Service manual
1. Precaution
1.1 Safety Precaution
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage.
Before service unit, be sure to read this service manual at first.
1.2 Warning
Installation
Do not use a defective or underrated circuit breaker.
Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a
qualified electrician, or an Authorized service center.
Do not disassemble or repair the product, there is risk of
fire or electric shock.
Always ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of control box
securely.
There is risk of fire of electric shock.
Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fore or electric
shock.
Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
Do not modify or extend the power cable.
There is risk of fire or electric shock.
Do not install, remove, or reinstall the unit by
yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
Be caution when unpacking and installing the
product.
Sharp edges could cause injury, be especially careful of
the case edges and the fins on the condenser and
evaporator.
For installation, always contact the dealer or an
Authorized service center.
There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation
stand.
It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate
with age.
If the base collapses, the air conditioner could fall with it,
causing property damage, product failure, and personal
injury.
Do not let the air conditioner run for a long time
when the humidity is very high and a door or a
1
windows is left open.
Moisture may condense and wet or damage furniture.
Take care to ensure that power cable could not be
pulled out or damaged during operation.
There is risk of fire or electric shock.
Do not place anything on the power cable.
There is risk of fire or electric shock.
Do not plug or unplug the power supply plug during
operation.
There is risk of fire or electric shock.
Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
Do not place a heater or other appliance near the
power cable.
There is risk of fire and electric shock.
Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric shock.
Do not store or use flammable gas or combustible
near the product.
There is risk of fire or failure of product.
Do not use the product in a tightly closed space for a
long time.
Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas and
open a window for ventilation before turn the
product on.
Do not use the telephone or turn switches on or off.
There is risk of explosion or fire.
If strange sounds, or small or smoke comes from
product. Turn the breaker off or disconnect the
power supply cable.
There is risk of electric shock or fire.
Stop operation and close the window in storm or
hurricane. If possible, remove the product from the
window before the hurricane arrives.
There is risk of property damage, failure of product, or
electric shock.
Do not open the inlet grill of the product during
operation. (Do not touch the electrostatic filter, if the
Service manual
unit is so equipped.)
There is risk of physical injury, electric shock, or product
failure.
When the product is soaked (flooded or submerged),
contact an Authorized service center.
There is risk of fire or electric shock.
Be caution that water could not enter the product.
There is risk of fire, electric shock, or product damage.
Ventilate the product from time to time when
operating it together with a stove, etc.
There is risk of fire or electric shock.
Turn the main power off when cleaning or
maintaining the product.
There is risk of electric shock.
When the product is not be used for a long time,
disconnect the power supply plug or turn off the
breaker.
There is risk of product damage or failure, or unintended
operation.
Take care to ensure that nobody could step on or fall
onto the outdoor unit.
This could result in personal injury and product damage.
CAUTION
Always check for gas (refrigerant) leakage after
installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained
away properly.
A bad connection may cause water leakage.
Keep level even when installing the product.
To avoid vibration of water leakage.
Do not install the product where the noise or hot air
from the outdoor unit could damage the
neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the
product.
Avoid personal injury.
Do not install the product where it will be exposed to
sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion,
particularly on the condenser and evaporator fins, could
cause product malfunction or inefficient operation.
Operational
Do not expose the skin directly to cool air for long
periods of time. (Do not sit in the draft).
This could harm to your health.
Do not use the product for special purposes, such
as preserving foods, works of art, etc. It is a
consumer air conditioner, not a precision refrigerant
system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
It may cause product failure.
Use a soft cloth to clean. Do not use harsh
detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the
plastic parts of the product.
Do not touch the metal parts of the product when
removing the air filter. They are very sharp.
There is risk of personal injury.
Do not step on pr put anything on the product.
(outdoor units)
There is risk of personal injury and failure of product.
Always insert the filter securely. Clean the filter
every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner
and could cause product malfunction or damage.
Do not insert hands or other object through air inlet
or outlet while the product is operated.
There are sharp and moving parts that could cause
personal injury.
Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
Use a firm stool or ladder when cleaning or
maintaining the product.
Be careful and avoid personal injury.
Replace the all batteries in the remote control with
new ones of the same type. Do not mix old and mew
batteries or different types of batteries.
There is risk of fire or explosion.
Do not recharge or disassemble the batteries. Do not
dispose of batteries in a fire.
They may burn of explode.
If the liquid from the batteries gets onto your skin or
clothes, wash it well with clean water. Do not use the
remote of the batteries have leaked.
The chemical in batteries could cause burns or other
health hazards.
2
Service manual
2. Function
Indoor unit
Operation ON/OFF by remote controller
Sensing by room temperature
Room temperature sensor.
Pipe temperature sensor.
Room temperature control
Maintain the room temperature in accordance with the setting temperature.
Starting temperature control
Indoor fan is delayed for 5 sec at the starting.
Time Delay Safety control
Restarting is for approx. 3 minutes..
