This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes. This appliance
is only for use with the type of gas indicated on the rating
plate. This appliance is not convertible for use with other
gases, unless a certified kit is used.
In the Commonwealth of Massachusetts & New York:
• Installation must be performed by a licensed plumber or
gas fitter.
See Table of Contents for location of additional New York
& Commonwealth of Massachusetts requirements.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING: IF THE INFORMATION IN THIS MANUAL
IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY: Do not store or use gasoline
or other flammable vapors or liquids in the vicinity of this or any other appliance.
FOR YOUR SAFETY: What to do if you smell gas:
ELITE
B-VENTED GAS FIREPLACES
P/N 850,025M REV. B 01/2007
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE
LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE POUR
RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU
POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE
BLESSURE OU LA MORT.
POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser
d'essence ni d'autre vapeurs ou liquides inflammables
dans le voisinage de cet appareil ou de tout autre
appareil.
®
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow your gas suppliers
instructions.
• If your gas supplier cannot be reached, call the
fire department.
Installation and service must be performed by a
qualified installer, service agency or the gas
supplier.
OTL Report No. 116-F-07A-5
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une
odeur de gaz:
• Ne pas tenter d'allumer d'appareil.
• Ne touchez à aucun interrupteur. Ne pas vous servir
des téléphones se trouvant dans le batiment où
vous vous trouvez.
• Evacuez la piéce, le bâtiment ou la zone.
• Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suivez les instructions du
fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service dos incendies.
L'installation et service doit être exécuté par un qualifié
installeur, agence de service ou le fournisseur de gaz.
This installation manual will help you achieve a
safe, efficient and dependable installation for
your appliance and vent system.
Please read and understand these
instructions before beginning your
installation.
PACKAGING
The assembled vented gas fireplace is packaged with:
1 - one log set located within the firebox.
2 -one plastic bag containing the literature
package, which consists of the homeowner's
manual, installation instructions, log placement guide and warranty, 8 (EBVST), 4
(EBVPF, EBVCL and EBVCR) nailing flanges;
plastic bag is located on top of the fireplace.
3 -two hoods (EBVST, EBVCR, EBVCL), or
three hoods (EBVPF) taped to the top of the
fireplace.
4 - one plastic bag of glowing embers, one
plastic bag of decorative volcanic stone and
one bag of vermiculate is located in the
bottom compartment.
INTRODUCTION
These vented gas fireplaces are designed for
residential applications. They must be installed
with approved type-B, 6 in. double wall vent
pipe systems routed to the outside atmosphere.
The millivolt appliances are designed to operate
on either natural or propane gas. A millivolt gas
control valve with piezo ignition system provides
safe, efficient operation. If any optional accessories which require electrical power are being
installed, the electrical power must be provided
at the time of appliance installation.
Electronic appliances are designed to operate
on natural or propane gas. An electronic intermittent pilot ignition system provides safe,
efficient operation. External electrical power is
required to operate these units.
These appliances comply with National Safety
Standards and are tested and listed by OmniTest Laboratories (Report No. 116-F-07A-5) to
ANSI Z21.50 - 2003 (in Canada, CSA 2.22 -
2003), and CAN/CGA-2.17-M91 in both USA
and Canada, as vented gas fireplaces.
Massachusetts And New York City, NY
Requirements
These appliances are approved for installation
in the following USA locations listed in the
following:
Massachusetts:
Installation of these fireplaces are approved
for installation in the US state of Massachusetts if the following additional requirements
are met-
• Installation and repair must be done by a
plumber or gas fitter licensed in the Commonwealth of Massachusetts.
• The flexible gas line connector used shall not
exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a Thandle type valve.
New York City, NY:
Installation of these fireplaces are approved
for installation in New Your City in the US state
of New York, if the following additional requirements are met-
• An outside air kit (FOAK-4 or FOAK-4LD)
must be installed.
GENERAL INFORMATION
WARNING: THESE FIREPLACES ARE
VENTED DECORATIVE GAS APPLIANCES.
DO NOT BURN WOOD OR OTHER MATERIAL IN THESE APPLIANCES.
Note: Installation and repair should be per-
formed by a qualified service person. The appliance should be inspected annually by a qualified professional service technician. More frequent inspections and cleanings may be required due to excessive lint from carpeting,
bedding material, etc. It is imperative that the
control compartment, burners and circulating
air passage ways of the appliance be kept clean.
