Midea MSMBB-12CRDN1-MP0W, MSMBC-18CRDN1-MP0W, MSMBD-22CRDN1-MP5W Service Manual

Revision A: 1502250001, Content updated.
National Electrical Code NFPA70/ANSI C1-1993 or current edition and Canadian Electrical Code Part1 CSA C.22.1.
Installation or repairs made by unqualified persons can result in hazards to you and others.
Failure to carefully read and follow all instructions in this manual can result in equipment
SERVICE MANUAl
DC Inverter Air Conditioner
Table of Contents
1. Precaution
2. Part Names
3. Dimension
4. Refrigerant Cycle Diagram
5. Printed Circuit Board Connector Wiring Diagram of Outdoor Unit
6. Installation Details
7. Operation Characteristics
8. Electronic Function
9. Troubleshooting
10. Disassembly Instructions
Mini Split 3D
MSMBB-12CRDN1-MP0W MSMBC-18CRDN1-MP0W MSMBD-22CRDN1-MP5W
WARNING
Installation MUST conform with local building codes or, in the absence of local codes, with the
malfunction, property damage, personal injury and/or death.
Models:
This Manual Is For Qualified Service Engineer Use Only
1. Precaution
..................................................................................................................................................... 1
1.1 Safety Precaution .......................................................................................................................... 1
1.2 Warning .......................................................................................................................................... 1
2. Part Names
.................................................................................................................................................... 4
2.1 Model Names of Indoor/Outdoor units .......................................................................................... 4
2.2 Part names of Indoor/Outdoor units .............................................................................................. 5
3. Dimension
..................................................................................................................................................... 6
3.1 Indoor Unit ..................................................................................................................................... 6
3.2 Outdoor Unit................................................................................................................................... 8
4. Refrigerant Cycle Diagram
.......................................................................................................................... 9
5. Printed Circuit Board Connector Wiring Diagram of Outdoor unit
....................................................... 10
6 Installation Details
....................................................................................................................................... 12
6.1 Wrench torque sheet for installation ............................................................................................ 12
6.2 Connecting the cables ................................................................................................................. 12
6.3 Pipe length and the elevation ...................................................................................................... 12
6.4 Installation for the first time .......................................................................................................... 13
6.5 Adding the refrigerant after running the system for many years ................................................. 14
6.6 Procedure when servicing the indoor unit refrigeration circuit. .................................................. 14
6.7 Evacuation after servicing the outdoor unit refrigeration circuit. ................................................ 16
7. Operation Characteristics
......................................................................................................................... 18
8. Electronic function
..................................................................................................................................... 19
8.1 Abbreviation ................................................................................................................................. 19
8.2 Display function ........................................................................................................................... 19
8.3 Main Protection ............................................................................................................................ 20
8.4 Operation Modes and Functions ................................................................................................. 21
9. Troubleshooting
......................................................................................................................................... 26
9.1 Indoor Unit Error Display ............................................................................................................. 27
9.2 Outdoor unit error display ............................................................................................................ 28
9.3 Diagnosis and Solution ................................................................................................................ 31
10 Disassembly Instructions
......................................................................................................................... 56
10.1 Indoor unit .................................................................................................................................. 56
10.2 Outdoor unit ............................................................................................................................... 60
Table Of Contents
1
1. Precaution
1.1 Safety Precaution
n To prevent injury to the user or other
people and property damage, the following instructions must be followed.
n Incorrect operation due to ignoring
instruction will cause harm or damage.
n Before service the unit, be sure to
read this service manual at first.
1.2 Warning
Ø Installation
n Do not use a defective or underrated
circuit breaker. Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
n For electrical work, contact the dealer,
seller, a qualified electrician, or an authorized service center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
n Always ground the product.
There is risk of fire or electric shock.
n Install the panel and the cover of
control box securely.
There is risk of fire of electric shock.
n Always install a dedicated circuit and
breaker.
Improper wiring or installation may cause electric shock.
n Use the correctly rated breaker of
fuse.
There is risk of fire or electric shock.
n Do not modify or extend the power
cable.
There is risk of fire or electric shock.
n Do not install, remove, or reinstall the
unit by yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
n Be caution when unpacking and
installing the product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and evaporator.
n For installation, always contact the
dealer or an authorized service center.
n Do not install the product on a
defective installation stand.
n Be sure the installation area does not
deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
n Do not let the air conditioner run for a
long time when the humidity is very high and a door or a window is left open.
n Take care to ensure that power cable
could not be pulled out or damaged during operation.
