3 Combination Ratio ................................................................................ 8
3
Page 5
V6-i VRF 50/60Hz
Midea V6-i Series Engineering Data Book
Abbreviation
code
Type
Abbreviation
code
Type
Q1
One-way Cassette
T1
High Static Pressure Duct
Q2
Two-way Cassette
G
Wall-mounted
Q4C
Compact Four-way Cassette
DL
Ceiling & Floor
Q4
Four-way Cassette
F
Floor Standing
T2
Medium Static Pressure Duct
Z
Console
Capacity
Capacity
index
Q1
Q2
Q4C
Q4
T2
T1 G DL F Z
kW
HP
1.8
0.6
18
18
———————
18 — 2.2
0.8
22
22
22
22 — 22 — 22 — 22
22
2.8 1 28
28
28
28
28
28 — 28 — 28
28
3.6
1.25
36
36
36
36
36
36 — 36
36
36
36
4.5
1.6
45
45
45
45
45
45 — 45
45
45
45
5.6 2 56
56
56 — 56
56 — 56
56
56 — 7.1
2.5
71
71
71 — 71
71
71
71
71
71 — 8.0 3 80
———
80
80
80
80
80
80 — 9.0
3.2
90
———
90
90
90
90
90
90 — 10.0
3.6
100
———
100
— — — — —
—
11.2 4 112
———
112
112
112 — 112
—
—
14.0 5 140
———
140
140
140 — 140
—
—
16.0 6 160
—————
160 — 160
—
—
20.0 7 200
—————
200
— — —
—
25.0 9 250
—————
250
— — —
—
28.0
10
280
—————
280
— — —
—
40.0
14
400
—————
400
— — —
—
45.0
16
450
—————
450
— — —
—
56.0
20
560
—————
560
— — —
—
Capacity
12.5kW
14kW
20kW
25kW
28kW
Capacity index
125
140
200
250
280
Capacity
200m3/h
300m3/h
400m3/h
500m3/h
800m3/h
1000m3/h
1500m3/h
2000m3/h
1 Indoor and Outdoor Unit Capacities
1.1 Indoor Units
1.1.1 Standard indoor units
Table 1-1.1: Standard indoor unit abbreviation codes
Table 1-1.2: Standard indoor unit capacity range
1.1.2 Fresh air processing unit
Table 1-1.3: Fresh air processing unit capacity range
1.2 Heat recovery ventilator
Table 1-1.4: Heat recovery ventilator capacity range
4
Page 6
V6-i VRF 50/60Hz
Part 1 - General Information
Capacity
Model Name
8HP
MV6-i252WV2GN1-E
10HP
MV6-i280WV2GN1-E
12HP
MV6-i335WV2GN1-E
14HP
MV6-i400WV2GN1-E
16HP
MV6-i450WV2GN1-E
18HP
MV6-i500WV2GN1-E
20HP
MV6-i560WV2GN1-E
22HP
MV6-i615WV2GN1-E
24HP
MV6-i670WV2GN1-E
26HP
MV6-i730WV2GN1-E
28HP
MV6-i785WV2GN1-E
30HP
MV6-i850WV2GN1-E
32HP
MV6-i900WV2GN1-E
1.3 Outdoor Units
Table 1-1.5: Outdoor unit capacity range
5
Page 7
V6-i VRF 50/60Hz
Midea V6-i Series Engineering Data Book
One-way Cassette
Two-way Cassette
Q1 Q2
Compact Four-way Cassette
Four-way Cassette
Q4C
Q4
Medium Static Pressure Duct
High Static Pressure Duct
T2 T1
Wall-mounted
Ceiling & Floor
G DL
Floor Standing
Console
F Z
Fresh Air Processing Unit
FA
Heat Recovery Ventilator
2 External Appearance
2.1 Indoor Units
2.1.1 Standard indoor units
Table 1-2.1: Standard indoor unit appearance
2.1.2 Fresh air processing unit
Table 1-2.2: Fresh air processing unit appearance
2.2 Heat Recovery Ventilator
Table 1-2.3: Heat recovery ventilator appearance
6
Page 8
V6-i VRF 50/60Hz
Part 1
- General Information
8/10/12HP
(with single fan)
14/16/18HP
(with single fan)
20/22HP
(with dual fans)
24/26/28/30/32HP
(with dual fans)
2.3 Outdoor Units
Table 1-2.4: Outdoor unit appearance
7
Page 9
V6-i VRF 50/60Hz
Midea V6-i Series Engineering Data Book
Type
Minimum
combination ratio
Maximum combination ratio
Standard indoor
units only
Fresh air processing
units only
Fresh air processing units and
standard indoor units together
V6-i Series outdoor units
50%
130%
100%
100%1
Outdoor unit capacity
Sum of capacity indexes of
connected indoor units (standard
indoor units only)
Sum of capacity indexes of connected indoor
units (fresh air processing units and standard
indoor units together)
Maximum number of
connected indoor
units
kW
HP
Capacity
index
25.2 8 252
126 to 327.6
126 to 252
13
28.0
10
280
140 to 364
140 to 280
16
33.5
12
335
167.5 to 435.5
167.5 to 335
20
40.0
14
400
200 to 520
200 to 400
23
45.0
16
450
225 to 585
225 to 450
26
50.0
18
500
250 to 650
250 to 500
29
56.0
20
560
280 to 728
280 to 560
33
61.5
22
615
307.5 to 799.5
307.5 to 615
36
67.0
24
670
335 to 871
335 to 670
39
73.0
26
730
365 to 949
365 to 730
43
78.5
28
785
392.5 to 1020.5
392.5 to 785
46
85.0
30
850
425 to 1105
425 to 850
50
90.0
32
900
450 to 1170
450 to 900
53
Combination ratio =
Sum of capacity indexes of the indoor units
Capacity index of the outdoor unit
3 Combination Ratio
Table 1-5.1: Indoor and outdoor unit combination ratio limitations
Notes:
1. When fresh air processing units are installed together with standard indoor units, the total capacity of the fresh air processing units must not exceed 30%
of the capacity of the outdoor unit and the combination ratio must not exceed 100%.
Table 1-5.2: Combinations of Indoor and outdoor units
8
Page 10
-i V6-i VRF 50/60Hz
Part 2
- Component Layout
and
Refrigerant Circuits
Part 2
Component Layout and
Refrigerant Circuits
1 Layout of Functional Components ....................................................... 10
3 Standby Control ................................................................................... 35
4 Startup Control .................................................................................... 36
5 Normal Operation Control ................................................................... 38
6 Protection Control ............................................................................... 43
7 Special Control ..................................................................................... 45
33
Page 35
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
Legend
Numbers in the top right-hand
corners of boxes indicate the
relevant section of text on the
following pages.
Conditions met
for oil return
Conditions met
for defrosting
Thermo on
Special control
Outdoor unit duty cycling
Oil return operation
Defrosting operation
7
Stop operation
A unit stops when the load demanded decreases
2
Standby control
Crankcase heater control
3
Startup control
Startup control for heating operation
4
Thermo on
Normal operation control
Outdoor fan control
5
Protection control
Compressor and inverter module protection
Disable heating control
6
1 General Control Scheme Flowchart
Sections 3-2 to 3-7 on the following pages detail when each of the controls in the flowchart below is activated.
