR HOODS FOR FIXED OUTSIDE AIR
(UNITS WITH MANUAL ECONOMIZER)
These hoods are factory installed. The dampers may be
adjusted by loosening the thumb screw, turning the lever to
the desired position, and retightening the thumb screw.
AIR HOODS FOR ECONOMIZER
There are (3) economizer outside air intake hoods provided
with the unit. The hood on the end of the unit is factory
mounted. The (2) front and rear hoods are made operational
per the following instructions.
Remove the screws holding the economizer hood shipping
covers in place. Discard covers.
Rotate the hoods out (each hood is hinged in the lower corner). Secure the hoods with screws along the top and sides.
Apply a bead of RTV sealer along the edge of both hoods
and each pivot joint to prevent water leakage.
Seal any unused screw holes with RTV or by replacing the
screw.
AIR HOODS FOR EXHAUST AIR
When furnished, these hoods and dampers are factory
DUCTWORK
Ductwork should be designed and sized according to the
methods in Manual Q of the Air Conditioning Contractors of
America (ACCA).
A closed return duct system should be used. This will not pre-
clude use of economizers or outdoor fresh air intake. The
supply and return air duct connections at the unit should be
made with flexible joints to minimize noise.
Johnson Controls Unitary Products13
installed.
CONDENSATE DRAIN
There is one condensate drain connection. Trap the connection per Figure 4. The trap and drain lines should be protected from freezing.
Plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install condensate drain lines
from the 1-1/2 inch NPT female connections on the unit to an
open drain.
882108-YIM-B-1012
D R A I N C O N N E C T I O N
F A C T O R Y I N S T A L L E D
H
FILTERS
U N I T B A S E
Y
R O O F
C U R B
O R
P E R I M E T E R
S U P P O R T
S T R U C T U R E
F I E L D S U P P L I E D
Throwaway or rigid filters are supplied with each unit. Filters
must always be installed ahead of evaporator coil and must
be kept clean or replaced with same size and type. Dirty filters will reduce the capacity of the unit and will result in
frosted coils or safety shutdown. Required filter sizes are
shown in Table 15. The unit should not be operated without
filters properly installed.
THERMOSTAT (CONSTANT VOLUME UNITS)
Y - M I N I M U M 2 "
H - 1 / 2 " P L U S T O T A L S T A T I C P R E S S U R E - M I N I M U M
FIGURE 4 -RECOMMENDED DRAIN PIPING
SERVICE ACCESS
Access to all serviceable components is provided by the following hinged doors:
•Furnace compartment
•Supply Air Fan compartment Evaporator Coil compartment (three doors)
Refer to Figure 1 for location of these access panels.
Make sure that all screws and panel latches are
replaced and properly positioned on the unit to
maintain an air-tight seal.
T 7 3 0 0 T H E R M O S T A T S U B B A S E
R C G Y 1 Y 2 Y 3 Y 4 W 1 W 2 A 1 C T T
R E M O T E
2 T H O 4 7 0 2 2 2 4
S E N S O R
R
Y 1
G
Y 2
Y 3
Y 4
W 1
W 2
A 1
C
L 1
A
P O W E R S U P P L Y
P O W E R W I R I N G
L 2 L 3
T B 1
B
E Q U I P . G N D .
C
FIGURE 5 -TYPICAL THERMOSTAT WIRING
The thermostat, if used, should be located on an inside wall
approximately 56 inches above the floor where it will not be
subject to drafts, sun exposure or heat from electrical fixtures
or appliances. Follow manufacturer's instructions enclosed
with sensor for general installation procedure (See Figure 5).
Refer to Table 13 for control wire sizing and maximum length.
TABLE 13: CONTROL WIRE SIZES
WIRE SIZEMAXIMUM LENGTH
20 AWG100 Feet
COMPRESSORS
18 AWG150 Feet
Units are shipped with compressor mountings factoryadjusted and ready for operation.
DO NOT loosen compressor mounting bolts.