There is risk of fire or electric shock.
n Do not place anything on the power
cable.
There is risk of fire or electric shock.
n Do not plug or unplug the power
supply plug during operation.
There is risk of fire or electric shock.
n Do not touch (operation) the product
with wet hands.
n Do not place a heater or other
appliance near the power cable.
There is risk of fire and electric shock.
n Do not allow water to run into
electrical parts.
It may cause fire, failure of the product, or electric shock.
n Do not store or use flammable gas or
combustible near the product.
There is risk of fire or failure of product.
n Do not use the product in a tightly
closed space for a long time.
Oxygen deficiency could occur.
n When flammable gas leaks, turn off
the gas and open a window for ventilation before turn the product on.
n If strange sounds or smoke comes
from product, turn the breaker off or disconnect the power supply cable.
2
There is risk of electric shock or fire.
n Stop operation and close the window
in storm or hurricane. If possible, remove the product from the window before the hurricane arrives.
There is risk of property damage, failure of product, or electric shock.
n Do not open the inlet grill of the
product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
There is risk of physical injury, electric shock, or product failure.
n When the product is soaked, contact
an authorized service center.
There is risk of fire or electric shock.
n Be caution that water could not enter
the product.
There is risk of fire, electric shock, or product damage.
n Ventilate the product from time to
time when operating it together with a stove etc.
There is risk of fire or electric shock.
n Turn the main power off when
cleaning or maintaining the product.
There is risk of electric shock.
n When the product is not be used for a
long time, disconnect the power supply plug or turn off the breaker.
There is risk of product damage or failure, or unintended operation.
n Take care to ensure that nobody
could step on or fall onto the outdoor unit.
This could result in personal injury and product damage.
Ø CAUTION
n Always check for gas (refrigerant)
leakage after installation or repair of product.
Low refrigerant levels may cause failure of product.
n Install the drain hose to ensure that
water is drained away properly.
A bad connection may cause water leakage.
n Keep level even when installing the
product.
It can avoid vibration of water leakage.
n Do not install the product where the
noise or hot air from the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
n Use two or more people to lift and
transport the product.
n Do not install the product where it will
be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Ø Operational
n Do not expose the skin directly to
cool air for long time. (Do not sit in the draft).
n Do not use the product for special
purposes, such as preserving foods, works of art etc. It is a consumer air conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
n Do not block the inlet or outlet of air
flow.
n Use a soft cloth to clean. Do not use
harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
n Do not touch the metal parts of the
product when removing the air filter. They are very sharp.
n Do not step on or put anything on the
product. (outdoor units)
n Always insert the filter securely.
Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
n Do not insert hands or other objects
through air inlet or outlet while the product is operated.
n Do not drink the water drained from
the product.
3
n Use a firm stool or ladder when
cleaning or maintaining the product.
Be careful and avoid personal injury.
n Replace the all batteries in the remote
control with new ones of the same type. Do not mix old and new batteries or different types of batteries.
There is risk of fire or explosion.
n Do not recharge or disassemble the
batteries. Do not dispose of batteries in a fire.
They may burn of explode.
n If the liquid from the batteries gets
onto your skin or clothes, wash it well with clean water. Do not use the remote of the batteries have leaked.
4
2. Part Names
2.1 Model Names of Indoor/Outdoor units
Series
Capacity Indoor units
Outdoor units
Inverter
12k MSMBB-12CRDN1-MP0W MOB1-12CDN1-MP0W 18k MSMBC-18CRDN1-MP0W MOC-18CDN1-MP0W 22k MSMBD-22CRDN1-MP5W MOF1-22CDN1-MP5W
5
2.2 Part names of Indoor/Outdoor units
6
3. Dimension
3.1 Indoor Unit
Model W D H
MSMBB-12CRDN1-MP0W
810 mm
(31.89in)
200 mm
(7.87in)
300 mm
(11.81in)
MSMBC-18CRDN1-MP0W
980 mm
(38.58in)
225 mm
(8.86in)
325 mm
(12.80in)
MSMBD-22CRDN1-MP5W
1090 mm
(42.91in)
235 mm
(9.25in)
338 mm
(13.31in)
7
For MSMBB-12CRDN1-MP0W,
For MSMBC-18CRDN1-MP0W,
For MSMBD-22CRDN1-MP5W,
8
3.2 Outdoor Unit
More than 60cm(23.6in)
More than 70cm(27.6in)
More than 30cm(11.8in)
More than 60cm(23.6in) (Service space)
Fence or
obstacles
More than 30cm(11.8in)
Note: The above drawing is only for reference. The appearance of your units may be different.
