The MidNite Solar SMA E-Panel is designed for single & multiple inverter installations.
Use this installation manual to aid in installation. The installation of electrical systems such as this fall
under the guidelines of the NEC in the USA. Canadian electrical codes have jurisdiction in Canada.
These instructions are not intended to be used in lieu of these local and federal codes, but rather are
used as specific to this product. You may need to consult with a professional solar installer or electrical
inspector when in doubt on code specific questions and system installation issues. Even though the EPanel incorporates and simplifies numerous separate electrical circuits into one enclosure, an inverter
system such as this is still a very sophisticated and somewhat complicated electrical system.
MidNite Solar Inc.
17722 – 67th Ave Ne 360-403-7207 Voice
Arlington, Wa 98223 USA 360-691-6862 Fax www.midnitesolar.com
Symbols used in this manual:
Caution: Indicates a condition where injury or damage may occur if instructions are not followed.
Danger: Indicates a condition where injury or death may occur if instructions are not followed.
Symboles utilisez dans ce manuel:
Attention: Indique un risque des blessures graves ou du dommage si on ne suit pas des instructions
dans ce manuel.
Danger: Indique un risque des blessures graves ou du mort si on ne suit pas des instructions dans ce
manuel.
SMA E-Panel installation manual
This Manual contains information for MidNite Solar SMA E-Panel Model Numbers:
Masters:
MNE250SMA-AC SINGLE Single -
MNE250SMA-OG SINGLE Single – Off Grid
MNE250SMA-OG/AC DM Master – Dual Off Grid
MNE250SMA-QUAD MASTER Master – Quad System AC Coupled / Off Grid
MNE250SMA-3PH MASTER Master - 3 Phase
Slaves:
MNE250SMA-Slave Slave (right hand unit) for dual, 3PH and Quads
Backplates – Autoformer
MNESMA tall BP Back plate for AC coupled Master holds inv, E-Panel and autoformer
MNESMA short BP Short back plate for inverter and E-Panel
MNX-240 6000 watt autoformer for single inverter AC coupled system
2 | P a g e 10- 234- 1 R E V : A
SMA E-Panel installation manual
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS - These instructions contain important safety and operating
instructions for the MidNite SMA E-Panel.
If you do not fully understand any of the concepts, terminology, or hazards outlined in these instructions, please refer installation to a
qualified dealer, electrician or installer. These instructions are not meant to be a complete explanation of a renewable energy system.
GENERAL PRECAUTIONS
If service or repair should become necessary, contact MidNite Solar Inc. Improper servicing may result in a risk of shock, fire or
explosion. To reduce these risks, disconnect all wiring before attempting any maintenance or cleaning. Turning off the inverter will
not reduce these risks. Solar modules produce power when exposed to light. When it is not possible to disconnect the power coming
from the Photovoltaics by an external means such as a combiner, cover the modules with an opaque material before servicing any
connected equipment.
Do not work alone. Someone should be in the range of your voice or close enough to come to your aid when you work with or near
Batteries.
Remove rings, bracelets, necklaces, watches etc. when working with photovoltaic modules or other electrical equipment. Power from
an illuminated photovoltaic array makes a very effective arc welder with dire consequences if one of the welded pieces is on your
person.
All installations must comply with national and local electrical codes. Professional installation is recommended.
Wiring must be done in accordance with the National Electrical Code ANSI/NFPA 70. Use Class 1 wiring methods
for field wiring connections to terminals of a Class 2 circuit. Use only 14-1/0 gauge AWM wire. Select the wire
gauge used based on the protection provided by the circuit breakers/fuses.
MidNite products are not intended for use in connection with Life Support Systems. MidNite Solar makes no
warranty or representation in connection with their products for such uses.
Disclaimer
Every effort is made to ensure the completeness and accuracy of all technical reference material, still,
unless specifically agreed to in writing, MidNite Solar Inc.
(a) Makes no warranty as to the accuracy, sufficiency or suitability of any technical or other information
provided in its manuals or other documentation.
(b) Assumes no responsibility or liability for loss or damage whether direct, indirect, consequential or
incidental, which might arise out of use of such information. The use of any such information will be
entirely at the user's risk.
If service or repair of the E-Panel should become necessary, contact MidNite Solar Inc. For other parts of
the system refer to the manual included with that equipment and contact the manufacturer for support.
Improper servicing may result in a risk of shock, fire or explosion. To reduce these risks, disconnect all
wiring before attempting any maintenance or cleaning. Turning off the inverter will not reduce these risks.
Solar modules produce power when exposed to light. When it is not possible to disconnect the power
coming from the Photovoltaics by an external means such as a combiner, cover the modules with an
opaque material before servicing any connected equipment.
