Midea MSQ-07CR, MSQ-07HR, MSQ-09CR, MSQ-09HR, MSQ-12CR Service Manual

...
Page 1
1
MSQ-07CR; MSQ-07HR MSQ-09CR; MSQ-09HR MSQ-12CR; MSQ-12HR
Page 2
2
Content
1.
1.1. Safety Precaution ......................................................................................................... Ошибка! Закладка не определена.
1.2. Warning ........................................................................................................................ Ошибка! Закладка не определена.
2. Function ................................................................................................................................................................................ 3
3. Dimension ............................................................................................................................................................................. 5
3.1 Indoor unit .............................................................................................................................................................................. 5
3.2 Outdoor unit ............................................................................................................................................................................ 6
4. Specification ......................................................................................................................................................................... 8
5. Refrigerant cycle diagram .................................................................................................................................................. 10
6. Operation limits .................................................................................................................................................................. 11
6.1 Cooling operation ................................................................................................................................................................. 11
6.2 Heating operation ................................................................................................................................................................. 11
7. Schematic diagram and Wiring diagram ........................................................................................................................... 12
7.1. Schematic diagram ............................................................................................................................................................... 12
7.2. Wiring diagram ..................................................................................................................................................................... 13
8. Installation details .............................................................................................................................................................. 16
8.1 Wrench torque sheet for installation ...................................................................................................................................... 16
8.2 Connecting the cables .......................................................................................................................................................... 16
8.3 Pipe length and the elevation ................................................................................................................................................ 16
8.4 Air purging of the piping and indoor unit ................................................................................................................................ 17
8.5 Pumping down (Re-installation) ............................................................................................................................................ 18
8.6 Re-air purging (Re-installation) ............................................................................................................................................. 19
8.7 Balance refrigerant of the 2-way, 3-way valves ..................................................................................................................... 20
8.8 Evacuation............................................................................................................................................................................ 21
8.9 Gas charging ........................................................................................................................................................................ 22
9. Pressure table ..................................................................................................................................................................... 23
9.1 MSQ3-07CR ......................................................................................................................................................................... 23
9.2 MSQ3-07HR ......................................................................................................................................................................... 23
9.3 MSQ3-09CR ......................................................................................................................................................................... 24
9.4 MSQ3-09HR ......................................................................................................................................................................... 24
9.5 MSQ3-12CR ......................................................................................................................................................................... 25
9.6 MSQ3-12HR ......................................................................................................................................................................... 25
10. Capacity table ..................................................................................................................................................................... 26
10.1 MSQ3-07CR ......................................................................................................................................................................... 26
10.2 MSQ3-07HR ......................................................................................................................................................................... 26
10.3 MSQ3-09CR ......................................................................................................................................................................... 27
10.4 MSQ3-09HR ......................................................................................................................................................................... 28
10.5 MSQ3-12CR ......................................................................................................................................................................... 29
10.6 MSQ3-12HR ......................................................................................................................................................................... 29
11. E l ectr o nic fun ction ............................................................................................................................................................. 31
11.1 Proper symbols and their meaning ....................................................................................................................................... 31
11.2 Function ............................................................................................................................................................................... 31
Page 3
3
11.3 Protection ............................................................................................................................................................................. 31
11.4 Fan-only mode ..................................................................................................................................................................... 32
11.5 Cooling mode ....................................................................................................................................................................... 32
11.6 Dehumidifying mode ............................................................................................................................................................. 33
11.7 Heating mode ....................................................................................................................................................................... 34
11.8 Defrosting mode(available for heating mode) ........................................................................................................................ 35
11.9 Auto mode ............................................................................................................................................................................ 36
11.10 Force cooling function ........................................................................................................................................................... 36
11.11 Sleep mode .......................................................................................................................................................................... 37
11.12 Auto restart function.............................................................................................................................................................. 37
12. Model and Parameters ....................................................................................................................................................... 38
13. Troubleshooting ................................................................................................................................................................. 39
13.1. For all cooling only model ..................................................................................................................................................... 39
13.2. For all heat pump model ....................................................................................................................................................... 39
13.3. Diagnostic chart .................................................................................................................................................................... 40
13.4. Resetting phenomenon often occurs during operation. ......................................................................................................... 41
13.5. Operation lamp flashes and Timer lamp off. .......................................................................................................................... 41
13.6. Operation lamp flashes and Timer lamp on. .......................................................................................................................... 41
13.7. Operation lamp off and Timer lamp flashes ........................................................................................................................... 42
13.8. Operation lamp on and Timer lamp flashes ........................................................................................................................... 42
13.9. Operation lamp flashes, Timer lamp flashes . ....................................................................................................................... 42
14. Characteristic of temperature sensor ............................................................................................................................... 43
Page 4
Service manual
2
1. Precaution
1.1. Safety Precaution
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. Before service unit, be sure to read this service manual at first.
1.2. Warning
Installation
Do not use a defective or underrated circuit breaker. Use this
appliance on a dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the dealer, s el l er, a qualified
electrician, or an Authorized service center.
Do not disassemble or repair the product, there is risk of
fire or electric shock.
Always ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
There is risk of fire of electric shock.
Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fore or electr ic
shock.
Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
Do not modify or extend the power cable.
There is risk of fire or electric shock.
Do not install, remove, or reinstall the unit by yourself
(customer).
There is risk of fire, electric shock, explosion, or injury.
Be caution when unpacking and installing the product.
Sharp edges could cause injury, be especially careful of
the case edges and the fins on the condenser and
evaporator.
For installation, always contact the dealer or an Authorized
service center.
There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorat e with age.
If the base collapse s, t he air conditioner coul d fall with it,
causing property damage, product failure, and personal
injury.
Do not let the air conditioner run for a long time when the
humidity is very high and a door or a windows is left open.
Moisture may condense and wet or damage furniture.
Take care to ensure that power cable could not be pulled out or
damaged during operation.
There is risk of fire or electric shock.
Do not place anything on the power cable.
There is risk of fire or electric shock.
Do not plug or unplug the power supply plug during operation.
There is risk of fire or electric shock.
Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
Do not place a heater or other appliance near the power cable.
There is risk of fire and electric shock.
Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric shoc k.
Do not store or use flammable gas or combustible near the
product.
There is risk of fire or failure of product.
Do not use the product in a tightly closed space for a long time.
Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas and open a window
for ventilation before turn the product on.
Do not use the telephone or turn switches on or off.
There is risk of explosion or fire.
If strange sounds, or small or smoke comes from product. Turn
the breaker off or disconnect the power supply cable.