14Johnson Controls Unitary Products
SPACE SENSOR (VARIABLE AIR VOLUME UNITS)
The space sensor, if used, should be located on an inside
wall approximately 56 inch above the floor where it will not be
subject to drafts, sun exposure or heat from electrical fixtures
or appliances. Follow manufacturer's instructions enclosed
with sensor for general installation procedure.
882108-YIM-B-1012
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of National
Electrical Code (NEC) ANSI / NFPA 70-Latest Edition and / or
local ordinances. The unit must be electrically grounded in
accordance with the NEC and / or local codes. Voltage tolerances which must be maintained at the compressor terminals
during starting and running conditions are indicated on the
unit Rating Plate and Table 1.
The internal wiring harnesses furnished with this unit are an
integral part of the design certified unit. Field alteration to
comply with electrical codes should not be required. If any of
the wire supplied with the unit must be replaced, replacement
wire must be of the type shown on the wiring diagram and the
same minimum gauge as the replaced wire.
Power supply to the unit must be NEC Class 1 and must
comply with all applicable codes. A disconnect switch must
be provided (factory option available). The switch must be
separate from all other circuits. Wire entry at knockout openings requires conduit fittings to comply with NEC and/or Local
Codes. Refer to Figures 11, 12, 13, and 14 for installation
location of openings.
If installing a field mounted disconnect on the unit, refer to
Figure 15 for the recommended mounting location.
Unitstrut™ or equivalent rails should be mounted as shown to
provide structure for mounting. The location of the rails
should be adjusted to fit the disconnect within the dimensions
shown. Conduit run from the disconnect to the power entry
location in the baserail should be routed so that it does not
interfere with the doors of the unit access panels.
Refer to Figure 5 for typical field wiring and to the appropriate
unit wiring diagram mounted inside control doors for control
circuit and power wiring information.
POWER WIRING DETAIL
Units are factory wired for the voltage shown on the unit
nameplate. The main power block requires copper wires.
Refer to Electrical Data Tables 17 through 28 to size power
wiring, fuses and disconnect switch. All field supplied wiring,
fuses and disconnects must comply with applicable NEC
codes.
Power wiring is brought into the unit through the side of the
baserail or the bottom of the unit/control box inside the curb.
The baserail has a 2-1/2” diameter hole for field wiring and a
3-5/8” hole is provided for a through-the-curb connection. A
removable patch plate covers both the openings.
Waterproof connections MUST be used to ensure
that water cannot penetrate the roof or roof curb.
ERV
The ERV [Energy Recovery Ventilation] is a separate air handler that attaches to the exhaust end of the 25-40T Millennium packaged rooftop unit. The ERV is shipped separately
and assembled to the Millennium at the jobsite. An 'ERV' Millennium is shipped with an end configuration and electric
hookups designed to mate with the ERV. This option is available only with the Simplicity® control, and no other power
exhaust option can be supplied if an ERV is selected.
Use care to avoid damage when drilling holes for
the disconnect mounting.
NOTE: Since not all local codes allow mounting a discon-
nect on the unit, please confirm compliance with
local code before mounting a disconnect on the unit.
Electrical wiring must be sized properly to carry the load.
Each unit must be wired with a separate branch circuit fed
directly from the meter panel and properly fused.
When connecting electrical power and control wiring to the unit, waterproof connectors MUST BE
USED so that water or moisture cannot be drawn
into the unit during normal operation. The above
waterproofing conditions will also apply when
installing a field-supplied disconnect switch.
Johnson Controls Unitary Products15
The ERV incorporates a rotating heat exchange wheel and a
pair of exhaust blowers. It exhausts return air through the
wheel, capturing the thermal energy of the exiting hot or cold
air as it passes. As the wheel rotates, the incoming airstream,
pulled through by the supply fan, regains that energy.