Abnormal shutdown
System stops
Compressor startup delay control
Startup control for cooling operation
Component control during normal operation
Compressor output control
Compressor step control
Operation priority and rotation of compressors
Electronic expansion valve control
High pressure protection control
Low pressure protection control
Discharge temperature protection control
control
34
Page 36
V6-i VRF 50/60Hz
Part 3
- Control
Figure 3-3.1: Crankcase heater controlled according to outdoor ambient temperature
Figure 3-3.2: Crankcase heater controlled according to discharge temperature
Ambient temperature < 35 oC
Ambient temperature > 40 oC
Crankcase heater off
Crankcase heater is controlled according to discharge temperature
Discharge temperature < 40 oC
Discharge temperature > 50 oC
Crankcase heater off
Crankcase heater on
2 Stop Operation
The stop operation occurs for one of the three following reasons:
1. Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a 'stop with
thermo off' operation and an error code is displayed on the outdoor unit digital displays.
2. The system stops when the set temperature has been reached.
3 Standby Control
3.1 Crankcase Heater Control
The crankcase heater is used to prevent refrigerant from mixing with compressor oil when the compressors are stopped.
The crankcase heater is controlled according to outdoor ambient temperature and discharge temperature. When the
outdoor ambient temperature is above 40°C, the crankcase heater is off; when the outdoor ambient temperature is below
35°C, the crankcase heater is controlled according to discharge temperature. Refer to Figures 3-3.1 and 3-3.2.
35
Page 37
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
Component
Wiring
diagram
label
8-12HP
14-18HP
20-24HP
26-28HP
30-32HP
Control functions and states
Inverter compressor A
COMP(A)
●●●●●
Controlled according to load requirement,
operating frequency increased by 1 step / sec
Inverter compressor B
COMP(B)
● ● ●
DC fan motor A
FANA
●●●●●
Fan speed1 controlled according to discharge
pressure (Pc):
At initial speed for 90 seconds.
Subsequently, P
c
checked every 10
seconds:
P
c
≥ 2.7MPa => 1 step increase.
P
c
≤ 2.1MPa => 1 step decrease.
DC fan motor B
FANB
● ● ●
Electronic expansion
valve A
EXVA
●●●●●
Position (steps) from 0 (fully closed) to 480 or
3000 (fully open), controlled according to
discharge temperature
Electronic expansion
valve C
EXVC
●●●●●
Position (steps) from 0 (fully closed) to 480
(fully open), controlled according to
temperature different between plate heat
exchanger inlet and outlet
Four-way valve
ST1
●●●●●
Off
Solenoid valve (oil
balance)
SV4
●●●●●
Closed for 200 secs, open for 600 secs, then
closed
Solenoid valve (fast
defrosting (in cooling)
and unloading (in
heating))
SV5
●●●●●
Open for 4 mins, then closed
Solenoid valve (EXV
bypass)
SV6
●●●●●
Open for 10 mins, then controlled according
to pressure
Solenoid valve (indoor
units bypass)
SV7
●
●
Controlled according to load requirement
Solenoid valve
(inverter compressor A
vapor injection)
SV8A
●● ●●
Controlled according to inverter compressor
A
Solenoid valve
(inverter compressor B
vapor injection)
SV8B
● ●
Controlled according to inverter compressor
B
Solenoid valve
(inverter compressor B
pressure balance)
SV9
● ● ●
Open before compressor B startup
Notes:
1. Refer to Table 3-5.3 in Part 3, 5.6 “Outdoor Fan Control” for more information on fan speed steps.
4 Startup Control
4.1 Compressor Startup Delay Control
In initial startup control, compressor startup is delayed for 12 minutes in order to let the outdoor unit search for the indoor
units’ addresses. In restart control (except in oil return operation and defrosting operation), compressor startup is delayed
such that a minimum of 7 minutes has elapsed since the compressor stopped, in order to prevent frequent compressor
on/off and to equalize the pressure within the refrigerant system.
4.2 Startup Control for Cooling Operation
Table 3-4.1: Component control during startup in cooling mode
36
Page 38
V6-i VRF 50/60Hz
Part 3
- Control
Component
Wiring
diagram
label
8-12HP
14-18HP
20-24HP
26-28HP
30-32HP
Control functions and states
Inverter compressor A
COMP(A)
●●●●●
Controlled according to load requirement,
operating frequency increased by 1 step /
sec
Inverter compressor B
COMP(B)
● ● ●
DC fan motor A
FANA
●●●●●
Open once the four-way valve has opened,
controlled according to outdoor ambient
temperature and load requirement
DC fan motor B
FANB
● ● ●
Electronic expansion
valve A
EXVA
●●●●●
Position (steps) from 0 (fully closed) to 480
or 3000 (fully open), controlled according
to discharge superheat
Electronic expansion
valve C
EXVC
●●●●●
Position (steps) from 0 (fully closed) to 480
(fully open), controlled according to
temperature different between plate heat
exchanger inlet and outlet
Four-way valve
ST1
●●●●●
On
Solenoid valve (oil
balance)
SV4
●●●●●
Closed for 200 secs, open for 600 secs, then
closed
Solenoid valve (fast
defrosting (in cooling)
and unloading (in
heating))
SV5
●●●●●
Open for 4 mins, then closed
Solenoid valve (EXV
bypass)
SV6
●●●●●
Off
Solenoid valve (indoor
units bypass)
SV7
●
●
Controlled according to load requirement
Solenoid valve (inverter
compressor A vapor
injection)
SV8A
●● ●●
Controlled according to inverter
compressor A
Solenoid valve (inverter
compressor B vapor
injection)
SV8B
● ●
Controlled according to inverter
compressor B
Solenoid valve (inverter
compressor B pressure
balance)
SV9
● ● ●
Open before compressor B startup
4.3 Startup Control for Heating Operation
Table 3-4.2: Component control during startup in heating mode
37
Page 39
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
Component
Wiring
diagram
label
8-12HP
14-18HP
20-24HP
26-28HP
30-32HP
Control functions and states
Inverter compressor A
COMP(A)
●●●●●
Controlled according to load requirement
Inverter compressor B
COMP(B)
● ● ●
DC fan motor A
FANA
●●●●●
Controlled according to discharge pressure
DC fan motor B
FANB
● ● ●
Electronic expansion
valve A
EXVA
●●●●●
Position (steps) from 0 (fully closed) to 480
or 3000 (fully open), controlled according to
discharge temperature
Electronic expansion
valve C
EXVC
●●●●●
Position (steps) from 0 (fully closed) to 480
(fully open), controlled according to
temperature different between plate heat
exchanger inlet and outlet
Four-way valve
ST1
●●●●●
On
Solenoid valve (oil
balance)
SV4
●●●●●
Open regularly
Solenoid valve (fast
defrosting (in cooling)
and unloading (in
heating))
SV5
●●●●●
Controlled according to ambient
temperature, discharge pressure, discharge
temperature, compressor running
frequency and discharge superheat
Solenoid valve (EXV
bypass)
SV6
●●●●●
Controlled according to discharge pressure
and discharge temperature
Solenoid valve (indoor
units bypass)
SV7
●
●
Controlled according to load requirement
Solenoid valve (inverter
compressor A vapor
injection)
SV8A
●●●●●
Controlled according to inverter compressor
A on/off
Solenoid valve (inverter
compressor B vapor
injection)
SV8B
● ●
Controlled according to inverter compressor
B on/off
Solenoid valve (inverter
compressor B pressure
balance)
SV9
● ● ●
Open before compressor B startup and close
after compressor B running for 15 seconds.