Model W D H W1 A B
MOB1-12CDN1-MP0W
780mm (30.7in)
250mm
(9.8in)
540mm (21.3in)
843mm (33.2in)
549mm (21.6in)
276mm (10.9in)
MOC-18CDN1-MP0W
760 mm
(29.92in)
285 mm
(11.22in)
590 mm
(23.23in)
823 mm
(32.4in)
530 mm
(50.87in)
290 mm
(11.42in)
MOF1-22CDN1-MP5W
845mm (33.3in)
320mm (12.6in)
700mm (27.6in)
908mm (35.7in)
560mm (22.0in)
335mm (13.2in)
9
4. Refrigerant Cycle Diagram
For cooling only models,
INDOOR
OUTDOOR
LIQUID SIDE
GAS SIDE
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
CAPILIARY TUBE
10
5. Printed Circuit Board Connector Wiring Diagram of Outdoor unit
MOB1-12CDN1-MP0W,
U
V
W
T3-TipeT4-OutDoorTP
PFC-1310
202302130949 CE-KFR26W/BP2(MDY02+1243).D.13.WP2-1
[1.4]2014.02.20
HF
LF
IC2
IC6 PC851
IC5PC817
CN27
FAN_C
CN26 FAN_C
BR2
HS3
OCP1
COM1
HIN1
VB1
HS1
FO2
OCP2
FO1
LS1
U
LS2
V
LS3
W
VBB
VCC3
VB3
COM3
LIN3
OCP3
FO3
HS2
VB2
VCC2
HIN2
COM2
LIN2
VCC1
LIN1
HIN3
IPM1
BR1
PTC1
CN2
CN1
CN8
CN7
CN21
+
LED1 Yellow
C6
R33 R16
C23
C7
L1
RY1
D3
D1
E8
R67
R66R61
R57R56
R53
R4
C9
CN19AC_FAN
D4
C28
C18
R77
D5
C54
R65
R64
R5
C52
ZR2
ZR1
RY5
RY4
RY3
RY2
R58
R55R47
R46
R45
R44
R43
R42
R39
R36
R35
R32
R31
R30 R29
R21
R19
R18
R17
R15
R14
R11
R10
R9
R8
R7
R6
R2
Q1
IC7
IC1
FUSE1T20A/250VAC
E17
E21
E15
E12E9
+
+
E6
DSA1
D7
D6
D2
C49
C42
C41
C40
C39
C38
C36
C35
C33
C31
C30
C26
C25
C24
C22
C20
C16
C15
C14
C13
C12
C11
C10
C3
C2
C1
IC8
+
-
~~
SSR1
E1
E4
E5
R59
R12
C27
E2
R78
E3
T1
C29
IC10
CN22
CN14 TestPort
C32 C34
C58
C61
C62
C63
C76
C77
C85
C89
C90
C91
C98
C100
C108
C113
C71C51
C148
CN28E2-Burning
CN29Simulation
D13
D14
E11
E13
E10
IC4-1
L3
R24
R25
R26
R27
R28
R60
R63
R82
R83
R84
R85
R86R87
R88
R89
R90
R92
R94
R96
R97
R99
R101R103
R105
R111
R118
R122
R129 R20
R48
R51
R49
R50
R145
R146
C37
C70
C80
R13
E16
R3
R37
R38
R79
R91
C8
C17
R40
R41
R1
C82 C83
IC9
IC4
D9
R54
CN9
Earth
LED2RED
R23
CN42
CompTop
C21
C19
R34
C5
C45
C46
CN60
CN11
4-WAY-L
CN12
4-WAY-N
CN23
N-IN
CN24
L-IN
CN25
S
CN20
C4
R52
C43
C44
C81
R22
D8
X1
DZ1DZ4
DZ5
DZ2
IC3
C47
C48
DZ3
connect to the terminal
CN24(L-IN)-CN23(N-IN)
208-230V AC
power supply
when 4-way is ON, output 208-230VAC
connect to the 4-WAY
CN12 CN11
when heater is ON, output 208-230VAC
CN60
connect to compressor heater
3-4 0VAC / 208-230VAC (high speed running)
5
4
3
2
1
connect to outdoor AC FAN
CN19
2-4 0VAC / 208-230VAC (low speed Running)
1
2
3
4
5
CN27 CN26
AC FAN-CAPACITOR
208-230VAC
CN20
CN1
connect TO REACTOR 2-10V AC(standby); 30-150V AC(running);
connect to the compressor 0VAC (standby) 10-200VAC (running)
W
V
U
CN22
room temp sensor(3-4) RT pipe temp sensor(1-2) RT
Exaust temp sensor(5-6) RT
123546
NO USE
CN29
NO USE
CN28
210-300VDC (Running)
CAPACITOR Voltage
290-330VDC (standby)
+-
LED1
CN14
connect to detector
test port
MOC-18CDN1-MP0W
11
MOF1-22CDN1-MP5W
12
6 Installation Details
6.1 Wrench torque sheet for installation
Outside diameter Torque
Additional tightening
torque
Ф6.35mm 1/4in 1500N.cm(153kgf.cm) 1600N.cm(163kgf.cm)
Ф9.52mm 3/8in 2500N.cm(255kgf.cm) 2600N.cm(265kgf.cm)
Ф12.7mm 1/2in 3500N.cm(357kgf.cm) 3600N.cm(367kgf.cm)
Ф15.9mm 5/8in 4500N.cm(459kgf.cm) 4700N.cm(479kgf.cm)
Ф19mm 3/4in 6500N.cm(663kgf.cm) 6700N.cm(683kgf.cm)
6.2 Connecting the cables
The power cord should be selected according to the following specifications sheet.
