Mighty Module MM1520, 1521, 1524 User Manual

MM1520, 1521 and 1524
STRAIN GAUGE INPUT
DUAL LIMIT ALARMS
DESCRIPTION
The MM1520 Series Strain Gauge input alarms monitor a DC input signal from a strain gauge or bridge and provide dual setpoint alarm outputs when the input exceeds the alarm values. Each unit can be supplied as a HI/HI, HI/LO or LO/LO alarm. The output relays are normally de-energized, and energize for an alarm condition. Two sets of red/green LED indicate alarm status to make setup easier. Deadband on both alarms is fixed at 0.25% of span.
MODEL NUMBERS
These instructions cover the following setpoint styles:
MM1520 Strain Gauge Input Dual Alarm
(25-turn screwdriver adj)
MM1521 Strain Gauge Input Dual Alarm
(Single turn dial)
MM1524 Strain Gauge Input Dual Alarm
(10-turn precision dial)
OPTIONS
These instructions cover the following op­tions on the MM1520. Options installed are listed on the label attached to the side of the module.
H/H, H/L, L/L H = High alarm.
Alarm occurs on an increasing signal.
L = Low alarm.
Alarm occurs on a decreasing signal.
NO/NC
Normally open or normally closed relay contacts: (see specifications)
R The Normal condition for the relays is
de-energized. They energize for alarm conditions. Option R (Reverse sense) reverses this logic (Failsafe).
U All circuit boards conformal coated for
protection against moisture.
CONTROLS
The MM1520, MM1521 and MM1524 mod­ules contain two setpoint controls, zero and span adjustments, plus a bridge excitation voltage adjustment. The setpoint control in the MM1520 is a 25-turn blind trimpot. MM1521 and MM1524 contain 1-turn and 25­turn respectively.
CALIBRATION
Modules are shipped with ZERO, SPAN and excitation voltage precalibrated. The user needs only adjust the SETPOINT and DEADBAND for the desired response.
Refer to the instrument's label to determine your instrument's supply voltage and input and output ranges. Refer to the "BLOCK DIAGRAM AND PIN CONNECTIONS" for pin connections.
Connect the alarm input to its mating input device, or to a precision resistance bridge capable of simulating the input device.
(If it is necessary to recalibrate using electronic inputs, refer to the ELECTRONIC CALIBRATION section.)
To calibrate the alarm setpoints, adjust the input to the desired alarm 1 setpoint. Adjust the SETPOINT 1 control until its LED switches to red (ccw for a high alarm, cw for low).
Change the input to the desired alarm 2 setpoint and similarly adjust the SETPOINT 2 control.
If there is a need to recalibrate ZERO, SPAN and excitation voltage, proceed as follows:
Measure the voltage between +EXC & -EXC VOLT ADJ control for the desired excitation voltage. The voltage is adjustable from 4 to 12 VDC.
Set the input to the low end of the input range. Turn the SETPOINT 1 control fully ccw. Adjust the ZERO control until the SETPOINT 1 LED color switches.
Change the input to the high end of the input range. Turn the SETPOINT 2 control fully cw. Adjust the SPAN control until the SETPOINT 2 LED color switches.
Repeat until the ZERO and SPAN settings are both correct. After adjusting the ZERO and SPAN controls, the SETPOINT controls should be reset as described above.
ELECTRONIC CALIBRATION
If it is necessary to recalibrate using electronic inputs, proceed as follows:
Measure the voltage between +EXC and
-EXC using a precision digital voltmeter. Connect a calibrated millivolt signal source between the +SIG and -SIG inputs. Determine the input voltage required at each calibration point. The required voltage equals the bridge sensitivity in millivolts per volt, multiplied by the excitation voltage. For example, a sensitivity of 2 mV/V multiplied by 10 V excitation results in a 20 mV input signal.
RELAY CONTACT PROTECTION
When inductive loads such as motors, relays or transformers are switched, voltage tran­sients may be generated which exceed the ratings of the relay contacts. The resulting arcing can quickly destroy the contacts. (Refer to the SPECIFICATIONS for the relay contact ratings.)
Surge supression is required across induc­tive loads to guard against premature relay failure. FIGURE 1 illustrates diode surge supression for a DC load. The diode's oper­ating (peak inverse) voltage should exceed the load's supply voltage by at least 50% and should have a current rating of at least one ampere.
FIGURE 2 shows surge suppression for an AC load, using an MOV (Metal Oxide Varis­tor) and a capacitor. The breakdown voltage ratings of both the MOV and the capacitor must exceed the peak AC voltage.
With normal sine-wave power, PEAK = 1.414 x RMS voltage. For 115 VAC power a 200 volt peak rating is recommended.
1 2
SPECIFICATIONS
Input Span Limits
0.5 mV/V to 1 V/V
Input Impedance
200 kilohms
Excitation
adjustable 4 V to 12 V, 40 mA max
Excitation Stability
+0.005% per °C
Deadband
0.25% to 100% of span
Setpoint (Each alarm)
0 to 100% of span
Response Time
100 milliseconds
Stability
+0.04% of span per °C
Common Mode Rejection
120 dB, DC to 60 Hz
Operating Temperature
0 °C to 60 °C / 32 °F to 140 °F
Relay Contacts (SPST)*
Resistive Load: 5 A max, 150 W max,
220 VAC max, 30 VDC max Inductive Load : 1/8 HP max at
120/240 VAC
Power Options
115 or 230 VAC, 50 or 60 Hz 12 V or 24 VDC, 2.5 W max
*Due to pins available, only one set of contacts is available for each relay.
WARRANTY
The Mighty Module Series of products carry a limited warranty of 10 + 5 years. In the event of a failure due to defective material or workmanship, during the 10 year period, the unit will be repaired or replaced at no charge. For a period of 5 years after the initial 10 year warranty, the unit will be repaired, if possible, for a cost of 10% of the original purchase price.
Relays are not covered by the warranty.
MOUNTING
MM1520, MM1521 and MM1524 are designed to plug into a standard 11-pin relay socket. (MP011) is a 11-pin socket suitable for mounting on a flat surface or in a piece of PVC track.
Spring holddown clips are available for install­ations where vibration may be a problem. Use (CLP1) for MM1520 and (CLP2) for MM1521 and MM1524.
A DIN rail mounted socket (DMP011) is available for 35mm symmetrical rail.
CASE DIMENSIONS INCHES (mm)
MM1520, MM1521 and MM1524
Specifications are subject to change without notice. ©2008 Wilkerson Instrument Co., Inc. DWG#101320B 3/15
3 4
Loading...