4.2Filling stopped due to low mains water pressure8
4.3Hours run facility8
4.4Hours run reset8
5Alarm conditions9
5.1Low Water Level Alarm9
5.2Optional System Failure/leak alert9
5.3High or low pressure alarms9
5.4Pump Failure9
5.5Frequent use alarm10
5.6Frequent use reset10
Installation
Mains/boosted cold water supply
Connection to the system
Overflow Connection
Dimensions
4
4
5
5
6
8
6Fault diagnosis11
7Manual override12
8Audible alarm override12
9Service Mode ( adjusting settings )12
10Menu functions13
11Maintenance13
12Pump Curve and Data14
2
Page 3
Technical Data
Electrical Details
Supply Voltage
Full Load Current
Start Current
Fuse Rating
Max Load BMS Relays
Connection Details
W ater Inlet
Water Outlet
Maxi SingleMaxi Plus
230 Volt
2.5 Amp
2.5 Amp
5 Amp
5 Amp
Maxi Single (HP)Maxi Plus (HP)
230 Volt
4.5 Amp
4.5 Amp
8 Amp
5 Amp
15mm Compression
15mm Compression
230 Volt
2.5 Amp
2.5 Amp
5 Amp
5 Amp
230 Volt
4.5 Amp
4.5 Amp
8 Amp
5 Amp
3/4” BSP
Max Coldfill PressureMaxi 3.0 Bar / Maxi HP 6.0 Bar
Dimensions
Unit Weight
Height
Width
Depth
27 Kg
35 Kg29 Kg38 Kg
600mm
465mm
390mm
3
Page 4
Maxi & Maxi Plus pressurisation units
TheMaxi range is a fully automatic heating / chiller system pressurisation device, and is suitable for the water
management in all domestic and commercialheating and cooling systems. It is supplied as a fully commissioned unit and
should require no "on site" commissioning.
1 Installation
Allproductsshould be installed by a competent person with regard to the relevant requirements of the Health and
Safety Regulations, Building Regulations, IEE Regulations, Water Supply (water
(Scotland) and any other local bye-laws or planning requirements.
Regulations, Water Bye-laws
The
crystal display to be easily read.
Maxi is intended formounting: the unit should be situated in such a position as to enable the liquid
1.1 Mains/boosted cold water supply
TheMaxi is designedto be connected directly to the mains cold water supply, or a boosted cold water supply, the
unit is supplied complete with all necessary isolating valves, but an inlet water isolating valve is recommended. The water
inlet is 15mm compression and should be connected to the mains cold water supply by 15mm copper tube or equivalent
approved plastic pipework. If the
to install a single check valve adjacent to the mains cold water supply.
To reduce the pressure drop on very long supply routes then 22mm supply pipework is recommended.
Maxi is sited some distancefrom the mains cold water supply it may be advisable
4
Page 5
1.2 Connection to the system
The Mikrofill Maxi is connected to the heating/chiller system by way of the 15mm outlet valve, the pipework from the unit
should be made in 15mm copper or similarly approved plastic pipework. A suitably sized expansion vessel should be
incorporated into the system at this point. Please refer to typical installation diagram on page 3. If you require any
assistance regarding vessel sizing please contact our technical sales department. The final connection into the
heating/chiller systemshould be sized accordingly, recommendations are shown below:
For vessel sizes in excess of 1000L capacityplease contact our technical sales department.
IMPORTANT NOTE
The expansion vessel nitrogen/air charge must be set at the same pressure as the cold fill pressure of the system.* All
Mikrofill expansion vessels are factory commissioned to the correct pressure.
* When the installed height of the expansion vessel is different to that of the MAXI then please contact our service
department who will advise on the nitrogen/air charge.
1.3 Overflow connection
The Maxi is supplied with a 3/4" bsp plastic overflow (warning pipe) connection which should be led to a drain and be
visible at point of discharge, MIKROFILL SYSTEMS LTD cannot accept any responsibility for flood damage caused by failure
toconnect the overflow.
The expansion vessel is usually
connected on the inlet side of the
pump on the system return. For
systems exceeding 90oC contact
our technical department for
advice.
See notes on pipework sizing on
page 5.
Mains
cold
water
Overflow
Alternative
pump position
6
Page 7
2 Electrical connections
The Mikroll Maxi requires a permanent 230V 50Hz 1 phase supply rated at 6 amp. The unit is internally fused at 5 amp
(seeelectrical installation diagram).
The Maxi also incorporates two BMS relays oering volt free contacts for the remote indication of high or low pressure
conditions within the heating/chiller system. These relays are also independently fused at 5 amp to protect the Mikroll
Maxi from external electrical faults. A further volt free rel
control circuits. Should either of the alarmrelays operate then the relay will shut down the boiler or chiller, indication of
any alarm situation will be indicated onthe display. The relays aresuitable for use oncontrol voltages up to 250V.
