Miele MNTSVBE User Manual

INSTALLATION INSTRUCTIONS
B-VENT MULTI-OPEN
This appliance may be installed in an aftermarket perma­nently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
In the Commonwealth of Massachusetts & New York:
Installation must be performed by a licensed plumber or gas fitter. See Table of Contents for location of additional New York & Commonwealth of Massachusetts requirements.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING: IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO­SION MAY RESULT CAUSING PROPERTY DAM­AGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors or liquids in the vicin­ity of this or any other appliance.
FOR YOUR SAFETY: What to do if you smell gas:
ELITE
B-VENTED GAS FIREPLACES P/N 850,025M REV. B 01/2007
SERIES
MODELS
sledoMtlovilliMsledoMcinortcelE
MNTSVBEMPTSVBEENTSVBEENRCVBE MNFPVBEMPFPVBEENFPVBEENLCVBE
MNRCVBEMPRCVBE
MNLCVBEMPLCVBE
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE POUR RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE BLESSURE OU LA MORT.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser d'essence ni d'autre vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
®
• DO NOT light any appliance.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow your gas suppliers instructions.
• If your gas supplier cannot be reached, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
OTL Report No. 116-F-07A-5
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une odeur de gaz:
Ne pas tenter d'allumer d'appareil.
Ne touchez à aucun interrupteur. Ne pas vous servir
des téléphones se trouvant dans le batiment où vous vous trouvez.
Evacuez la piéce, le bâtiment ou la zone.
Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suivez les instructions du fournisseur.
Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service dos incendies.
L'installation et service doit être exécuté par un qualifié installeur, agence de service ou le fournisseur de gaz.
1
TABLE OF CONTENTS
Packaging ........................................ page 2
Introduction ..................................... page 2
General Information......................... page 2
Massachusetts and New York
Requirements ................................ page 2
Location .......................................... page 4
Appliance and Vent Clearances ....... page 4
Vent Termination Clearances ........... page 4
Typical Installation Sequence .......... page 4
Detailed Installation Steps ............... page 5
Step 1. Framing ............................. page 5
Step 2. Routing Gas Line ............... page 5
Step 3. Install the Venting System. page 5
Fireplace Specifications ................... page 6
Step 4. Field Wiring ....................... page 10
Step 5. Connecting Gas Line.......... page 11
Step 6. Outside Air Kit Installation . page 12
Step 7. Installing Logs................... page 13
Step 8. Checking Unit Operation ..... page 13
Step 9. Installing Glass Enclosure
Panels.......................................... page 13
Step 10. Burner Adjustment ............ page 14
Step 11. Spillage Test and Safety
Limit Switch Operation ................ page 14
Step 12. Hood Installation ............... page 15
Finishing Requirements ................... page 15
Cold Climate Insulation.................... page 15
Gas Conversion Kits.................. page 16
This installation manual will help you achieve a safe, efficient and dependable installation for your appliance and vent system.
Please read and understand these
instructions before beginning your
installation.
PACKAGING
The assembled vented gas fireplace is pack­aged with:
1 - one log set located within the firebox. 2 -one plastic bag containing the literature
package, which consists of the homeowner's manual, installation instructions, log place­ment guide and warranty, 8 (EBVST), 4 (EBVPF, EBVCL and EBVCR) nailing flanges; plastic bag is located on top of the fireplace.
3 -two hoods (EBVST, EBVCR, EBVCL), or
three hoods (EBVPF) taped to the top of the fireplace.
4 - one plastic bag of glowing embers, one
plastic bag of decorative volcanic stone and one bag of vermiculate is located in the bottom compartment.
INTRODUCTION
These vented gas fireplaces are designed for residential applications. They must be installed with approved type-B, 6 in. double wall vent pipe systems routed to the outside atmosphere.
The millivolt appliances are designed to operate on either natural or propane gas. A millivolt gas control valve with piezo ignition system provides safe, efficient operation. If any optional accesso­ries which require electrical power are being installed, the electrical power must be provided at the time of appliance installation.
Electronic appliances are designed to operate on natural or propane gas. An electronic inter­mittent pilot ignition system provides safe, efficient operation. External electrical power is required to operate these units.
These appliances comply with National Safety Standards and are tested and listed by Omni­Test Laboratories (Report No. 116-F-07A-5) to ANSI Z21.50 - 2003 (in Canada, CSA 2.22 -
2003), and CAN/CGA-2.17-M91 in both USA and Canada, as vented gas fireplaces.
Massachusetts And New York City, NY Requirements
These appliances are approved for installation in the following USA locations listed in the following:
Massachusetts:
Installation of these fireplaces are approved for installation in the US state of Massachu­setts if the following additional requirements are met-
Installation and repair must be done by a plumber or gas fitter licensed in the Common­wealth of Massachusetts.
The flexible gas line connector used shall not exceed 36 inches (92 centimeters) in length.
The individual manual shut-off must be a T­handle type valve.
New York City, NY:
Installation of these fireplaces are approved for installation in New Your City in the US state of New York, if the following additional re­quirements are met-
An outside air kit (FOAK-4 or FOAK-4LD) must be installed.
GENERAL INFORMATION
WARNING: THESE FIREPLACES ARE VENTED DECORATIVE GAS APPLIANCES. DO NOT BURN WOOD OR OTHER MATE­RIAL IN THESE APPLIANCES.
Note: Installation and repair should be per-
formed by a qualified service person. The appli­ance should be inspected annually by a quali­fied professional service technician. More fre­quent inspections and cleanings may be re­quired due to excessive lint from carpeting, bedding material, etc. It is imperative that the control compartment, burners and circulating air passage ways of the appliance be kept clean.
TYPICAL INSTALLATION
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
2
These appliances may be used for bedroom installations in the United States and are listed accordingly. These units may not be installed in bedrooms in Canada.
Installation must conform to local codes. In the absence of local codes, installation must com­ply with the current National Fuel Gas Code, ANSI Z223.1. (In Canada, the current CAN-1 B149 installation code.) Electrical wiring must comply with the National Electrical Code ANSI/ NFPA 70 - (latest edition). (In Canada, the current CSA C22-1 Canadian Electrical Code.)
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Offset Venting
Vertical Venting
Figure 1
S'assurer que le brùleur et le compartiment des commandes sont propres. Voir les instruc­tions d'installation et d'utilisation qui accompagnent l'appareil.
Provide adequate clearances around air open­ings and adequate accessibility clearance for service and proper operation. Never obstruct the front, back and/or side viewing surfaces of the appliance.
These appliances are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the perfor­mance of this system and may be dangerous.
Millivolt Models -
Millivolt models come standard with the manually-modulated gas valve; flame ap­pearance and heat output can be con­trolled at the gas valve. Input of millivolt models is shown in the following table:
sledoMtlovilliM
enaporPdnalarutaN
sledoMsaG
,MNFPVBE,MNTSVBE
,MPFPVBE,MPTSVBE
,MNRCVBE,MNLCVBE
MPRCVBE,MPLCVBE
Electronic Models -
Electronic models have a fixed rate gas valve. Input of electronic models is shown in the following table:
*sledoMcinortcelE
sledoMsaGlarutaN
,ENFPVBE,ENTSVBE005,73
,ENRCVBE,ENLCVBE000,43
* See page 16 for Electronic Models conversion from Natural gas to Propane.
