Midmark M7-2 Service manual

®
Go To Table Of Contents
Place Order
To purchase a printed copy of this manual,
click on the "Place Order" button below.
SpeedClave Steam Sterilizers
Model Numbers:
M7 M7
Serial Number Prefixes:
MH, MJ, MK, ML, MM, MN, V
V
Ser vice and
Par ts Manual
SF-1855 Part No. 004-0454-00 Rev. D (4/1/08)
FOR USE BY MIDMARK TRAINED TECHNICIANS ONLY
GENERAL INFORMATION
Next
Back
Symbols ....................................i
Ordering Parts .......................... i
Model / Serial Number
Location .................................. i
Weights, Dimensions,
Electrical Specifications ....... ii
Model Identification /
Compliance Chart .................. iii
Special Tools ............................ iv
Warranty Information............... iv
General Information
ACCESS PROCEDURES
Removing & Installing:
Covers / Panels ........................ C-2
Tray Plate / Rack ...................... C-3
Draining / Filling Reservoir .....C-4
Section C
WIRING DIAGRAMS & SCHEMATICS
115 VAC models
M7 (-011 / -013 / -014 / -015) ........
M7 (-020 / -022) ............................
:
D-2 D-3
OPERATION & TROUBLESHOOTING
Electrical System:
M7 (-011 thru -016) .......................
M7 (-020 thru -022) .......................
Filling the Chamber ................. A-8
Heat-Up / Sterilization.............. A-14
Section A
Venting the Chamber ............... A-20
A-2 A-4
230 VAC models
M7 (-012 / -016) ............................
Section D
M7 (-021) ......................................
EXPLODED VIEWS / PARTS LISTS
M7 M7
TESTING & REPAIR
Checking for
Pressure Leaks ...................... B-2
Fuse........................................... B-3
Bellows ..................................... B-4
Fill / Vent Valve:
Section B
Table Of Contents
Manual ..........................................
Electronic ......................................
Temperature Regulator Assy .. B-12
Heating Element ....................... B-18
Overheat Thermostats ............. B-22
Pressure Relief Valve ............... B-25
Timer ......................................... B-26
Timer Buzzer ............................ B-30
Temperature Gauge ................. B-31
Door Assembly......................... B-32
Reservoir Tank.......................... B-34
Chamber Assembly ................. B-36
B-6 B-8
Section E
Section E
:
(-011 thru -016) ....................
(-020 thru -022)
:................... E-3
D-4 D-5
E-2
Symbols
Go To Table Of Contents
Next
Back
Caution
Indicates a potentially hazardous situation which could result in injury if not avoided.
Equipment Alert
Indicates a potentially hazardous situation which could result in equipment damage if not avoided.
Note
Amplifies a procedure, practice, or condition.
Indicates that the component the check mark appears beside should be tested before replacing it. In Section A, test the components in the order indicated. (ex.
1st
33
3
33
then,
33
3
33
Refer to Section B for component testing procedures.
2nd
)
33
3
33
Ordering Parts
General Information
Model / Serial Number Location
R
Serial Number
(all models)
Model & Serial Number
The following information is required when ordering parts:
Serial number & model number
Part number for desired part.
[Refer to Section E: Exploded Views / Parts Lists]
Non-warranty parts orders may be faxed to Midmark using the Fax Order Form in the back of this manual.
For warranty parts orders, call Midmark's Technical Service Department with the required information.
Hours: 8:00 am until 5:00 pm EST [Monday - Friday] Phone: 1-(800)-Midmark
General Information
M7 (-011 thru -016)
Location: bottom of unit
M7 (-020 thru -022)
Location: back of unit
i
© Midmark Corporation 2004 SF-1854
General Information
Go To Table Of Contents
Next
Back
Weights, Dimensions, Electrical Specifications
ATTENTION
A separate (dedicated) electrical circuit is recommended for all models. Do not connect to a circuit with other devices, unless the circuit is rated for the additional load.
R
A
M7 (-011 thru -016)
Dimensions
Height Width Depth
Chamber Size: ..................................... Diameter: 7.5 in. (19 cm)
Depth: 14.25 in. (36.2 cm)
Shipping Carton:
(Length x Width x Height) ..................
(61 cm x 40.6 cm x 40.6 cm)
Weight:
Shipping Weight ................................. 39 lbs (17.7 kg)
w/reservoir empty .............................. 30 lbs (13.6 kg)
w/reservoir full ................................... 41.8 lbs (19 kg)
Reservoir Capacity: ............................ Approx. 1.3 gallon (4.9 liters)
at FULL mark
Pressure Relief Valve:
opens at approximately: ....................