There is risk of electric shock or fire.
Stop operation and close the window in storm or hurricane. If
possible, remove the product from the window before the hurricane arrives.
There is risk of property damage, failure of product, or
electric shock.
Do not open the inlet grill of the product during operation. (Do
not touch the electrostatic filter, if the unit is so equipped.)
There is risk of physical injury, electric shock, or product
failure.
When the product is soaked (flooded or submerged), contact an
Authorized service center.
There is risk of fire or electric s hoc k.
Be caution that water could not enter the product.
There is risk of fire, electric shock, or product damage.
Ventilate the product from time to time when operating it
together with a stove, etc.
There is risk of fire or electric shock.
Turn the main power off when cleaning or maintaining the
product.
There is risk of electric shock.
When the product is not be used for a long time, disconnect the
Page 5
Service manual
2
power supply plug or turn off the breaker.
There is risk of product d ama g e or fa ilure, or unintended
operation.
Take care to ensure that nobody could step on or fall onto the
outdoor unit.
This could result in personal in jury and pr od uct d ama ge.
 CAUTION
Always check for gas (refrigerant) leakage after installation or
repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away
properly.
A bad connection may cau se w ater leakage.
Keep level even when installing the product.
To avoid vibration of water leakage.
Do not install the product where the noise or hot air from the
outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
Avoid personal injury.
Do not install the product where it will be exposed to sea wind
(salt spray) directly.
It may cause corrosion on the product. Corrosion,
particularly on the condenser and evaporator fins, could
cause product malfunction or inefficient operation.
Operational
Do not expose the skin directly to cool air for long periods of
time. (Do not sit in the draft).
This could harm to your health.
Do not use the product for special purposes, such as preserving
foods, works of art, etc. It is a consumer air conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
It may cause product failure.
Use a soft cloth to clean. Do not use harsh detergents, solvents,
etc.
There is risk of fire, electric shock, or damage to the
plastic parts of the product.
Do not touch the metal parts of the product when removing the
air filter. They are very sharp.
There is risk of personal injury.
Do not step on pr put anything on the product. (outdoor units)
There is risk of personal injury and failure of product.
Always insert the filter securely. Clean the filter every two weeks
or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner
and could cause product malfunction or damage.
Do not insert hands or other object through air inlet or outlet
while the product is operated.
There are sharp and moving parts that could cause
personal injury.
Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
Use a firm stool or ladder when cleaning or maintaining the
product.
Be careful and avoid personal injury.
Replace the all batteries in the remote control with new ones of
the same type. Do not mix old and mew batteries or different types of batteries.
There is risk of fire or explosion.
Do not recharge or disassemble the batteries. Do not dispose of
batteries in a fire.
They may burn of explode.
If the liquid from the batteries gets onto your skin or clothes,
wash it well with clean water. Do not use the remote of the batteries have leaked.
The chemical in batteries could cause burns or other
health hazards.
Page 6
Service manual
3
2. Function
The function will be operate in any operation mode.
Indoor unit
Operation ON/OFF by remote controller
Maintain the room temperature in accordance with the setting temperature.
Room temperature
Indoor fan is delayed for 5 sec at the starting.
Starting temperature control
Restarting is for approx. 3 minutes..
Time Delay Safety control
Turbo wind, high, med, low, breeze.
Indoor fan speed control
Light up in the LED (LCD) for each operation mode.
The fan is turn to low speed (cooling/heating).
The unit will be turn off after seven hours.
Sleep mode auto control
The function is usually used in rainy days in
springtime or damp areas.
Independent dehumidification
Operation indication Lamps (LED)
The louver can be set at the desired position or swing up and
down automatically
Air flow Direction
The unit can be change by the room temperature.
Auto mode
Easy clean panel
Flexible wiring connection
Defrost mode
Temp. Compensation
Auto-restart function
Self-diag. function
Page 7
Service manual
4
The unit has 3 mins delay between continuously ON/OFF operations.
Outdoor unit
Power relay control
Bird tail propeller fan makes the outdoor unit run more quietly.
Low noise air flow system
The hydrophilic fin can improve the heating efficiency at operation mode.
Hydrophilic aluminum fin
It is only operated in the heating operation mode except defrosting operation.
Discharge pipe temperature protect
Anti-rust cabinet
Valve protection cover
4 way valve control
Page 8
Service manual
5
3. Dimension
3.1 Indoor unit
MSQ-07/09/12C(H)R
Page 9
Service manual
6
3.2 Outdoor unit
MSQ-07/09C(H)R
Page 10
Service manual
7
MSQ-12C(H)R
Page 11
Service manual
8
4. Specification
Model
MSQ3-07CR-QB8H
MSQ3-07HR-QB8H
MSQ3-09CR-QB8H
Power supply
Ph-V-Hz
1, 220-240V~,50Hz
1, 220-240V~,50Hz
1, 220-240V~,50Hz
Cooling
Capacity
Btu/h
7000
7000
9000
Input
W
820
820
1000
Rated current
A
3.6
3.6
4.1
EER
W/W
9.55
9.55
9.55
Heating
Capacity
Btu/h 8000 Input
W 720 Rated current
A 3.2 COP
W/W 10.2 Max. input consumption
W
1000
1000
1300
Max. current
A 5 5
6.3
Starting current
A
14
14
19.8
Compressor
Model
2P14C225ANA
2P14C235ANA
PH180X1C-4DZDE3
Type
ROTARY
Rotary
Rotary
Brand
Matsushita
GD Matsushita
GD TOSHIBA
Capacity
Btu/h
7455
7455
10287
Input
W
725
725
965
Rated current(RLA)
A
3.4
3.4
4.5
Locked rotor Amp(LRA)
A
14
14
19.8
Thermal protector
B150-145-241E
B150-145-241E
B160-135-141E
Capacitor
uF
25
25
30
Refrigerant oil
ml
270
270
400
Indoor fan
motor
Model
RPG20D
RPG20D
RPG20D
Brand
Welling
Welling
Welling
Input
W
32
32
32
Capacitor
uF
1.2
1.2
1.2
Speed(hi/mi/lo)
r/min
1040/900/800
1040/900/800
1040/900/800
Indoor air flow (Hi/Mi/Lo)
m3/h
490
520/470/420
520
Indoor noise level (Hi/Mi/Lo)
dB(A)
34/31/25
35/31/26
35/31/26
Outdoor fan
motor
Model
YDK24-6T
YDK24-6T
YDK24-6T
Brand
Welling
WELLING
WELLING
Input
W
62
62
62
Capacitor
uF
2.5
2.5
2.5μF/450V
Speed
r/min
815
815
815
Outdoor air flow
m3/h
1400
1400
1500
Outdoor noise level
dB(A)
49
52
50
Refrigerant type R22
g
580
620
650
Design pressure
MPa
2.6
2.6
2.6
Refrigerant
piping
Liquid side/ Gas side
mm(inch)
Ф
6.35/Ф9.53
Ф
6.35/Ф9.53
Ф
6.35/Ф9.53
Max. refrigerant pipe length
m
10
10
10
Max. difference in level
m 5 5
5
Plug type
CS-006/15A 250V
16A
CS-006/15A 250V
Thermostat type
Electronic control
Electronic control
Electronic control
Operation temp
17-30
17-30
17-30
Ambient temp
18-45
-7 - 45
18-45
Application area
m2
12-16
12-16
14-21
Note:
Th e noise date is base on hemi-anechoic chamber, during actual operation; these values are normal ly somewhat different as a result of
ambient condition.