TYPICAL INSTALLATION
DO NOT ATTEMPT TO ALTER OR MODIFY
THE CONSTRUCTION OF THE APPLIANCE OR
ITS COMPONENTS. ANY MODIFICATION OR
ALTERATION MAY VOID THE WARRANTY,
CERTIFICATION AND LISTINGS OF THIS UNIT.
2
These appliances may be used for bedroom
installations in the United States and are
listed accordingly. These units may not be
installed in bedrooms in Canada.
Installation must conform to local codes. In the
absence of local codes, installation must comply with the current National Fuel Gas Code,
ANSI Z223.1. (In Canada, the current CAN-1
B149 installation code.) Electrical wiring must
comply with the National Electrical Code ANSI/
NFPA 70 - (latest edition). (In Canada, the
current CSA C22-1 Canadian Electrical Code.)
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Offset Venting
Vertical Venting
Figure 1
S'assurer que le brùleur et le compartiment des
commandes sont propres. Voir les instructions d'installation et d'utilisation qui
accompagnent l'appareil.
Provide adequate clearances around air openings and adequate accessibility clearance for
service and proper operation. Never obstruct
the front, back and/or side viewing surfaces of
the appliance.
These appliances are designed to operate on
natural or propane gas only. The use of other fuels
or combination of fuels will degrade the performance of this system and may be dangerous.
Millivolt Models -
Millivolt models come standard with the
manually-modulated gas valve; flame appearance and heat output can be controlled at the gas valve. Input of millivolt
models is shown in the following table:
sledoMtlovilliM
enaporPdnalarutaN
sledoMsaG
,MNFPVBE,MNTSVBE
,MPFPVBE,MPTSVBE
,MNRCVBE,MNLCVBE
MPRCVBE,MPLCVBE
Electronic Models -
Electronic models have a fixed rate gas valve.
Input of electronic models is shown in the
following table:
*sledoMcinortcelE
sledoMsaGlarutaN
,ENFPVBE,ENTSVBE005,73
,ENRCVBE,ENLCVBE000,43
* See page 16 for Electronic Models conversion from
Natural gas to Propane.
All Models -
Maximum manifold pressure is 3.5 in. w.c.
(0.87 kPa) for natural gas and 10 in. w.c.
(2.49 kPa) for LP/Propane gas.
Installations at Altitudes of 0 to 4500 ft.Units are tested and approved for elevations
of 0 to 4500 feet (0 to 1372 meters).
Installations at Altitudes above 4500 ft.For elevations above 4500 feet (1372
meters), install the unit according to the
regulations of the local authorities having
jurisdiction and, in the USA, the latest edition
of the National Fuel Gas Code (ANSI Z223.1)
or, in Canada, the latest edition of the
CAN1-B149.1 and .2 codes.
The millivolt appliances are manually controlled
and feature a spark ignitor (piezo) that allows
the appliance's pilot gas to be lit without the use
of matches or batteries. This system will still
function in the event of a power outage.
Do not use these appliances if any part has
been under water. Immediately call a qualified, professional service technician to inspect
the appliance and to replace any parts of the
control system and any gas control which
have been under water.
Ne pas se servir de cet appareil s'il a été plongé
dans l'eau, complètement ou en partie. Appeler
un technicien qualifié pour inspecter l'appareil et
remplacer toute partie du système de contrôle et
toute commande qui ont été plongés dans l'eau.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home,
where not prohibited by local codes. This
appliance is only for use with the type of
gas indicated on the rating plate. This appliance is not convertible for use with
other gases, unless a certified kit is used.
Cet appareil peut être installé dans un maison
préfabriquée (É.-U. seulement) ou mobile
déjà installée à demeure si les réglements
locaux le permettent.
Cet appareil doit être utilisé uniquement avec
les types de gaz indiqués sur la plaque
signalétique. Ne pas l'utiliser avec d'autres gaz
sauf si un kit de conversion certifié est installé.
Test gage connections are provided on the
front of the millivolt gas control valve (identified IN for the inlet and OUT for the manifold side). A ¹⁄₈" NPT test gage connection is
provided at the inlet and outlet side of
the electronic gas control valve.
Minimum inlet gas pressure to these appliances
is 5.0 inches water column (1.24 kPa) for natural
gas and 11.0 inches water column (2.74 kPa) for
propane for the purpose of input adjustment.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Maximum inlet gas supply pressure to these
appliances is 10.5 inches water column (2.61
kPa) for natural gas and 13.0 inches water
column (3.23 kPa) for propane.