All Models -
Maximum manifold pressure is 3.5 in. w.c. (0.87 kPa) for natural gas and 10 in. w.c. (2.49 kPa) for LP/Propane gas.
Installations at Altitudes of 0 to 4500 ft.­Units are tested and approved for elevations of 0 to 4500 feet (0 to 1372 meters).
Installations at Altitudes above 4500 ft.­For elevations above 4500 feet (1372 meters), install the unit according to the regulations of the local authorities having jurisdiction and, in the USA, the latest edition of the National Fuel Gas Code (ANSI Z223.1) or, in Canada, the latest edition of the CAN1-B149.1 and .2 codes.
)H/UTB(etartupnI
detaludom-yllaunaM
005,73OT000,03 000,43OT000,72 000,43OT000,82 000,43OT000,72
)H/UTB(etartupnI
etaRdexiF
Table 1
shows the units' gas orifice size
for the elevations indicated.
.taN.porP
23#05#
43#05#
ezisecifirO
noitavelE
)sretem(teeF
0054-0
)2731-0(
ledoM
.oN
TSVBE FPVBE
RCVBE LCVBE
Table 1
The millivolt appliances are manually controlled and feature a spark ignitor (piezo) that allows the appliance's pilot gas to be lit without the use of matches or batteries. This system will still function in the event of a power outage.
Do not use these appliances if any part has been under water. Immediately call a quali­fied, professional service technician to inspect the appliance and to replace any parts of the control system and any gas control which have been under water.
Ne pas se servir de cet appareil s'il a été plongé dans l'eau, complètement ou en partie. Appeler un technicien qualifié pour inspecter l'appareil et remplacer toute partie du système de contrôle et toute commande qui ont été plongés dans l'eau.
This appliance may be installed in an af­termarket permanently located, manufac­tured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This ap­pliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil peut être installé dans un maison préfabriquée (É.-U. seulement) ou mobile déjà installée à demeure si les réglements locaux le permettent.
Cet appareil doit être utilisé uniquement avec les types de gaz indiqués sur la plaque signalétique. Ne pas l'utiliser avec d'autres gaz sauf si un kit de conversion certifié est installé.
Test gage connections are provided on the front of the millivolt gas control valve (iden­tified IN for the inlet and OUT for the mani­fold side). A ¹⁄₈" NPT test gage connection is provided at the inlet and outlet side of the electronic gas control valve.
Minimum inlet gas pressure to these appliances is 5.0 inches water column (1.24 kPa) for natural gas and 11.0 inches water column (2.74 kPa) for propane for the purpose of input adjustment.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Maximum inlet gas supply pressure to these appliances is 10.5 inches water column (2.61 kPa) for natural gas and 13.0 inches water column (3.23 kPa) for propane.
These appliances must be isolated from the gas supply piping system (by closing their individual manual shut-off valve) during any pressure test­ing of the gas supply piping system at test pressures equal to or less than ¹⁄₂ psig (3.5 kPa).
These appliances and their individual shut-off valves must be disconnected from the gas supply piping system during any pressure testing of that system at pressures in excess of ¹⁄₂ psig (3.5 kPa).
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air immediately. Turn off the gas supply to the appliance and have it ser­viced by a qualified professional, as it may not be operating correctly.
WARNING: B-VENT APPLIANCES ARE NOT DESIGNED TO OPERATE IN NEGATIVELY PRESSURED ENVIRONMENTS (PRESSURE WITHIN THE HOME IS LESS THAN PRES­SURES OUTSIDE). SIGNIFICANT NEGA­TIVELY PRESSURED ENVIRONMENTS CAUSED BY WEATHER, HOME DESIGN, OR OTHER DEVICES MAY IMPACT THE OPERATION OF THESE APPLIANCES. NEGATIVE PRESSURES MAY RESULT IN POOR FLAME APPEARANCE, SOOTING, DAMAGE TO PROPERTY AND/OR SEVERE PERSONAL INJURY. DO NOT OPERATE THESE APPLIANCES IN NEGATIVELY PRES­SURED ENVIRONMENTS. PROVIDING AD­EQUATE VENTILATION TO THE APPIANCE FOR COMBUSTION AIR WILL ELIMINATE A NEGATIVE PRESSURE ENVIRONMENT.
WARNING: FAILURE TO COMPLY WITH THE INSTALLATION AND OPERATING IN­STRUCTIONS PROVIDED IN THIS DOCU­MENT WILL RESULT IN AN IMPROP­ERLY INSTALLED AND OPERATING AP­PLIANCE, VOIDING ITS WARRANTY. ANY CHANGE TO THIS APPLIANCE AND/OR ITS OPERATING CONTROLS IS DANGER­OUS. IMPROPER INSTALLATION OR USE OF THIS APPLIANCE CAN CAUSE SERI­OUS INJURY OR DEATH FROM FIRE, BURNS, EXPLOSION OR CARBON MON­OXIDE POISONING.
3
Corner - Right
(EBCR-2)
**See-Through
(EBST-2)
Peninsula
(EBPF-2)
*See-Through
one side flush with a wall
Figure 2
WARNING: CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES. USE CAUTION AROUND THE APPLIANCE TO AVOID BURNS OR CLOTHING IGNITION. YOUNG CHILDREN SHOULD BE CARE­FULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE.
TYPICAL LOCATIONS
Corner - Left
(EBCL-2)
Bay
(EBBAY)
(EBST-2) -
*When See-Through (EBST-2) is installed with one side flush with a wall,opposite wall must not extend beyond either viewing side of the fireplace.
**
When See-Through (EBST-2) is installed in the middle of a room, do not extend side walls beyond either viewing side of the fireplace.
APPLIANCE AND VENT CLEARANCES
The appliance is approved with zero clear­ance to combustible materials on all sides (as detailed in tion: When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit.
Table 2)
, with the following excep-
Gas vent caps that are located 8' or more from a portion of a building which extends at an angle greater than 45° upward from the hori­zontal may terminate in accordance with
ure 3 )
, provided that in no case shall any
(Fig-
discharge opening on the cap be less than 2' (610 mm) horizontally from the roof surface (National Fuel Gas Code ANSI Z223.1 (NFPA
54) 7.6.2) (CAN/CGA B149).
These instructions should be used as a guideline and do not supersede local codes in any way.
Multiple Terminations – These appliances may vent adjacent to and at the same level with any other gas appliances (including di­rect-vent appliances) provided that there is at least 2 ft. (0.6m) between the proximal edges of the vent caps. These appliances may be vented adjacent to a chimney vent servicing a solid fuel fireplace provided the B-vent cap is at least 2 ft. (0.6m) away from the nearest point of the chimney opening.
Note: Venting terminals shall not be recessed into a wall or siding.
WARNING: DO NOT PLACE CLOTHING OR OTHER FLAMMABLE MATERIALS ON OR NEAR THIS APPLIANCE.
AVERTISSEMENT: SURVEILLER LES ENFANTS. GARDER LES VÊTEMENTS, LES MEUBLES, L'ESSENCE OU AUTRES LIQUIDES À VAPEUR INFLAMMABLES À COTE DE L'APPAREIL.
These appliances are equipped with an inte­gral combustion air door and actuator arm. Combustion air kits are optional.Install as shown in Step 6 on page 12.
LOCATION
In selecting the location, the aesthetic and func­tional use of the appliance are primary concerns. However, vent system routing to the outside atmosphere and access to the fuel supply are also important. Consideration should be given to traffic ways, furniture, draperies, etc., due to high surface temperatures ( should also be free of electrical, plumbing or other heating/air conditioning ducting.
