8.1.4 Indoor fan normal working amp is less than 1A,
8.1.5 Outdoor fan. Normal working amp is less than 1.5A
8.1.6 Four-way valve normal working amp is less than 1A.
8.1.7 Swing motor: DC12V.
8.1.8 Compressor: single-phase power supply. Its normal working amp is less than 15A
8.2 Proper symbols and their meanings:
TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
: Self-protection amp of compressor, continue three seconds until turns off the compressor.
I
3sec
: Self-protection amp of compressor, continue five minutes until turns off the compressor.
I
5MIN
: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.
I
FAN
I
RESTORE
TH
TM
TL
: Amp self-protection return value
DEFROST
DEFROST
DEFROST
: High wind, defrosting temperature difference
: Middle wind, defrosting temperature difference
: Low wind, defrosting temperature difference
TE1: Anti-cold wind, from Fan Off to Breeze temperature
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature
8.3 Functions
Remote receiving
Testing and forced running
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
Anti frozen at cooling mode
25
8.4 Protection
8.4.1 3 minutes delay at restart for compressor.
8.4.2 Sensor protection at open circuit and breaking disconnection
8.4.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or
too low(lower than 400RPM), the unit stops and LED displays failure information and can’t returns to
normal operation automatically.
8.4.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED
displays failure information and can’t returns to normal operation automatically.
8.4.5 The current protection of the compressor
Condition Indoor fan Compressor Outdoor fan Remark
Current up
Current down
I< I
RESTORE
I
FAN
I
5MIN
I
5MIN
I
FAN
RESTORE
I< I
On On On
RESTORE
<I< I
FAN
<I<I
Off Off After 5 Minutes
5MIN
<I< I
Off Off After 3 Seconds
3SEC
<I< I
Off Off After 3 Seconds
3SEC
<I<I
Off Off After 5 Minutes
5MIN
<I< I
FAN
On On On
RESTORE
On On Off Heating mode I
Low speed On On Cooling mode
On On Off Heating mode I
Low speed On On Cooling mode
If compressor turns off for continuously 4 times due to current protection in 5 minutes from
Compressor On, the unit stops and LED displays failure information and can’t returns to normal
operation automatically.
8.5 Fan-only mode
Fan speed is high/mid/low/ Auto
8.6 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:
Condition
T=Indoor Temp.
Compressor Outdoor fan
Ts= S e t t i n g Tem p .
T> Ts+1 On On Room temp. up
T<Ts+1 Off Off
T> Ts On On Room temp. down
T<Ts Off Off
Auto fan at cooling mode:
Condition
T=Indoor Temp.-Setting Temp.
Room temp. up
T<4℃ Low
4℃<T<5℃ Med.
T>5℃ High
Room temp. down
T> 4℃ High
1<T<℃4℃ Med.
T<1℃ Low
26
Indoor fan speed
Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )
Evaporator Temp. up
Evaporator Temp. down
Condition
Temp. Time
T> TE6 On On
T< TE6 >5 Minutes Off Off
T> TE5 On On
T< TE5 >5 Minutes Off Off
Compressor Outdoor fan
8.7 Dehumidifying mode
8.7.1 The 4-way valve is off in dehumidifying mode
8.7.2 Compressor and Indoor Fan actions in dehumidifying mode
NO Conditions Indoor Fan Compressor and Outdoor Fan
1 TA ≥ TS+2
2 TS ≤TA <TS+ 2
3 TA < TS
LOW
BREEZE
LOW
BREEZE
LOW
BREEZE
ON 6minutes
OFF 4minutes
ON 5minutes
OFF 5minutes
ON 4minutes
OFF 6minutes
Repeat on and off cycle.
27
8.7.3 Low room temperature protection:
When room temperature decreases to below 10℃, compressor and outdoor fan will stop(indoor fan
is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13℃.
8.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that
of cooling mode.
8.7.5 At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode.
8.8 Heating mode
8.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve
must delay 2 minutes compared with compressor if the compressor changed into non-heating mode
or turned off. 4-way valve doesn't delay in dehumidifying mode.
8.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except
for the defrosting mode or the end of defrost.
8.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes
after starting and then judge temperature. Meanwhile other protections are still valid.
Condition Compressor Outdoor fan
T> Ts+3* Off Off Room temp. up
T<Ts+3* On On
T< Ts+2* On On Room temp. down
T>Ts+2* Off Off
* This parameter can be changed from 0 to 3.
8.8.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind
function prevails.
Optional 1:
Anti-cold wind control function at heating mode
Condition
T= Indoor exchanger temp.