The Millennium ERV has a terminal block and mating connectors to simplify hooking up the two systems. The controls
of both units are factory set to interact properly . Power for the
ERV blower motors and controls is provided through the Millennium unit. The Millennium /ERV dataplate information
includes the ERV electrical load.
The Millennium Simplicity® control has parameters for the
ERV; refer to the parameter list. When economizer and ERV
options are selected on the same unit, the Simplicity® control
and the ERV have specific connections and internal rules for
that operation.
Also refer to the ERV Installation Instructions packaged with
the ERV.
882108-YIM-B-1012
GAS HEATING
On VAV units with gas fired furnace, ALL INDIVIDUAL ROOM DAMPER BOXES MUST BE CONTROLLED FULL OPEN DURING HEATING
OPERATION TO ENSURE PROPER AIRFLOW
OVER THE FURNACE. A control contact powered
by the “VAV OPEN” terminals on the Simplicity®
control is provided for the damper box interlock.
this contact is normally open, and is closed during
heating operation.
GAS PIPING
Proper sizing of gas piping depends on the cubic feet per
hour of gas flow required, specific gravity of the gas and the
length of run. National Fuel Gas Code Z223.1-Latest Edition
should be followed in all cases unless superseded by local
codes or gas company requirements. Refer to Table 14.
The heating value of the gas may differ with locality. The
value should be checked with the local gas utility.
FIGURE 6 -TYPICAL GAS PIPING CONNECTION
Gas piping recommendations:
1. A drip leg and a ground joint union must be installed in
the gas piping.
2. When required by local codes, a manual shut-off valve
will have to be installed outside of the unit.
3. Use wrought iron or steel pipe for all gas lines. Pipe dope
should be applied sparingly to male threads only.
Maximum capacity of pipe in cubic feet of gas
per hour (based upon a pressure drop of 0.3 inch
water column and 0.6 specific gravity gas.
NOTE: There may be a local gas utility requirement specify-
ing a minimum diameter for gas piping. All units
require a 1-1/4 inch pipe connection at the entrance
fitting. Line should not be sized smaller than the
entrance fitting size.
NOMINAL IRON PIPE, SIZE
1-1/4 IN.
1
1-1/2 IN.
1
2 IN.
1
GAS CONNECTION
The gas supply line should be routed within the space and
penetrate the roof at the gas inlet connection of the unit.
Refer to Figures 11 through 14 to locate the access opening.
Typical supply piping arrangements are shown in Figure 6.
Natural gas may contain some propane. Propane,
is an excellent solvent and will quickly dissolve
white lead or most standard commercial pipe sealing compounds. Therefore, special shellac base
pipe dope compounds such as Gaskolac or Stalastic, and compounds such as Rectorseal #5,
Clyde’s or John Crane must be applied for wrought
iron or steel pipe.
4. All piping should be cleaned of dirt and scale by hammering on the outside of the pipe and blowing out the
loose particles. Before initial start-up, be sure that all of
the gas lines external to the unit have been purged of air.
5. The gas supply should be a separate line and installed in
accordance with all safety codes as prescribed under
Limitations. After the gas connections have been completed, open the main shutoff valve admitting normal gas
pressure to the mains. Check all joints for leaks with
soap solution or other material suitable for the purpose.
NEVER USE A FLAME.
6. The furnace and its individual manual shut-off valve must
be disconnected from the gas supply piping system
during any pressure testing of that system at test pressures in excess of 0.5 psig.
16Johnson Controls Unitary Products
Disconnect gas piping from unit when leak testing
at pressures greater than 0.5 psig. Pressures
greater than 0.5 psig will cause gas valve damage
resulting in a hazardous condition. If gas valve is
subjected to pressure greater than 0.5 psig, it must
be replaced.
882108-YIM-B-1012
VENT AND COMBUSTION AIR
NOTE: All the hoods and hardware are shipped within the
evaporator section. Each hood must be properly
attached to the furnace doors to assure proper
operation and compliance with CSA/ETL safety certification. (Refer to Figure 7.)