Appliance Amps AWG Wire Size
10 18 13 16 18 14 25 12 30 10
The cable size and the current of the fuse or switch are determined by the maximum current indicated on the nameplate which located on the side panel of the unit. Please refer to the nameplate before selecting the cable, fuse and switch.
6.3 Pipe length and the elevation
Models
Pipe size
Gas Liquid
MSMBB-12CRDN1-MP0W+MOB1-12CDN1-M P0W
3/8in
(Ф9.52mm)
1/4in
(Ф6.35mm)
MSMBC-18CRDN1-MP0W+MOC-18CDN1-M P0W
1/2in
(Ф12.7mm)
1/4in
(Ф6.35mm)
MSMBD-22CRDN1-MP5W+MOF1-22CDN1-
M P5W
5/8in
(Ф15.9mm)
3/8in
(Ф9.52mm)
Models
Standa
rd
length
Max.
Elevation
Max.
Length
A
Additional
refrigerant
MSMBB-12CRDN1-MP0W+ MOB1-12CDN1-M P0W
7.5m
(24.6ft)
10m
(32.8ft)
25m
(82.0ft)
15g/m
(0.16oz/ft)
MSMBC-18CRDN1-MP0W+ MOC-18CDN1-M P0W
7.5m
(24.6ft)
20m
(65.6ft)
30m
(98.4ft)
15g/m
(0.16oz/ft)
MSMBD-22CRDN1-MP5 W+MOF1-22CDN1-M P5W
7.5m
(24.6ft)
20m
(65.6ft)
30m
(98.4ft)
30g/m
(0.32oz/ft)
13
6.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may
freeze and block capillary tubing.
Water when mixed with the refrigerant and oil
will create an acid that will damage the motor windings and components in the refrigerant
system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested and evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit Connections with a soft brush to check for leakage of the connecting points of the piping. If bubbles come out, the pipes have leakage.
1. Air purging with vacuum pump
1) Completely tighten the flare nuts of the
indoor and outdoor units, confirm that both the 2-way and 3-way valves are set to the
Front seated.
2) Connect the low pressure gauge to the 3 way
service valve access port..
3) Connect the middle hose of the gauge
manifold (usually yellow) to the vacuum pump.
4) Fully open the handle for the low pressure
gauge..
5) Start the vacuum pump and operate according
to manufacture spec's.
6) Perform an evacuation for a minimum of 30 minutes and check that the low pressure (compound) gauge indicates a vacuum of 29.9 in/hg (500 microns) A vacuum gauge should be used if available. If the proper vacuum cannot be achieved the vacuum pump should be run for an additional 20 minutes. If after the additional 20 minutes the vacuum still cannot be achieved the is a leak in the system and must be located and repaired. follow the leak checking procedure as mentioned before. If the vacuum is achieved, close the low pressure gauge handle off and shut the vacuum pump off. Recheck the reading after 10 minutes, the vacuum may change slightly, this is normal.
7) The system is now dry and free of
contaminates, refrigerant pressure should now be added to the system from a source other than the system before opening the 2 way and 3 way valves for system operation.
8) The 2 way and 3 way valve can now be
opened for the system operation
2. Air purging by refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way
valves are set to the closed position.