The above design and specifications are subject to change without prior notice for product improvement.
Page 12
Service manual
9
Model
MSQ3-09HR-QB6
MSQ3-12CR-QB8
MSQ3-12HR-QB6
Power supply
Ph-V-Hz
220V~,50Hz
220V~,50Hz
220V~,50Hz
Cooling
Capacity
Btu/h
9000
12000
12000
Input
W
1000
1350
1350
Rated current
A
4.5
6.0
6.0
EER
W/W
9.55
9.55
9.55
Heating
Capacity
Btu/h
10000
_
13500
Input
W
980 _ 1230
Rated current
A
4.4 _ 5.6
COP
W/W
10.2 _ 10.2
Max. input consumption
W
1300
1700
1700
Max. current
A 6 8.0
8.0
Starting current
A
19.8
26
30
Compressor
Model
2P18S225ANK
PH200X2C-8FTC
PH225X2C-4FT
Type
Rotary
Rotary
Rotary
Brand
GD Matsushita
TOSHIBA
GD Matsushita
Capacity
Btu/h
9911
11839
13204
Input
W
970
1135
1250
Rated current(RLA)
A
4.5
5.2
5.7
Locked rotor Amp(LRA)
A
19.8
26
30
Thermal protector
External
UP3QE0591-T51
External
Capacitor
uF
30
25μF/370V
35
Refrigerant oil
ml
SUNISO 350
440
480
Indoor fan
motor
Model
RPG13H
RPG13H
RPG13H
Brand
WELLING
WELLING
WELLING
Input
W
33
33
33
Capacitor
uF
1.2μF/450V
1.2μF/450V
1.2μF/450V
Speed(hi/mi/lo)
r/min
1060/940/880
1130
1130/1080/1030
Indoor air flow (Hi/Mi/Lo)
m3/h
520/470/420
550
550/500/450
Indoor noise level (Hi/Mi/Lo)
dB(A)
35/31/26
37/33/27
37/33/27
Outdoor fan
motor
Model
YDK24-6T
YDK24-6
YDK24-6
Brand
WELLING
WELLING
WELLING
Input
W
62
72
72
Capacitor
uF
2.5μF/450V
2.5μF/450V
2.5μF/450V
Speed
r/min
800
850
850
Outdoor air flow
m3/h
1500
1800
1800
Outdoor noise level
dB(A)
53
52
52
Refrigerant type R22
g
870
730
860
Design pressure
MPa
2.6
2.6
2.6
Refrigerant
piping
Liquid side/ Gas side
mm(inch
Ф
6.35/Ф9.53
Ф
6.35/Ф12.7
Ф
6.35/Ф12.7
Max. refrigerant pipe
m
10
10
10
Max. difference in level
m 5 3X1.5mm2
No
Plug type
16A
CS-006/15A
16A
Thermostat type
Electronic control
Electronic control
Electronic control
Operation temp
17-30
17-30
17-30
Ambient temp
-7 - 45
18-45
-7 - 45
Application area
m2
14-21
18-26
18-26
Note:
Th e noise date is base on hemi-anechoic chamber, during actual operation; these values are normally somewhat different as a result of
ambient condition.
The above design and specifications are subject to change without prior notice for product improvement.
Page 13
Service manual
10
5. Refrigerant cycle diagram
 Cooling only
 Heat pump mode
Page 14
Service manual
11
6. Operation limits
6.1 Cooling operation
Outdoor unit air temp.℃ DB
Indoor air temp. DB
Note: The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial
pull-down stage.
6.2 Heating operation Indoor air temp. DB
Outdoor unit air temp.℃ DB
Note: The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial
pull-down stage.
Page 15
Service manual
12
7. Schematic diagram and Wiring diagram
7.1. Schematic diagram
Page 16
Service manual
13
7.2. Wiring diagram
MSQ3-07CR, MSQ3-09CR, MSQ3-12CR
Page 17
Service manual
14
MSQ3-07HR, MSQ3-09HR, MSQ3-12HR
MSQ3-12HR
Page 18
Service manual
15
Page 19
Service manual
16
8. Installation de tails
8.1 Wrench torque sheet for installation
Outside diameter Torque
mm inch Kg.m
φ6.35
1/4 1.8
φ9.52
3/8 4.2
φ12.7
1/2 5.5
8.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit 7K 9K 12K
mm2 1.0 1.0 1.5
8.3 Pipe length and the elevation
Capacity
Btu/h
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max. Pipe
length
A (m)
Additional
refrigerant
(g/m)
GAS LIQUID
07k~09K
3/8’’ (φ9.52) 1/4’’ (φ6.35)
5 5 10 30
12K
1/2’’ (φ12.7) 1/4’’ (φ6.35)
5 5 10 30
Caution:
Capacity is base on standard length and maximum allowance length is base of reliability.
Oil trap should be install per 5-7 meters.
In case that
more than 5m.
Page 20
Service manual
17
8.4 Air purging of the piping and indoor unit
Required tools:
Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak detector.
Note:
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, it will affect the compressor, reduce
the cooling capacity, and could lead to a malfunction of unit.
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas leakage from the
refrigeration cycle.
Procedure
1. Recheck the piping connections.
2. Open the valve stem of the 2-way valve counterclockwise approximately 90’, wait 10 seconds, and then set it to closed
position.
Be sure to use a hexagonal wrench to operate the valve
stem
3. Check for gas leakage.
Check the flare connection for gas leakage
4. Purge the air from the system.
Set the 2-way valve to the open position and remove the
cap from the 3-way valve’s service port.