The products of combustion are discharged horizontally
through hooded openings in the gas heat access doors.
7. A 1/8 inch N.P.T. plugged tapping, accessible for test
gage connection, must be installed immediately
upstream of the gas supply connection to the furnace.
EXHAUST VENT OUTLET
COMBUSTION
AIR INLET
VENT FLUE
ASSEMBLY
REMOVE SHIPPING
LABELS PRIOR TO
VENT INSTALLATION
HEAT SECTION DOOR
FIGURE 7 -VENT AND COMBUSTION AIR
HOODS
(Figure 7)
1. Remove the shipping covers that are attached to the
heat section door covering the flue outlets.
2. Locate the flue which is shipped in the evaporator section.
3. Place the flue over the flue outlet and attach with screws
provided.
4. Refer to the Gas Furnace Operation Instruction in the
Start-up Section of this manual for further instructions.
10'
RIGHT
END
60"
60"
REAR
60"
FRONT
LEFT
END
60"
* Front is the side with access to the Electrical/Gas Controls
LEFT
RIGHT
REAR
FRONT
TOP
60"
60"
60"
60"
10'
NOTE: DO NOT use the unit roof to support any type of
structure bracing.
FIGURE 8 -CLEARANCES
Johnson Controls Unitary Products17
882108-YIM-B-1012
ELECTRIC HEAT
Units with electric heat are fully wired and operational when
shipped. Constant volume units are designed for two equal
steps of capacity for 80 and three for 108 kWH heat; 40 kW
heat is one step only . Heat outputs on VA V units are all turned
on together at full heat capacity.
HOT WATER HEAT
The YORK Millennium units (25, 30, and 40 Ton sizes) can be
furnished with a YORK hot water coil as the heat source. One
or two row coil units will be factory installed in the heating
section.
NOTE: The hot water control valve will not be provided. The
installer will need to provide a hot water control
valve, to connect the hot water piping and power
wiring at the job site for the hot water heat section to
be operational.
There are no provisions in the coil or control
sequence to prevent freezing of condensate. The
control valve, piping and field installed wiring connections are particularly vulnerable because they
are installed in the vestibule outside of the conditioned air stream. The installing party will be
responsible for properly insulating and installing
power and control wiring, to the actuator and piping.
In one row hot water coil systems DO NOT exceed
a 40 gallons per minute flow rate.
In two row hot water coil systems DO NOT exceed
an 80 gallons per minute flow rate.
Condensate will freeze on the control valve and
piping if they are not properly insulated. Insulating
the control valve and piping is the responsibility of
the installing party.
DO NOT use hot water coils as steam coils under
any circumstances.
All piping, control valves, and wiring that is field
installed must be properly insulated and conform
to all local and national codes.
NOTE: For all hot water coils the entering water tempera-
ture should not exceed 200°F.
The hot water coil is located downstream of the supply air fan
and just above the supply air opening in the bottom of the
unit.
Refer to Tables 50 through 58 and Figures 27 through 40 for
flow rate and capacity.
PIPING CONNECTIONS
The hot water piping must enter the unit through the floor of
the heat section compartment. The access doors to the compartment are gasketed so the compartment can be sealed.
However, as added protection for water leakage into the
space, the piping access holes should be sealed with a heat
resistant mastic Figure 9 shows the location of the compartment and piping connections.
Piping access holes should be sealed with a heat
resistant mastic to prevent damage to equipment.
18Johnson Controls Unitary Products
882108-YIM-B-1012
DO NOT use tin based solder. Brazing with tin
based solder could cause equipment damage or
possible injury to tenants of the structure that is
being conditioned.