3 | P a g e 10- 234- 1 R E V : A
SMA E-Panel installation manual
INSTRUCTIONS DE SECURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS
Ces instructions contiennent des informations importantes pour utiliser le Midnite Solar SMA MNX240 Autotransformer en toute sécurité.
1. Avant l’utilisez cet appareil lis et comprends toutes les instructions et avertissements.
2. Si vous ne comprenez pas l’une des concepts ou des instructions contenu dans cette manuel
consulter un agent spécialisé.
3. Si des réparations sont nécessaires contactez MidNite Solar pour plus des informations. Danger
de choc électrique et de risque de brulure. Rien à dépanner à l'intérieure du cette appareil. Ne
pas ouvrir le couver. Pour toute réparation ou service d'entretien, consulter un agent spécialisé.
Il y’a peut-être plusieurs sources d’alimentation dans cette system. Débrancher toutes les
interrupteurs avant toute d'entretien où nettoyage.
4. Ne travaillez pas seul. Quelqu'un devrait toujours être à proximité pour aider en cas d'une
situation d'urgence.
5.Retirer bagues, bracelets, colliers, montres, et quelles choses comme ça. Il y’a risque des
6. Le câblage doit être fait en conformité avec le National Electrical Code ANSI / NFPA 70.
Utiliser des méthodes de câblage de catégorie 1 pour les connexions de câblage sur .des
terminaux d'un circuit de classe 2. Utilisez uniquement des fils de AWM de calibre 14-1/0.
Sélectionnez le type de câble utilisé sur la base de la protection prévue par les disjoncteurs /
fusibles.
4 | P a g e 10- 234- 1 R E V : A
SMA E-Panel installation manual
Table of Contents
Model Number Descriptions ................................................................................................................... 2
Single ............................................................................................................................................ 19, 22, 44
AC Coupled Dual ....................................................................................................................... 19, 27, 46
Off Grid Single ............................................................................................................................ 20, 21, 44
Off Grid Dual .................................................................................................................................... 25, 26
Three Phase ....................................................................................................................................... 28, 29
Tightening torque for electrical connections ................................................................................. 30, 43
Classic Charge Controller with arc fault detection ............................................................................. 31
Whiz Bang Jr. ......................................................................................................................................... 36
Slave unit ................................................................................................................................................. 49
Exchanging bus bars. ............................................................................................................................. 50
4 9-565-1 1" Grommets
1 9-314-1 2" Grommet
9 6-032-1 1/4-20 Bolts 4 to mount the e-panel, 5 extra to mount the inverter
2 6-010-2 2 M6 Screws and other hardware for mounting inverter to backplate
1 10-234-1 Manual
Dual System:
8 9-565-1 1" Grommets
2 9-314-1 2" Grommet
18 6-032-1 1/4-20 Bolts 4 to mount the e-panel, 5 extra to mount the inverter
4 6-010-2 2 M6 Screws and other hardware for mounting inverter to backplate
2 9-489-1 10.5" Conduit
4 9-490-1 Conduit terminal adaptors
4 9-235-1 Conduit lock nuts
4 9-236-1 Conduit bushings
4 Additional connecting wires
1 10-234-1 Manual
Slave Unit:
4 9-565-1 1" Grommets
1 9-314-1 2" Grommet
9 6-032-1 1/4-20 Bolts 4 to mount the e-panel, 5 extra to mount the inverter
2 6-010-2 2 M6 Screws and other hardware for mounting inverter to backplate
4 5-015-1 Insulator, Black
4 5-015-6 Insulator, Blue
2 5-097-1 Insulator cover Black
4 6-037-1 Taptite screws
2 Conduit sets for 3 phase
3 Conduit sets for quads
2 Required connecting wire sets for 3 phase
3 Required connecting wire sets for quads
Units shipped with a Battery Combiner:
6 | P a g e 10- 234- 1 R E V : A
DC Negative
500Amp/50mv
Shunt
Battery Plus Bus
MNSMARB
Relay board
Charge Controller
breakers*
PV
Positive and negative
input connections
Ground Busbar
AC Neutral busbar
AC Input
AC Output
under charge
controller breakers
Charge Controller
breakers*
DC Disconnect
Breaker – Relay
trippable
Bypass Breakers
Dinrail for
additional breakers
AC or DC
E-Panel Component location
Not all components installed on all models.
*If not used for the Classic these breaker
locations are available for extra load breakers.
SMA E-Panel installation manual
7 | P a g e 10- 234- 1 R E V : A
Left: MNSMA Short BP Backplate
Typical backplate installation, shown mounted on wall with the inverter
mounting bracket installed (inverter mounting bracket supplied with
inverter).