2). With a container of refrigerant and a gauge
manifold set, connect the low pressure gauge hose
14
to the 3 way valve service port and a charging
cylinder to the service port of the 3-way valve.
3). Open the valve on the refrigerant container and
the low pressure gauge to allow the refrigerant to enter the system, next loosen the flare connection on the 2 way valve line to purge the air and contaminants from the system for 30 to 50 seconds, then retighten the connection.
4). Next allow the pressure from the refrigerant to
reach 100 psi and then close the low pressure gauge and the refrigerant container and check the 2 way and 3 way valve line connections for leaks with liquid soap or electronic leak detector.
5). After the system has been check for leaks the
pressure should be adjusted to about 25 to 50 psi.
6). You can now disconnect the gauge manifold
and refrigerant container from the system and open the 2 way and 3 way valves for system operation
7). Mount the valve stems nuts and the service port cap. Be sure to use a torque wrench to tighten the service port cap to a torque 18N·m(13.27 ft.lbs). Be sure to check the gas leakage.
6.5 Adding the refrigerant after running the system for many years
Procedure
1). 1st step; Connect the low pressure gauge from
the gauge manifold set to the 3 way service valve (this is the blue hose on most sets) 2nd step; Connect the middle hose from the manifold set to the refrigerant container (this is the yellow line on most sets). with refrigerant 410A the container must be inverted (upside down) when adding the refrigerant. Note that the 2 way and 3 way valves
must be in the open position. 3rd step; the air in the gauge hoses needs to be purged out. use the pressure from the system to purge the low side line, loosen the connection on the manifold for a second, next open the to valve on the refrigerant container to pressurize the line, now loosen that hose at the manifold for a second and purge that line.
3) Next step is to set the refrigerant container on
an electronic charging scale and record the weight or zero the scale depending on the scale used. Next determine the refrigerant charge to be added.
4) Start the unit in the cooling mode and lower the
set point so the unit wont shut off during the charging procedure.
5) Refrigerant can now be added to the system,
open the low pressure valve on the gauge manifold set to start charging the unit with liquid refrigerant, keep track of the refrigerant being added to the system (do not overcharge the system)
6). Once the correct charge has been added to the
system close the low pressure valve on the gauge manifold set and record the operating pressure. The system is now charged and the unit can be shut off. Close the valve on the refrigerant container and disconnect the hose from the manifold set, also disconnect the hose from the 3 way valve and replace and torque all caps.
7). Mount the valve stem caps and the service
port Use torque wrench to tighten the service port cap to a torque of 18N.m(13.27 ft,lbs).
Always leak check after servicing the refrigerant system.
6.6 Procedure when servicing the indoor
unit refrigeration circuit.
1. Pumping down the system (isolating the
refrigerant charge in the condensing unit)
15
Procedure
1). With the unit in the cooling mode and a low set
point remove all caps from the 3 way and 2 way valves, next attach the low pressure gauge to the 3 way service valve port and purge the air from that hose by loosening the hose at the manifold for a second, be sure the low pressure gauge valve is closed. be sure to record the operating pressure, you will need to know this when you complete the service on the indoor unit and restart the system. Now prepare to close both valves on the unit starting with the 2 way valve (this is called front seating the valve) also prepare to shut the power off to the outdoor unit.
2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose. Open the handle Lo valve of the manifold valve slightly to purge air from the charge hose for 5 seconds and then close it quickly.
4). Now close the 2 way valve and monitor the low
pressure gauge. the pressure will start to drop.
5). Operate the unit in the cooling mode and
disconnect the power to the outdoor unit when the low side gauge reads a slight vacuum, running the compressor in a vacuum could damage the motor windings. Note that units with extended lines and additional refrigerant charge may not be able to achieve a vacuum, this is because the outdoor unit can only store a certain amount of refrigerant, this is normal (the amperage of the compressor will have to be monitored in this case) Stop compressor when the amperage approaches the name plate FLA rating indicates 0.1Mpa(14.5Psi).
6). Now close the 3 way valve right away. the
pressure will rise during this time, this is normal. There will be some pressure left in the system this is normal, The indoor unit is now ready to be serviced.
Disconnect the charge set, and tighten the 2-way and 3-way valves stem nuts. Use a torque wrench to tighten the 3-way valves service port cap to a torque of 18N.m(= 13.27
ft.lbs).
Be sure to check for gas leakage.
2. Sweeping (air purging) the system with
refrigerant after the service to the refrigerant circuit of the indoor unit is complete.