Open after compressor B stop 10 seconds
and keep open 60 seconds.
5 Normal Operation Control
5.1 Component Control during Normal Operation
Table 3-5.1: Component control during normal cooling operation
38
Page 40
V6-i VRF 50/60Hz
Part 3
- Control
Component
Wiring
diagram
label
8-12HP
14-18HP
20-24HP
26-28HP
30-32HP
Control functions and states
Inverter compressor A
COMP(A)
●●●●●
Controlled according to load requirement
Inverter compressor B
COMP(B)
● ● ●
DC fan motor A
FANA
●●●●●
Controlled according to outdoor ambient
temperature, outdoor heat exchanger pipe
temperature, discharge pressure and load
requirement
DC fan motor B
FANB
● ● ●
Electronic expansion
valve A
EXVA
●●●●●
Position (steps) from 0 (fully closed) to 480
or 3000 (fully open), controlled according to
discharge superheat
Electronic expansion
valve C
EXVC
●●●●●
Position (steps) from 0 (fully closed) to 480
(fully open), controlled according to
temperature different between plate heat
exchanger inlet and outlet
Four-way valve
ST1
●●●●●
On
Solenoid valve (oil
balance)
SV4
●●●●●
Open regularly
Solenoid valve (fast
defrosting (in cooling)
and unloading (in
heating))
SV5
●●●●●
Controlled according to ambient
temperature, discharge pressure, discharge
temperature, compressor running
frequency and discharge superheat
Solenoid valve (EXV
bypass)
SV6
●●●●●
Off
Solenoid valve (indoor
units bypass)
SV7
●
●
Controlled according to load requirement
Solenoid valve (inverter
compressor A vapor
injection)
SV8A
●● ●●
Controlled according to inverter compressor
A on/off
Solenoid valve (inverter
compressor B vapor
injection)
SV8B
● ●
Controlled according to inverter compressor
B on/off
Solenoid valve (inverter
compressor B pressure
balance)
SV9
● ● ●
Open before compressor B startup and close
after compressor B running for 15 seconds.
Open after compressor B stop 10 seconds
and keep open 60 seconds.
Table 3-5.2: Component control during heating operation
39
Page 41
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
Figure 3-5.1: Compressor priority and rotation – one outdoor unit
BP
No. 1
BP1
No. 1 No. 2
BP2
5.2 Compressor Output Control
The compressor rotation speed is controlled according to the load requirement. Before compressor startup, the outdoor
unit first estimates the indoor unit load requirement according to the nominal capacity of indoor units currently running,
and then correct for ambient temperature. The compressors then start up according to the corrected load requirement.
During operation the compressors are controlled according to the nominal capacity of indoor units currently running and
the indoor unit heat exchanger temperatures.
5.3 Compressor Step Control
The running speed of the compressors in rotations per second (rps) is one third of the frequency (in Hz) of the electrical
input to the compressor motors. The compressor speed can be altered in increments of 1 rps.
5.4 Operating Priority and Rotation of Compressors
Figures 3-5.1 shows the compressor operating priority and rotation in the outdoor unit. In units with two compressors,
inverter compressor A (BP1) operates in priority to inverter compressor B (BP2).
40
Page 42
V6-i VRF 50/60Hz
Part 3
- Control
Fan speed index
Fan speed (rpm)
8-18HP
20-22HP
24-32HP
FANA / FANB
FANA / FANB
0 0 0 / 0
0 / 0
1
120
150 / 0
120 / 0
2
150
190 / 0
150 / 0
3
170
230 / 0
170 / 0
4
190
270 / 0
190 / 0
5
210
310 / 0 (150 / 150)
210 / 0
6
230
350 / 0 (180 / 180)
230 / 0
7
250
380 / 0 (210 / 210)
250 / 0 (120 / 120)
8
270
410 / 0 (240 / 240)
270 / 0 ( 150 / 150)
9
290
280 / 280
330 / 0 (170 / 170)
10
310
320 / 320
370 / 0 (190 / 190)
11
330
360 / 360
210 / 210
12
350
400 / 400
230 / 230
13
370
440 / 440
250 / 250
14
390
480 / 480
270 / 270
15
410
520 / 520
290 / 290
16
430
560 / 560
310 / 310
17
450
600 / 600
330 / 330
18
470
640 / 640
350 / 350
19
490
680 / 680
370 / 370
20
510
720 / 720
400 / 400
21
530
760 / 760
430 / 430
22
560
800 / 800
470 / 470
5.5 Electronic Expansion Valve Control
EXVA control
The position of electronic expansion valves EXVA is controlled in steps from 0 (fully closed) to 480 (fully open) or 3000
(fully open).
In cooling mode:
When the outdoor unit is in standby:
EXVA is at position 352 (steps) or 2112 (steps).
When the outdoor unit is running:
EXVA is controlled according to discharge temperature.
In heating mode:
When the outdoor unit is in standby:
EXVA is at position 352 (steps) or 2112 (steps).
When the outdoor unit is running:
EXVA is controlled according to discharge superheat.
EXVC control
The positions of electronic expansion valves EXVC are controlled in steps from 0 (fully closed) to 480 (fully open).
In cooling / heating mode:
When the outdoor unit is in standby:
EXVC is fully closed.
When the outdoor unit is running:
EXVC is controlled according to temperature different between plate heat exchanger inlet and outlet.
5.6 Outdoor Fan Control
The speed of the outdoor unit fans is adjusted in steps, as shown in Table 3-5.3.
Table 3-5.3: Outdoor fan speed steps
41
Page 43
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
23
580
840 / 840
510 / 510
24
600
880 / 880
550 / 550
25
630
910 / 910
600 / 600
26
650
940 / 940
650 / 650
27
700
980 / 980
700 / 700
28
750
1010 / 1010
750 / 750
29
800
1020 / 1020
800 / 800
30
850
1050 / 1050
830 / 830
31
880
1080 / 1080
850 / 850
32
920
1120 / 1120
870 / 870
33
920
1140 / 1140
890 / 890
34
920
1140 / 1140
920 / 920
35
920
1140 / 1140
920 / 920
36 (ESP 40Pa mode)
950
1200 / 1200
950 / 950
37 (ESP 60Pa mode)
980
1200 / 1200
980 / 980
Note:
1. For 20-22HP unit fan speed 5 to 8 and 24-32HP unit fan speed 7 to 10, when fan speed decreases, the fan speed is shown in the bracket; when fan speed
increases, the fan speed is shown without bracket.
42
Page 44
V6-i VRF 50/60Hz
Part 3
- Control
Figure 3-6.1: High pressure protection control
Notes:
1. P
c
: Discharge pressure
Figure 3-6.2: Low pressure protection control
Notes:
1. P
e
: Suction pressure
Figure 3-6.3: Discharge temperature protection control
When P2 protection occurs 3 times
in 60 minutes, the H5 error is
displayed. When an H5 error occurs,
a manual system restart is required
before the system can resume
operation.