Using the hexagonal wrench to press the valve core pin,
discharge for three seconds and then wait for one
minute.
5. Use torque wrench to tighten the service port cap to a torque
of 1.8 kg.m. (18n.m)
6. Set the 3-way valve to the opened position.
7. Mounted the valve stem nuts to the 2-way and 3-way valves.
8. Check for gas leakage.
At this time, especially check for gas leakage from the
2-way and 3-way stem nuts, and from the service port.
Caution:
If gas leakage is discovered in step (3) above, take the
following measures.
If the leaks stop when the piping connections are tightened
further, continue working from step (4).
If the gas leaks do not stop when the connections are
retightened, repair the location of the leak, discharge all of the
gas through the service port, and then recharge with the
specified amount of gas from a gas cylinder.
Page 21
Service manual
18
8.5 Pumping down (Re-installation)
Procedure
1. Confirm that both the 2-way and 3-way valves are set to the opened position.
Remove the valve stem caps and confirm that the valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then connect the charge set to the service port of the 3-way valve. Connect the charge hose with the push pin to the gas service port.
4. Air purging of the charge hose.
Open the low-pressure valve on the charge set slightly to purge air from the charge hose.
5. Set the 2-way valve to the close position.
6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
7. Immediately set the 3-way valve to the closed position.
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
8. Disconnect the charge set, and amount the 2-way and 3-way valve’s stem nuts and service port caps.
Use a torque wrench to tighten the service port cap to a torque of 1.8 kg.m.
Be sure to check for gas leakage.
Page 22
Service manual
19
8.6 Re-air purging (Re-installation)
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the closed position.
2. Connect the charge set and a charging cylinder to the service port of the 3-way valve. Leave the valve on the charging cylinder closed.
3. Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve
approximately 45’ for 3 seconds then closing it for 1 minutes; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut to on the 2-way valve.
4. Check the gas leakage.
Check the flare connections for gas leakage.
5. Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant until the gauge indicate 0.3 to 0.5 Mpa.
6. Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open position. Be sure to use a hexagonal wrench to operate the valve stems.
7. Mount the valve stems nuts and the service port cap.
Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
Be sure to check the gas leakage.
Page 23
Service manual
20
8.7 Balance refrigerant of the 2-way, 3-way valves
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the open position.
2. Connect the charge set to the 3-way valve’s service port.
Leave the valve on the charge set closed.
Connect the charge hose with the push pin to the service port.
3. Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa.
If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is higher than 0.1Mpa, discharge the
refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If this is the case, it will not be necessary to apply a evacuation.
Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil sill be discharged.
Page 24
Service manual
21
8.8 Evacuation
Procedure:
1. Connect the vacuum pump to the charge set’s centre hose.
2. Evacuation for approximately one hour.
Confirm that the gauge needle has moved toward -0.1 Mpa (-76 cmHg) [vacuum of 4 mmHg or less].
3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
Vacuum pump oil, if the vacuum pump oil becomes dirty or depleted, replenish as needle.
Page 25
Service manual
22
8.9 Gas charging
Procedure:
1. Connect the charge hose to the charging cylinder.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder.
2. Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid
refrigerant).
3. Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
If the system cannot be charge with the specified amount of refrigerant, if can be charged with a little at a time (approximately
150g each time0 while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1
minute and then repeat the procedure.(pumping down-pin).
4. Immediately disconnect the charge hose from the 3-way valve’s service port.
Stopping partway will allow the refrigerant to be discharged.
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before
disconnecting the hose.
5. Mounted the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
Page 26
Service manual
23
9. Pressure table
Note:
The pressure data is from 3 way valve, the pressure data are pressure above atmosphere.
D: Dry bulb temp.