Procedure:
Sweeping the system can be used when the unit has been pumped down, this eliminates the need to loosen the flare connection on the 2 way valve (loosening and retightening flare connections could cause a refrigerant leak)
1). Confirm that both the 2-way and 3-way
valves are set to the closed position.
2). Connect the charge set and a charging
cylinder to the service port of the 3-way valve Leave the valve on the Refrigerant container.
3). Do not loosen the flare connection, Start with
the hose from the low pressure gauge that has been connected to the 3 way valve service port and loosen it at the gauge manifold connection, next open the 2 way valve 1/2 half of a turn (this will release the refrigerant that has been isolated in the outdoor unit) The refrigerant will travel thru the small refrigerant line and evaporator coil in the indoor unit and back out the low pressure hose that has been loosened let the refrigerant sweep for about 50 seconds, this will push and remove
16
any air moisture and noncodensables from the refrigeration circuit. After 50 seconds has passed tighten the hose on the low pressure gauge. The sweep is now complete. Next step, open the 2 way valve all the way then the 3 way valve all the way and check for leaks.
4). Next step, Start the unit in the cooling mode
and check the pressure (remember the pressure you recorded?) The unit is going to be low on refrigerant from the sweeping process, add refrigerant as needed from the refrigerant container in the liquid state to achieve the operating pressure that you recorded. The process is now complete.
Check the flare connections for gas leakage.
5). Discharge the refrigerant. Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the 2-way valve approximately 45 until the gauge indicates 0.3Mpa(43.5Psi) to 0.5
Mpa(72.5Psi).
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open position Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m. Be sure to check the gas leakage.
6.7 Evacuation after servicing the outdoor
unit refrigeration circuit.
1. Evacuation of the complete refrigeration
circuit, Indoor and outdoor unit.
Procedure:
1). Confirm that both the 2-way and 3-way
valves are set to the opened position.
2). Connect the vacuum pump to 3-way valves
service port.
3). Evacuation for approximately one hour.
Confirm that the compound meter indicates
-0.1Mpa(14.5Psi), 500 Microns / 29.9 in,hg.
4). Close the valve (Low side) on the charge set,
turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the
vacuum pump.
2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging
cylinder, open the 2-way valve and the 3-way valve Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic
scale and record the weight.
4). Open the valves (Low side) on the charge
set and charge the system with liquid refrigerant If the system cannot be charge with the specified amount of refrigerant, or can be
17
charged with a little at a time (approximately 150g each time) , operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure.
5).When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way valves service port immediately If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose.
6). Mounted the valve stem caps and the service port. Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.
18
7. Operation Characteristics
Temperature
Mode
Cooling operation Heating operation Drying operation
Room temperature
17℃~32
(62℉~90)
0℃~30
(32℉~86)
10℃~32
(50℉~90)
Outdoor temperature
0°C50°C
(32°F122°F)
-15°C30°C (5°F86°F)
0°C50°C
(32°F122°F)
-15°C50°C
(5°F122°F)
(For the models with
low temperature cooling system)
!"(#)
$
+32
CAUTION:
1. If the air conditioner is used beyond the above conditions, certain safety protection features may
come into operation and cause the unit to operate abnormally.
2. The room relative humidity should be less than 80%. If the air conditioner operates beyond this figure, the surface of the air conditioner may attract condensation. Please set the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode.
3. The optimum performance will be achieved during this operating temperature zone.
19
8. Electronic function
8.1 Abbreviation
T1: Indoor room temperature T2: Coil temperature of evaporator T3: Coil temperature of condenser T4: Outdoor ambient temperature T5: Compressor discharge temperature
8.2 Display function
8.2.1 Icon explanation on indoor display board.
Digital display: Displays the temperature settings when the air conditioner is operational. Displays the room temperature in FAN mode. Displays the self-diagnostic codes.
Dispalys ’ for three seconds when Timer ON, Fresh, Swing, Turbo or Silence feature is activated.
Dispalys ’ for three seconds when Timer OFF is set.
Dispalys for three seconds when Fresh, Swing, Turbo or Silence feature is cancelled.
Dispalys under deforsting operation.
Dispalys when anti-cold air feature is activated under heating mode.
Dispalys during self clean operation (if aplicable).
Dispalys under 8 heating operation (if aplicable). When ECO function(optional) is actived,the
illuminates gradually one by one as
In one second interval.
WIFI control display(optional) Displays when the WIFI control feature is acticated.(Not available when the unit does not have this function)
NOTE: A guide on using the infrared remotr is included in this literature package.
Loading...
+ 49 hidden pages