Electrical Requirements: ....................
Compliance Chart]
Power Consumption:
100 VAC models ................................
115 VAC models ................................
230 VAC models ................................
[Refer to illustration]:
(A) ...........................................
(B) ............................................
(C) ...........................................
12.8 in. (32.5 cm)
13.5 in. (34.3 cm)
18.1 in. (46 cm)
24 in. x 16 in. x 16 in.
34 psi (234 kPa)
[See Model Identification /
1150 watts, 12 amps @ 100 VAC 1150 watts, 10 amps @ 120 VAC 1150 watts, 5 amps @ 240 VAC
B
C
M7 (-020 thru -022)
Dimensions
Height Width Depth
Chamber Size: ..................................... Diameter: 7.5 in. (19 cm)
Depth: 14.25 in. (36.2 cm)
Shipping Carton:
(Length x Width x Height) ..................
(61 cm x 40.6 cm x 40.6 cm)
Weight:
Shipping Weight ................................. 39 lbs (17.7 kg)
w/reservoir empty .............................. 30 lbs (13.6 kg)
w/reservoir full ................................... 41.8 lbs (19 kg)
Reservoir Capacity: ............................ Approx. 1.3 gallon (4.9 liters)
at FULL mark
Pressure Relief Valve:
opens at approximately: ....................
Electrical Requirements: ....................
Compliance Chart]
Power Consumption:
115 VAC models ................................
230 VAC models ................................
[Refer to illustration]:
(A) ...........................................
(B) ............................................
(C) ...........................................
13 in. (33 cm) 14 in. (35.6 cm) 19 in. (48.3 cm)
24 in. x 16 in. x 16 in.
34 psi (234 kPa)
[See Model Identification /
1300 watts, 10 amps @ 115 VAC 1300 watts, 5 amps @ 230 VAC
ii
© Midmark Corporation 2004 SF-1854
Rev.12/04
Fuse
(back of unit)
115 VAC models ................................
230 VAC models ................................
:
12 amp, 250 V, Fast-Acting, 1/4" x 1-1/4" 8 amp, 250 V, Fast-Acting, 5 x 20 mm
Model Identification / Compliance Chart
Go To Table Of Contents
Next
Back
ledoM noitpircseD
General Information
:oTseilpmoC :sgnitaRlacirtcelE
laireS
rebmuN
sexiferP
LU
445
LU
1-A01016
140-2-01016
ASC/NAC
,2.22C
151#
ASC/NAC
,2.22C
0101#
69-140-2.0101#
CAV spmA
selcyC
)zH(
110-7M
210-7M
310-7M
410-7M
510-7M
610-7M
020-7M
120-7M
220-7M
)CAV511(
)CAV032(
)CAV001(
)CAV511(
)CAV511(
)CAV032(
)CAV511(
)CAV032(
)CAV511(
reziliretS7MrettiR
reziliretS7MkramdiM
reziliretS7MkramdiM
reziliretS7MkramdiM
reziliretS7MetnalAibaD
reziliretS7MetnalAibaD
reziliretS7MkramdiM
reziliretS7MkramdiM
reziliretS7MrettiR
HM & V
JM & V
KM & V
MM & V
NM & V
V
V
V
xx
x x
xx
V&LM
x x
xx
x x
xx
x x
xx
5110106
042/022 5 05
0012106
511 01 06
5110106
032 5 06
5110106
032 5 05
5110106
© Midmark Corporation 2004 SF-1854
iii
General Information
Go To Table Of Contents
Next
Back
Special Tools
This table lists all special tools needed to diagnose and repair the sterilizer.
looTlaicepS rerutcafnaM rebmuNtraP looTfoesopruP
retemitluMlatigiD
retemomrehTlatigiD
elbaliavayllaicremmoCepytynaskcehcegatlov/ytiunitnocmrofrepoT
elbaliavayllaicremmoC epytyna erutarepmetrebmahcyfirevoT
Warranty Information
SCOPE OF WARRANTY
Midmark Corporation (“Midmark”) warrants to the original purchaser its new Alternate Care products and components (except for components not warranted under “Exclusions”) manufac­tured by Midmark to be free from defects in material and workmanship under normal use and service. Midmark’s obligation under this warranty is limited to the repair or replacement, at Midmark’s option, of the parts or the products the defects of which are reported to Midmark within the applicable warranty period and which, upon examination by Midmark, prove to be defective.
APPLICABLE WARRANTY PERIOD
The applicable warranty period, measured from the date of delivery to the original user, shall be one (1) year for all warranted products and components.