The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materi­als. However, if installed on combustible mate­rials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bottom surface must be used.
4
Figure 2
). The location
KCAB
SEDIS
)mm31(.ni2/1
srecaps)mm0(.ni0
)mm31(.ni2/1
srecaps)mm0(.ni0
SRECAPSPOT )mm0(.ni0
ROOLF )mm0(.ni0
mottoBmorF
ottinUfo
)mm6261(.ni46
gnilieC
TNEV )mm4.52(.ni1
SECNARAELCECIVRES
GNIWEIV
-SEDIS KCAB,TNORF(
)sretem9.0(.teeF3
)EDISRO
Table 2
In addition, when the unit is installed in the middle of a room, the side walls surrounding the unit must not extend beyond the front or rear edge of the unit. See
Figure 2
.
Vertical Vent Termination Clearances
Gas Vent Rule – Gas vent caps are not permit-
ted within 8 feet (2.4 mm) of a vertical wall or similar obstruction.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
X
12
Roof Pitch is X/12
Minimum Height from Roof to Lowest Discharge Opening
Minimum Height
Roof Slope
from Roof to Lowest
Discharge Opening
Feet Meters
Flat to 6/12 1' 0" 0.3 Over 7/12 to 9/12 2' 0" 0.6 Over 10/12 to 12/12 4' 0" 1.2 Over 13/12 to 16/12 6' 0" 1.8 Over 17/12 to 21/12 8' 0" 2.4
Figure 3
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation follows, however, each installation is unique resulting in variations to those described.
See the page numbers references in the follow­ing steps for detailed procedures.
Step 1. (page 5) Construct the appliance framing. Position the appliance within the framing and secure with nailing brackets. Step 2. (page 5) Route gas supply line to appliance location. Step 3. (page 5) Install the vent system and exterior termination.
Step 4. (page 10) Field Wiring a. Millivolt Appliances The operating con-
trol switch is factory installed. b. Electronic Appliances – Connect 120 Vac electrical power to the appliance receptacle. Step 5. (page 11) Make connection to gas supply.
Step 6. (page 12) Outside Air Kit Installation Step 7. (page 13) Install the log set, ver-
miculite and glowing embers. Step 8. (page 13) Checkout appliance op­eration. Step 9. (page 13) Install glass enclosure panels.
Step 10. (page 14) Burner Adjustment. Step 11. (page 14) Spillage Test and Safety
Limit Switch Operation.
Step 12. (page 15) Install the hoods.
Top Radiant Panel
Top Bustle
Bottom
Bustle
Unit Parts Identification
Control Compartment Access Panel
Figure 4
3- Open the control compartment access
panel, by actuating the spring-loaded mag­netic catches securing the panel, gently de­pressing the outer top corners of the panel until the catches "pop" the panel free and allowing it to swing out and down to open.
See
Figure 20 on page 12.
4 - Open the latches (located on the left and
right sides of the unit front opening, under the firebox floor) securing the glass enclosure panel. Remove the panel by tilting it outward at the bottom and lifting it up. Set the door aside protecting it from inadvertent damage.
See
Figure 24 on page 13.
Step 1. FRAMING
If the appliance is to be elevated above floor level, a solid continuous platform must be constructed. Headers may be in direct contact with the appliance top spacers but must not be supported by them or notched to fit around them. All construction above the appliance must be self supporting, DO NOT use the appliance for structural support.
Side Nailing Flanges
The fireplace should be secured to the framing at the side(s) and/or rear of the unit using the factory-provided nailing flanges. Install the nail­ing flanges - 8 (EBVST), 4 (EBVPF, EBVCL,
Figure 5
EBVCR) - as shown in
using the existing screws. Position the fireplace within the fram­ing. When required, the flanges may be bent 90 degrees by hand or with the assistance of a hammer. Use wood screws to secure the nailing flanges to the framing.
See Table 2 on page 4
for clearances of framing members to cabinet parts in the nailing flange area. The nailing flange itself is exempt from these clearances.
Floor Nailing Tabs
Secure the fireplace to the floor as shown in
Figure 5.
Step 2. ROUTING GAS LINE
DETAILED INSTALLATION STEPS
The appliance is shipped with all gas controls and components installed and pre-wired.
1 - Remove the shipping carton. 2 - Remove the top radiant panel;
(EBVPF - NO NAILING FLANGES ON END WITH GLASS PANEL)
Nailing
Flanges
Turn tabs down and secure to the floor with 8d nails or other appropriate fasteners on all sides of the unit which do not have viewing glass panels.
EBVST SHOWN
see Figure 4.
Remove these two screws and use them when installing the nailing flanges.
Figure 5
Frame these appliances as illustrated in
Fig­ures 8 (EBVST), 9 (EBVPF), 10 (EBVCL) or 11 (EBVCR) on pages 6 and 7.
All framing details must allow for a minimum clearance to combustible framing members as shown in
Table 2 on page 4
(FOR EBVCR VIEW, INTERCHANGE SIDES)
.
EBVCL SHOWN
Route a ¹⁄₂" (13 mm) gas line as shown in
Figures 8 (EBVST), 9 (EBVPF), 10 (EBVCL) or 11 (EBVCR) on pages 6 and 7
. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations.
All appliances are factory-equipped with a flex­ible gas line connector and ¹⁄₂ inch shutoff valve.
(See step 5 on page 11).
Step 3. Install the Vent System & Exterior Termination -
In the United States, vent installation must conform with local building codes. In the ab­sence of local codes, vents must be installed in accordance with the current edition of the National Fuel Gas Code (ANSI-Z223.1).
In Canada, vent installation must conform with local building codes. In the absence of local codes, vents must be installed in ac­cordance with the current edition of the Na­tional Standard of Canada CAN/CGA-B149.1 or B149.2 Installation Code.
This gas fireplace must be vertically vented using listed 6 in. type-B, double-walled vent pipe and a listed vent termination.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
5
10 ft.
*41¹⁄₂ (1054)
40¹⁄₈
(1019)
EBVPF (Peninsula)
inches (millimeters)
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
6¹⁄₄
(159)
Minimum Framing Stud size is 2 x 4
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm) clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension permits easier fireplace installation, if unit is installed after framing is erected.)
22³⁄₄**
(578)
**Based on 5/8 drywall. Use 23” for 1/2” drywall.
Minimum
Figure 6
FIREPLACE FRAMING SPECIFICATIONS
Minimum
Figure 7
12 ft.
60 degrees
max.
Slip the first 6 inch (152 mm) section of B­Vent over the fireplace flue outlet and secure with four sheetmetal screws (# 8 or larger), and install the remainder of the B-Vent to the outside. Minimum overall height of the vent system and appliance must be 10' (2.54 m) vertical - no offset
(see Figure 6 );
or 12' (3.7 m) when an offset up to 60 degrees from the vertical is used - this offset may start at the fireplace flue collar
(see Figure 7 ).
The maximum overall height of the vent system and appliance should not exceed 40 feet.
Install the B-vent system in accordance with the vent manufacturer's instructions.
CAUTION: THIS APPLIANCE CANNOT BE VENTED HORIZONTALLY.
Note: Refer to the vent manufacturers in-
stallation instructions for variations of vent­ing techniques. If common venting of sev­eral units is contemplated, it should be dis­cussed with an architect and the local Build­ing Department.