( 1 O R 2 R O W )
C O N D E N S I N G
S E C T I O N
8 8 . 7 5 "
O U T S I D E O F
B A S E R A I L
1 5 . 8 "
1 1 . 8 8 "
H E A T S E C T I O N
C O M P A R T M E N T
2 . 2 5 "
H O T W A T E R
C O I L
2 6 "
I N L E T ( 2 " )
C
L
O U T L E T ( 2 " )
8 . 3 8 "
2 . 5 5 "
FIGURE 9 -HOT WATER PIPING CROSS-SEC-
TION
STEAM HEAT
The YORK Millennium units (25, 30 and 40 Ton sizes) can be
furnished with a YORK single row steam coil. YORK steam
coils are a factory installed option.
T O P V I E W
C O N D E N S I N G
S E C T I O N
O U T S I D E O F
B A S E R A I L
1 5 . 8 "
S T E A M
C O I L
2 6 "
O U T L E T ( 1 1 / 2 " )
I N L E T ( 2 " )
8 "
8 . 3 8 "
All piping and control valves, and wiring that is
field installed must be properly insulated and conform to all local and national codes.
There are no provisions in the coil or control
sequence to prevent freezing of condensate. The
control valve, piping and field installed wiring connections are particularly vulnerable because they
are installed in the vestibule outside of the conditioned air stream. The installing party will be
responsible for properly insulating and installing
power and control wiring, to the actuator and piping.
DO NOT use steam coils as hot water coils under
any circumstances.
In steam coil systems, the steam pressure shall
not exceed 15 PSI.
PIPING CONNECTIONS
Refer to Tables 46 through 49 and Figures 41 and 42 for flow
rate and capacity.
The steam piping must enter the unit through the floor of the
heat section compartment. The access doors to the compartment are gasketed so the compartment can be sealed. However, as added protection for condensate leakage into the
space, the piping access holes should be sealed with a heat
resistant mastic. The following figure illustrates the location of
the compartment and piping connections.
2 . 5 5 "
C
L
8 8 . 7 5 "
Piping access holes should be sealed with a heat
resistant mastic to prevent damage to equipment.
H E A T S E C T I O N
C O M P A R T M E N T
9 "
FIGURE 10 - STEAM PIPING CROSS-SECTION
NOTE: The steam control valve, power and control wiring to
the actuator of the valve is the responsibility of the
installing party.
Johnson Controls Unitary Products19
DO NOT use tin based solder. Brazing with tin
based solder could cause equipment damage or
possible injury to tenants of the structure that is
being conditioned.
882108-YIM-B-1012
STATIC PRESSURE CONTROL PLASTIC TUBING
On units with variable frequency drives (VFD’s) or inlet guide
vanes (IGV's) on the supply blower and/or power exhaust
fans, pressure sensing tubing must be field supplied and
installed. All tubing must be installed from the transducers
(located in the unit) to the location in the building (or
ductwork) where a constant pressure is desired. The tubing
must also be installed from the transducers to a low-side reference to the atmosphere.
The supply air duct pressure sensor (DPS) is located in the
control box directly below the Millennium Simplicity® control.
Plastic tubing (1/4”) must be run from the high pressure tap of
the transducer to a static pressure tap (field supplied) in the
supply duct located at a point where constant pressure is
desired. Tubing must also be run between the low pressure
tap of the transducer to atmospheric pressure. Changing the
adjustment is done to the duct pressure setpoint in the control.
EXHAUST STATIC PRESSURE
If a modulating-damper or variable frequency drive power
exhaust is installed, there will be a building pressure sensor
(BPS) in the control box directly below the Millennium Sim-plicity® control. This ± .25 0-5VDC transducer sends a building pressure signal to the control. A sensing tube must be
installed from a representative location in the building to the
HI port of the transducer. Tubing must also be run between
the low pressure tap of the transducer to atmospheric pressure.
Changing the adjustment is done to the building pressure setpoint in the control.
Do not run plastic tubes in the supply or return air
ducts as air movement could cause erroneous
sensing. If tubes penetrate bottom of unit be sure
openings are sealed against air and water leakage.