EXCLUSIONS
This warranty does not cover and Midmark shall not be liable for the following: (1) repairs and replacements because of misuse, abuse, negligence, alteration, accident, freight damage, or tampering; (2) products which are not installed, used, and properly cleaned as required in the Midmark “Installation” and or “Installation / Operation Manual for this applicable product. (3) products considered to be of a consumable nature; (4) accessories or parts not manufactured by Midmark; (5) charges by anyone for adjustments, repairs, replacement parts, installation, or other work performed upon or in connection with such products which is not expressly authorized in writing in advance by Midmark.
EXCLUSIVE REMEDY
Midmark’s only obligation under this warranty is the repair or replacement of defective parts. Midmark shall not be liable for any direct, special, indirect, incidental, exemplary, or consequen tial damages or delay, including, but not limited to, damages for loss of profits or loss of use.
NO AUTHORIZATION
No person or firm is authorized to create for Midmark any other obligation or liability in connection with the products.
ADDITIONAL INFORMATION
Failure to follow the guidelines listed below will void the warranty and/or render the table unsafe for use.
If a malfunction is detected, do not use the table
until necessary repairs are made.
Do not attempt to disassemble table, replace
components, or perform adjustments unless you are a Midmark authorized service technician.
Do not use another manufacturer's parts to replace
malfunctioning components. Use only Midmark replacement parts
THIS WARRANTY IS MIDMARK’S ONLY WARRANTY AND IS IN LIEU OF ALL OTHER WARRANTIES, EX­PRESS OR IMPLIED. MIDMARK MAKES NO IMPLIED WARRANTIES OF ANY KIND INCLUDING ANY WAR­RANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE. THIS WARRANTY IS LIMITED TO THE REPAIR OR REPLACEMENT OF DEFECTIVE PARTS.
SF-1487 REV. A1
iv
© Midmark Corporation 2004 SF-1854
Operation & Troubleshooting
Go To Table Of Contents
Next
Back
Operation & Troubleshooting
Mode Page
Electrical System:
M7 (-011 thru -016) ...........................
M7 (-020 thru -022) ...........................
Filling the Chamber .............................. A-8
Heat Up / Sterilization ........................... A-14
Venting the Chamber ............................ A-20
A-2
A-4
Models:
Serial Numbers:
Section A
© Midmark Corporation 2004 SF-1854
A-1
Operation & Troubleshooting
Go To Table Of Contents
Back
Next
Electrical System - [M7 (-011 thru -016)]
The illustration shows all of the electrical components of the sterilzer.
Refer to the following page for a detailed description of current flow.
Overheat
Thermostat
(Manual-Reset)
Com.
Overheat
Thermostat
(Auto-Reset)
Troubleshooting
[Electrical System]
Problem: Page
Heating element does not turn ON:
- Heater light is OFF ...............................
- Heater light is ON
.............................
Sterilizer shuts down before
timer setting expires .........................
Timer buzzer does not function ...........
A-6
A-7
A-17
A-19
Electrical System
A-2
© Midmark Corporation 2004 SF-1854
Heating Element
Com.
Temperature
Regulator
Relay
Serial Numbers:
Heater
Light
Models:
Timer
Buzzer
Timer
MA670901i
M7 (-011 thru -016)
all
Operation & Troubleshooting
Go To Table Of Contents
Next
Back
Electrical System - [M7 (-011 thru -016)]
With the power cord properly connected...
Overheat Thermostats
Current
closed)
If either thermostat opens from the timer until the thermostat is reset or replaced.
NOTE
The Manual-Reset Thermostat contacts open at approximately 285°F (140°C). To reset, allow unit to cool, then press RESET button on front of unit.
The Auto-Reset Thermostat contacts open at approximately 295°F (146°C). This thermostat automatically resets when the unit cools to approx. 265°F (129°C).
Timer
Current is supplied to the timer thru the two overheat thermostats.
When the timer is turned ON...
Timer
The timer motor and the temperature regulator relay. The timer motor runs, and begins to count down the time it was set for.
(The contacts to the timer buzzer remain open).
(115 / 230 VAC)
overheat thermostats. This current supplies power to the timer.
(normally open)
continuously flows thru the two
(overheat or malfunction),
timer contacts close, and voltage is supplied to the
(normally
voltage is removed
When the timer is turned ON (continued)...
Heater Light & Heating Element
When the contacts of the temperature regulator relay are closed, current is supplied to the heater light and the heating element.
As the relay contacts open and close, the heating element cycles ON / OFF. This continues until the timer setting expires.
The heater light is illuminated whenever the heating element is ON.
When the timer setting expires...
Timer & Timer Buzzer
The contacts to the temperature regulator relay open, stopping the current flow to the heater light & heating element.