Pc > 4.4MPa
Pc < 3.2MPa
Normal operation
High pressure protection, error code P1 is displayed
Pe < 0.05MPa
Pe > 0.15MPa
Normal operation
Low pressure protection, error code P2 is displayed
120oC
100oC
90oC
Discharge temperature
Compressor off
90oC
6 Protection Control
6.1 High Pressure Protection Control
This control protects the system from abnormally high pressure and protects the compressors from transient spikes in
pressure.
6.2 Low Pressure Protection Control
This control protects the system from abnormally low pressure and protects the compressors from transient drops in
pressure.
6.3 Discharge Temperature Protection Control
This control protects the compressors from abnormally high temperatures and transient spikes in temperature. It is
performed for each compressor.
When the discharge temperature rises above 120°C the system displays P4 protection and all units stop running. When P4
protection occurs 3 times in 100 minutes, the H6 error is displayed. When an H6 error occurs, a manual system restart is
required before the system can resume operation.
43
Page 45
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
Figure 3-6.4: Compressor current protection control
Compressor model
AA55PHDG –D1YG
DC80PHDG –D1YG
Current
max
24.6
33
Figure 3-6.5: Inverter module temperature protection control
Notes:
1. T
f
: Heat sink temperature
Figure 3-6.6: Disable heating control
When PL protection occurs 3 times
in 100 minutes, the C7 error is
displayed. When a C7 error occurs, a
manual system restart is required
before the system can resume
operation.
Current ≥ Current
max
Current < Current
max
Normal operation
Compressor current protection, error code xP3 is displayed
Tf > 75oC
Tf < 73oC
Normal operation
Compressor output reduced
Tf > 80oC
Tf < 65oC
Inverter module temperature protection,
error code PL is displayed
Outdoor ambient temperature > 25oC
Outdoor ambient temperature < 23oC
Heating operation
Units stop
6.4 Compressor and Inverter Module Protection Control
This control protects the compressors from abnormally high currents and protects the inverter modules from abnormally
high temperatures. It is performed for each compressor and inverter module.
6.5 Disable Heating Control
When the outdoor ambient temperature rises above 25°C heating mode is disabled to prevent the mechanical load on
compressors becoming too high and to prevent low compression ratios which can result in insufficient compressor internal
oil lubrication.
44
Page 46
V6-i VRF 50/60Hz
Part 3
- Control
Table 3-7.1: Outdoor unit component control during oil return operation in cooling mode
Component
Wiring
diagram label
8-12HP
14-18HP
20-24HP
26-28HP
30-32HP
Control functions and states
Inverter compressor A
COMP(A)
●●●●●
Fixed frequency
Inverter compressor B
COMP(B)
● ● ●
DC fan motor A
FANA
●●●●●
Fan speed controlled according
to discharge pressure
DC fan motor B
FANB
● ● ●
Electronic expansion valve A
EXVA
●●●●●
Position 480 (steps) or 3000
(steps)
Electronic expansion valve C
EXVC
●●●●●
Position 96 (steps)
Four-way valve
ST1
●●●●●
Off
Solenoid valve (oil balance)
SV4
●●●●●
Normal control
Solenoid valve (fast defrosting)
SV5
●●●●●
On
Solenoid valve (EXV bypass)
SV6
●●●●●
On
Solenoid valve (indoor units
bypass)
SV7
●
●
Normal control
Solenoid valve (inverter
compressor A vapor injection)
SV8A
●● ●●
Controlled according to inverter
compressor A
Solenoid valve (inverter
compressor B vapor injection)
SV8B
● ●
Controlled according to inverter
compressor B
Solenoid valve (inverter
compressor B pressure balance)
SV9
● ● ●
Open before compressor B
startup
Table 3-7.2: Indoor unit component control during oil return operation in cooling mode
Component
Unit state
Control functions and states
Fan
Thermo on
Remote controller setting
Standby
Off
Thermo off
Off
Electronic expansion valve
Thermo on
Normal control
Standby
300 (steps)
Thermo off
300 (steps)
7 Special Control
7.1 Oil Return Operation
In order to prevent compressors from running out of oil, the oil return operation is conducted to recover oil that has
flowed out of the compressor(s) and into the piping system. This operation is performed for all units including units that
are in standby. When the outdoor unit is running in oil return, the digital display on outdoor main PCB will display “d0”.
Timing of oil return operation:
When the initial cumulative operating time reaches 140 minutes and then every 8 hours.
Tables 3-7.1 and 3-7.2 show component control during oil return operation in cooling mode.
45
Page 47
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
Table 3-7.3: Outdoor unit component control during oil return operation in heating mode
Component
Wiring
diagram label
8-12HP
14-18HP
20-24HP
26-28HP
30-32HP
Control functions and states
Inverter compressor A
COMP(A)
●●●●●
Fixed frequency
Inverter compressor B
COMP(B)
● ● ●
DC fan motor A
FANA
●●●●●
Fan speed controlled according
to discharge pressure
DC fan motor B
FANB
● ● ●
Electronic expansion valve A
EXVA
●●●●●
Position 480 (steps) or 3000
(steps)
Electronic expansion valve C
EXVC
●●●●●
Position 96 (steps)
Four-way valve
ST1
●●●●●
Off
Solenoid valve (oil balance)
SV4
●●●●●
Normal control
Solenoid valve (fast defrosting)
SV5
●●●●●
On
Solenoid valve (EXV bypass)
SV6
●●●●●
On
Solenoid valve (indoor units
bypass)
SV7
●
●
Normal control
Solenoid valve (inverter
compressor A vapor injection)
SV8A
●● ●●
Off
Solenoid valve (inverter
compressor B vapor injection)
SV8B
● ●
Off
Solenoid valve (inverter
compressor B pressure balance)
SV9
● ● ●
Open before compressor B
startup
Table 3-7.4: Indoor unit component control during oil return operation in heating mode
Component
Unit state
Control functions and states
Fan
Thermo on
Off
Standby
Off
Thermo off
Off
Electronic expansion valve
Thermo on
480 (steps)
Standby
480 (steps)
Thermo off
480 (steps)
Tables 3-7.3 and 3-7.4 show component control during oil return operation in heating mode.
46
Page 48
V6-i VRF 50/60Hz
Part 3
- Control
Table 3-7.5: Outdoor unit component control during defrosting operation
Component
Wiring
diagram label
8-12HP
14-18HP
20-24HP
26-28HP
30-32HP
Control functions and states
Inverter compressor A
COMP(A)
●●●●●
Fixed frequency
Inverter compressor B
COMP(B)
● ● ●
DC fan motor A
FANA
●●●●●
Off
DC fan motor B
FANB
● ● ●
Electronic expansion valve A
EXVA
●●●●●
Position 480 (steps) or 3000
(steps)
Electronic expansion valve C
EXVC
●●●●●
Position 480 (steps)
Four-way valve
ST1
●●●●●
Off
Solenoid valve (oil balance)
SV4
●●●●●
Normal control
Solenoid valve (fast defrosting)
SV5
●●●●●
On
Solenoid valve (EXV bypass)
SV6
●●●●●
On
Solenoid valve (indoor units
bypass)
SV7
●
●
Normal control
Solenoid valve (inverter
compressor A vapor injection)
SV8A
●● ●●
Off
Solenoid valve (inverter
compressor B vapor injection)
SV8B
● ●
Off
Solenoid valve (inverter
compressor B pressure balance)
SV9
● ● ●
Open before compressor B
startup
Table 3-7.6: Indoor unit component control during defrosting operation
Component
Unit state
Control functions and states
Fan
Thermo on
Off
Standby
Off
Thermo off
Off
Electronic expansion valve
Thermo on
480 (steps)
Standby
480 (steps)
Thermo off
480 (steps)
7.2 Defrosting Operation
In order to recover heating capacity, the defrosting operation is conducted when the outdoor unit heat exchanger is
performing as an evaporator. The defrosting operation is controlled according to outdoor ambient temperature, outdoor
heat exchanger temperature, indoor heat exchanger temperature and outdoor unit running time. When the outdoor unit is
running in defrosting, the digital display on outdoor main PCB will display “df”.