Do not place insulation materials within 1 in. of the gas vent system.
EBVST (See-Through)
inches (millimeters)
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm) clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension permits easier fireplace installation, if unit is installed after framing is erected.)
**Based on 5/8 drywall. Use 23 for 1/2 drywall.
Figure 8
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
Minimum Framing Stud size is 2 x 4
41¹⁄₂
(1054)
6¹⁄₄
(159)
22³⁄₄**
(578)
*41¹⁄₂
(1054)
Figure 9
6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
FIREPLACE FRAMING SPECIFICATIONS CONTINUED
EBVCL (Corner-Left)
inches (millimeters)
*41¹⁄₂
(1054)
9³⁄₄
(248)
24
(610)
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm) clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension permits easier fireplace installation, if unit is installed after framing is erected.)
Minimum Framing Stud size is 2 x 4
Center of gas line
is 3 in. (76 mm)
6¹⁄₄
(159)
40¹⁄₈
(1019)
Optional Gas Line
Location Center of gas line
is 3 in. (76 mm) up from floor.
Gas Line
up from floor.
EBVCR (Corner-Right)
inches (millimeters)
40¹⁄₈
(1019)
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm) clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension permits easier fireplace installation, if unit is installed after framing is erected.)
Minimum Framing Stud size is 2 x 4
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
*41¹⁄₂
(1054)
9⁷⁄₈
(251)
24
(610)
Figure 10
Figure 11
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
7
FIREPLACE SPECIFICATIONS
EBVST (See-Through)
Figure 12
1/2
(13)
DETAIL OF FINISH WALL BRACKET
(610)
ELECTRICAL INLETS
GAS INLET
3 (76)
6⁷⁄₈
(175)
40¹⁄₈
20¹⁄₁₆ (510)
B
12 (305)
A - 6 (152) DIA. FLUE OUTLET B - 8 (203) DIA. FLUE COLLAR
FINISH WALL BRACKET
(Front and back edge of unit top)
FRAMING SPACERS
(Top and Both Sides)
A
(1019)
TOP VIEW
¹⁄₂ (13)
CONTROL COMPARTMENT ACCESS PANEL
4⁹⁄₁₆
(116)
3 (76)
4 (102)
37
(940)
¹⁄₂ (13)
40¹⁄₈
(1019)
24
41
(1041)
4⁹⁄₁₆
(116)
FRONT VIEW
(70)
6⁷⁄₈
(175)
RIGHT SIDE VIEWLEFT SIDE VIEW
2³⁄₄
12
(305)
OUTSIDE AIR SHUTTER
ELECTRICAL INLETS
GAS INLET
40¹⁄₈
20¹⁄₁₆ (510)
B
¹⁄₂
(13)
FRAMING SPACERS (Top and Side)
12 (305)
A - 6 (152) DIA. FLUE OUTLET B - 8 (203) DIA. FLUE COLLAR
DETAIL OF
FINISH WALL BRACKET
¹⁄₂
(13)
EBVPF (Peninsula)
Figure 13
FINISH WALL BRACKET
(Front, back, and left edge of unit top)
A
(1019)
TOP VIEW
6⁷⁄₈
(175)
2³⁄₄
(70)
12
(305)
4⁹⁄₁₆
(116)
RIGHT SIDE VIEW
24
(610)
4 (102)
OUTSIDE AIR SHUTTER
41
(1041)
CONTROL COMPARTMENT
LEFT SIDE VIEW
8
FRONT VIEW
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
ACCESS PANEL
37
(940)
ELECTRICAL INLETS
GAS INLET
3 (76)
FIREPLACE SPECIFICATIONS CONTINUED
EBVCL (Corner-Left)
Figure 14
FINISH WALL BRACKET
(Front and left edge of unit top)
20¹⁄₁₆ (510)
A - 6 (152) DIA. FLUE OUTLET B - 8 (203) DIA. FLUE COLLAR
B
A
12 (305)
FRAMING SPACERS
(Top, Side and Back)
DETAIL OF
FINISH WALL BRACKET
¹⁄₂
(13)
24
(610)
LEFT SIDE VIEW
EBVCR (Corner-Right)
Figure 15
41
(1041)
12 (305)
40¹⁄₈
(1019)
¹⁄₂
(13)
TOP VIEW
2³⁄₄
(70)
4 (102)
OUTSIDE AIR
37
(940)
FRONT VIEW RIGHT SIDE VIEW
20¹⁄₁₆ (510)
CONTROL COMPARTMENT ACCESS PANEL
TOP VIEW
B
A
SHUTTER
ELECTRICAL INLETS
GAS INLET
3 (76)
6⁷⁄₈
(175)
A - 6 (152) DIA. FLUE OUTLET
B - 8 (203) DIA. FLUE COLLAR
12
(305)
¹⁄₂
(13)
4⁹⁄₁₆
(116)
DETAIL OF FINISH WALL BRACKET
¹⁄₂
(13)
OUTSIDE AIR SHUTTER
ELECTRICAL INLETS
GAS INLET
3 (76)
6⁷⁄₈
(175)
12
(305)
¹⁄₂
(13)
FRAMING SPACERS (Top, Side and Back)
2³⁄₄
(70)
LEFT SIDE VIEW
40¹⁄₈
(1019)
FRONT VIEW
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
CONTROL COMPARTMENT ACCESS PANEL
FINISH WALL BRACKET (Front and right edge of unit top)
4 (102)
41
(1041)
37
(940)
24
(610)
RIGHT SIDE VIEW
9
Step 4. FIELD WIRING
Refer to Section A for millivolt appliances and Section B for electronic appliances. The gas valve is set in place and pre-wired at the factory on both models.
A. Millivolt Wiring
1. Appliance-mounted ON/OFF burner control
switch (rocker switch) is factory installed in the modesty panel. Optional wall-mounted switch, thermostat, or one of the optional remote control kits may also be used.
2. If wall-mounted ON/OFF control or thermo-
stat is selected, mount it in a convenient location on a wall near the fireplace.
3. Wire the control switch within the millivolt
control circuit using the 15 feet of 2 con­ductor wire supplied with the unit.
Note: The supplied 15 feet of 2 conductor
wire has one end of each conductor con­nected to the gas valve circuit and the other end of each conductor placed loose inside the lower compartment of the unit.
Caution: do not connect the optional wall
switch to a 120V power supply.
4. If an optional control switch is installed,
turn the appliance-mounted ON/OFF burner control switch to the OFF position.
(See Figure 16 )
Millivolt Wiring Diagram
If any of the original wire as supplied must be replaced, it must be replaced with Type AWM 105°C – 18 GA. wire.
White
TH
TP
TP
TH
LIMIT SWITCH
*OPTIONAL WALL-MOUNTED ON/OFF
SWITCH OR OPTIONAL THERMOSTAT
OR OPTIONAL REMOTE RECEIVER
*Turn the appliance-mounted ON/OFF burner control
Thermopile
White
switch to the OFF position if an optional
Black
APPLIANCE-MOUNTED ON/OFF SWITCH
control switch is installed.
Schematic Representation Only
Field Wired Factory Wired
Figure 16
B. Electronic Wiring
(also see Figure 18 on page 11 )
Note: The electronic appliance must be con-
nected to the main power supply.
1. Route a 3-wire 120Vac 60Hz 1ph power
supply to the appliance junction box.