20Johnson Controls Unitary Products
64"
RETURN AIR
SUPPLY AIR
92"
REAR
DETAIL
FRONT
SEE
B
SEE
DETAIL
C
882108-YIM-B-1012
RIGHT
END
72.25”
99.5”
131.5”
LEFT
END
4-5/8”
1-1/2" FPT
DETAIL A
(DRAIN CONNECTION)
LEFT
END
80.93"
4.5"
BASE RAIL
83"
REAR
4.5"
SEE
71.61"
26"
DETAIL
A
38.59"
6.46"
127.5"
FRONT
C
4.5"
BASE RAIL
DETAIL B
(ELECTRICAL CONNECTION)
FOR COOLING ONLY AND ALL HEATING APPLICATIONS
L
2.31”
Ø 2-1/2”
OPEN
3.625"
240"
3-5/8"
6.45"
15.89"
RIGHT
END
2-1/2”
DIA. HOLES
12"
MIN
C
L
28”
1-1/4” NPT
(GAS CONNECTION
THROUGH CURB)
88.7 "
7”
DETAIL C
TO GAS VALVE
MANIFOLD
11”
FIGURE 11 - BOTTOM SUPPLY AND RETURN
Johnson Controls Unitary Products21
882108-YIM-B-1012
LEFT END
RETURN AIR
SUPPLY AIR
7-7/8”
64"
LEFT END
76-3/8”
92"
8
0.93"
REAR
REAR
24.9”
SEE
DETAIL
A
"
6.25”
FRONT
4.5"
71.61"
SEE
DETAIL
B
6.46"
SEE
DETAIL
C
3.625"
26"
FRONT
240"
NOTE:
FACTORY INSTALLED POWER
EXHAUST CANNOT BE ORDERED
WITH END RETURN.
RIGHT END
72.25”
99.5”
131.5”
RIGHT
END
OPEN
12"
MIN
15.89"
C
L
88.7"
4-5/8”
BASE RAIL
1-1/2" FPT
BASE RAIL
DETAIL A
(DRAIN CONNECTION)
(ELECTRICAL CONNECTION)
FOR COOLING ONLY AND ALL HEATING APPLICATIONS
FIGURE 12 - END RETURN, BOTTOM SUPPLY
2-1/2"
DETAIL B
2.31”
3-5/8"
6.45"
2-1/2”
DIA. HOLES
28”
1-1/4” NPT
7”
DETAIL C
(GAS CONNECTION
THROUGH CURB)
TO GAS VALVE
MANIFOLD
11”
22Johnson Controls Unitary Products
FRONT SUPPLY: FOR COOLING ONLY APPLICATIONS
REAR SUPPLY: FOR COOLING ONLY OR GAS HEAT APPLICATIONS
882108-YIM-B-1012
FRONT
64"
RETURN AIR
SUPPLY AIR
REAR
92"
LEFT END
80.93"
4.5"
REAR
RIGHT END
26"
55"
72.25”
99.5”
FRONT
SEE
DETAIL
B
8.15"
SEE
DETAIL
C
131.5”
RIGHT
END
REAR
OPEN
SEE
DETAIL
A
6.46"
3.625"
12"
MIN
38.59"
FRONT
4.5"
2.31”
BASE RAIL
2-1/2"
DETAIL B
(ELECTRICAL CONNECTION)
FOR COOLING ONLY AND ALL HEATING APPLICATIONS
240"
2-1/2”
DIA. HOLES
3-5/8"
6.45"
28”
1-1/4” NPT
DETAIL C
(GAS CONNECTION
THROUGH CURB)
TO GAS VALVE
MANIFOLD
7”
11”
LEFT END
4-5/8”
BASE RAIL
1-1/2" FPT
DETAIL A
(DRAIN CONNECTION)
83"
FIGURE 13 - BOTTOM RETURN, FRONT & REAR SUPPLY
Johnson Controls Unitary Products23
882108-YIM-B-1012
FRONT SUPPLY: FOR COOLING ONLY APPLICATIONS
REAR SUPPLY: FOR COOLING ONLY OR GAS HEAT APPLICATIONS