W: Wet bulb temp.
9.1 MSQ-07CR
Cooling mode
Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D
15ºC W
Pressure
(kg/cm2 )
6.2 6.7 7.2 8.0 8.5 9.4
24ºC D
17ºC W
Pressure
(kg/cm2)
6.3 6.5 7.5 8.1 8.7 9.5
27ºC D
19ºC W
Pressure
(kg/cm2)
6.1 6.8 7.7 8.2 9.0 10.0
32ºC D
23ºC W
Pressure
(kg/cm
2
)
7.0 7.3 7.8 8.4 9.2 10.1
9.2 MSQ-07HR
Cooling mode
Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D
15ºC W
Pressure
( kg/cm2 )
6.2 6.7 7.2 8.0 8.5 9.4
24ºC D
17ºC W
Pressure
( kg/cm2 )
6.3 6.5 7.5 8.1 8.7 9.5
27ºC D
19ºC W
Pressure
( kg/cm2 )
6.1 6.8 7.7 8.2 9.0 10.0
32ºC D
23ºC W
Pressure
( kg/cm
2
)
7.0 7.3 7.8 8.4 9.2 10.1
Heating mode OUTDOOR CONDITIONS
Indoor Conditions Pressure
12ºC D
11ºC W
7ºC D
6ºC W
0ºC D
-1ºC W
-
4ºC D
-6ºC W
-7ºC D
-9ºC W
-15ºC D
-xºC W
15ºC
Pressure
( kg/cm2 )
24.0 23.0 21.5 21.0 20..5 /
18ºC
Pressure
( kg/cm2 )
24.6 23.5 23.0 22.6 20.8 /
20ºC
Pressure
( kg/cm2 )
25.0 24.2 24.0 23.0 21.0 /
22ºC
Pressure
( kg/cm2 )
25.3 24.6 24.5 23.8 21.7 /
Page 27
Service manual
24
9.3 MSQ-09CR
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D
15ºC W
Pressure
( kg/cm2 )
7.8 8.1 8.4 9.0 9.3 10.0
24ºC D
17ºC W
Pressure
( kg/cm2 )
7.9 8.2 8.7 9.0 9.5 10.1
27ºC D
19ºC W
Pressure
( kg/cm2 )
8.0 8.5 9.2 9.9 10.2 10.8
32ºC D
23ºC W
Pressure
( kg/cm
2
)
8.8 9.1 9.2 10.0 10.5 11.2
9.4 MSQ-09HR
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D
15ºC W
Pressure
( kg/cm
2
)
7.8 8.1 8.4 9.0 9.3 10.0
24ºC D
17ºC W
Pressure
( kg/cm
2
)
7.9 8.2 8.7 9.0 9.5 10.1
27ºC D
19ºC W
Pressure
( kg/cm
2
)
8.0 8.5 9.2 9.9 10.2 10.8
32ºC D
23ºC W
Pressure
( kg/cm
2
)
8.8 9.1 9.2 10.0 10.5 11.2
Heating mode OUTDOOR CONDITIONS
Indoor Conditions Pressure
12ºC D
11ºC W
7ºC D
6ºC W
0ºC D
-1ºC W
-
4ºC D
-6ºC W
-7ºC D
-9ºC W
-15ºC D
-xºC W
15ºC
Pressure
( kg/cm
2
)
26.5 25.0 22.0 21.5 20.5 /
18ºC
Pressure
( kg/cm2 )
27.0 26.0 23.5 22.5 20.8 /
20ºC
Pressure
( kg/cm2 )
27.5 26.5 25.0 23.0 21.0 /
22ºC
Pressure
( kg/cm2 )
28.5 27.0 25.5 23.9 21.5 /
Page 28
Service manual
25
9.5 MSQ-12CR
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D
15ºC W
Pressure
( kg/cm
2
)
8.4 8.5 8.8 8.9 9.4 9.9
24ºC D
17ºC W
Pressure
( kg/cm
2
)
8.6 8.8 9.2 9.4 10.0 10.4
27ºC D
19ºC W
Pressure
( kg/cm
2
)
8.8 9.2 9.4 9.8 10.3 10.9
32ºC D
23ºC W
Pressure
( kg/cm
2
)
9.2 9.6 9.9 10.4 10.8 11.2
9.6 MSQ-12HR
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D
15ºC W
Pressure
( kg/cm
2
)
8.4 8.5 8.8 8.9 9.4 9.9
24ºC D
17ºC W
Pressure
( kg/cm
2
)
8.6 8.8 9.2 9.4 10.0 10.4
27ºC D
19ºC W
Pressure
( kg/cm
2
)
8.8 9.2 9.4 9.8 10.3 10.9
32ºC D
23ºC W
Pressure
( kg/cm
2
)
9.2 9.6 9.9 10.4 10.8 11.2
Heating mode OUTDOOR CONDITIONS
Indoor Conditions Pressure
12ºC D
11ºC W
7ºC D
6ºC W
0ºC D
-1ºC W
-
4ºC D
-6ºC W
-7ºC D
-9ºC W
-15ºC D
-xºC W
15ºC
Pressure
( kg/cm
2
)
27.4 25.9 22.2 21.4 20.0 /
18ºC
Pressure
( kg/cm
2
)
29.8 27.2 23.8 22.0 21.1 /
20ºC
Pressure
( kg/cm
2
)
30.2 29.1 24.2 23.6 22.1 /
22ºC
Pressure
( kg/cm2 )
32.4 30.1 25.4 24.0 22.7 /
Page 29
Service manual
26
10. Capacity table
10.1 MSQ-07CR SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D
15ºC W
Total capacity kW 2.02 1.92 1.79 1.64 1.51 1.41
Sensitive capacity kW 1.44 1.39 1.34 1.27 1.20 1.15
Input kW. 0.70 0.76 0.82 0.88 0.95 1.00
24ºC D
17ºC W
Total capacity kW 2.16 2.07 1.95 1.83 1.71 1.60
Sensitive capacity kW 1.53 1.48 1.43 1.38 1.34 1.32
Input kW. 0.70 0.77 0.84 0.90 0.97 1.03
27ºC D
19ºC W
Total capacity kW 2.32 2.27
2.15 1.98 1.81 1.65
Sensitive capacity kW 1.65 1.62 1.56 1.48 1.41 1.34
Input kW. 0.72 0.79 0.85 0.92 0.99 1.05
32ºC D
23ºC W
Total capacity kW 2.54 2.45 2.36 2.28 2.18 2.07
Sensitive capacity kW 1.57 1.59 1.57 1.55 1.53 1.54
Input kW. 0.71 0.79 0.87 0.95 1.03 1.10
10.2 MSQ-07HR SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D
15ºC W
Total capacity kW 2.02 1.92 1.79 1.64 1.51 1.41
Sensitive capacity kW 1.44 1.39 1.34 1.27 1.20 1.15
Input kW. 0.70 0.76 0.82 0.88 0.95 1.00
24ºC D
17ºC W
Total capacity kW 2.16 2.07 1.95 1.83 1.71 1.60
Sensitive capacity kW 1.53 1.48 1.43 1.38 1.34 1.32
Input kW. 0.70 0.77 0.84 0.90 0.97 1.03
27ºC D
19ºC W
Total capacity kW 2.33 2.28
2.11 1.99 1.82 1.66
Sensitive capacity kW 1.66 1.63 1.57 1.49 1.42 1.35
Input kW. 0.72 0.79 0.85 0.92 0.99 1.05
32ºC D
23ºC W
Total capacity kW 2.54 2.45 2.36 2.28 2.18 2.07
Sensitive capacity kW 1.57 1.59 1.57 1.55 1.53 1.54
Input kW. 0.71 0.79 0.87 0.95 1.03 1.10
Page 30
Service manual
27
WINTER OUTDOOR CONDITIONS
Indoor Conditions
12ºC D
11ºC W
7
ºC D
6ºC W
4
ºC D
3ºC W
0
ºC D
-1ºC W
-4
ºC D
-6ºC W
-7
ºC D
-8ºC W
15ºC
Capacity kW 2.89 2.59 2.41 1.54 1.31 1.27
Input kW. 0.97 0.84 0.75 0.65 0.63 0.64
18ºC
Capacity kW 2.74 2.47 2.25 1.47 1.37 1.21
Input kW. 0.97 0.84 0.76 0.69 0.66 0.64
20ºC
Capacity kW 2.72
2.49 2.22 1.41 1.28 1.25
Input kW. 1.00 0.88 0.79 0.69 0.65 0.62
22ºC