2. Open the control compartment access
panel, by actuating the spring-loaded magnetic catches securing the panel, gently depressing the outer top corners of the panel until the catches "pop" the panel free and allowing it to swing out and down to open.
3. Remove the bottom control compartment
access panel by compressing the spring­loaded hinge pin on the left side until it disengages from the left cabinet panel hole. Pull the panel away from the fire-
See Figure 20 on page 12.
place.
4. Remove the modesty panel by pulling the
bottom edge of the modesty panel out of the locking slots of the cabinet bottom. Then tilt the top edge at a 45° angel and lift out. Remove the modesty panel care­fully, so that none of the wires become loose or disconnected.
5. Remove the outlet receptacle by remov-
ing the two securing screws. See
(The left and right designations used
17.
Figure
here are reversed in EBVCR applications.)
6. Install a field-provided strain relief in the
cabinet knockout opening for the protec­tion of the power supply wires.
7. Connect the power supply wires to the
receptacle as shown in
Figure 18 on
page 11.
8. Connect the ground supply wire and the
green wire attached to the outlet receptacle's green ground screw.
9. Appliance-mounted ON/OFF burner con-
trol switch (rocker switch) is factory in­stalled in the modesty panel. Optional wall-mounted switch, thermostat, or one of the optional remote control kits may also be used.
10
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
FIREBOX BOTTOM
1. If any of the original wire as supplied must be replaced,
1. it must be replaced with Type AWM 105°C – 18 GA.
wire.
2. 120V, 60Hz – Less than 3 amps.
BK
Transf. 120 V.
24 V
Factory Wired Field Wired
BL
Electronic Wiring Diagram (Honeywell)
R
WT
BL
W
Gas Valve
B
APPLIANCE-MOUNTED ON/OFF SWITCH
R
IGNITER
PILOT
ASSEMBLY
BK
Schematic Representation Only
*ON/OFF Switch (Integral
with Gas Valve)
**OPTIONAL WALL SWITCH
OR OPTIONAL THERMOSTAT
OR OPTIONAL REMOTE
RECEIVER
*Leave the ON/OFF switch, which is integral
with the gas valve, in the ON position.
**Turn the appliance-mounted ON/OFF burner control switch to
the OFF position if an optional control switch is installed.
LIMIT SWITCH
WT
G
Junction Box
White
Green
Red
Black
Neutral Side of Receptacle
Tab Intact
Green Ground Screw
Hot Side of Receptacle
Ta b Broken
120 VAC - Black
neerG-dnuo
r
G
Optional
Accessory
Switch
e
tihW
-
lartueN
OUTLET RECEPTACLE
JUNCTION BOX
CABINET
RIGHT SIDE
PANEL
10. If wall-mounted ON/OFF switch or thermo-
stat is to be used, mount it in a convenient location on a wall near the fireplace.
11. If the wall-mounted ON/OFF switch is to be
used, wire it to the the low voltage circuit as shown in
Figure 18.
Note: The supplied 15 feet of 2 conductor wire
has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the lower com­partment of the unit.
12. After wiring is complete, reinstall the out-
let receptacle; install the field-provided the metal junction box cover plate; rein­stall the modesty panel.
OUTLET RECEPTACLE
BOX SECURING SCREW
AND EBCL-2 OUTLET RECEPTACLE SHOWN.
EBCR-2 HAS THE OUTLET RECEPTACLE LOCATED IN
EBBAY OUTLET RECEPTACLE LOCATED IN
THE REAR LEFT CORNER OF THE UNIT
EBST-2, EBPF-2
THE LEFT CORNER OF THE UNIT
VIEW OF RIGHT BOTTOM CORNER OF UNIT
OUTLET RECEPTACLE INSTALLATION
Figure 17
Note: The gas valve ON/OFF switch is shown in Figure 18. It is integral with the gas valve and should be set to the ON position.
IMPORTANT: Ground supply wire must be connected to the green wire attached to the outlet receptacle's green ground screw. See
Figure 18
. Failure to do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70-
Figure 18
(latest edition). (In Canada, the current CSA C22-1 Canadian Electrical Code.)
Step 5. CONNECTING GAS LINE
Make gas line connections. All codes require a shut-off valve mounted in the supply line.
Figure 19 on page 12
illustrates two methods for connecting the gas supply. The flex-line method is acceptable in the U.S., however, Canadian requirements vary depending on lo­cality. Installation must be in compliance with local codes.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
11
Gas Valve
Gas Flex Line Connector
³₈" NPT ₂ ³₈ Flare Fitting
³₈ Flex Tubing
³₈" Flare
¹₂" x
Shut-Off Valve
Step 6. Outside Air Kits – Optional outside make-
up air kits, Model FOAK-4 or FAOK-4LD, may be used with these appliances. Refer to the installa­tion instructions packaged with the air kits for specific installation information. If used, the out­side air kit must be installed before the fireplace is framed and enclosed in the finished wall.
³₈" Nipple
³₈"
Union
³₈" Close Nipple
Figure 19 -
GAS CONNECTION
These appliances are equipped with a gas flex line for use (where permitted) in connecting the unit to the gas line. A gas flex line is provided to aid in attaching the B-vent appliance to the gas supply. The gas flex line can only be used where local codes permit. See
Figure 19
for flex line description. The flex line is rated for both natu­ral and propane gas. A manual shut off valve is also provided with the flex line.
The gas control valve is located in the lower control compartment. To access the valve proceed as follows:
1- Open the control compartment access panel,
(Figure 20 )
by actuating the spring-loaded magnetic catches securing the panel, gently depressing the outer top corners of the panel until the catches "pop" the panel free and allowing it to swing out and down to open.
2- Remove the bottom control compartment
access panel by compressing the spring­loaded hinge pin on the left side until it disengages from the left cabinet panel hole. Pull the panel away from the fireplace.
See
Figure 20.
3- Remove the modesty panel by pulling the
bottom edge of the modesty panel out of the locking slots of the cabinet bottom. Then tilt the top edge at a 45° angel and lift out. Remove the modesty panel care­fully, so that none of the wires become loose or disconnected.
The millivolt control valve has a ³⁄₈" (10 mm) NPT thread inlet port. The electronic control valve has a ¹⁄₂" (13 mm) NPT thread inlet port and is fitted with a ¹⁄₂" x ³⁄₈" (13 mm x 10 mm) NPT fitting.
Secure all joints tightly using appropriate tools and sealing compounds (ensure pro­pane resistant compounds are used in pro­pane applications).
Gas Stub
¹₂
x
³₈" Shut-Off Valve
Hinge Pin
ON/OFF Switch
Piezo Ignitor
Modesty Panel
³₈ "
Reducer
Modesty Panel Lock Slot
Figure 20
Turn on gas supply and test for gas leaks using a soapy water solution. Never use an open
flame to check for leaks.
A. Mix a 50% dish soap, 50% water solution.
B. Light the appliance (refer to the lighting
instructions provided in the Homeowner's Care and Operation Instructions).
C. Brush all joints and connections with the soapy water solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob to the OFF posi­tion. Either tighten or refasten the leaking connection and retest as described above.
D. When the gas lines are tested and leak free, observe the individual tongues of flame on the burner. Make sure all ports are open and producing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.
Gas Valve
Control Compartment Access panel
Outside air drawn into the fireplace supplies air to the fire for combustion. Only one outside air duct is necessary, if installed. See the
Figures on pages 8, 9 and 10
for the location
of the units outside air inlet.
