GD Midea Refrigeration Equipment Co. Ltd                  Service manual for K portable Series 
6 
No power  Check voltage at electrical outlet. Correct if none. 
Water alarm  Check and correct if water alarm happens. 
Power supply cord 
Check voltage at the power cord terminal on Main PCB. Replace 
the power cord if none.
Transformer (Discharge 
transformer before testing)
Check resistance between the two input/output lines on 
transformer. Replace the transformer if either of the input/output 
is open or the transformer is damaged. 
Wire disconnected or 
connection loose
Connect wire. Refer to wiring diagram for terminal identification. 
Repair or replace loose terminal. 
Main PCB failure 
Select fan speed and Check the voltage on main PCB. Replace 
the main PCB if no voltage in anyone.
Capacitor (Discharge 
capacitor before testing)
Test capacitor.                       
Replace if not within +/-10% of manufacture's rating. Replace if 
shorted, open or damaged.
Fan motor will not 
run. 
Will not rotate
Fan blower hitting scroll. Realign assembly.           
Check fan motor bearings. Replace the motor if motor shaft do 
not rotate.
Fan blower 
Replace the fan blower if cracked, out of balance, or partially 
missing. 
Loose screws  Tighten them. 
Fan motor noise. 
Worn bearings 
Replace the motor if knocking sounds continue when running or 
loose, or the motor hums or noise appears to be internal while 
running. 
Voltage  Check voltage. Call Supply Authority if not within limits. 
Wiring 
Check the wire connections, if loose, repair or replace the 
terminal. If wires are off, refer to wiring diagram for identification, 
and replace. Check wire locations. If not per wiring diagram, 
correct. 
Main PCB failure  Check voltage of main PCB. Replace the main PCB if open. 
Capacitor (Discharge 
capacitor before testing)
Check the capacitor.                     
Replace if not within +/-10% of manufacturers rating. Replace if 
shorted, open, or damaged. 
Room temp sensor 
Check the temperature setting if not at the coolest (in cooling 
mode) or the warmest (in heating mode). Set it if not. 
Compressor will not 
run while fan motor 
runs. 
Compressor
Check the compressor for open circuit or ground. If open or 
grounded, replace the compressor.
Excessive noise.  Copper tubing 
Remove the cabinet and carefully rearrange tubing not to contact 
cabinet, compressor, shroud and barrier. 
Water tank full  Check and pour if the water tank is full. 
Water depth sensor if failure Check and replace if failure.  
Water pump failure  Check and replace if the pump if failure.  
Water depth is over load in 
chassis
Check and drainage the water in the chassis by open the 
drainage hose on the chassis.
Water full alarm 
Water depth sensing 
structure 
Check and replace or realign if the structure is failure.