The contacts to the timer buzzer close and current flows to the timer buzzer. When voltage is applied, the buzzer emits an audible signal.
The contacts to the timer motor remain closed for one minute. After one minute the contacts to the timer motor & the timer buzzer open, stopping the current flow to these two components.
Temperature Regulator Relay
Current is supplied to the temperature regulator relay thru the timer. If the chamber temperature is lower than the temperature knob setting*, the relay contacts are closed. When these contacts are closed, current flows thru the relay to the heating element and the heater light.
The diaphragm cup of the relay expands as the temperature & pressure inside the chamber increase. When the chamber temperature reaches the temperature knob setting, the relay contacts open, and voltage is removed from the heating element & heater light.
[* The minimum temperature knob setting is approx. 220°F (104°C)]
Models:
Serial Numbers:
M7 (-011 thru -016)
all
Electrical System
© Midmark Corporation 2004 SF-1854
A-3
Operation & Troubleshooting
Go To Table Of Contents
Next
Back
Electrical System - [M7 (-020 thru -022)]
The illustration shows all of the electrical components of the sterilzer.
Refer to the following page for a detailed description of current flow.
Fuse
Overheat
Thermostat
(Manual-Reset)
Troubleshooting
[Electrical System]
Problem: Page
When Fill/Vent Switch is pressed:
- Chamber does not FILL .......................
- Chamber does not VENT .....................
Heating element does not turn ON:
- Heater light is OFF ...............................
- Heater light is ON
.............................
Sterilizer shuts down before
timer setting expires .........................
Timer buzzer does not function ...........
A-11
A-23
A-6
A-7
A-17
A-19
Com.
Heating Element
Com.
Temperature
Regulator
Relay
Heater
Light
Timer
Buzzer
Com.
Overheat
Thermostat
(Auto-Reset)
Timer
Fill / Vent
Switch
Fill / Vent
Valve
MA670900i
Electrical System
A-4
© Midmark Corporation 2004 SF-1854
Models:
Serial Numbers:
M7 (-020 thru -022)
all
Operation & Troubleshooting
Go To Table Of Contents
Next
Back
Electrical System - [M7 (-020 thru -022)]
With the power cord properly connected...
Fuse
Current back of the unit. This current supplies power to the fill / vent switch and the overheat thermostats.
Fill / Vent Switch
Current is supplied to the fill / vent switch thru the fuse.
Overheat Thermostats & Timer
Current is supplied to the two overheat thermostats thru the fuse. Current continuously flows thru the thermostats to the timer.
If either thermostat opens from the timer until the thermostat is reset or replaced.
NOTE
The Manual-Reset Thermostat contacts open at approximately 285°F (140°C). To reset, allow unit to cool, then press RESET button on front of unit.
The Auto-Reset Thermostat contacts open at approximately 295°F (146°C). This thermostat automatically resets when the unit cools to approx. 265°F (129°C).
(115 / 230 VAC)
continuously flows thru the fuse located in the
(overheat or malfunction),
voltage is removed
When the timer is turned ON (continued)...
Temperature Regulator Relay
Current is supplied to the temperature regulator relay thru the timer. If the chamber temperature is lower than the temperature knob setting*, the relay contacts are closed. When these contacts are closed, current flows thru the relay to the heating element and the heater light.
[* The minimum temperature knob setting is approx. 220°F (104°C)]
The diaphragm cup of the relay expands as the temperature & pressure inside the chamber increase. When the chamber temperature reaches the temperature knob setting, the relay contacts open, and voltage is removed from the heating element & heater light.
Heater Light & Heating Element
When the contacts of the temperature regulator relay are closed, current is supplied to the heater light and the heating element. As the relay contacts open and close, the heating element cycles ON / OFF. This continues until the timer setting expires. The heater light is illuminated whenever the heating element is ON.
When the timer setting expires...
Timer & Timer Buzzer
The contacts to the temperature regulator relay open, stopping the current flow to the heater light & heating element.
When filling the chamber (pressing the fill/vent switch)...
Fill / Vent Switch
The contacts of the switch are closed, current is supplied to the fill / vent valve.
Fill / Vent Valve
When current is applied to the When the valve is open, water flows into the chamber.
When the Timer is turned ON...
Timer
The
(normally open)
timer motor and the temperature regulator relay. The timer motor runs, and begins to count down the time it was set for.
(The contacts to the timer buzzer remain open).
Models:
Serial Numbers:
(normally open)
timer contacts close, and voltage is supplied to the
switch close. When the contacts of the
(normally closed)
valve, the valve opens.