If additional length of duct is necessary, pur­chase locally available U.L. Class 0 or Class 1 metallic ducting. The duct may extend up to 50' (15.24 m) in any direction.
Note: When installing the air duct vertically, DO NOT terminate the duct closer than 3'
below the chimney top.
Outside combustion air ducting may be run upwards or vertically through framing and ceiling joists, with the hood installed through an outside wall and 3' (1 m) below the termi­nation. Ducting may also be run downward through floor Joists and under the home to a ventilated crawlspace not considered part of the living area of the home.
Note: Do not terminate outside air kit in attic space under any circumstances.
CAUTION: NEVER LOCATE INLET WHERE IT CAN BE BLOCKED BY SHRUBS, SNOW DRIFTS, ETC. NEVER LOCATE INLET IN GA­RAGE OR ANY AREA WHERE THERE IS AN­OTHER FUEL BURNING APPLIANCE OR PROD­UCTS EMITTING COMBUSTIBLE GASES SUCH AS PAINT, GASOLINE, ETC. IN COLD CLI­MATES, IT IS RECOMMENDED THE COMBUS­TION AIR DUCT BE INSULATED.
After completing the installation of the op­tional outside air vent system, the outside air control lever must be put in service and tested to ensure proper operation before completing any enclosure around the firebox. Failure to do so may result in extensive and costly re­work. Before the operation of the vent system can be tested, the lever securing screw must be removed.
See Figure 21 on page 13.
The hand operated outside air control lever is located on the right side (EBVST, EBVPF, and EBVCL) or left side (EBVCR) of the fireplace opening.
See Figure 21 on page 13.
To open the outside air shutter, open the bottom control access panel, reach into the gap between the firebox bottom and the modesty panel, and pull the outside air control lever all the way out.
12
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
The outside air shutter should be fully open when the fireplace is in use and completely closed when the fireplace is not being used. Closing it when not in use will prevent outside cold air from entering the dwelling.
Outside Air Control Lever with Stop Behind
Securing Screw
Outside Air Shutter in the Closed Position
Control Compartment Access Panel
Outside Air Control Lever
and Securing Screw Location
(EBVST, EBVPF and EBVCR Units Shown)
Figure 21
Operate the actuator through several cycles including the closed position. Ensuring proper operation and freedom of movement. Return the actuator arm to the closed position.
When first lighting the appliance, it will take a few minutes for the line to purge itself of air. Once purging is complete, the pilot and burner will light and operate as indicated in the instruction manual. Subsequent lightings of the appliance will not require such purg­ing. Inspect the pilot flame (remove logs, if necessary, handling carefully).
Millivolt Appliance Checkout
The pilot flame should be steady and, not lifting or floating. Flame should be blue in color with traces of orange at the outer edge.
The top ³⁄₈" (10 mm) at the pilot generator (thermopile) and the top ¹⁄₈" min (tip) of the quick drop out thermocouple should be en­gulfed in the pilot flame. The flame should project 1" (25 mm) beyond the hood at all three ports
(Figure 22)
.
Replace logs after pilot inspection.
To light the burner; turn ON the modesty panel mounted ON/OFF switch and rotate the gas valve control knob counterclockwise to the ON position.
Ignitor Rod
MILLIVOLT
Thermocouple
Hood
Step 9. INSTALLING GLASS ENCLOSURE PANELS
1. Visually inspect the gasket on the backside
of the panels. The gasket surface must be clean, free of irregularities and seated firmly.
2. Position the glass enclosure panel in front of the firebox opening at a 45 degree angle and engage the top flange over the lip at the top of the firebox opening.
3. Swing the glass enclosure panel down and back. Ensure the gasket seats evenly as the panel draws shut. Engage the Vee-flanges at the bottom of the panel with the latches; then close the latches to secure the panel.
4. After installing the front glass enclosure panel, reinstall the bottom control compart­ment access panel by inserting the right side locating pin into the right side cabinet panel and then the left side spring-loaded pin into the left side cabinet panel.
Lower Compartment Door and Hinge
Modesty Panel
See Figure 24.
Top Flange (Glass Enclosure Panel Frame)
Front Glass Enclosure Panel
Step 7. INSTALLING LOGS, VERMICULITE, DECORATIVE VOLCANIC STONE AND GLOWING EMBERS
The log set is located within the firebox. One plastic bag of glowing embers, one plastic bag of decorative volcanic stone and one bag of vermiculate, is located in the bottom compart­ment. Refer to the Log Placement Guide for detailed placement instructions for the log set and glowing embers. See the Homeowners Manual for placement instructions of vermicu­late, decorative volcanic stone and rockwool.
Step 8. CHECKING APPLIANCE OPERATION
With gas line installed run initial system check­out before closing up the front of the unit. Follow the pilot lighting instructions provided in the Homeowner's Care and Operation In­structions. For piezo ignitor location see
20 on page 12
(millivolt appliances only).
Note: Lighting instructions may also be found on the pull out lighting instruction labels attached to the gas control valve.
To access the label, see the procedure on the previous page described for accessing the gas control valve.
Figure
³⁄₈" Min (9 mm)
Pilot Nozzels
Thermopile
Figure 22
Electronic Appliance Checkout
To light the burner, turn ‘ON’ the modesty panel mounted ON/OFF switch and turn the gas control switch to the “ON” position. Ensure the ignitor lights the pilot. The pilot flame should engulf the flame rod as shown in
ELECTRONIC Proper Flame
Adjustment
Pilot Nozzle
Figure 23
3/8 To 1/2 Inch
(9 mm to 13 mm)
Ground Electrode
Flame Rod
Hot Surface
Igniter
.
Figure 23
Glass Enclosure
Bottom Vee-flanges
(Glass Enclosure
Panel Frame)
Figure 24
-
Panel Latch
EBVST SHOWN
Firebox Floor
Installing the Glass Enclosure Panel
WARNING: HANDLE THE GLASS WITH EXTREME CARE! TEMPERED GLASS IS SUSCEPTIBLE TO DAMAGE (SCRATCHES, FOR EXAMPLE) – HANDLE GLASS DOOR (GLASS ENCLOSURE PANEL) GENTLY WHILE REINSTALLING IT.
WARNING: NEVER OPERATE THE APPLI­ANCE WITHOUT THE FRONT GLASS EN­CLOSURE PANEL IN PLACE AND SECURE.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
13
Step 10. BURNER ADJUSTMENTS
Note -
The air shutter for the burner primary air
opening is factory-set. Do not adjust the factory­set position. The factory-set position is shown in
Figure 25.
*Air Shutter Burner Venturi
Tube
Orifice
Millivolt Shown
*Note - Do Not Adjust the Factory-Set Position.
The shutter opening is shown in the table below.
Opening
RENRUBNIAM
GNITTESRETTUHSYROTCAF
saGlarutaN
sledoM
sehcni
)mm(
enaporP
saG
sehcni
)mm(
TSVBE FPVBE
RCVBE
61/1)5.1(11(61/7)
LCVBE
Figure 25
Manually-Reset Safety Limit Switch
This appliance is equipped with a manually-reset blocked flue safety limit switch. Refer to
Figure 26
for its location. If, during appliance operation, the flame goes out (independently of the burner on/ off wall switch), it may be due to the operation of this safety limit switch. First allow the appliance
to cool, then reset the safety switch by pushing the red reset button on the back of the switch.