Capacity kW 2.54 2.43 2.13 1.31 1.29 1.21
Input kW. 0.92 0.87 0.79 0.68 0.66 0.61
10.3 MSQ-09CR SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D
15ºC W
Total capacity kW 2.44 2.32 2.16 1.98 1.82 1.70
Sensitive capacity kW 1.68 1.63 1.56 1.48 1.40 1.34
Input kW. 0.87 0.95 1.02 1.09 1.17 1.24
24ºC D
17ºC W
Total capacity kW 2.62 2.50 2.36 2.20 2.07 1.94
Sensitive capacity kW 1.78 1.73 1.67 1.61 1.56 1.54
Input kW. 0.87 0.95 1.03 1.11 1.20 1.28
27ºC D
19ºC W
Total capacity kW 2.80 2.75
2.60 2.40 2.18 1.99
Sensitive capacity kW 1.93 1.89 1.82 1.73 1.64 1.57
Input kW. 0.89 0.97 1.05 1.14 1.22 1.30
32ºC D
23ºC W
Total capacity kW 3.12 2.98 2.86 2.76 2.63 2.50
Sensitive capacity kW 1.83 1.85 1.84 1.81 1.78 1.79
Input kW. 0.88 0.98 1.07 1.17 1.27 1.37
Page 31
Service manual
28
10.4 MSQ-09HR SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D
15ºC W
Total capacity kW 2.44 2.32 2.16 1.98 1.82 1.70
Sensitive capacity kW 1.68 1.63 1.56 1.48 1.40 1.34
Input kW. 0.87 0.95 1.02 1.09 1.17 1.24
24ºC D
17ºC W
Total capacity kW 2.62 2.50 2.36 2.20 2.07 1.94
Sensitive capacity kW 1.78 1.73 1.67 1.61 1.56 1.54
Input kW. 0.87 0.95 1.03 1.11 1.20 1.28
27ºC D
19ºC W
Total capacity kW 2.82 2.77
2.62 2.42 2.20 2.01
Sensitive capacity kW 1.93 1.89 1.82 1.73 1.64 1.57
Input kW. 0.89 0.97 1.05 1.14 1.22 1.30
32ºC D
23ºC W
Total capacity kW 3.12 2.98 2.86 2.76 2.63 2.50
Sensitive capacity kW 1.83 1.85 1.84 1.81 1.78 1.79
Input kW. 0.88 0.98 1.07 1.17 1.27 1.37
WINTER OUTDOOR CONDITIONS
Indoor Conditions
12ºC D
11ºC W
7
ºC D
6ºC W
4
ºC D
3ºC W
0
ºC D
-1ºC W
-4
ºC D
-6ºC W
-7
ºC D
-8ºC W
15ºC
Capacity kW 3.58 3.18 2.80 1.82 1.52 1.47
Input kW. 1.18 1.05 0.94 0.81 0.75 0.80
18ºC
Capacity kW 3.37 3.02 2.72 1.73 1.60 1.41
Input kW. 1.20 1.05 0.96 0.86 0.83 0.84
20ºC
Capacity kW 3.35
3.05 2.70 1.64 1.48 1.44
Input kW. 1.24 1.08 0.98 0.86 0.82 0.82
22ºC
Capacity kW 3.11 2.97 2.57 1.40 1.50 1.39
Input kW. 1.14 1.07 0.98 0.86 0.82 0.79
Page 32
Service manual
29
10.5 MSQ-12CR SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D
15ºC W
Total capacity kW 3.31 3.14 2.92 2.68 2.45 2.28
Sensitive capacity kW 2.53 2.28 2.18 2.07 1.96 1.88
Input kW. 1.11 1.21 1.32 1.42 1.52 1.63
24ºC D
17ºC W
Total capacity kW 3.55 3.39 3.19 2.99 2.79 2.61
Sensitive capacity kW 2.50 2.42 2.34 2.25 2.19 2.16
Input kW. 1.11 1.22 1.34 1.45 1.56 1.67
27ºC D
19ºC W
Total capacity kW 3.81 3.73
3.53 3.24 2.96 2.69
Sensitive capacity kW 2.71 2.65 2.55 2.42 2.30 2.19
Input kW. 1.14 1.25 1.36 1.48 1.59 1.71
32ºC D
23ºC W
Total capacity kW 4.05 3.96 3.88 3.75 3.57 3.39
Sensitive capacity kW 2.56 2.59 2.57 2.53 2.50 2.51
Input kW. 1.15 1.26 1.43 1.53 1.66 1.80
10.6 MSQ-12HR SUMMER OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D
15ºC W
Total capacity kW 3.35 3.18 2.96 2.72 2.49 2.32
Sensitive capacity kW 2.53 2.28 2.18 2.07 1.96 1.88
Input kW. 1.15 1.25 1.36 1.46 1.56 1.67
24ºC D
17ºC W
Total capacity kW 3.59 3.43 3.23 3.03 2.83 2.65
Sensitive capacity kW 2.50 2.42 2.34 2.25 2.19 2.16
Input kW. 1.15 1.26 1.38 1.49 1.60 1.71
27ºC D
19ºC W
Total capacity kW 3.85 3.77
3.57 3.29 3.00 2.73
Sensitive capacity kW 2.71 2.65 2.55 2.42 2.30 2.19
Input kW. 1.18 1.29 1.40 1.52 1.63 1.75
32ºC D
23ºC W
Total capacity kW 4.09 4.00 3.92 3.79 3.61 3.43
Sensitive capacity kW 2.56 2.59 2.57 2.53 2.50 2.51
Input kW. 1.17 1.30 1.43 1.57 1.70 1.84
Page 33
Service manual
30
WINTER OUTDOOR CONDITIONS
Indoor Conditions
12ºC D
11ºC W
7
ºC D
6ºC W
4
ºC D
3ºC W
0
ºC D
-1ºC W
-4
ºC D
-6ºC W
-7
ºC D
-8ºC W
15ºC
Capacity kW 4.67 4.14 3.64 2.31 1.90 1.83
Input kW. 1.36 1.29 1.14 0.96 0.88 0.84
18ºC
Capacity kW 4.39 3.92 3.52 2.18 2.00 1.84
Input kW. 1.50 1.29 1.16 1.03 0.97 0.87
20ºC
Capacity kW 4.36
3.96 3.49 2.07 1.84 1.80
Input kW. 1.54 1.33 1.19 1.03 0.98 0.88
22ºC
Capacity kW 4.06 3.85 3.32 1.73 1.86 1.73
Input kW. 1.63 1.33 1.20 1.00 0.98 0.92
Page 34
Service manual
31
11. Electronic function
11.1 Proper symbols and their meaning TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
I
3sec
: Self-protection amp of compressor, continue three seconds until turns off the compressor.
I
5MIN
: Self-protection amp of compressor, continue five minutes until turns off the compressor.
I
FAN
: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.
I
RESTORE
: Amp self-protection return value
TH
DEFROST
: High wind, defrosting temperature difference
TM
DEFROST
: Middle wind, defrosting temperature difference
TL
DEFROST
: Low wind, defrosting temperature difference
TE1: Anti-cold wind, from Fan Off to Breeze temperature TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature
11.2 Function
Remote receiving
Testing and forced running
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
Anti frozen at cooling mode
11.3 Protection
11.3.1 3 minutes delay at restart for compressor.