CAUTION: The inverter is extremely heavy. Use extreme
caution when lifting the inverter. Refer to the inverter manual for
safe and proper inverter installation instructions. Make sure the
wall or other mounting surface can support the weight.
Encore, cet appareil est tellement lourd, sauvegarder vous-même.
SMA E-Panel installation manual
Mounting the SMA E-Panel to the wall:
This section describes the general instructions for installing components to the wall or other mounting surface. When
you have completed this section then refer to the appropriate section for your model for specific instructions on
wiring and wiring diagrams.
Pre-Wired systems start on Page 13.
Note: The SMA E-Panel system should only be installed with the backplate. Failure to use the backplate can result in
poor alignment of system components resulting in a less reliable and non-code compliant installation.
Tools Required:
Long #2 Phillips Screwdriver
Medium slotted Screwdriver
Torque Screwdriver for electrical connections
9/16” Wrench
Large Allen wrench for inverter DC connections
Drill for pilot holes if required
Be sure to comply with all local and national code requirements including National Electrical Code, ANSI/NFPA 70.
Use Class 1 wiring methods for field wiring connections to terminals of a Class 2 circuit. Select the wire gauge used
based on the protection provided by the circuit breakers/fuses.
The SMA E-Panel is a type 1 enclosure suitable for installation in an indoor location protected from rain / snow etc.
When installing the system make sure to observe NEC maximum height requirements.
The system when complete will be quite heavy. Ensure that the wall can handle the weight of the system
and use appropriate fasteners. Have help when positioning and mounting system components to the wall.
Mise en garde! Cet appareil est assez lourd. S’assurer que le mur peut supporter le système. C’est nécessaire d’avoir assistance pour installer le système.
High voltage is present throughout the system. Disconnect all sources of power and exercise extreme
caution when working with, on or around this equipment.
Attention: Il y a haute tension partout. Débrancher toutes les sources d’alimentation et faire attention autour
de le système. Lire aussi le manuel de l’inverter pour plus des informations.
Install the backplate either MNESMA tall BP or MNESMA short BP to the selected surface using a minimum of four
5/16 lag bolts with a minimum length of 2”.
The inverter should be installed before the E-Panel. Use ¼-20 bolts to attach the inverter mounting bracket, E-Panel
and MNX240 (if so equipped) to the backplate. The MNX240 requires the tall backplate.
8 | P a g e 10- 234- 1 R E V : A
Install the inverter mounting bracket before
mounting the backplate to the wall. Use ¼20 bolts and flat washers. Pressed in nuts
are provided on the backplate.
Ensure that the inverter bracket is centered
and is resting on the mounting screws
(down on the screws and not slid up).
Mounting on back of inverter
Inverter mounting bracket
mounted to backplate
Backplate mounted to wall
The inverter rests on the tab of the
inverter mounting bracket.
Caution!!
The inverter is very heavy. Have
strong persons assist you.
Attention!!
L’inverter est très lourd. Avez des
gens très forts vous assister.
Secure inverter to bracket with the
M6x10 screws provided.
Left and right sides.
Cover with fan grills provided.
The grills are marked left and
right.
SMA E-Panel installation manual
Mounting the SMA E-Panel to the wall cont.:
9 | P a g e 10- 234- 1 R E V : A
Inverter lower mounting screw locations.
The inverter is spaced away from
the back plate at the four lower
mounting screws.
These two mounting locations are not used
Inverter lower mounting screws installed
SMA E-Panel installation manual
Mounting the SMA E-Panel to the wall cont.:
10 | P a g e 10- 234- 1 R E V : A
E-Panel mounting holes
E-Panel mounting holes.
Place the E-Panel below the inverter and line up the E-Panel mounting holes with the holes in the backplate.
Attach the E-Panel to the backplate with ¼-20 bolts. Pressed in nuts are provided on the backplate.
Remove the deadfront
(metal front cover) by
removing the screws in the
four corners and the two
on the DC disconnect
breaker.
When reinstalling the
deadfront ensure that the
breaker handles are
protruding through the
slider as shown.
Slider
SMA E-Panel installation manual
Mounting the SMA E-Panel to the wall cont.:
11 | P a g e 10- 234- 1 R E V : A
Attaching the Autoformer – Required for AC coupling of a single Sunny Island inverter.
The tall backplate is required when using the MNX240 AutoFormer.
The optional 6000 Watt Autoformer for single inverter AC Coupled systems mounts above the inverter.
Position the MNX240 Autoformer above the inverter and line up the mounting holes. Install with ¼-20
hardware.