47
Page 49
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
48
Page 50
V6-i VRF 50/60Hz
Part 4
- Field Settings
Part 4
Field Settings
1Outdoor Unit Field Settings ................................................................. 50
49
Page 51
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
Switch
Setting
Switch positions1
Description
S4
Static pressure
Standard static pressure (default)
Low static pressure mode (reserved)
Medium static pressure mode (reserved)
High static pressure mode (reserved)
Super high static pressure mode (reserved)
S5
Priority mode2
Auto priority (default)
Cooling priority
VIP priority or voting priority
Heating only
Cooling only
Set priority mode via centralized controller (reserved)
S6-1
Reserved
Reserved
S6-2
Clear indoor
unit addresses
No action (default)
Clear indoor unit addresses
Table continued on next page …
1 Outdoor Unit Field Settings
1.1 PCB Switches and Switch Settings
Figure 4-1.1: Outdoor unit main PCB switches
Table 4-1.1: Outdoor unit main PCB switch settings
50
Page 52
V6-i VRF 50/60Hz
Part 4
- Field Settings
Switch
Setting
Switch positions1
Description
S6-3
Addressing
mode
Auto addressing (default)
Manual addressing
S8-1
Reserved
Reserved
S8-2
Start-up time
Start-up time is 12 minutes (default)
Start-up time is 7 minutes
S8-3
Reserved
Reserved
S7
Reserved
Reserved
S9
Reserved
Reserved
S13
Controller type
Use the new centralized controller (default)
Use the old centralized controller
ENC2
Outdoor unit
capacity3
Only 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C should be selected
0: 8HP; 1: 10HP; 2: 12HP; 3: 14HP; 4: 16HP; 5: 18HP; 6: 20HP; 7: 22HP; 8: 24HP;
9: 26HP; A: 28HP; B:30HP; C:32HP
ENC4
Network
address
Only 0, 1, 2, 3, 4, 5, 6, 7 should be selected (default is 0)
ENC3 S12
Number of
indoor units
The number of indoor units is in the range 0-15
0-9 on ENC3 indicate 0-9 indoor units; A-F on ENC3 indicate 10-15 indoor units
The number of indoor units is in the range 16-31
0-9 on ENC3 indicate 16-25 indoor units; A-F on ENC3 indicate 26-31 indoor units
The number of indoor units is in the range 32-47
0-9 on ENC3 indicate 32-41 indoor units; A-F on ENC3 indicate 42-47 indoor units
The number of indoor units is in the range 48-63
0-9 on ENC3 indicate 48-57 indoor units; A-F on ENC3 indicate 58-63 indoor units
ENC4
Silent mode4
0
Night silent time is 6h/10h (default)
1
Night silent time is 6h/12h
2
Night silent time is 8h/10h
3
Night silent time is 8h/12h
4
No silent mode
5
Silent mode 1 (only limit max. fan speed)
6
Silent mode 2 (only limit max. fan speed)
7
Silent mode 3 (only limit max. fan speed)
8
Super silent mode 1 (limit max. fan speed and compressor frequency)
9
Super silent mode 2 (limit max. fan speed and compressor frequency)
A
Super silent mode 3 (limit max. fan speed and compressor frequency)
B
Super silent mode 4 (limit max. fan speed and compressor frequency)
F
Set silent mode via centralized controller (reserved)
Notes:
1. Black denotes the switch position.
2. Refer to Part 4, 1.2.1 “Priority mode setting”.
3. Switch ENC2 is factory-set and its setting should not be changed.
4. Refer to Part 4, 1.2.2 “Silent mode setting”.
Table 4-1.1: Outdoor unit main PCB switch settings (continued)
51
Page 53
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
Figure 4-1.2: Indoor unit digital displays and LED indicators
DEF./FAN LED
Digital display
18oC
13oC
Outdoor ambient temperature
Cooling priority
Heating priority
1.2 Modes Set on Main PCB
1.2.1 Priority mode setting
Priority mode can be set on the outdoor unit. When an indoor unit is in mode conflict with the outdoor unit the unit
displays the mode conflict error. If the indoor unit has a digital display, it will display error code E0; if the indoor unit
display board has LED indicators, the “DEF./FAN” LED will flash rapidly.
There are five priority mode options:
1. Auto priority mode (default): In auto priority mode, the outdoor unit will operate in heating priority mode or cooling
priority mode according to the outdoor ambient temperature.
a) When the outdoor ambient temperature is below 13
heating priority mode does not change until the outdoor ambient temperature is above 18oC.
b) When the outdoor ambient temperature is above 18
cooling priority mode does not change until the outdoor ambient temperature is below 13oC.
c) When the outdoor unit restarts under the outdoor ambient between 13
same priority as before the last stop.
d) When the outdoor unit is initial startup under outdoor ambient temperature between 13
outdoor unit runs in heating priority mode.
Figure 4-1.3: Auto priority mode control
o
C, the outdoor units run in heating priority mode. The
o
C, the outdoor units run in cooling priority mode. The
o
C and 18oC, the outdoor unit runs the
o
C and 18oC, the
1.1. Heating priority mode:
a) During cooling operation: If an indoor unit requests heating, the outdoor unit stops and then restarts in heating
mode after 5 minutes. Indoor units requesting heating then start in heating mode and indoor units requesting
cooling display the mode conflict error.
b) During heating operation: If an indoor unit requests cooling, the outdoor unit ignores the request and continues
to run in heating mode. The indoor unit requesting cooling displays the mode conflict error. If all the indoor units
requesting heating are later turned off and one or more indoor units are still requesting cooling, the outdoor unit
restarts in cooling mode after 5 minutes and any indoor units requesting cooling then start in cooling mode.
1.2. Cooling priority mode:
a) During heating operation: If an indoor unit requests cooling, the outdoor unit stops and then restarts in cooling
mode after 5 minutes. Indoor units requesting cooling then start in cooling mode and indoor units requesting
heating display the mode conflict error.
b) During cooling operation: If an indoor unit requests heating, the outdoor units ignore the request and continue
to run in cooling mode. The indoor unit requesting heating displays the mode conflict error. If all the indoor units
requesting cooling are later turned off and one or more indoor units are still requesting heating, the outdoor unit
restarts in heating mode after 5 minutes and any indoor units requesting heating then start in heating mode.