11.3.2 Sensor protection at open circuit and breaking disconnection
11.3.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or too low(lower than 300RPM), the unit stops and LED displays failure information and can’t returns to normal operation autom aticall y.
11.3.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED displays failure
information and can’t returns to normal operation autom atically.
11.3.5 The current protection of the compressor
11.3.6
Page 35
Service manual
32
11.3.7
Current up
I restore
I fan
I 5min
I 3sec
Indoor fan: On compressor: On outdoor fan:On
The outdoor fan turn off (heating) The outdoor fan turn low speed (cooling)
Compressor turn off (after 5 minute later)
Compressor turn off (after 3 minute later)
Current down
If compressor turns off for continuously 4 times due to current protection in 5 minutes from Compressor On, the unit stops and LED
displays failure information and can’t returns to normal operation automatically.
11.4 Fan-only mode
Fan speed is high/mid/low/ Auto
11.5 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:
0
T-Ts
Room temp. up
Room temp. down
1
Compressor on
outdoor fan on
Compressor off
outdoor fan off
Page 36
Service manual
33
Auto fan at cooling mode:
3
T-Ts
Room temp. up
Room temp. down
5
High fan
Low fan
1
Mid. fan
Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )
TE5
T
EVAP. temp. up
EVAP. temp. down
TE6
Compressor and
outdoor fan on
Compressor and outdoor
fan off (after 5 mins)
11.6 Dehumidifying mode
11.6.1 The 4-way valve is off in dehumidifying mode
11.6.2 Compressor and Indoor Fan actions in dehumidifying mode
11.6.3
0 TA-TS
2
C
B
A
Block
Indoor Fan
Compressor and Outdoor Fan
LOW ON 6minutes
BREEZE OFF 4minutes
LOW ON 5minutes
BREEZE OFF 5minutes
LOW ON 4minutes
BREEZE OFF 6minutes
A
B
C
Repeat on and off cycle.
11.6.4 Low room temperature protection:
When room temperature decreases to below 10, compressor and outdoor fan will stop(indoor fan is Breeze). Dehumidifying
operation will be resumed when room temperature restores to over 13℃.
11.6.5 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that of cooling mode.
11.6.6 At dehumidifying mode, t he action of fans of indoor is the same as that of air-only mode.
Page 37
Service manual
34
11.7 Heating mode
11.7.1 Generally, t he 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve must delay 2 minutes compared with compressor if the compressor changed into non-heating mode or turned off. 4-way valve doesn't delay in
dehumidifying mode
11.7.2 Generally, t he outdoor fan is turned off with the on-off action of compressor in heating mode, except for the defrosting mode or the end of defrost
11.7.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes after starting and then judge temperature. Meanwhile other protections are still valid.
Ts+2*
T
Room temp. up
Room temp. down
Ts+3*
Compressor and
outdoor fan off
Compressor and
outdoor fan on
Ts
* This parameter can be changed from 0 to 3
11.7.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Ant i -cold wind functi on prevails .
Anti-cold wind control function at heating mode (T=indoor exchanger temp.)
T
T temp. up
T temp. down
TE2
Setting fan speed
Fan off
Breeze
TE3
TE1
TE4
Indoor fan changes breeze when compressor stop, after 127 second, indoor fan stop
11.7.5 Auto wind at heating mode
Page 38
Service manual
35
11.7.6
0
T-Ts
Room temp. up
Room temp. down
2
Med fan
High fan
11.7.7
11.7.8 Indoor evaporator high-temperature protection at heating mode (T=indoor exchanger temp.)
11.7.9
T
T temp. up
T temp. down
TE7
Compressor on Fan on
TE8
TE9
Compressor off Fan off
Compressor on Fan off
11.7.10
11.7.11 The louver opens to Standard Angle ANGLHEAT when power is on for the first time
11.8 Defrosting mode(available for heating mode)
11.8.1 Defrosting condition: Defrosting starts when either of the following ①&②: ① A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:
TM def.
TA-TS
TH def.
High fanMed fanLow fan
TL def.
Breeze
② Calculate from the end of latest defrost, evaporator high temp. Protection only closes outdoor fan with the compressor still
running. Add up to 90 minutes.
Page 39
Service manual
36
11.8.2 Defrosting time
If the temperature difference condition ① is satisfied for less than 40 minutes, this can be regarded as severe frosting. The
defrosting time is 10 minutes.
If the temperature difference condition ② is satisfied for more than 40 minutes, the defrosting time is 7.5minutes.
If the temperature difference condition ① is satisfied out of 40 minutes, generally the defrosting time is 7.5minutes, after three
continuous 7.5-minute defrost, the fourth should be 10 minutes defrost. The circulation is as following:
7.5 minutes defrost
7.5 minutes defrost
7.5 minutes defrost
10 minutes
defrost
11.8.3 Ending condition of defrosting
If one of following conditions is satisfied, end the defrost and turn into heating mode:
A. The defrost time has reached to 7.5 or 10 minutes.
B. The compressor current has reached to I
DEFROST
or above, I
DEROST
differs in different models
11.8.4 Defrosting Actions
Defrost 10or 7.5minutes
45S 25S
Compressor
4-way Valve 23S
40S
Outdoor Fan
Indoor Fan
10S
11.9 Auto mode
11.9.1 The air conditioner automatically selects one of the following operation modes: cooling, heating or fan only according to the temperature difference between room temperature (TA) and set temperature (TS).
11.9.2
-1
TA-TS
2
Heating (fan only at cooling)
Fan only Cooling
11.9.3 The indoor fan blows automatically in corresponding selected mode
11.9.4 The motion of indoor fan’s blade should accord with the selected operation mode
11.9.5 One mode should be carried out for at least 15 minutes once selected. If the compressor cannot start for 15 minutes, reselect the operation mode according to the room temp. and set temp., or reselect when the set temp. varies
11.10 Force cooling function
11.10.1 Select forced cooling function with the forced cooling button or the switch.
11.10.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan mode is set as low, the A/C operates at the DRY mode with a set temp. of 24
Page 40
Service manual
37
11.10.3 All protections of remote control cooling are available at forced cooling operation
11.10.4 Forced Auto function
Select forced auto function with the forced auto button or the switch.