These appliances must be isolated from the gas
supply piping system (by closing their individual
manual shut-off valve) during any pressure testing of the gas supply piping system at test
pressures equal to or less than ¹⁄₂ psig (3.5 kPa).
These appliances and their individual shut-off
valves must be disconnected from the gas supply
piping system during any pressure testing of that
system at pressures in excess of ¹⁄₂ psig (3.5 kPa).
These appliances must not be connected to
a chimney or flue serving a separate solid
fuel burning appliance.
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning are similar to
the flu with headaches, dizziness and/or
nausea. If you have these signs, obtain
fresh air immediately. Turn off the gas
supply to the appliance and have it serviced by a qualified professional, as it may
not be operating correctly.
WARNING: B-VENT APPLIANCES ARE NOT
DESIGNED TO OPERATE IN NEGATIVELY
PRESSURED ENVIRONMENTS (PRESSURE
WITHIN THE HOME IS LESS THAN PRESSURES OUTSIDE). SIGNIFICANT NEGATIVELY PRESSURED ENVIRONMENTS
CAUSED BY WEATHER, HOME DESIGN,
OR OTHER DEVICES MAY IMPACT THE
OPERATION OF THESE APPLIANCES.
NEGATIVE PRESSURES MAY RESULT IN
POOR FLAME APPEARANCE, SOOTING,
DAMAGE TO PROPERTY AND/OR SEVERE
PERSONAL INJURY. DO NOT OPERATE
THESE APPLIANCES IN NEGATIVELY PRESSURED ENVIRONMENTS. PROVIDING ADEQUATE VENTILATION TO THE APPIANCE
FOR COMBUSTION AIR WILL ELIMINATE A
NEGATIVE PRESSURE ENVIRONMENT.
WARNING: FAILURE TO COMPLY WITH
THE INSTALLATION AND OPERATING INSTRUCTIONS PROVIDED IN THIS DOCUMENT WILL RESULT IN AN IMPROPERLY INSTALLED AND OPERATING APPLIANCE, VOIDING ITS WARRANTY. ANY
CHANGE TO THIS APPLIANCE AND/OR
ITS OPERATING CONTROLS IS DANGEROUS. IMPROPER INSTALLATION OR USE
OF THIS APPLIANCE CAN CAUSE SERIOUS INJURY OR DEATH FROM FIRE,
BURNS, EXPLOSION OR CARBON MONOXIDE POISONING.
3
Corner - Right
(EBCR-2)
**See-Through
(EBST-2)
Peninsula
(EBPF-2)
*See-Through
one side flush with a wall
Figure 2
WARNING: CHILDREN AND ADULTS
SHOULD BE ALERTED TO THE HAZARDS
OF HIGH SURFACE TEMPERATURES. USE
CAUTION AROUND THE APPLIANCE TO
AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CAREFULLY SUPERVISED WHEN THEY ARE IN
THE SAME ROOM AS THE APPLIANCE.
TYPICAL LOCATIONS
Corner - Left
(EBCL-2)
Bay
(EBBAY)
(EBST-2) -
*When See-Through (EBST-2) is
installed with one side flush
with a wall,opposite wall must
not extend beyond either
viewing side of the fireplace.
**
When See-Through (EBST-2) is
installed in the middle of a room,
do not extend side walls beyond
either viewing side of the fireplace.
APPLIANCE AND VENT CLEARANCES
The appliance is approved with zero clearance to combustible materials on all sides (as
detailed in
tion: When the unit is installed with one side
flush with a wall, the wall on the other side of
the unit must not extend beyond the front
edge of the unit.
Table 2)
, with the following excep-
Gas vent caps that are located 8' or more from
a portion of a building which extends at an
angle greater than 45° upward from the horizontal may terminate in accordance with
ure 3 )
, provided that in no case shall any
(Fig-
discharge opening on the cap be less than 2'
(610 mm) horizontally from the roof surface
(National Fuel Gas Code ANSI Z223.1 (NFPA
54) 7.6.2) (CAN/CGA B149).
These instructions should be used as a
guideline and do not supersede local codes
in any way.
Multiple Terminations – These appliances
may vent adjacent to and at the same level
with any other gas appliances (including direct-vent appliances) provided that there is at
least 2 ft. (0.6m) between the proximal edges
of the vent caps. These appliances may be
vented adjacent to a chimney vent servicing a
solid fuel fireplace provided the B-vent cap is
at least 2 ft. (0.6m) away from the nearest
point of the chimney opening.
Note: Venting terminals shall not be recessed
into a wall or siding.
