Mikrofill Maxi Single, Maxi Single (HP), Maxi Plus, Maxi Plus (HP) Technical Documentation Manual

I N S P I R E D E F F I C I E N C Y
MAXI & MAXI PLUS Floor mounted Pressure manager
TECHNICAL DOCUMENTATION
Issue 06/14
stnetnoC stnetnoC
3Technical Data
1.1
1.2
1.3
1.4 2 Electrical connections 7
2.1 Electrical diagram 7 3 Keypad Function 8
4 Status Display
4.1 Pressure correct 8
4.2 Filling stopped due to low mains water pressure 8
4.3 Hours run facility 8
4.4 Hours run reset 8
5 Alarm conditions 9
5.1 Low Water Level Alarm 9
5.2 Optional System Failure/leak alert 9
5.3 High or low pressure alarms 9
5.4 Pump Failure 9
5.5 Frequent use alarm 10
5.6 Frequent use reset 10
Installation Mains/boosted cold water supply Connection to the system Overflow Connection Dimensions
6 Fault diagnosis 11
7 Manual override 12
8 Audible alarm override 12
9 Service Mode ( adjusting settings ) 12
10 Menu functions 13
11 Maintenance 13
12 Pump Curve and Data 14
2
Technical Data
Electrical Details
Supply Voltage
Full Load Current
Start Current
Fuse Rating
Max Load BMS Relays
Connection Details
W ater Inlet
Water Outlet
Maxi Single Maxi Plus
230 Volt
2.5 Amp
2.5 Amp
5 Amp
5 Amp
Maxi Single (HP) Maxi Plus (HP)
230 Volt
4.5 Amp
4.5 Amp
8 Amp
5 Amp
15mm Compression
15mm Compression
230 Volt
2.5 Amp
2.5 Amp
5 Amp
5 Amp
230 Volt
4.5 Amp
4.5 Amp
8 Amp
5 Amp
3/4” BSP
Max Coldfill Pressure Maxi 3.0 Bar / Maxi HP 6.0 Bar
Dimensions
Unit Weight
Height
Width
Depth
27 Kg
35 Kg 29 Kg 38 Kg
600mm
465mm
390mm
3
Maxi & Maxi Plus pressurisation units
The Maxi range is a fully automatic heating / chiller system pressurisation device, and is suitable for the water management in all domestic and commercialheating and cooling systems. It is supplied as a fully commissioned unit and should require no "on site" commissioning.
1 Installation
All productsshould be installed by a competent person with regard to the relevant requirements of the Health and Safety Regulations, Building Regulations, IEE Regulations, Water Supply (water (Scotland) and any other local bye-laws or planning requirements.
Regulations, Water Bye-laws
The crystal display to be easily read.
Maxi is intended for mounting: the unit should be situated in such a position as to enable the liquid
1.1 Mains/boosted cold water supply
The Maxi is designedto be connected directly to the mains cold water supply, or a boosted cold water supply, the unit is supplied complete with all necessary isolating valves, but an inlet water isolating valve is recommended. The water inlet is 15mm compression and should be connected to the mains cold water supply by 15mm copper tube or equivalent approved plastic pipework. If the to install a single check valve adjacent to the mains cold water supply.
To reduce the pressure drop on very long supply routes then 22mm supply pipework is recommended.
Maxi is sited some distancefrom the mains cold water supply it may be advisable
4
1.2 Connection to the system
The Mikrofill Maxi is connected to the heating/chiller system by way of the 15mm outlet valve, the pipework from the unit should be made in 15mm copper or similarly approved plastic pipework. A suitably sized expansion vessel should be incorporated into the system at this point. Please refer to typical installation diagram on page 3. If you require any assistance regarding vessel sizing please contact our technical sales department. The final connection into the heating/chiller systemshould be sized accordingly, recommendations are shown below:
Vessel sizeupto100L 1/2" (15mm) expansion pipework. Vessel sizeupto300L 3/4" (22mm) expansion pipework Vessel sizeupto1000L 1" (28mm) expansion pipework.
For vessel sizes in excess of 1000L capacityplease contact our technical sales department.
IMPORTANT NOTE
The expansion vessel nitrogen/air charge must be set at the same pressure as the cold fill pressure of the system.* All Mikrofill expansion vessels are factory commissioned to the correct pressure.
* When the installed height of the expansion vessel is different to that of the MAXI then please contact our service department who will advise on the nitrogen/air charge.
1.3 Overflow connection
The Maxi is supplied with a 3/4" bsp plastic overflow (warning pipe) connection which should be led to a drain and be visible at point of discharge, MIKROFILL SYSTEMS LTD cannot accept any responsibility for flood damage caused by failure toconnect the overflow.
5