Indoor exchanger temp. up
Indoor exchanger temp. down
T<TE1 Off
TE1<T<TE2 Breeze
T>TE2 Setting fan speed
T> TE3 Setting fan speed
TE3<T<TE4 Breeze
T<TE4 Off
Indoor fan speed
Option 2:
Indoor fan changes breeze when compressor stop, after 127 second, indoor fan stop.
8.8.5 Auto wind at heating mode
Condition
T=Indoor Temp.-Setting Temp.
T<2℃ High Room temp. up
T>2℃ Med.
T> 0℃ Med. Room temp. down
T<0℃ High
Indoor fan speed
28
8.8.6 Indoor evaporator high-temperature protection at heating mode
Condition
T= Indoor exchanger temp.
Indoor exchanger temp. up
T<TE8 On On
TE8<T<TE7 On Off
T>TE7 Off Off
T>TE9 Off Off Indoor exchanger temp. down
T<TE9 On On
8.8.7. The louver opens to Standard Angle ANGLHEAT when power is on for the first time
8.9 Defrosting operation (Available for heating only).
8.9.1 Defrosting condition: Defrosting starts when either of the following ①&②: ① A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:
℃
Fan speed is high ≤TH
Fan speed is mid ≤TM
Fan speed is low ≤TL
Breeze Meet only if it is Breeze
Temp. of evaporator---room temp.
Compressor Outdoor fan
DEFROST
DEFROST
DEFROST
② Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor fan
with the compressor still running. Add up to 90 minutes.
8.9.2 Defrosting time
(a) For defrosting condition ① leading to frost——both condition A and B are satisfied, if B is
satisfied before A, this can be regarded as severe frosting, and the defrosting time is 10 minutes,
or the defrosting time is 7.5 minutes.
(b) For defrosting condition ② leading to frost, the defrosting time is 10 minutes.
(c) For any case leading to frost, if A/C defrosts for 7.5 minutes three times, the forth defrosting time is
If one of following conditions is satisfied, end the defrost and turn into heating mode:
A. The defrost time has reached to 7.5 or 10 minutes.
B. The compressor current has reached to I
DEFROST
or above, I
DEROST
differs in different models.
29
8.9.4 Defrosting Actions:
45S 25S
Compressor
4-way Valve 23S
40S
Outdoor Fan
Indoor Fan
10S
Defrost 10or 6minutes
8.10 Automatic operation mode
8.10.1 The air conditioner automatically selects one of the following operation modes: cooling, heating or
fan only according to the temp. difference between room temp. (TA) and set temp. (TS).
TA—TS Operation mode
TA—TS>2℃ Cooling
-1 ≤TA℃-TS≤+2℃ Fan-only
TA-TS<-1℃Heating (air-only for cooling only type)
8.10.2 The indoor fan blows automatically in corresponding selected mode.
8.10.3 The motion of indoor fan’s blade should accord with the selected operation mode.
8.10.4 One mode should be carried out for at least 15 minutes once selected. If the compressor cannot
start for 15 minutes, reselect the operation mode according to the room temp. and set temp., or
reselect when the set temp. varies.
8.11 Forced cooling function
8.11.1 Select forced cooling function with the forced cooling button or the switch.
8.11.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan mode is
set as low, the A/C operates at the DRY mode with a set temp. of 24℃.
8.11.3 All protections of remote control cooling are available at forced cooling operation.
8.12 Forced Auto function
Select forced auto function with the forced auto button or the switch.
In forced auto status the A/C operates at remote control mode with a set temp. of 24℃.
8.13 Timer Function
8.14 Sleep mode
8.14.1 The sleep function is available at cooling, heating or auto mode.
8.14.2 Cooling:
The set temperature rise 1℃ per hour. Two hours later, the set temperature will maintain as a
30
constant and the fan speed is kept at low speed.
The total time is 7 hours, after 7 hours the unit stops.
8.14.3 Heating:
The set temperature decrease 1℃ per hour. Two hours later, the set temperature will maintain as a
constant and the air circulation is kept at low speed (Cold air proof function takes precedence over
all).
The total time is 7 hours, after 7 hours the unit stops.
8.14.4 Auto:
The economic running function operates in accordance with selected running mode by auto mode.
The total time is 7 hours, after 7 hours the unit stops.
8.15 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings before
the power failure when power returns.
8.16 PLASMA ( optional):
Starts with indoor fan.
Note: Plasma and Anion can be use together.
8.17 Anion (optional)
Starts with indoor fan.