WARNING: DO NOT PLACE CLOTHING
OR OTHER FLAMMABLE MATERIALS
ON OR NEAR THIS APPLIANCE.
AVERTISSEMENT: SURVEILLER LES
ENFANTS. GARDER LES VÊTEMENTS,
LES MEUBLES, L'ESSENCE OU AUTRES
LIQUIDES À VAPEUR INFLAMMABLES À
COTE DE L'APPAREIL.
These appliances are equipped with an integral combustion air door and actuator arm.
Combustion air kits are optional.Install as
shown in Step 6 on page 12.
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns.
However, vent system routing to the outside
atmosphere and access to the fuel supply are
also important. Consideration should be given to
traffic ways, furniture, draperies, etc., due to high
surface temperatures (
should also be free of electrical, plumbing or
other heating/air conditioning ducting.
The appliance should be mounted on a fully
supported base extending the full width and
depth of the unit. The appliance may be located
on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile, etc., a metal
or wood barrier covering the entire bottom
surface must be used.
4
Figure 2
). The location
KCAB
SEDIS
)mm31(.ni2/1
srecaps)mm0(.ni0
)mm31(.ni2/1
srecaps)mm0(.ni0
SRECAPSPOT)mm0(.ni0
ROOLF)mm0(.ni0
mottoBmorF
ottinUfo
)mm6261(.ni46
gnilieC
TNEV)mm4.52(.ni1
SECNARAELCECIVRES
GNIWEIV
-SEDIS
KCAB,TNORF(
)sretem9.0(.teeF3
)EDISRO
Table 2
In addition, when the unit is installed in the
middle of a room, the side walls surrounding
the unit must not extend beyond the front or
rear edge of the unit. See
Figure 2
.
Vertical Vent Termination Clearances
Gas Vent Rule – Gas vent caps are not permit-
ted within 8 feet (2.4 mm) of a vertical wall or
similar obstruction.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
X
12
Roof Pitch is X/12
Minimum Height from Roof
to Lowest Discharge Opening
Minimum Height
Roof Slope
from Roof to Lowest
Discharge Opening
FeetMeters
Flat to 6/121' 0"0.3
Over 7/12 to 9/122' 0"0.6
Over 10/12 to 12/124' 0"1.2
Over 13/12 to 16/126' 0"1.8
Over 17/12 to 21/128' 0"2.4
Figure 3
TYPICAL INSTALLATION SEQUENCE
The typical sequence of installation follows,
however, each installation is unique resulting in
variations to those described.
See the page numbers references in the following steps for detailed procedures.
Step 1. (page 5) Construct the appliance
framing. Position the appliance within the
framing and secure with nailing brackets.
Step 2. (page 5) Route gas supply line to
appliance location.
Step 3. (page 5) Install the vent system
and exterior termination.
Step 4. (page 10) Field Wiring
a. Millivolt Appliances – The operating con-
trol switch is factory installed.
b. Electronic Appliances – Connect 120 Vac
electrical power to the appliance receptacle.
Step 5. (page 11) Make connection to gas
supply.
Step 6. (page 12) Outside Air Kit Installation
Step 7. (page 13) Install the log set, ver-
Step 10. (page 14) Burner Adjustment.
Step 11. (page 14) Spillage Test and Safety
Limit Switch Operation.
Step 12. (page 15) Install the hoods.
Top Radiant
Panel
Top Bustle
Bottom
Bustle
Unit Parts Identification
Control
Compartment
Access Panel
Figure 4
3- Open the control compartment access
panel, by actuating the spring-loaded magnetic catches securing the panel, gently depressing the outer top corners of the panel
until the catches "pop" the panel free and
allowing it to swing out and down to open.
See
Figure 20 on page 12.
4 - Open the latches (located on the left and
right sides of the unit front opening, under the
firebox floor) securing the glass enclosure panel.
Remove the panel by tilting it outward at the
bottom and lifting it up. Set the door aside
protecting it from inadvertent damage.
See
Figure 24 on page 13.
Step 1. FRAMING
If the appliance is to be elevated above floor
level, a solid continuous platform must be
constructed. Headers may be in direct contact
with the appliance top spacers but must not be
supported by them or notched to fit around
them. All construction above the appliance
must be self supporting, DO NOT use the
appliance for structural support.