M7 (-020 thru -022)
all
The contacts to the timer buzzer close and current flows to the timer buzzer. When voltage is applied, the buzzer emits an audible signal.
The contacts to the timer motor remain closed for one minute. After one minute the contacts to the timer motor & the timer buzzer open, stopping the current flow to these two components.
When pressing the Fill / Vent Switch (to VENT the chamber)...
Fill / Vent Switch
The contacts of the switch are closed, current is supplied to the fill / vent valve.
(normally open)
switch close. When the contacts of the
Fill / Vent Valve
When current is applied to the When the valve is open, steam is released thru the condensing coil & the water is returned to the reservoir .
(normally closed)
Electrical System
© Midmark Corporation 2004 SF-1854
valve, the valve opens.
A-5
Operation & Troubleshooting
Go To Table Of Contents
Next
Back
Refer To: Page
Operation & Troubleshooting ................ A-1
Component Testing / Repair ................. B-1
Access Procedures .............................. C-1
Wiring Diagrams ................................... D-1
Exploded Views / Part Numbers ........... E-1
4th
Loose / Damaged Wire Connections
Check all wiring connections. (Power cord, overheat thermostats, etc.)
33
3
33
Problem: Heating element does not turn ON.
M7 (-020 thru -022) only
Fuse
[Heater light is OFF]
3rd
33
3
33
Timer
Press RESET button
Allow unit to cool for 15-20 minutes before pressing RESET button.
1st
7th
33
3
33
R
33
3
33
Temperature Regulator Assy.
Overheat Thermostats
5th
6th
33
3
33
Check supply voltage
(A dedicated circuit is recommended)
33
3
33
MA670800i
2nd
33
3
33
Electrical System
A-6
© Midmark Corporation 2004 SF-1854
Models:
Serial Numbers:
M7 (-011 thru -016)
all
M7 (-020 thru -022)
all
Problem: Heating element does not turn ON.
Go To Table Of Contents
Next
Back
[Heater light is ON]
Operation & Troubleshooting
Refer To: Page
Operation & Troubleshooting ................ A-1
Component Testing / Repair ................. B-1
Access Procedures .............................. C-1
Wiring Diagrams ................................... D-1
Exploded Views / Part Numbers ........... E-1
Models:
Serial Numbers:
Heating
1st
33
3
33
Element
M7 (-011 thru -016)
all
R
M7 (-020 thru -022)
all
MA672300i
Electrical System
© Midmark Corporation 2004 SF-1854
A-7
Operation & Troubleshooting
Go To Table Of Contents
Next
Back
Filling the Chamber
The illustrations show the water flow when filling the chamber.
Refer to the following page for a detailed description of this process.
M7 (-011 thru -016)
Reservoir
Troubleshooting
[Filling the Chamber]
Problem: Page
Chamber does not fill:
- M7 (-011 thru -016) ..............................
- M7 (-020 thru -022) ..............................
A-10
A-11
Water continuously flows into chamber:
- M7 (-011 thru -016) ..............................
- M7 (-020 thru -022)
...........................
A-12
A-13
M7 (-020 thru -022)
Filling the Chamber
A-8
© Midmark Corporation 2004 SF-1854
Fill / Vent Valve
(open)
= Water
Models:
Serial Numbers:
M7 (-011 thru -016)
all
Filter Screen
Fill / Vent Valve
(open)
M7 (-020 thru -022)
all
Reservoir
MA671500i
Filling the Chamber
Go To Table Of Contents
Next
Back
Operation & Troubleshooting
M7 (-011 thru -016)
When the Fill / Vent Lever is pressed and held...
Fill Vent Valve
The
(normally closed - manual)
from the reservoir flows thru the fill / vent valve into the chamber.
When the Fill / Vent Lever is released...
Fill / Vent Valve
The valve closes, and stops the flow of water into the chamber.
R
valve opens. When the valve is open, water
M7 (-020 thru -022)
When the Fill / Vent Switch is pressed and held...
Fill / Vent Switch & Valve
Current voltage is applied, the is open, water from the reservoir flows into the chamber thru the valve and filter screen.
When the Fill / Vent Switch is released...
Fill / Vent Switch & Valve
The fill/vent switch opens, stopping the current flow to the fill/vent valve. When voltage is removed, the valve closes. When the valve closes, water stops flowing into the chamber.