To access the blocked flue safety limit switch
refer to
Figure 26:
A - To access the blocked flue safety switch when top radiant panel is not covered with non-
combustible material:
1 - Lift up and remove top radiant panel/eyebrow assembly on the control side of unit. 2 - Reach between the cabinet side and the firebox side wall and locate the blocked flue safety
switch.
3 - Push the red reset button on the switch.
The applilance should then relight and remain lit. If this does not occur, turn off the appliance and
call a qualified service technician.
B - To access the blocked flue safety switch when top radiant panel is covered with non-
combustible material:
NOTE - This procedure should only be performed by a qualified service technician. Important - Turn electrical power off before beginning this procedure.
1 - Lower bottom hinged panel on the control side of the fireplace. Remove the modesty panel
and glass enclosure panel as described on page 5, Steps 3, 4, 5 and 6 under "Detailed Installation Steps" heading.
2 - Remove the side baffle securing screws (5) and then remove the baffle. 3 - Remove the safety switch bracket securing screws (2), and pull the switch/bracket assembly
through the side panel slot.
4 - Push the red reset button on the switch. 5 - Reinstall the switch/bracket assembly. 6 - Reinstall the side baffle. 7 - Reinstall front glass door. 8 - Raise the bottom hinged panel.
Step 11. Spillage Test and Safety Limit Switch Operation
Spillage Test
After appliance installation, perform this spillage test to verify that proper venting conditions exist:
1 - Place unit in its normally-operated con­dition, that is, with the glass enclosure pan­els in place. 2 - Close all doors and windows in the room. Turn on all exhaust fans in the house.
3 - Light the appliance. 4 - Wait 15 minutes. 5 - To check for venting action, start by
holding a smoke producing device within an inch of one edge (side edge, not top or bottom edge) of one glass enclosure panel. The smoke should be drawn toward the edge of the glass enclosure panel. Continue the test by moving the smoke producing device along the entire length of both side-edges of the glass door. Repeat the test for all glass enclosure panels.
6 - If the smoke is not drawn towards the edges of the glass door turn off the appli­ance and call a qualified service technican.
The appliance should then relight and remain lit. If this does not occur, check unit for a blocked flue condition.
SAFETY SWITCH LOCATION (EBVCL SHOWN) EBVST and EBVPF Safety Switch Location Also as Shown;
FIREBOX
SIDE WALL
BRACKET
SECURING SCREW
SAFETY SWITCH
EBVCR Location on the Left End of the Fireplace.
FIREBOX SIDE BAFFLE SECURING SCREW
FIREBOX SIDE BAFFLE
CABINET
SIDE WALL
MANUALLY-RESET SAFETY LIMIT SWITCH
TOP RADIANT PANEL
AND EYEBROW
Figure 26
14
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Step 12. HOOD INSTALLATION
COLD CLIMATE INSULATION
All of these appliances must have hoods installed prior to operating on all sides with glass enclosure panels.
On all clean face units, slide the hoods into the slots on the lower edges of the radiant panels (
Figure 28
).
FINISHING REQUIREMENTS Wall Details
Complete finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thickness of the finished wall (
Figures 28
).
A hearth extension is not required with this appliance. If a hearth extension is used, do not block the control compartment access panel. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements.
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the appliance front face. See Figures 28.
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with these exceptions: they must not cover any portion of the glass or louvers; they must not cover any portion of the top radiant panel and the air gaps surrounding the top radiant panel.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel.
(See Figure 27)
. Mantels constructed of non-combustible materials may be installed at any height
above the appliance opening; however, do not allow anything to hang below the hood.
MANTEL CLEARANCES
Inches (mm)
12 (305) MANTEL
10 (254) MANTEL
8 (203) MANTEL
14
(356)
12
(305)
10
(254)
8
(203)
6
(152)
6 (152) MANTEL
4 (102) MANTEL
2 (51) MANTEL
4
(102)
TOP OF APPLIANCE
For cold climate installations, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level. Gas line holes and other open­ings should be caulked or stuffed with unfaced fiberglass insulation. In cold climates, if the fireplace is being installed on a cement slab, a sheet of plywood or other raised platform can be placed underneath to prevent conducting cold up into the room. It also helps to sheetrock inside surfaces and tape for maximum air tightness and caulk firestops.
Combustible Wall
Framing
Combustible
Wall Framing
Spacer
Combustible Finished Wall Materials May Touch Top of Unit
Hood must be installed as shown.
Clean Face Models
This Area Must Remain Clear of Combustible Materials
1" Min (25 mm)
Top of Appliance
Radiant panel
Top of Door Frame
Figure 28
Figure 27
NOTE - Hood shown as positioned
in louvered front model. The hood position in the flush faced front model is lower than shown.
*Note - The side walls of mantels may protrude beyond the front face of the fireplace a maximum of 5 inches (127mm) at 0 inch clearance to the sides of the fireplace.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
15
GAS CONVERSION KITS
WARNING: THIS CONVERSION KIT SHALL BE INSTALLED BY A QUALIFIED SERVICE AGENCY IN ACCORDANCE WITH THE MANUFACTURER'S IN­STRUCTIONS AND ALL APPLICABLE CODES AND REQUIREMENTS OF THE AUTHORIZED AGENCY HAVING JURISDICTION. IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EX­ACTLY, A FIRE, EXPLOSION OR PRODUCTION OF CARBON MONOXIDE MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE. THE INSTALLATION IS NOT PROPER AND COMPLETE UNTIL THE OPERATION OF THE CON­VERTED APPLIANCE IS CHECKED AS SPECIFIED IN THE OWNER INSTRUCTIONS SUPPLIED WITH THE KIT. THE QUALIFIED SERVICE AGENCY PERFORM­ING THIS INSTALLATION ASSUMES RESPONSI­BILITY FOR THIS CONVERSION.
In Canada: THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN1-B149.1 AND .2 INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE EFFECTUÉE CONFORMÉMENT AUX RECOMMANDATIONS DES AUTORITÉS PROVINCIALES AYANT JURIDICTION ET CONFORMÉMENT AUX EXIGENCES DU CODE D'INSTALLATION CAN1­B149.1 ET.2.
Gas conversion kits are available to convert your appliance from the use of one type of gas to the use of another. These kits contain all the necessary components needed to complete the task including labeling that must be affixed to ensure safe operation.
Kit part numbers are listed here and the follow­ing steps detail the conversion procedure.
Step 1. Turn off the gas supply to the appliance. a. Open the control compartment access panel,
by actuating the spring-loaded magnetic catches securing the panel, gently depress­ing the outer top corners of the panel until the catches "pop" the panel free and allowing it to swing out and down to open.
b. Remove the bottom control compartment
access panel by compressing the spring­loaded hinge pin on the left side until it disengages from the left cabinet panel hole. Pull the panel away from the fire-
See Figure 20 on page 12.
place.
c. Remove the modesty panel by pulling the
bottom right corner of the modesty panel out slightly to disengage the snap-fit fea­ture; lift the modesty panel by the tab on the panel's right end, pull the right end of the panel away from the cabinet and then pull the panel diagonally out of the left side cabinet panel slots. (In the above proce­dure, reverse the words "left" and "right" for EBVCR models). Remove the modesty panel carefully, so that none of the wires become loose or disconnected.
d. Locate the latch at the top of the control
compartment. To disengage the latch from the bottom vee-flange of the glass enclo­sure panel, reach for the handles located towards the back of the latch and pull the handl down toward the front of the unit.
e. Swing the bottom of the door out and raise
it slightly to lift the top flange of the door frame away from the appliance.