Side Nailing Flanges
The fireplace should be secured to the framing at
the side(s) and/or rear of the unit using the
factory-provided nailing flanges. Install the nailing flanges - 8 (EBVST), 4 (EBVPF, EBVCL,
Figure 5
EBVCR) - as shown in
using the existing
screws. Position the fireplace within the framing. When required, the flanges may be bent 90
degrees by hand or with the assistance of a
hammer. Use wood screws to secure the nailing
flanges to the framing.
See Table 2 on page 4
for
clearances of framing members to cabinet parts
in the nailing flange area. The nailing flange itself
is exempt from these clearances.
Floor Nailing Tabs
Secure the fireplace to the floor as shown in
Figure 5.
Step 2. ROUTING GAS LINE
DETAILED INSTALLATION STEPS
The appliance is shipped with all gas controls
and components installed and pre-wired.
1 - Remove the shipping carton.
2 - Remove the top radiant panel;
(EBVPF - NO NAILING FLANGES ON END WITH GLASS PANEL)
Nailing
Flanges
Turn tabs down and secure to the floor with
8d nails or other appropriate fasteners on all sides
of the unit which do not have viewing glass panels.
EBVST SHOWN
see Figure 4.
Remove these two screws and use them
when installing the nailing flanges.
Figure 5
Frame these appliances as illustrated in
Figures 8 (EBVST), 9 (EBVPF), 10 (EBVCL) or
11 (EBVCR) on pages 6 and 7.
All framing
details must allow for a minimum clearance
to combustible framing members as shown
in
Table 2 on page 4
(FOR EBVCR VIEW, INTERCHANGE SIDES)
.
EBVCL SHOWN
Route a ¹⁄₂" (13 mm) gas line as shown in
Figures 8 (EBVST), 9 (EBVPF), 10 (EBVCL) or
11 (EBVCR) on pages 6 and 7
. Gas lines must
be routed, constructed and made of materials
that are in strict accordance with local codes
and regulations.
All appliances are factory-equipped with a flexible gas line connector and ¹⁄₂ inch shutoff valve.
(See step 5 on page 11).
Step 3. Install the Vent System &
Exterior Termination -
In the United States, vent installation must
conform with local building codes. In the absence of local codes, vents must be installed in
accordance with the current edition of the
National Fuel Gas Code (ANSI-Z223.1).
In Canada, vent installation must conform
with local building codes. In the absence of
local codes, vents must be installed in accordance with the current edition of the National Standard of Canada CAN/CGA-B149.1
or B149.2 Installation Code.
This gas fireplace must be vertically vented
using listed 6 in. type-B, double-walled vent
pipe and a listed vent termination.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
5
10 ft.
*41¹⁄₂
(1054)
40¹⁄₈
(1019)
EBVPF
(Peninsula)
inches (millimeters)
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
6¹⁄₄
(159)
Minimum Framing
Stud size is 2 x 4
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)
clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension permits
easier fireplace installation, if unit is installed after framing is erected.)
22³⁄₄**
(578)
**Based on 5/8” drywall. Use 23” for 1/2” drywall.
Minimum
Figure 6
FIREPLACE FRAMING SPECIFICATIONS
Minimum
Figure 7
12 ft.
60 degrees
max.
Slip the first 6 inch (152 mm) section of BVent over the fireplace flue outlet and secure
with four sheetmetal screws (# 8 or larger),
and install the remainder of the B-Vent to the
outside. Minimum overall height of the vent
system and appliance must be 10' (2.54 m)
vertical - no offset
(see Figure 6 );
or 12' (3.7
m) when an offset up to 60 degrees from the
vertical is used - this offset may start at the
fireplace flue collar
(see Figure 7 ).
The
maximum overall height of the vent system
and appliance should not exceed 40 feet.
Install the B-vent system in accordance with
the vent manufacturer's instructions.
CAUTION: THIS APPLIANCE CANNOT BE
VENTED HORIZONTALLY.
Note: Refer to the vent manufacturers in-
stallation instructions for variations of venting techniques. If common venting of several units is contemplated, it should be discussed with an architect and the local Building Department.
Do not place insulation materials within 1 in.
of the gas vent system.
EBVST
(See-Through)
inches (millimeters)
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm)
clearance between framing and unit framing spacers. (The 41¹⁄₂ in. dimension permits
easier fireplace installation, if unit is installed after framing is erected.)
**Based on 5/8” drywall. Use 23” for 1/2” drywall.
Figure 8
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
Minimum Framing
Stud size is 2 x 4
41¹⁄₂
(1054)
6¹⁄₄
(159)
22³⁄₄**
(578)
*41¹⁄₂
(1054)
Figure 9
6
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.