Mikrofill 3 Technical Documentation Manual

PRESSURISA TIO N U NIT
MIKROFILL 3 PRESSURISATION UNIT
TECHNICAL DOCUMENTATION
ISSUE 12/15 Rev. 01
INSP I R E D E FFI C IENC Y
TABLE OF CONTENTS
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Technical Data
Electrical Details Connection Details Installation Mains / Boosted Cold Water Supply Fill Pressure Connection to the System Drain Dimensions Diagram of a Typical Installation Wall Mounting Plate Dimensions for Fixing
Electrical Connections
Electrical Diagram Electrical Data
Keypad Functions
System Data Up Power Down Service Mode
Status Display
Pressure Correct System Filling Filling Stopped due to Low Mains Water Pressure Frequent Use
Service Mode
Adjusting Settings
Parameter Functions
Fault Diagnosis
Status / Fault Conditions Status / Fault Conditions continued.
Manual Override
Component List
Maintenance
Removing the Controls Assembly Cleaning the Solenoid Valves Cleaning the Inlet Ballofix Valve
Declaration of Conformity
04
05
06
07
08
09
10
10
11
12
13
14
14
15
16
17
18
TECHNICAL DATA
WRAS Approval Number:
ELECTRICAL DETAILS
• Supply Voltage:
• Full Load Current:
• Start Current:
• Fuse Rating:
• Maximum Load BMS Relays:
CONNECTION DETAILS
• Cold Water Inlet:
• System Outlet:
• Drain (via Tundish):
• Maximum Inlet Pressure:
• Maximum Cold Fill Pressure:
•Nominal Flow Rate:
•Dry Weight:
1806078
230 Volt
1 Amp
1 Amp
3 Amp
5 Amp
15mm Compression
15mm Compression
¾” BSP
5 Bar
4.7 Bar
14 l/min at 2 Bar
5 kg
TECHNICAL DATA
The Mikrofill 3 is a fully automatic sealed system filling device and is suitable for the water management in domestic and commercial heating and cooling systems. It is designed for use in a normal environment. It is not
suitable for installation outside, or in environments where there are excessively cold temperatures.
INSTALLATION
All Mikrofill products should be installed by a competent person with regard to the relevant requirements of the Health and Safety Regulations, Building Regulations, IEE Regulations, Water Supply (Water Fittings) Regulations, Water By-laws (Scotland) and any other by-laws or planning requirements.
The Mikrofill 3 is WRAS approved with certificate number 1806078.
It is intended for wall mounting (see page 08) and should be mounted at such a height as to enable the display to be easily read.
MAINS / BOOSTED COLD WATER SUPPLY
The Mikrofill 3 is designed to be connected directly to the mains cold water supply, or a boosted cold water supply. The unit is supplied complete with all necessary isolating valves and incorporates a basket filter in the inlet ballofix valve.
A flexible hose is supplied with the unit which MUST be connected to the inlet ballofix valve, as shown in the diagram to the left. Failure to do so may result in damage to the inlet pressure sensor due to water hammer, resulting in a SENSOR FAILURE. Under such circumstances, this would not be considered a warranty fault.
The water inlet connection is 15mm compression and should be connected to the mains cold water supply by 15mm copper pipe or equivalent approved plastic pipework.
If the Mikrofill 3 is sited some distance from the mains cold water supply it may be advisable to install a single check valve adjacent to the mains cold water supply.
To reduce the pressure drop on very long supply routes 22mm supply pipework is recommended.
FILL PRESSURE
The Mikrofill 3 is capable of filling a system to within 0.3 bar of its current inlet water pressure.
Where the incoming water pressure exceeds 5 bar please contact our technical department on 03452 60 60 20 for further installation information.
FLEXIBLE HOSE
TECHNICAL DATA
CONNECTION TO THE SYSTEM
The Mikrofill 3 is connected to the system by way of the 15mm outlet isolation valve. The pipework from the unit should be made in 15mm copper or similarly approved plastic pipework. A suitable sized expansion vessel should be incorporated into the system at this point (please refer to the typical installation diagram on page 07 for more information).
Please contact our technical department on 03452 60 60 20 if you require any assistance regarding vessel sizing.
The final connection into the system should be sized accordingly, recommendations are shown below:
• Vessel size up to ½”
• Vessel size up to ¾”
• Vessel size up to 1”
For vessel sizes in excess of 1000L capacity please contact our technical department.
IMPORTANT NOTE:
DRAIN
Following every fill procedure the unit will discharge a small amount of water, establishing an air break. For this, the unit is supplied fitted with a ¾” BSP tundish, which must be connected to a suitable drain.
Mikrofill Systems Ltd. cannot accept responsibility for any consequential damage caused by failure to connect the tundish to a suitable drain.
100L: 300L:
1000L:
(15mm) expansion pipework (22mm) expansion pipework (28mm) expansion pipework
The expansion vessel air / nitrogen charge must be set to the same pressure as the cold fill pressure of the system.
If the installed height of the expansion vessel is different to that of the unit then please contact our technical department who will advise on the air / nitrogen charge required.
A suitably sized pressure relief / safety valve MUST be fitted on all sealed systems.
Loading...
+ 14 hidden pages