Once the Mikroll Maxi has been correctly connected the unit is ready for use. Ensure that the unit has anadequate water
supply and the servicevalves are open. Check for wat
to vent the pump(s) before operation. This is achieved by slackening the brass plug (14mm A/F).situated on the pump
ho
using, until all air is eliminated. Switch on electrical supply to the unit and the on/o switch to the lower right hand
side of the unit and the unit will start to pressurise the system. When the system has achievedthe set pressure, the unit
will stop lling, and go tostandby.
Important note, " pump type" pressurisation units are not designed to ll systems fromempty, they are only capable of " top
up" and pressurisation. The systemshould be lled by other means in compliance with the water regulations. The Mikroll
Maxi is capable and approved to ll heating/chiller systems.
ay is included in the unit, this is to interlock the boiler or chiller
er leaks. Although every Maxi unit is factory tested it is still advisable
2.1 Electrical diagram
Electrical data
Supply: 230V 1ph 6 amp
Full loadcurrent: 2.5 amp
Start current: 4.5 amp
Fuserating: 5 am p / 8 amp
BMS relays and boiler/chiller
relays: volt free contacts rated
at 250VAC at 5 amp
All relays are independently
fused at 5 amp
Low pressurealarm High pressurealarmBoiler/chiller
common alarm
230 VAC 50Hz
7
Page 8
3 Keypad function
System Data Button
This button operates a scroll function normally for information only. When in the service mode, it allows selection
of particular setting parameters.
Button - used when in service mode to increase parameter values
Button - used when in service mode to decrease parameter values
Service Mode
A multi-function button that, when in operational mode, is used to mute alarm conditions. In normal mode the
keypad buttons are for information only and do not affect any of the parameters preset in the service mode.
( For information on service mode see section 8,page12 )
4 Status Display
4.1 Pressure Correct
The Maxi continuously monitors the system pressure, when the system pressure is within the set parameters the unit
will show Pressure Correct on the LCD display
4.2 Hours run /water usage
This is accessed by scrolling the system data button.
4.3 Hours run / water usage reset
This is achieved by depressing the buttons simultaneously.
8
Page 9
5 Alarmconditions
Please note the Maxi is a factory pre-commissioned product, should you require to change any of the preset parameters pleasesee "Settings" .
5.1 Low water level alarm
The Maxi continuously monitors the water level in the feed tank. If this falls to below an acceptable level then the unit will
operate a safety shut down. When water level is reinstated the unit will automatically reset.
Optional system failure/leak alert
5.2
The Maxi can differentiate between normal system fill rates and excessive water demand usually due to a severe
system leakage. If this situation occurs the Maxi will shut down, and issue a leak alert warning showing ‘System
Failure’ on the LCD. This alert must be reset manually, by switching off the Maxi and switching back on. If the
leak has been rectified the unit will operate as normal.
In some cases it may be required to disable or enable the leak alert facility.
To disable/enable the leak alert press and hold the service button until the display shows ‘ Service mode’
on the LCD display. Use the system data button to scroll through the settings to leak alert and enable /
disable using the or buttons
5.3 High or low pressure alarms
If, for any reason the system water pressure reaches a high or low condition, as determined by the preset parameters the
LCDwill show the alarmmessage, the relevant BMS relay will operate and the Boiler/chiller control relay will shut down the
boiler or chiller. When normal operating pressure is resumed the unit will automatically reset,
5.4 Pump failure
The Maxi can alsodetermine whether a pumphas developeda fault. This is achieved bymonitoring the system pressure and
if an increase in pressure is not sensed in a set period of time it will stop operation of that pump and the " pump failure"
message will appear on the LCD. If the Maxi Plus is used, it will automatically change to the remaining pump, and a pump
failure message will be displayed.
9
Page 10
5.5 Frequent use alarm
This alarmis to assist in diagnosing any leaks that may be present inthe heating (or cooling system). If in any 24 hr period
the Maxi operates more than a preset limit i.e. 5, then a frequent use alarmwill show, (the operation of the system will not
be affected, this function is for information only).
5.6 Frequent use reset
This is achievedby switchingthe power supply to the unit off and on again.
10
Page 11
6 Fault diagnosis
System faults will be apparent from the alarm message displayed. The Maxi itself has a full self-diagnostic
microprocessor unit which continually self-checks the operation. If an internal fault is diagnosed then the fault will
be displayed on the screen, e.g. sensor failure.