Plastic cover installation:
To install the cover line up both molded in hinge pins
with the cover mounting brackets and slide down into
position.
Hinge Pin
Cover mounting bracket on E-Panel
Hinge pin installed into mounting bracket
MNX240 Autotransformer
Shutoff / Circuit Breakers
Hookup terminal blocks
Hot
Neutral
SMA E-Panel installation manual
12 | P a g e 10- 234- 1 R E V : A
Above: Quad system with Battery Combiner.
Studs are shown for reference and are at 16” centers.
If mounting on plywood use ¾” material.
Use a minimum of eight 1/4” screws per backplate.
Pre-Wired Systems: Systems are available pre-assembled / pre-wired. It is not necessary to disassemble
systems to mount them on the wall. One way to install a pre-Wired system is to find where the bottom of the
backplate will be when installed and securely screw a 2x4 to the wall with the top just at where the backplate
will be. Place the bottom of the backplate on the 2x4 and have two people tip it up into place and secure the
backplate to the wall with a minimum of 8 ¼” screws at least 2” long.
Left Side knockout location
Front
Top
2/0 Battery cable lengths necessary to complete
installation as shown above:
E-Panel
Positive
Negative
#1
71”
71”
#2
45”
41”
#3
30”
44”
#4
60”
75”
SMA E-Panel installation manual
Mounting the SMA E-Panel to the wall continued:
13 | P a g e 10- 234- 1 R E V : A
Bottom knockout location
Right Side knockout location
Front
Top
SMA E-Panel installation manual
14 | P a g e 10- 234- 1 R E V : A
Negative connections to inverters
Positive connections to inverters
Negative shunt connection
To batteries
For installations not using the Battery Combiner connect a positive wire from the E-Panel breaker to the
battery bank positive and a negative wire from the E-Panel shunt. These wires should be kept as short as
possible. Running the wires close together will reduce ripple currents.
AC Wiring:
This varies greatly depending on your system configuration. The following wiring diagrams show on and off
grid, with and without a generator, AC coupled and three phase systems. Please pay special attention to the
information on AC coupled systems. Use appropriate conduit and fittings for a safe, reliable, code compliant
system.
Slave units are shipped with red mounting blocks and covers for AC in and AC out installed. Black and blue
mounting blocks and covers are included. Should you desire to change the mounting blocks and covers to
match the desired wire color (L1 Black, L2 Red and L3 Blue) Simply pull the cover off, press the retaining
tab on the mounting block to release the terminal block and remove the terminal block. There is a Phillips
screw in each mounting block. Remove and retain the screw. Using the new color reverse the process to
reinstall. Note: Use caution when tightening the screws. The chassis can be stripped if the screws are overtightened. Should this occur the use a slightly longer #10 screw and a #10 nut from behind.
Positive connections to batteries
SMA E-Panel installation manual
System wiring
The SMA E-Panel is a complex system and should be wired by a qualified electrician.
Danger: Hazardous voltages are present throughout the system. All power must be removed
before attempting any wiring or maintenance of the system.
Danger: Il y a haute tension partout dans le système entière. Débrancher toutes les sources
d’alimentation avant faisant des connections ou l’entretien.
The following pages contain wiring diagrams for many configurations. Follow the appropriate one for
your installation such as on or off grid, AC Coupled or three phase. The diagrams below also cover
single, dual and quad systems with up to 7 Classic Charge Controllers. Components sold separately.
If you are unsure of any aspect of the installation contact a licensed electrician or MidNite Solar at
360.403.7207.
DC Wiring:
If using the optional Battery Combiner run 4/0 wire from the battery breaker to the positive connection
in the Battery Combiner and 4/0 wire from the E-Panel shunt. It is acceptable to use black wire if the
ends are clearly marked red or white as appropriate. Use copper wire of adequate gauge (Determined by
breaker size) rated for a minimum of 75°C. Always use approved conduit and fittings.
Use 4/0 wire for a 250 Amp battery breaker and 2/0 for a 175 Amp battery breaker.
15 | P a g e 10- 234- 1 R E V : A
Bushing
Nut
Fitting
Conduit
Fitting
Nut
Bushing
Conduit and fitting parts
With one inverter installed, remove the top
and bottom knockouts (see image next page)
that face the other E-Panel and push one of
the fittings from the outside through the
knockout opening into the E-Panel.
Inside the E-Panel, secure the fitting with
one of the nuts and a bushing
These instructions are for installing the supplied conduits and fittings in a system with a Battery
Combiner.
SMA E-Panel installation manual
INSTALLING CONDUIT BETWEEN E-PANELS:
16 | P a g e 10- 234- 1 R E V : A
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.