52
Page 54
V6-i VRF 50/60Hz
Part 4
- Field Settings
Table 4-1.2: Night silent time setting
Switch
Switch positions
Description
X
Y
ENC4
0
Night silent time is 6h/10h (default)
6
10 1 Night silent time is 6h/12h
6
12 2 Night silent time is 8h/10h
8
10 3 Night silent time is 8h/12h
8
12
Operation
sound dB
Load
Maximum
output
8:00
14:00
20:00
6:00
Night silent
mode activated
The outdoor unit senses the peak daytime
outdoor ambient temperature
3. The fan speed index is related to the fan speed in rpm and can take any integer value in the range 1 (slowest) to 35 (fastest).
4. 480P: steps = value displayed × 4; 3000P: steps = value displayed × 24.
5. Priority mode:
0: auto priority; 1: cooling priority; 2: VIP priority or voting priority; 3: heating only; 4: cooling only.
6. Silent mode:
0: night silent time 6h/10h; 1: night silent time 6h/12h; 2: night silent time 8h/10h; 3: night silent time 8h/12h; 4: no silent mode; 5: silent mode 1; 6:
7. Static pressure mode:
8. Refrigerant quantity:
9. Power mode:
silent mode 2; 7: silent mode 3; 8: super silent mode 1; 9: super silent mode 2; 10: super silent mode 3; 11: super silent mode 4.
40% capacity output; 10: auto power save mode, 100% capacity output; 11: auto power save mode, 90% capacity output; 12: auto power save
mode, 80% capacity output; 13: auto power save mode, 70% capacity output; 14: auto power save mode, 60% capacity output; 15: auto power save
mode, 50% capacity output; 16: auto power save mode, 40% capacity output;
Digital display output 2.2.5
64
Page 66
V6-i VRF 50/60Hz
Part 5
- Electrical Components and Wiring Diagrams
Table 5-3.1: LED indicators LED1 and LED2
Indicator
LED indicator function and status
LED 1
Inverter module operating indicator. Continuously on if the compressor is running normally and
flashing if an inverter module error has occurred1.
LED 2
Inverter module error indicator. Continuously on if an inverter module error has occurred1.
Compressor frequency variation greater than 15Hz within one
second protection
Displayed on the unit with the error
Yes
xL9
Actual compressor frequency differs from target frequency by
more than 15Hz protection
Displayed on the unit with the error
Yes
All electrical work must be carried out by competent and suitably qualified, certified and
accredited professionals and in accordance with all applicable legislation (all national, local and other laws,
Power-off the outdoor units before connecting or disconnecting any connections or wiring, otherwise electric
shock (which can cause physical injury or death) may occur or damage to components may occur.
Warning
Table 6-1.1: Error code table (continued)
Notes:
1. 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing compressor system A and 2
representing compressor system B. 'y' is a placeholder for the address (1 or 2) of the slave unit with the error.
2. For some error codes, a manual restart is required before the system can resume operation.
3. Once the EXV has been connected properly, the error code will flash to indicate that the connection has been re-established. A manual restart is then
required before the system can resume operation.
2 Troubleshooting
2.1 Warning
standards, codes, rules, regulations and other legislation that apply in a given situation).
71
Page 73
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
2.2 E1: Phase sequence error
Digital display output 2.2.1
Description 2.2.2
Phase sequence error.
All units stop running.
Error code is displayed on the outdoor unit with the error.
Trigger / recover condition 2.2.3
Trigger condition: Wrong phase connection for 1.6s or phase missing for 48s.
Recover condition: Correct phase connection.
Reset method: Manually restart.
Possible causes 2.2.4
Power supply phases not connected in correct sequence.
Power supply terminals loose.
Power supply abnormal.
Main PCB damaged.
72
Page 74
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
E1
The phase sequence of the 3-phase
power supply is incrorrect1
Yes
Exchange any two of the 3 phase wires
No
Some power supply terminals are loose2
Yes
Ensure all supply terminals are securely
fastened
No
The power supply is abnormal
Yes
Check the power supply equipment
No
Replace outdoor main PCB
Procedure 2.2.5
Notes:
1. The A, B, C terminals of the 3-phase power supply should match compressor phase sequence requirements. If the phase sequence is inverted, the
compressor will operate inversely. If the wiring connection of each outdoor unit is in A, B, C phase sequence, and multiple units are connected, the current
difference between C phase and A, B phases will be very large as the power supply load of each outdoor unit will be on C phase. This can easily lead to
tripped circuits and terminal wiring burnout. Therefore if multiple units are to be used, the phase sequence should be staggered, so that the current is
distributed among the three phases equally.
2. Loose power supply terminals can cause the compressors to operate abnormally and compressor current to be very large.
73
Page 75
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
2.3 E2: Communication error between indoor and outdoor unit
Digital display output 2.3.1
Description 2.3.2
Communication error between indoor and outdoor unit.
All units stop running.
Error code is only displayed on the outdoor unit.
Trigger / recover condition 2.3.3
Trigger condition: Indoor units and the outdoor unit cannot communicate for 2 minutes after the system is powered
on for 20 minutes.
Recover condition: Communication go back to normal.
Reset method: Resume automatically.
Possible causes 2.3.4
Communication wires between indoor and outdoor units not connected properly.
Indoor unit power supply abnormal.
Loosened wiring within electric control box.
Interference from high voltage wires or other sources of electromagnetic radiation.
Communication wire too long.
Damaged main PCB or electric control box communication terminals block.
74
Page 76
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
E2
Communication wires P Q E have short
circuited or disconnected1
Yes
Reconnect the communication wires
No
Communication wires P Q E are not
connected in a daisy chain
Yes
Connect the communication wires in a
daisy chain
No
IDU power supply is abnormal
Yes
Ensure normal power supply
No
Wires between outdoor main PCB and
electric control box communication
terminals block are loose
Yes
Ensure the wires are connected properly
No
Interference from high voltage (220V or
higher) wires
Yes
Ensure the communication wires and
high voltage wires are separated
No
Communication wires are close to a
source of electromagnetic radiation such
as transformer or strong fluorescent lamp
Yes
Remove the source of interference, or
add additional shielding to the
communication wires
No
The length of communication wire is over
1200m
Yes
Reduce the wire length to less than
1200m or strengthen the signal
No
Replacing outdoor main PCB resolves the
error
No
Replace electric control box
communication terminals block
Procedure 2.3.5
Notes:
1. Measure the resistance among P, Q and E. The normal resistance between P and Q is 120Ω, between P and E is infinite, between Q and E is infinite.
75
Page 77
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
2.4 E4: Temperature sensor (T3/T4) error
Digital display output 2.4.1
Description 2.4.2
Outdoor heat exchanger temperature sensor (T3) error or outdoor ambient temperature sensor (T4) error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.4.3
Trigger condition: The main control board cannot receive the feedback signal of temperature sensor T3 or T4.
Recover condition: The main control board can receive the feedback signal of temperature sensor T3 or T4.
Reset method: Resume automatically.
Possible causes 2.4.4
Temperature sensor not connected properly or has malfunctioned.
Damaged main PCB.
76
Page 78
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
E4
Temperature sensor connection on main
PCB is loose1
Yes
Ensure the sensor is connected properly
No
Temperature sensor has short-circuited
or failed2
Yes
Replace the sensor
No
Replace outdoor main PCB
Procedure 2.4.5
Notes:
1. Outdoor ambient temperature sensor (T4) and heat exchanger temperature sensor (T3) connection is port CN1 on the main PCB (labeled 11 in Figure 5-2.1
in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.1 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
77
Page 79
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
2.5 E5: Abnormal power supply voltage
Digital display output 2.5.1
Description 2.5.2
Abnormal power supply voltage.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.5.3
Trigger condition: Outdoor unit power supply phase voltage < 165V.