(line voltage)
flows thru the fill/vent switch to the fill/vent valve. When
(normally closed)
R
fill / vent valve opens. When the valve
Fill / Vent
Lever
Models:
Serial Numbers:
M7 (-011 thru -016)
all
M7 (-020 thru -022)
all
Fill / Vent
Switch
MA512903i
Filling the Chamber
© Midmark Corporation 2004 SF-1854
A-9
Operation & Troubleshooting
Go To Table Of Contents
Next
Back
Refer To: Page
Operation & Troubleshooting ................ A-1
Component Testing / Repair ................. B-1
Access Procedures .............................. C-1
Wiring Diagrams ................................... D-1
Exploded Views / Part Numbers ........... E-1
R
Problem: Chamber does not fill.
Low water in reservoir?
Add distilled water if necessary.
1st
33
3
33
Filling the Chamber
A-10
© Midmark Corporation 2004 SF-1854
Models:
Serial Numbers:
M7 (-011 thru -016)
all
Fill / Vent Valve & Tubing
Clean / adjust / replace as necessary.
MA672400i
2nd
33
3
33
Problem: Chamber does not fill.
Go To Table Of Contents
Next
Back
Operation & Troubleshooting
Refer To: Page
Operation & Troubleshooting ................ A-1
Component Testing / Repair ................. B-1
Access Procedures .............................. C-1
Wiring Diagrams ................................... D-1
Exploded Views / Part Numbers ........... E-1
Filter Screen
Clean / replace as necessary.
2nd
Fill / Vent Switch
33
3
33
R
6th
33
3
33
Fuse
Low water in reservoir?
Add distilled water if necessary.
4th
33
3
33
1st
33
3
33
Check supply voltage
(A dedicated circuit is recommended)
3rd
33
3
33
Models:
Serial Numbers:
M7 (-020 thru -022)
all
Fill / Vent Valve & Tubing
Clean / adjust / replace as necessary.
Filling the Chamber
© Midmark Corporation 2004 SF-1854
5th
33
3
33
A-11
Operation & Troubleshooting
Go To Table Of Contents
Next
Back
Refer To: Page
Operation & Troubleshooting ................ A-1
Component Testing / Repair ................. B-1
Access Procedures .............................. C-1
Wiring Diagrams ................................... D-1
Exploded Views / Part Numbers ........... E-1
R
Problem: Water continuously flows into chamber.
Filling the Chamber
A-12
© Midmark Corporation 2004 SF-1854
Models:
Serial Numbers:
M7 (-011 thru -016)
all
Fill / Vent Valve & Tubing
Clean / adjust / replace as necessary.
MA672400i
1st
33
3
33
Problem: Water continuously flows into chamber.
Go To Table Of Contents
Next
Back
R
Operation & Troubleshooting
Refer To: Page
Operation & Troubleshooting ................ A-1
Component Testing / Repair ................. B-1
Access Procedures .............................. C-1
Wiring Diagrams ................................... D-1
Exploded Views / Part Numbers ........... E-1
Models:
Serial Numbers:
Fill / Vent Switch
M7 (-020 thru -022)
all
2nd
33
3
33
Fill / Vent Valve & Tubing
Clean / adjust / replace as necessary.
Filling the Chamber
© Midmark Corporation 2004 SF-1854
1st
33
3
33
A-13
Operation & Troubleshooting
Go To Table Of Contents
Next
Back
Heat Up / Sterilization
The illustrations show the water / steam flow during heat up & sterilization.
Refer to the following page for a detailed description of this process.
Heat-Up
Bellows
(open)
Temperature
Regulator Relay
(closed)
Troubleshooting
[Heat-Up / Sterilization]
Problem: Page
Heating element does not turn ON:
- Heater light is OFF ...............................
- Heater light is ON
.............................
A-6 A-7
Heating element turns ON, but does not
reach required temperature ..............
A-16
Sterilizer shuts down before
timer setting expires .........................
A-17
Biological test strips indicate items
are not sterile ...................................
Timer buzzer does not function ...........
A-18
A-19
Sterilization
Pressure Relief Valve
(closed)
= Water
= Heated Water
= Steam
Heat-Up / Sterilization
A-14
© Midmark Corporation 2004 SF-1854
Fill / Vent Valve
(closed)
Note: Electronic valve is shown.
Manual valve is also closed.
Models:
Serial Numbers:
M7 (-011 thru -016)
all
Temperature
Regulator Relay
(closed / open)
Fill / Vent Valve
Note: Electronic valve is shown.
Manual valve is also closed.
M7 (-020 thru -022)
all
Bellows
(closed)
MA672000i
(closed)
Heat-Up / Sterilization
Go To Table Of Contents
Next
Back
Operation & Troubleshooting
When the timer is turned ON...
Timer
The
(normally open)
timer motor and the temperature regulator relay. The timer motor runs, and begins to count down the time it was set for.
timer contacts close, and voltage is supplied to the
(The contacts to the timer buzzer remain open).