Step 2. Carefully remove the logs. Exercise care as not to break the logs.
Step 3. Referring to
remove the burner.
AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION SERA INSTALLÉ PAR UNE AGENCE QUALIFIÉE DE SER­VICE CONFORMÉMENT AUX INSTRUCTIONS DU FABRICANT ET TOUTES EXIGENCES ET CODES APPLICABLES DE L'AUTORISÉS AVOIR LA JURIDICTION. SI L'INFORMATION DANS CETTE INSTRUCTION N'EST PAS SUIVIE EXACTEMENT, UN FEU, EXPLOSION OU PRO­DUCTION DE PROTOXYDE DE CARBONE PEUT RÉSULTER LE DOMMAGES CAUSER DE PROPRIÉTÉ, PERTE OU BLESSURE PERSONNELLE DE VIE. L'AGENCE QUALIFIÉE DE SERVICE EST ESPONSABLE DE L'INSTALLATION PROPRE DE CET ÉQUIPMENT. L'INSTALLATION N'EST PAS PROPRE ET COMPLÉTE JUSQU'À L'OPÉRATION DE L'APPAREIL CONVERTI EST CHÉQUE SUIVANT LES CRITÈRES ÉTABLIS DANS LES INSTRUCTIONS DE PROPRIÉTAIRE PROVISIONNÉES AVEC L'ÉQUIPEMENT.
tiKnoisrevnoCsaGenaporPoTlarutaN
.oNsledoMepyTtinU.oNgolataC
tlovillim8912H
cinortcele0022H
tiKnoisrevnoCsaGenaporPoTlarutaN
tlovillim8912H
cinortcele0022H
tiKnoisrevnoCsaGlarutaNotenaporP
tlovillim9912H
cinortcele1022H
tiKnoisrevnoCsaGlarutaNotenaporP
tlovillim3022H
cinortcele5022H
Figure 29 on page 17
TSVBE FPVBE
.oNsledoMepyTtinU.oNgolataC
RCVBE LCVBE
.oNledoMepyTtinU.oNgolataC
TSVBE FPVBE
.oNledoMepyTtinU.oNgolataC
RCVBE
LCVBE
,
16
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
FIREBOX BOTTOM
BURNER POSITIONING
PILOT ASSEMBLY
Figure 29
BACK OF FIREPLACE
PAN BURNER
PAN
BURNER
Pressure Regulator
Remove These Components
Figure 30
Step 6. Refer to
Figure 31
pilot hood assembly to access the hexed pilot orifice. Remove and replace the orifice with the one provided with the kit.
Pilot Orifice
and remove the
CONTROL
I
G N I
T E
Manifold Pressure Test Port
Slotted Cap
OFFION
Inlet Pressure Test Port
I S P
Adjusting Screw
Spring
Figure 32
Figure 33
See follows: Remove the ignitor assembly retainer clip, and carefully remove the ignitor assembly.
Exercise extreme care to prevent damage to or breakage of the ignitor assembly. Remove
the screw securing the pilot assembly to its mounting bracket. Back off the flare nut at the end of the pilot gas line to free the pilot assem­bly from the gas line. Remove the pilot orifice and replace it with the one provided with the conversion kit. Reinstall the pilot assembly by reversing the steps detailed here.
and replace the pilot orifice as
Millivolt Appliances
Step 4. SIT Systems - Refer to
Figure 30
and the instructions provided with the kit. Using a Torx T20, remove and discard the three pres­sure regulator mounting screws. Remove the pressure regulator, spring, poppet, diaphragm and bushing. Discard all removed compo- nents. Ensure the rubber gasket installed on the back of the replacement pressure regulator is properly positioned and install the new pres­sure regulator using the new screws supplied with the kit. Tighten screws to 25 In. lb. torque.
Step 5. Attach manometer to the manifold side pressure test fitting and verify manifold pres­sure reads 3.5 inches water column (0.87 kPa) for natural gas, and 10.0 inches water column (2.49 kPa) for propane gas.
Figure 31
Electronic Appliances
Step 7. Honeywell Electronic Valves - See
Figure 32
the kit. Remove the slotted cap screw, o-ring, pressure-regulating adjusting screw and spring. Retain all parts for possible later use. Install new components from the kit. Black cap and red spring for propane gas units. Silver cap and stainless steel spring fro natural gas units.
Before installing the cap, attach manometer to the manifold side pressure test fitting and adjust screw until pressure reads 3.5 inches water column (0.87 kPa) for natural gas, and
10.0 inches water column (2.49 kPa) for propane gas.
and the instructions provided with
When reinstalling the ignitor assembly, use extreme care to prevent damage and break­age. Do not apply any leverage to the ignitor assembly while restoring the retainer clip to its original position.
Pilot Orifice
Retaining
Flare Nut
Pilot Assembly
Ignitor Assembly
Clip
Note: If the ignitor is damaged, a replace­ment kit is available, order Catalog Number 87L54.
Figure 33
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
17
All Models
Step 8.
(Refer to Figure 29 )
A. Remove the orifice from the manifold
and replace it with the one provided in the kit. See the following table for orifice sizes for natural and propane models
Figure 34
B. Install the burners as shown in
illustrates the orifice.
Figure 29
The primary air opening can be adjusted by removing the venturi tube air shutter securing screw and placing it in the other hole provided nearby. The correct hole usage for this screw for the gas being used can be determined by the air shutter gap indicated in
ledoM
.oN
TSVBE FPVBE
RCVBE LCVBE
Figure 25 on page 14.
ezisecifirO
.taN.porP
23#05#
43#05#
teeF
Kit Catalog No.
H2199 and H2201
THIS APPLIANCE HAS BEEN CONVERTED TO:
NATURAL GAS
INPUT BTU/HR – 37,500 MANIFOLD PRESSURE – 3.5"
.
ORIFICE SIZE – #32
Step 9. Reassemble the remaining compo-
nents by reversing the procedures outlined in the preceding steps. Use pipe joint compound or Teflon tape on all pipe fittings before install­ing (ensure propane resistant compounds are used in propane applications, do not use pipe joint compounds on flare fittings).
Step 10. Attach the conversion label provided
.
Kit Catalog No.
H2203 and H2205
THIS APPLIANCE HAS BEEN CONVERTED TO:
NATURAL GAS
INPUT BTU/HR – 34,000 MANIFOLD PRESSURE – 3.5" ORIFICE SIZE – #34
in the conversion kit to the rating plate on the appliance.
Figure 35
shows all of the labels for
all of the kits covered by this manual as shown in the tables on page 17. Compare the label provided in the kit being installed to the appro­priate label shown in
Figure 35
.
Step 11. Turn on the gas supply and test for leaks as shown in
step 5 on page 11
.
Kit Catalog No.
noitavelE
)sretem(
0054-0
)2731-0(
H2198 and H2200
THIS APPLIANCE HAS BEEN CONVERTED TO:
PROPANE/LPG
INPUT BTU/HR – 34,000 MANIFOLD PRESSURE – 10.0" ORIFICE SIZE – #50
Figure 34
Figure 35
18
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
NOTES:
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
19
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2004 by LENNOX HEARTH PRODUCTS
P/N 850,025M REV. B 01/2007
20
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
1110 West Taft Avenue Orange, CA 92865
Loading...