Recover condition: Outdoor unit power supply phase voltage is > 180V.
Reset method: Resume automatically.
Possible causes 2.5.4
Outdoor unit power supply voltage is abnormal or a phase is missing.
Loosened wiring within electric control box.
High voltage circuit error.
Main PCB damaged.
78
Page 80
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
E5
ODU power supply is abnormal or a
phase is missing1
Yes
Provide normal power supply
No
Wires between outdoor main PCB, AC
filter boards and electric control box
power supply terminals are loose
Yes
Ensure the wires are connected properly
No
High voltage circuit error has occurred,
such as the compressor has
malfunctioned2, the fan motor has
short-circuited3, or the inverter module
has short-circuited4
Yes
Replace or repair the relevant parts
No
Replace outdoor main PCB
Figure 6-2.1: Inverter module terminals
Procedure 2.5.5
Notes:
1. The normal voltage between A and N, B and N, and C and N is 198-242V.
2. The normal resistances of the inverter compressor are 0.7-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances
differ from these specifications, the compressor has malfunctioned.
3. The normal resistances of the fan motor coil among U V W are less than 10Ω. If a measured resistance is 0Ω, the fan motor has short-circuited.
4. Set a multi-meter to buzzer mode and test any two terminals of P N U V W of the inverter module. If the buzzer sounds, the inverter module has
short-circuited.
79
Page 81
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
2.6 E7: Temperature sensor (T7C1/2) error
Digital display output 2.6.1
Description 2.6.2
A compressor top temperature sensor or discharge pipe temperature sensor (T7C1/2) error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.6.3
Trigger condition: Discharge pressure ≥ 3MPa and discharge temperature < 15
Recover condition: Discharge pressure and temperature go back to normal.
Reset method: Manually restart.
Possible causes 2.6.4
Temperature sensor not connected properly or has malfunctioned.
Damaged main PCB.
o
C for 2 minutes.
80
Page 82
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
E7
Temperature sensor connection on main
PCB is loose1
Yes
Ensure the sensor is connected properly
No
Temperature sensor has short-circuited
or failed2
Yes
Replace the sensor
No
Replace outdoor main PCB
Procedure 2.6.5
Notes:
1. Compressor top temperature sensor and discharge pipe temperature sensor connections are ports CN4 and CN5 on the main PCB (labeled 3 and 4,
respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.2 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
81
Page 83
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
2.7 E8: Outdoor unit address error
Digital display output 2.7.1
Description 2.7.2
Outdoor unit address error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.7.3
Trigger condition: Outdoor unit address is set more than 3.
Recover condition: Outdoor unit addresses are set from 0 to 3.
Reset method: Manually restart.
Possible causes 2.7.4
Invalid outdoor unit address.
Main PCB damaged.
82
Page 84
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
E8
The ODU's address is not in the valid
range1
Yes
Slave units addresses should be set from
1 to 3
No
Replace the outdoor main PCB
Procedure 2.7.5
Notes:
1. The V6 Individual outdoor unit address should be set as 0.
83
Page 85
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
2.8 xE9: EEPROM mismatch
Digital display output 2.8.1
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
Description 2.8.2
1E9 indicates a compressor A EEPROM mismatch.
2E9 indicates a compressor B EEPROM mismatch.
All units stop running.
Error code is only displayed on the unit with the error.
Outdoor unit was powered on immediately after being powered off.
Main PCB damaged.
84
Page 86
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
xE9
The outdoor unit was powered on
immediately after being powered off1
Yes
Power off the unit and wait for the digital
display to turn off before restarting the
unit
No
Replace outdoor main PCB
Procedure 2.8.5
Notes:
1. When performing a manual restart of an outdoor unit, once the unit has been powered off it should not be powered on again until the digital display has
turned off.
85
Page 87
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
2.9 xF1: DC bus voltage error
Digital display output 2.9.1
'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing
compressor system A and 2 representing compressor system B.
Description 2.9.2
1F1 indicates compressor A DC bus voltage error; 2F1 indicates compressor B DC bus voltage error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.9.3
Trigger condition: DC bus voltage < 350V or DC bus voltage > 700V continuously for 10 seconds.
Recover condition: DC bus voltage goes back to normal.
Reset method: Restart automatically.
Possible causes 2.9.4
Loosened wiring of the compressor inverter module.
Incorrect wiring of the reactor and DC bus wire.
Abnormal power supply.
Inverter module damaged.
86
Page 88
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
Figure 6-2.2: DC detection wire connection method
F1 error
Compressor inverter module wiring is
loosened
Reconnect cables based on
wiring diagram
Reactor and DC bus wiring is incorrectly
1
Reconnect the reactor and
DC bus wire based on wiring
diagram
The power supply is abnormal
No
No
Yes
Yes
Disconnect the
power supply
Check the power supply
equipment
Yes
Replace the inverter module
No
Procedure 2.9.5
Note:
1. The DC bus wire should run from the N_in terminal on the inverter module, through the current sensor (in the direction indicated by the
arrow on the current sensor), and end at the N_out terminal on the inverter module.
87
Page 89
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
2.10 F3, F5: Temperature sensor (T6B/T6A) error
Digital display output 2.10.1
Description 2.10.2
F3 indicates plate heat exchanger cooling refrigerant outlet temperature sensor (T6B) error.
F5 indicates plate heat exchanger cooling refrigerant inlet temperature sensor (T6A) error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.10.3
Trigger condition: Temperature sensor T6A(B) is open or short-circuit.
Recover condition: Temperature sensor T6A(B) connection ports can detect load.
Reset method: Resume automatically.
Possible causes 2.10.4
Temperature sensor not connected properly or has malfunctioned.
Damaged main PCB.
88
Page 90
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
F3 / F5
Temperature sensor connection on main
PCB is loose1
Yes
Ensure the sensor is connected properly
No
Temperature sensor has short-circuited
or failed2
Yes
Replace the sensor
No
Replace outdoor main PCB
Procedure 2.10.5
Notes:
1. Plate heat exchanger cooling refrigerant inlet temperature sensor (T6A) and plate heat exchanger cooling refrigerant outlet temperature sensor (T6B)
connection are port CN8 and CN8_1 on the main PCB (labeled 10 and 12, respectively, in Figure 5-2.1 in Part 5, 2.1 “Ports”).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Table 6-3.1 in Part 6, 3.1 “Temperature Sensor Resistance Characteristics”.
Electronic expansion valve connection error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.11.3
Trigger condition: The main control board cannot receive the feedback signal of EXV.
Recover condition: The main control board can receive the feedback signal of EXV.
Reset method: When the main control board can receive the feedback signal of EXV, F6 flashes, a manual system
restart id required before the system can resume operation.
Possible causes 2.11.4
Electronic expansion valve coil not connected properly or has malfunctioned.
Damaged main PCB.