Temper
Current is supplied to the temperature regulator relay thru the timer. If the chamber temperature is lower than the temperature knob setting*, the relay contacts are closed. When these contacts are closed, current flows thru the relay to the heating element and the heater light.
ature Regulator Relay
[* The minimum temperature knob setting is approx. 220°F (104°C)]
The diaphragm cup of the relay expands as the temperature & pressure inside the chamber increase. When the chamber temperature reaches the temperature knob setting, the relay contacts open, and voltage is removed from the heating element & heater light.
Heater Light & Heating Element
When the contacts of the temperature regulator relay are closed, current is supplied to the heater light and the heating element.
As the relay contacts open and close, the heating element cycles ON / OFF. This continues until the timer setting expires.
When the timer setting expires...
Timer &
The contacts to the temperature regulator relay open, stopping the current flow to the heater light & heating element.
The contacts to the timer buzzer close and current flows to the timer buzzer. When voltage is applied, the buzzer emits an audible signal.
The contacts to the timer motor remain closed for one minute. After one minute the contacts to the timer motor & the timer buzzer open, stopping the current flow to these two components.
Timer Buzzer
R
The heater light is illuminated whenever the heating element is ON.
Bello
ws & Pressure Relief Valve
Heat-Up: As the water in the chamber begins to boil, air is forced out of the chamber. This air passes thru the bellows into the reservoir.
Sterilization: When pure steam begins to flow thru the bellows, the bellows closes allowing pressure to build in the chamber. If the pressure in the chamber exceeds 34 psi (234 kPa), the pressure relief valve opens to prevent unsafe conditions.
Models:
Serial Numbers:
M7 (-011 thru -016)
all
M7 (-020 thru -022)
all
Temperature Knob
Timer Knob
MA672100i
Heat-Up / Sterilization
© Midmark Corporation 2004 SF-1854
A-15
Operation & Troubleshooting
Go To Table Of Contents
Next
Back
Refer To: Page
Operation & Troubleshooting ................ A-1
Component Testing / Repair ................. B-1
Access Procedures .............................. C-1
Wiring Diagrams ................................... D-1
Exploded Views / Part Numbers ........... E-1
Refer to Section B for checkpoints.
1st
33
3Check for pressure leaks.
33
Problem: Heating element turns ON, but does
not reach required temperature. [Heater light is ON]
Heating Element
Heat-Up / Sterilization
A-16
© Midmark Corporation 2004 SF-1854
3rd
33
3
33
Models:
Serial Numbers:
R
M7 (-011 thru -016)
all
M7 (-020 thru -022)
all
MA672700i
Temperature Regulator Assy.
2nd
33
3
33
Problem: Sterilizer shuts down before timer setting expires.
Go To Table Of Contents
Next
Back
Check for pressure leaks.
Refer to Section B for checkpoints.
1st
Operation & Troubleshooting
Refer To: Page
Operation & Troubleshooting ................ A-1
Component Testing / Repair ................. B-1
Access Procedures .............................. C-1
Wiring Diagrams ................................... D-1
Exploded Views / Part Numbers ........... E-1
33
3
33
Timer
Press RESET button
Allow unit to cool for 15-20 minutes before pressing RESET button.
2nd
33
3
33
5th
R
33
3
33
Temperature Regulator Assy.
4th
33
3
33
Overheat Thermostats
MA672800i
3rd
33
3
33
Models:
Serial Numbers:
M7 (-011 thru -016)
all
M7 (-020 thru -022)
all
Heat-Up / Sterilization
© Midmark Corporation 2004 SF-1854
A-17
Operation & Troubleshooting
Go To Table Of Contents
Next
Back
Refer To: Page
Operation & Troubleshooting ................ A-1
Component Testing / Repair ................. B-1
Access Procedures .............................. C-1
Wiring Diagrams ................................... D-1
Exploded Views / Part Numbers ........... E-1
Problem: Biological test strips indicate items are not sterile.
Type / condition of indicator strips
This unit requires test strips rated for:
Gravity Displacement Steam Sterilizers
Test strips must be stored in a cool, dry location. Failure to do so will result in faulty readings.
(Follow all instructions provided with test strips)
1st
33
3
33
Is the sterlizer overloaded?
Large loads or heavy linen packs may prevent strips from changing.
Are the correct trays being used?
Some trays may prevent proper air flow. Be sure trays are designed for this sterilizer.
3rd
2nd
33
3
33
33
3
33
4th
5th
33
3
33
33
3
33
Check for pressure leaks.
Refer to Section B for checkpoints.
R
Temperature Regulator Assy.