Indoor fan speed control
High, med, low, breeze.
Operation indication Lamps (LED)
Light up in the LED (LCD) for each operation mode.
Anion (Optional)
Tele Remote control (Optional)
Oxygen Generator (Optional)
UV Generator (Optional)
Two-direction air vane
The unit will decide the louver direction according to operation mode.
Anti-cold function
Prevent the cold wind at
the beginning of unit start.
Sleep mode auto control
The fan is turn to low speed (cooling/heating).
The unit will be turn off at the seventh hour.
Plasma (Optional)
The function will be operated
in any operation mode.
Independent dehumidification
The function is usually used in rainy days in
springtime or damp areas.
Temp. Compensation
Self-diag. function
Defrost mode
The function will be
operate in any operation
Auto-restart function
Air flow Direction control
The louver can be set at the desired position or swing up and
down automatically
Flexible wiring connection
Auto mode
The unit can be change by the room temperature.
3
Easy clean panel
Service manual
Outdoor unit
Power relay control
The unit has 3 mins delay between continuously ON/OFF operations.
Low ambient kit
The unit can operate in cooling mode at low ambient temperature conditions.
Low noise air flow system
Bird tail propeller fan makes the outdoor unit run more quietly.
Hydrophilic aluminum fin
The hydrophilic fin can improve the heating efficiency at operation mode.
4 way valve control
It is only operated in the heating operation mode except defrosting operation.
Discharge pipe temperature protect
Anti-rust cabinet
Valve protection cover
It protects the valves and prevents water from dripping.
TS: Setting temperature through the remote controller
I
: Self-protection amp of compressor, continue three seconds until turns off the compressor.
3sec
I
: Self-protection amp of compressor, continue five minutes until turns off the compressor.
5MIN
I
: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.
FAN
I
RESTORE
TH
TM
TL
TE1: Anti-cold wind, from Fan Off to Breeze temperature
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature
11.2 Function
Remote receiving
Testing and forced running
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
Anti frozen at cooling mode
11.3 Protection
11.3.1 3 minutes delay at restart for compressor.
11.3.2 Sensor protection at open circuit and breaking disconnection
11.3.3 Fan Speed is out of control. When Indoor Fan Speed is too high (higher than 2100RPM) or too
31
: Amp self-protection return value
DEFROST
DEFROST
: High wind, defrosting temperature difference
DEFROST
: Middle wind, defrosting temperature difference
: Low wind, defrosting temperature difference
low (lower than 300RPM) lasting 50 seconds, the unit stops and LED displays failure information and
can’t returns to normal operation automatically.
Service manual
11.3.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops
and LED displays failure information and can’t returns to normal operation automatically.
11.3.5 The current protection of the compressor
If compressor turns off for continuously 4 times due to current protection in 5 minutes from Compressor On,
the unit stops and LED displays failure information and can’t returns to normal operation automatically.
11.4 Fan-only mode
Fan speed is high/mid/low/ Auto
11.5 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:(T=indoor temperature)
32
Service manual
Fan
LOW
ON 6minutes
BREEZE
OFF 4minutes
LOW
ON 5minutes
BREEZE
OFF 5minutes
LOW
ON 4minutes
BREEZE
OFF 6minutes
Auto fan at cooling mode:
Anti-freezing control to indoor evaporator at cooling mode (T: evaporator temp.)
11.6 Dehumidifying mode
11.6.1 The 4-way valve is off in dehumidifying mode
11.6.2 Compressor and Indoor Fan actions in dehumidifying mode
Block
A
B
C
Repeat on and off cycle.
11.6.3 Low room temperature protection:
Indoor
Compressor and Outdoor Fan
When room temperature decreases to below 10℃, compressor and outdoor fan will stop(indoor fan is
33
Service manual
℃
Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13
.
11.6.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as
that of cooling mode.
11.6.5 At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode.
11.7 Heating mode
11.7.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way
valve must delay 2 minutes compared with compressor if the compressor changed into non-heating
mode or turned off. 4-way valve doesn't delay in dehumidifying mode
11.7.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode,
except for the defrosting mode or the end of defrost
11.7.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7
minutes after starting and then judge temperature. Meanwhile other protections are still valid.
* This parameter can be changed from 0 to 3
11.7.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function
prevails.
Anti-cold wind control function at heating mode (T=indoor exchanger temp.)
11.7.5 Auto wind at heating mode (T=indoor temp.)
34
Service manual
Low fan
Room temp. down
Med fan
0
2
Room temp. up
T-Ts
11.7.6 Indoor evaporator high-temperature protection at heating mode
(T=indoor exchanger temp.)
11.7.7 The louver opens to Standard Angle ANGLHEAT when power is on for the first time.
11.8 Defrosting mode (available for heating mode)
11.8.1 Defrosting condition: Defrosting starts when either of the following ①&②:
①
A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:
②
Calculate from the end of latest defrost, evaporator high temp. Protection only closes outdoor fan
with the compressor still running. Add up to 90 minutes.