Fault conditions
Fault indications
Low water level
Sensor failure
Low pressure alarm
High pressure alarm
Cause
No water in tank
Possible sensor fault
Incoming voltage instability
Systempressure low
Systempressure high
Remedies
Reinstate water supply to tank
1. Switch unit off and back on, if sensor failure does not
reappear on the display see note 2. If sensor failure does
reappear check sensors are connected to the printed
circuit board correctly. If the problem persists ring our
service department.
2. If this occurs switch the unit off and back on, the unit
should then operate as normal. If this fault appears on
a regular basis then a mains electrical filter (anti surge
device) is required. Ring our service department for
advice.
Check system for leaks. Switch unit off and back on to
reinstate. Check Low Alarmsetting.
Reduce pressure in system and check expansion vessel
air charge/size. Check High Alarmsetting.
Systemfailure
Pump failure
Frequent use alarm
The Mikrofill Maxi and Maxi Plus have been designed such that most apparent 'faults' can be
remediedon site, if in doubt ring our service department on08452 606020
Possible excess water leak
on the system
Possible pumpfault
Possible persistent leak on
system
Check system for leaks, then switch unit off and back on
toreinstate.
Switch unit off and back on to reinstate, if pump does
not operate when required replace pump.If pump
operates, dry run setting may need to be increased.
If the unit operates more than the set value in a 24hr
period the unit will bring up the frequent use alarm, this
will not stop the unit from operating but indicates that
there may be a small leak on the system. Switch the unit
off and back on to reinstate. Investigate possible leak.
11
Page 12
7 Manual override
In the unlikely event of a sensor failure the unit may give incorrect readings and could cause alarm conditions. If this
occurs, a manual override can be employed by depressing the and the service mode buttons simultaneously
for 3 seconds; thus reinstating the BMS relays in the unit. Before operating the manual override you must ensure there
is sufficient pressure in the system. The manual override must not be employed if the unit has shown a flood
alarm condition or, if there is insufficient pressure in the system.
8 Audible alarm mute
If the Mikrofill Maxi does indicate a fault, an audible alarm will sound. This can be muted by depressing the
service mode button.
9 Service Mode ( adjusting settings )
The settings can be adjusted on site as follows:
9.1 Press and hold the service mode button for approx 8 seconds
9.2 The display will indicate that you are now in the service mode
9.3 Use the system data button to scroll through the settings, each setting can be adjusted by use of the
buttons.
9.4 After adjusting the settings, the unit will return to its normal operating mode approximately 30 seconds after
release of the buttons.
12
Page 13
10 Menu Functions
Cold fill pressure - this is the required pressure of the system when the system is cold
Alarm low - the pressure at which the low pressure alarm relay will operate. Usually set 0.6 - 0.7 bar below
the cold fill pressure.
Alarm high - the pressure at which the high pressure alarm relay will operate. Usually set 0.2 bar below the
system safety valve setting.
Usage - for information on water used in the system, no setting required - please note, to zero the usage, the
buttons need to be pressed simultaneously for 3 seconds.
minutes ) the less responsive the flood protection, set at 0.00 to disable pump failure.
O&M Maxi 1109
prevents under shoot, decreasing time prevents over shoot.
Frequent use - this setting warns of frequent use which would indicate a system leak and will show a
warning message if in any 24hr period the unit operates in excess of the frequent use setting.
caused when pumps start.
Contrast adjust - alters the contrast of the LCD display.
Fault log - Logs the last five faults
MP - Low mains water pressure
LP - Low system pressure alarm
HP - High system pressure alarm
SF - Sensor failure
DR - Leak alert due to no increase in pressure while filling
FS - Leak alert due to drop in pressure while filling
11 Maintenance
Maxi - The filter which is housed in the inlet ball valve to the pump should be checked and cleaned annually.
EXPANSION VESSELS - Charge pressure should be checked annually, when the system is cold the air charge must be
equal to the cold fill pressure of the Maxi.
13
Page 14
12 Pump Curve and Data
7
6
5
4
3
Head (bar)
2
1
0
05101520253035
PRODUCT DATA
Mikrofill Pump Range Performance
Maxi Pump
Maxi HP Pump
Flow (l/min)
Pump
Max
Pressure
(bar)
Max
Flow
(l/min)
Input
Power
(W)
Current
(A)
Supply
Voltage
Frequency
Size (mm)
L x W x H
Weight
(kg)
Maxi Pump 3.65 29 510 2.53 230V ± 10%50 Hz 210 x 145 x 1858.3
Maxi HP 6.2 31 960 4.3 230V ± 10%50 Hz 220 x 145 x 1859.5
14
Page 15
Page 16
Mikrofill Systems Ltd
West Court
Merse Road
Redditch
B98 9HL
T
+44 (0) 8452 606020
F
+44 (0) 8452 606021
W
mikrofill.com
E
info@mikrofill.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.