In forced auto status the A/C operates at remote control mode with a set temp. of 24
11.11 Sleep mode
11.11.1 The sleep function is available at cooling, heating or auto mode
11.11.2 Cooling:
The set temperature rise 1per hour . Two hours later, the set temperature will maintain as a constant and the fan speed is kept at
low speed.
The total time is 7 hours, after 7 hours the unit stops
11.11.3 Heating:
The set temperature decrease 1per hour. Two hours later, the set temperature will m ai ntain as a constant and the air
circulation is kept at low speed (Cold air proof function takes precedence over all).
The total time is 7 hours, after 7 hours the unit stops
11.11.4 Auto:
After an hour running under economic mode, the set temp will rise 1,if it is under cooli ng mode; the set temp will decrease 1, if it is
under heating mode; the set temp will be changeless, if it is under fan-only mode; the condition will be the same after the air conditioner
running under economic mode after 2 hours, and during the next time the set temp do not change. The total time is 7 hours, after 7
hours the unit stops.
11.12 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings before the power failure when
power returns
Page 41
Service manual
38
12. Mode l and Parameters
Model MSQ-07CR MSQ-07HR MSQ-09CR MSQ-09HR MSQ-12CR MSQ-12HR I3SEC 8.5A 8.5A 10.0A 10.0A 11A 11A I5MIN 6.2A 6.2A 7.5A 7.5A 10A 10A
IFAN 5.2A 5.2A 6.2A 6.2A 8A 8A IRESTORE 4.2A 4.2A 5A 5A 6A 6A IDEFROST 3.2A 4.5A 5.5A
TE1 28 28 28 TE2 32 32 32 TE3 30 30 30 TE4 20 20 20 TE5 2 2 2 2 2 2 TE6 7 7 7 7 7 7 TE7 60 60 60 TE8 53 53 53 TE9 50 50 50
ANGLCOOL 200° 200° 200° 200° 200° 200°
ANGLHEAT 45° 45° 45°
ANGLOFF 132° 132° 132° 132° 132° 132°
TH
DEFROST
18 18 18
TM
DEFROST
19 19 19
TL
DEFROST
20 20 20
Page 42
Service manual
39
13. Troubleshooting
13.1. For all cooling only model
Failure phenomenon
Operation lamp Timer lamp
Indoor fan speed has been out of control for over 1 minute
X
Indoor room temp. or evaporator sensor i s open circ uit or
short circuit
On
Over current protection of the
compressor occurs 4 times
X
EEROM error
On
No over-zero signal
Extinguish
☆ Flash at 5Hz
13.2. For all heat pump model
Failure phenomenon
Operation lamp Timer lamp Defrosting lamp
Over current protection of the
compressor occurs 4 times
X
Indoor fan speed has been out of control for over 1 minute
X
No over-zero signal
Temp. sensor on indoor evaporator is open circuit or short
circuit
X X
Indoor room temp. sensor is open circuit or short circuit
X ☆ X
EEROM error
On ☆ X
 Extinguish Flash at 5Hz
Page 43
Service manual
40
13.3. Diagnostic chart
After energizing, no indicator is lighted and the air conditioner can’t be operated.
After energizing, the air conditioner can not be operated.
Check if AC 220V power supply outputs to indoor PCB.
Check if AC 220V exists at the primary coil of transformer.
Yes
YES
No
Check if AC 14.5V exists at the secondary coil of transformer.
Indoor PCB is defective.
Take off the secondary plug of transformer, and then check if AC
14.5V exists at the secondary coil of transformer.
No
Yes
Yes
Indoor PCB is defective.
Indoor PCB is defective.
No
Page 44
Service manual
41
13.4. Resetting phenomenon often occurs during operation. (That is automatically entering to the status when power is on.)
The reason is that the instantaneous voltage of main chip is less than 4.5V. Check accordi ng to the following procedure:
Resetting phenomenon often occurs during operation.
After changing indoor PCB, check if the failure realease.
Yes
After changing indoor fan motor, check if the failure realease.
Yes
YES
Yes
Power supply circuit has problems.
Indoor PCB is defective.
13.5. Operation lamp flashes and Timer lamp off.
Is connector connection good?
Is voltage being applied to the fan motor?
Fan motor is defective
Yes
No
Repair the connector.
No
Indoor PCB is defective.
13.6. Operation lamp flashes and Timer lamp on.
Is connector connection good?
Replace the sencor,
No
Repair the connector.
Page 45
Service manual
42
13.7. Operation lamp off and Timer lamp flashes
Operation lamp off and Timer lamp flashes
The voltage of power supply is too low (less than 187V).
No
Indoor PCB is defective.
After changing the main control board, check if the failure realease.
Power supply fault.
No
Outdoor unit fault (such
as the compressor).
13.8. Operation lamp on and Timer lamp flashes EEROM error, indoor PCB is defective.
13.9. Operation lamp flashes, Timer lamp flashes .
This is alarm signal when the main chip can’t detect over-zero signal. When such failure occurs, the main control board must have
fault.
Page 46
Service manual
43
14. Characteristic of temperature sensor
Temp. Resistance KΩ Temp. Resistance KΩ Temp.℃ Resistance KΩ
-10 62.2756 17 14.6181 44 4.3874
-9 58.7079 18 13.918 45 4.2126
-8 56.3694 19 13.2631 46 4.0459
-7 52.2438 20 12.6431 47 3.8867
-6 49.3161 21 12.0561 48 3.7348
-5 46.5725 22 11.5 49 3.5896
-4 44 23 10.9731 50 3.451
-3 41.5878 24 10.4736 51 3.3185
-2 39.8239 25 10 52 3.1918
-1 37.1988 26 9.5507 53 3.0707
0 35.2024 27 9.1245 54 2.959
1 33.3269 28 8.7198 55 2.8442
2 31.5635 29 8.3357 56 2.7382
3 29.9058 30 7.9708 57 2.6368
4 28.3459 31 7.6241 58 2.5397
5 26.8778 32 7.2946 59 2.4468
6 25.4954 33 6.9814 60 2.3577
7 24.1932 34 6.6835 61 2.2725
8 22.5662 35 6.4002 62 2.1907
9 21.8094 36 6.1306 63 2.1124
10 20.7184 37 5.8736 64 2.0373
11 19.6891 38 5.6296 65 1.9653
12 18.7177 39 5.3969 66 1.8963
13 17.8005 40 5.1752 67 1.830
14 16.9341 41 4.9639 68 1.7665
15 16.1156 42 4.7625 69 1.7055
16 15.3418 43 4.5705 70 1.6469
Loading...