11.8.2 Defrosting time
At condition ①, If item B is satisfied before item A, it would be regarded as severe frosting and the
defrosting time is 10 minutes. If item B is satisfied after item A, the defrosting time is 7.5minutes.
At condition
35
②
, the defrosting time is 10 minutes.
Service manual
After three times continuous 7.5-minute defrost, the fourth defrost time should be 10 minutes.
The circulation is as following:
11.8.3 Ending condition of defrosting
If one of following conditions is satisfied, end the defrost and turn into heating mode:
A. The defrost time has reached to 7.5 or 10 minutes.
B. The compressor current has reached to I
DEFROST
or above, I
differs in different models
DEROST
11.8.4 Defrosting Actions
11.9 Auto mode
11.9.1 The air conditioner automatically selects one of the following operation modes: cooling, heating
or fan only according to the temperature difference between room temperature (TA) and set
temperature (TS).
Heating (fan only at cooling only)Fan onlyCooling
-1
2
11.9.2 The indoor fan blows automatically in corresponding selected mode
11.9.3 The motion of indoor fan’s blade should accord with the selected operation mode
11.9.4 One mode should be carried out for at least 15 minutes once selected. If the compressor
cannot start for 15 minutes, reselect the operation mode according to the room temp. And set temp.,
or reselect when the set temp. varies
11.10 Force cooling function
36
TA-TS
Service manual
11.10.1 Select forced cooling function with the forced cooling button or the switch
11.10.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan
mode is set as low, the A/C operates at the DRY mode with a set temp. of 24℃
11.10.3 All protections of remote control cooling are available at forced cooling operation
11.10.4 Forced Auto function
Select forced auto function with the forced auto button or the switch.
In forced auto status the A/C operates at remote control mode with a set temp. of 24℃.
11.11 Sleep mode
11.11.1 The sleep function is available at cooling, heating or auto mode
11.11.2 Cooling:
The set temperature rise 1℃ per hour. Two hours later, the set temperature will maintain as a constant and
the fan speed is kept at low speed.
The total time is 7 hours, after 7 hours the unit stops
11.11.3 Heating:
The set temperature decrease 1℃ per hour. Two hours later, the set temperature will maintain as a
constant and the air circulation is kept at low speed (Anti-cold function takes precedence over all).
The total time is 7 hours, after 7 hours the unit stops
11.11.4 Auto:
After an hour running under economic mode, the set temp will rise 1℃,if it is under cooling mode; the set
temp will decrease 1℃,if it is under heating mode; the set temp will be changeless, if it is under fan-only
mode; the condition will be the same after the air conditioner running under economic mode after 2 hours,
and during the next time the set temp do not change. The total time is 7 hours, after 7 hours the unit stops.
11.12 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings before the
power failure when power returns
11.13 Turbo mode
In cooling mode, when pressing the turbo button on the remote controller, the unit will enter turbo mode with
ultra-high speed and reach the set temperature more quickly. After running 20 minutes in turbo mode, the
indoor fan will automatically recover the preset speed.
This indicator il luminates when TIMER is set ON/ OFF.
Operation
lamp
Timer
lamp
Over current protection of the compressor occurs 4 times
X
Flash at 5Hz
13. Troubleshooting
13.1 Display board
Signal receptor
5
22
1
1
AU TO indicator
Thi s indicator illuminates whe n the air conditioner is in AUTO oper ation.
22
DE FROST indi cator (F or Cool ing & H eating mo dels only)
Thi s indicator illuminates whe n the air conditioner start s defros tin g automati cally or
when the warm air control fea ture is ac tiv ated in heating oper ation.
3
TEMPERATURE indicator
Displays the te mperature settings when the air condition er is oper ational.
4
OPE RATION in dicator
This indicator flashe s after power is on and illum inates when the unit is in oper ation.
TIMER indicat or
5
13.2 Troubleshooting
4
3
Failure phenomenon
Indoor fan speed has been out of control for over 1 minute
Indoor room temp. or evaporator sensor is open circuit or short circuit
EEROM errorOn
No over-zero signal
r Extinguish
X
On
40
Service manual
13.3 Diagnostic chart
After energizing, no indicator is lighted and the air conditioner can’t be operated.
41
Service manual
13.4 Resetting phenomenon often occurs during operation.
(That is automatically entering to the status when power is on.)
The reason is that the instantaneous voltage of main chip is less than 4.5V. Check according to the
following procedure:
13.5 Operation lamp flashes and Timer lamp off.
13.6 Operation lamp flashes and Timer lamp on.
42
Service manual
13.7 Operation lamp off and Timer lamp flashes
13.8 Operation lamp on and Timer lamp flashes
EEROM error, indoor PCB is defective.
13.9 Operation lamp flashes, Timer lamp flashes .
This is alarm signal when the main chip can’t detect over-zero signal. When such failure occurs, the main