MA672900i
Heat-Up / Sterilization
A-18
© Midmark Corporation 2004 SF-1854
Models:
Serial Numbers:
M7 (-011 thru -016)
all
M7 (-020 thru -022)
all
Problem: Timer buzzer does not function.
Go To Table Of Contents
Next
Back
Operation & Troubleshooting
Refer To: Page
Operation & Troubleshooting ................ A-1
Component Testing / Repair ................. B-1
Access Procedures .............................. C-1
Wiring Diagrams ................................... D-1
Exploded Views / Part Numbers ........... E-1
Timer Buzzer
R
1st
33
3
33
MA672900i
Models:
Serial Numbers:
M7 (-011 thru -016)
all
M7 (-020 thru -022)
all
Heat-Up / Sterilization
© Midmark Corporation 2004 SF-1854
A-19
Operation & Troubleshooting
Go To Table Of Contents
Next
Back
Venting the Chamber
The illustrations show the steam / water flow when venting the chamber.
Refer to the following page for a detailed description of this process.
M7 (-011 thru -016)
Condensing Coil
Troubleshooting
[Venting the Chamber]
Problem: Page
Chamber will not vent:
- M7 (-011 thru -016) ..............................
- M7 (-020 thru -022) ..............................
M7 (-020 thru -022)
A-22
A-23
Venting the Chamber
A-20
© Midmark Corporation 2004 SF-1854
= Water
= Steam
Fill / Vent Valve
(open)
Models:
Serial Numbers:
M7 (-011 thru -016)
all
Fill / Vent Valve
(open)
M7 (-020 thru -022)
all
Filter Screen
Condensing Coil
MA672200i
Venting the Chamber
Go To Table Of Contents
Next
Back
Operation & Troubleshooting
Attention
The door handle
must be moved to the VENT position
before pressing the Fill / Vent Lever or Switch.
M7 (-011 thru -016)
When the Fill / Vent Lever is pressed and held...
Fill / Vent Valve
The
(normally closed - manual)
and steam back into the reservoir thru the valve and the condensing coil. When all of the pressure has been vented, the door will "pop".
Note: Release the lever when the door "pops".
If the lever is held too long, the chamber will begin to fill.
When the Fill / Vent Lever is released...
Fill / Vent Valve
The valve closes.
valve opens. Pressure forces water
M7 (-020 thru -022)
When the Fill / Vent Switch is pressed and held...
Fill / Vent Switch & Valve
Current voltage is applied, the water and steam back into the reservoir thru the valve and the condensing coil. When all of the pressure has been vented, the door will "pop".
Note: Release the lever when the door "pops".
When the Fill / Vent Switch is released...
Fill / Vent Switch & Valve
The fill/vent switch opens, stopping the current flow to the fill/vent valve. When voltage is removed, the valve closes.
(line voltage)
flows thru the fill/vent switch to the fill/vent valve. When
(normally closed)
fill / vent valve opens. Pressure forces
If the lever is held too long, the chamber will begin to fill.
Fill / Vent
Lever
Models:
Serial Numbers:
R
M7 (-011 thru -016)
all
M7 (-020 thru -022)
all
Fill / Vent
Switch
R
MA512903i
Venting the Chamber
© Midmark Corporation 2004 SF-1854
A-21
Operation & Troubleshooting
Go To Table Of Contents
Next
Back
Refer To: Page
Operation & Troubleshooting ................ A-1
Component Testing / Repair ................. B-1
Access Procedures .............................. C-1
Wiring Diagrams ................................... D-1
Exploded Views / Part Numbers ........... E-1
R
Problem: Chamber will not vent.
Venting the Chamber
A-22
© Midmark Corporation 2004 SF-1854
Models:
Serial Numbers:
M7 (-011 thru -016)
all
Fill / Vent Valve & Tubing
Clean / adjust / replace as necessary.
MA672400i
1st
33
3
33
Problem: Chamber will not vent.
Go To Table Of Contents
Next
Back
Operation & Troubleshooting
Refer To: Page
Operation & Troubleshooting ................ A-1
Component Testing / Repair ................. B-1
Access Procedures .............................. C-1
Wiring Diagrams ................................... D-1
Exploded Views / Part Numbers ........... E-1
Filter Screen
Clean / replace as necessary.
Models:
Serial Numbers:
1st
33
3
33
Fill / Vent Switch
M7 (-020 thru -022)
all
R
3rd
33
3
33
Fill / Vent Valve & Tubing
Clean / adjust / replace as necessary.
Venting the Chamber
© Midmark Corporation 2004 SF-1854
2nd
33
3
33
A-23
Go To Table Of Contents
Next
Back
Loading...
+ 82 hidden pages