Note: Plasma and Anion can be use together.
31
A
A
A
A
A
A
8.18 Models and Parameters
Model MSC-07CRN1MSC-07HRN1MSC-09CRN1MSC-09HRN1MSC-12CRN1 MSC-12HRN1
I3SEC 7.5A 7.5A 10.0A 10.0A12.0A 12.0A
I5MIN 6.2A 6.2A 7.5A 7.5A8.5A 8.5A
IFAN 5.2A 5.2A 5.5
IRESTORE 4.2A 4.2A 4.5A4.5A6.5A 6.5
IDEFROST 3.2A 3.5A5.0
TE1 28℃ 28℃ 34℃
TE2 32℃ 32℃ 37℃
TE3 30℃ 30℃ 33℃
TE4 26℃ 26℃ 22℃
TE5 4℃ 4℃ 4℃4℃3℃ 3℃
TE6 10℃ 10℃ 10℃10℃10℃ 10℃
TE7 60℃ 60℃ 63℃
TE8 53℃ 53℃ 53℃
TE9 50℃ 50℃ 50℃
NGLCOOL 200° 200° 200° 200° 155° 155°
NGLHEAT 0° 0°10°
NGLOFF 124° 124° 124° 124° 124° 124°
TH
TM
TL
17°C 17°C
18°C 18°C
19°C 19°C
5.5A 7.5A 7.5A
20°C
23°C
26°C
32
9.Troubleshooting
.
9.1 Display board
Signal receptor
5
4
1
AUTO indicator
1223
This indicator illuminates when the air conditioner is in AUTO operation.
This indicator illuminates when the air conditioner starts defrosting automatically or
when the warm air control feature is activated in heating oper ation.
3
TE MPER ATUR E ind i ca t or
Displays the temperature settings when the air conditioner is operational.
4
O P E R AT ION i n di cato r
This indicator flashes after power is on and illuminates when the unit is in operation.
TIMER indicator
5
This indicator il luminates when TIMER is set ON/OFF
9.2 Malfunction display
Failure phenomenon Operation lamp Timer lamp
Indoor fan speed has been out of control for over 1 minute
Indoor room temp. or evaporator sensor is open circuit or short circuit
Over current protection of the compressor occurs 4 tim es X
EEROM error On
No over-zero signal
☆
☆
☆ ☆
X
On
☆
☆
r Extinguish
☆ Flash at 5Hz
33
9.3 Diagnostic Chart
9.3.1 After energizing, no indicator is lighted and the air conditioner can’t be operated.
After energizing, the air conditioner can’t be operated
Check if AC220V power supply outputs to Indoor PCB.
Ye s
Check if AC220V exists at the prim ary coil of transformer.
Ye sNo
Indoor PCB is defective
Check if AC14.5V exists at the secondary coil of transformer.
No Yes
Yes
Take off the secondary plug of transformer, and then check if
AC14.5V exists at the secondary coil of transformer.
No
The transformer is defective. Indoor PCB is defective
9.3.2 Resetting phenomenon often occurs during operation. (That is automatically entering to the status when
power is on.)
The reason is that the instantaneous voltage of main chip is less than 4.5V. Check according to the following procedure:
Resetting phenomenon often occurs during operation.
Ye s
After changing Indoor PCB, check if the failure releases.
NoYes
After changing indoor fan motor, check if the failure releases.
Indoor PCB is defective
No
Power supply circuit has problems.
34
9.3.3 Failure phenomenon
Failure phenomenon Operation lamp Timer lamp
Indoor fan speed has been out of control for over 1 minute
Indoor room temp. or evaporator sensor is open circuit or short circuit
Over current protection of the compressor occurs 4 tim es X
EEROM error On
No over-zero signal
r Extinguish
☆ Flash at 5Hz
☆
☆
☆ ☆
X
On
☆
☆
9.3.3.1 Operation lamp flashes and Timer lamp off.
Is connector connection good?
No Yes
Is voltage being applied to the fan motor?
Repair the connector
Yes No
Fan motor is defective
Indoor PCB is defective
9.3.3.2 Operation lamp flashes and Timer lamp on.
Is connection to connector good?
Yes
Replace the sensor
No
Repair connector
9.3.3.3 Operation lamp off and Timer lamp flashes
Operation lamp off and Timer lam p flashes
After changing the main control board, check if the failure releases.
Yes
No Yes
The voltage of power supply is too low (less than 187V)?
Indoor PCB is defective
Ye sNo
Power supply fault Outdoor unit fault (such as the compressor)