90
Page 92
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
F6
Electronic expansion valve coil
connection on main PCB is loose1
Yes
Ensure the sensor is connected properly
No
Electronic expansion valve coil has
malfunctioned2
Yes
Replace the sensor
No
Replace outdoor main PCB
Figure 6-2.3: EXV coil wiring terminals
Procedure 2.11.5
Notes:
1. Electronic expansion valve coil connections are port CN70, CN71 and CN72 on the main PCB (labeled 18, 19 and 20, respectively, in Figure 5-2.1 in Part 5,
2.1 “Ports”).
2. The normal resistances between EXV coil wiring terminals RED and white / yellow / orange / blue are 40-50Ω. If any of the resistances differ from the value,
the EXV coil has malfunctioned.
91
Page 93
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
Incorrect compressor inverter module address setting.
Loosened communication wiring from the main PCB to
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
Description 2.12.2
1H0 indicates a communication error between the main control chip and the compressor A inverter driver chip.
2H0 indicates a communication error between the main control chip and the compressor B inverter driver chip.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.12.3
Trigger condition: Main control chip and inverter driver chip cannot communication for 2 minutes.
Recover condition: Communication go back to normal.
Reset method: Resume automatically.
Possible causes 2.12.4
Procedure 2.12.5
92
Page 94
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
S7 on inverter module
Inverter module address
0 for compressor inverter module A
1 for compressor inverter module B
Communication port CN26 on main PCB
Communication port CN8/CN9 on inverter module
CN41 Power for
Compressor inverter
CN61 High
pressure switch
connection port
Fuse 30A
CN30
Notes:
1. Compressor inverter module address is set through dial switch S7 on the inverter module. The compressor inverter module A/B location refers to the
wiring diagram.
2. Communication wire from outdoor main PCB CN26 to inverter module CN8/CN9.
3. LED1/2 on inverter module
4. Check the power supply for the compressor inverter module, port CN41 on filter board, the normal voltage should be DC310V; check the high pressure
switch connection port CN61 on filter board, the normal resistance should be zero; Check the single phase bridge and fuse on filter board; check the
connection cable from ODU main PCB port CN82 to filter board port CN30 which is DC310V power control port.
SMPS of
93
Page 95
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
Table 6-2.1: Specific error codes for error xH4
Specific error code1
Content
xL0
Inverter module protection
xL1
DC bus low voltage protection
xL2
DC bus high voltage protection
xL4
MCE error
xL5
Zero speed protection
xL7
Phase sequence error
xL8
Compressor frequency variation greater than 15Hz within one second protection
xL9
Actual compressor frequency differs from target frequency by more than 15Hz protection
Notes:
1. 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1 representing compressor system A and
2 representing compressor system B.
2.13xH4: Inverter module protection
Digital display output 2.13.1
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
Description 2.13.2
1H4 indicates compressor A inverter module protection.
2H4 indicates compressor B inverter module protection.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.13.3
Trigger condition: Compressor appears three inverter module protections.
Recover condition: Inverter module goes back to normal.
Reset method: Manually restart.
Possible causes 2.13.4
Inverter module protection.
DC bus low or high voltage protection.
MCE error.
Zero speed protection.
Phase sequence error.
Excessive compressor frequency variation.
Actual compressor frequency differs from target frequency.
Specific error codes for xH4 inverter module protection 2.13.5
If an xH4 error code is displayed, enter menu mode “n31” (refer to Part 5, 2.2.3 “menu mode”) to check the history error
code to check the following specific error code: xL0, xL1, xL2, xL4, xL5, xL7, xL8, xL9.
94
Page 96
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
Figure 6-2.4: LED indicators LED1 and LED2 on inverter module
Table 5-3.2: Errors indicated on LED1
LED1 flashing pattern
Corresponding error
Flashes 8 times and stops for 1 second, then repeats
xL0 - Inverter module protection
Flashes 9 times and stops for 1 second, then repeats
xL1 - DC bus low voltage protection
Flashes 10 times and stops for 1 second, then repeats
xL2 - DC bus high voltage protection
Flashes 12 times and stops for 1 second, then repeats
xL4 - MCE error
The specific error codes xL0, xL1, xL2 and xL4 can also be obtained from the inverter module LED indicators. If an inverter
module error has occurred, LED2 is continuously on and LED1 flashes.
95
Page 97
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
Figure 6-2.5: DC detection wire connection method
L0 protection
The DC bus wire connected incorrectly
1
Ensure the wire is
connected properly
The compressor wiring is connected
incorrectly
Reconnect the cables
based on wiring diagram
Replace the compressor
The inverter module is not well heat
dissipation
The IPM screws is loosen
Fasten IPM
screws again
The silica gel is coated not
well for heat radiation
Coat with silica
gel
The compressor has less than 12 hours
preheating before initial operating
Switch on power again to detect
whether the compressor can start
Refer to “P3 over current protection”
Replace the inverter
module
Ensure enough
preheating time
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
No
Disconnect
the power
supply
The resistance between 3 phases of
compressor is over 5Ω
The insulation resistance of
compressor is less than 100kΩ
L0: Inverter module protection 2.13.6
Note:
2. The DC bus wire should run from the N_in terminal on the inverter module, through the current sensor (in the direction indicated by the
arrow on the current sensor), and end at the N_out terminal on the inverter module.
96
Page 98
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
Figure 6-2.6: Inverter module terminals
L1 protection
The power supply is abnormal
Check the power supply
equipment
No output from bridge rectifier
Replace the inverter module
No
No
No
Yes
Yes
Yes
Yes
The DC bus voltage (P, N) is abnormal
1
The reactor performs well
Replace the
reactor
No
L1: DC bus low voltage protection 2.13.7
Note:
1. The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is lower than 350V, L1
protection will be appeared.
97
Page 99
V6-i VRF 50/60Hz
Midea V6-i Series Service Manual
Figure 6-2.7: Inverter module terminals
L2 protection
The power supply is abnormal
Check the power supply
equipment
The DC bus voltage (P, N) is abnormal
1
Replace the 3-phase bridge
rectifier
Replace the inverter module
No
No
Yes
Yes
L2: DC bus high voltage protection 2.13.8
Note:
1. The normal DC voltage between terminals P and N on inverter module should be 450-650V. When the voltage is higher than 700V, L2
protection will be appeared.
98
Page 100
V6-i VRF 50/60Hz
Part
6 - Diagnosis and Troubleshooting
S7 on inverter module
Inverter module address
0 for compressor inverter module A
1 for compressor inverter module B
L4 protection
ODU ventilation is not good
Remove barriers from heat
exchanger and air outlet of ODU
ODU stop valves are closedOpen the ODU stop valves
Reconnect the cables based on
wiring diagram
The resistance between 3 phases of
compressor is over 5Ω
Replace the compressor
The insulation resistance of
compressor is less than 100Ω
Replace the compressor inverter
board, restart the unit and the error is
solved
Refer to P1 or P3 troubleshooting
No
No
Yes
Yes
Disconnect
the power
supply
Compressor wiring is not properly
Inverter module address setting1 and
discharge temperature sensor wiring is
not properly
Reset the inverter module address
and reconnect the discharge
temperature sensor cables
Yes
Normal
Yes
Yes
Yes
Yes
No
No
No
No
No
L4: MCE error 2.13.9
Notes:
1. Compressor inverter module address is set through dial switch S7 on the inverter module. The compressor inverter module A/B location refers to the
wiring diagram.
99
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.