Midea MLCAC-UTSM-2010-10, MOUB-36HDN1-R, MOU-48HDN1, MOUB-48HDN1-R, MOUB-36HDN1-Q Service Manual

MIDEA LCAC
50Hz R410A DC Inverter
Service Manual
2011
MLCAC-UTSM-2010-10 Contents
Part 1 General Information ................................................................................................. 1
Part 2 Indoor Units .............................................................................................................. 6
Part 3 Outdoor Units ......................................................................................................... 67
Part 4 Installation .............................................................................................................. 96
Part 5 Control ................................................................................................................... 107
The specifications, designs, and information in this book are subject to change without notice for product improvement.
Contents i
MLCAC-UTSM-2010-10 General Information
Part 1
General Information
1. Model Names of Indoor/Outdoor Units ........................... 2
2. External Appearance ........................................................ 3
2.1 Indoor Units ................................................................................. 3
2.2 Outdoor Units .............................................................................. 3
3. Nomenclature .................................................................... 4
4. Features ............................................................................. 5
General Information 1
Model Names of Indoor/Outdoor Units MLCAC-UTSM-2010-10
Model Names of Indoor/Outdoor Units
1.1 Indoor Units
R410A (capacity multiplied by 1000Btu/h)
Type Function 36 48 Four-way cassette Cooling and heating Duct Cooling and heating Ceiling & floor Cooling and heating
1.2 Outdoor Units
Model of outdoor unit and corresponding indoor unit
Universal Outdoor unit Model Compressor type Compressor Brand Matched indoor units
MOUB-36HDN1-Q Rotary DC Inverter GUANGZHOU MITSUBISHI
MOUB-36HDN1-R Rotary DC Inverter GUANGZHOU MITSUBISHI
MOU-48HDN1 Rotary DC Inverter GUANGZHOU MITSUBISHI
MOUB-48HDN1-R Rotary DC Inverter GUANGZHOU MITSUBISHI
MTB-36HWDN1 MUB-36HRDN1 MCC-36HRDN1
MTB-48HWDN1 MUB-48HRDN1 MCC-48HRDN1
2 General Information
MLCAC-UTSM-2010-10 External Appearance
External Appearance
2.1 Indoor Units
Duct
Ceiling & Floor
Four-way Cassette
2.2 Outdoor Units
MOUB-36HDN1-R
MOUB-36HDN1-Q,
MOU-48HDN1, MOUB-48HDN1-R
General Information 3
Nomenclature MLCAC-UTSM-2010-10
Nomenclature
1.1 Indoor Unit
M U B - 18 H R D N1
Refrigerant Type N1 R410A
DC Inverter
Control Mode R Remote Control
Function Code C cooling Only H cooling & Heating
Capacity (¡ Á1000Btu/h)
Product Series A First Time Design B Second Time Design C Third Time Design
3.2 Outdoor Unit
M O U D - 60 H D N1- R
Product Category C Cassette Type T Duct Type U Ceiling & Floor Type H High Static Pressure Duct Type
Midea
Power Supply R 380~415V, 3N, 50Hz
-- 220~240V, 1N, 50Hz
Refrigerant N1 R410A
DC Inverter
Function Code C cooling only H cooling & heating
Capacity (¡ Á1000Btu/h)
Product Series A Time A Designed B Time B Designed
C Time C Designed D
F Console Type
Time D Designed
Universal Outdoor Unit O Outdoor unit U Universal
Midea
4 General Information
MLCAC-UTSM-2010-10 Features
Features
4.1 Universal outdoor unit design Indoor unit with the same capacity can match with the same outdoor unit.
4.2 High efficiency and energy saving.
Thanks to the DC inverter technology and optimized piping system, the EER and COP of whole
series can easily reach A-class.
4.3 Low noise and low starting current.
Thanks to the DC inverter technology, the system can work with low noise, and very small starting
current.
4.4 Intelligent refrigerant adjustment technology.
Throttle part is made up of capillary and electronic expansion valve (EXV). The outdoor unit can
output the most accurate capacity in any condition.
4.5 Working in cooling mode under -15. Outdoor unit built-in with low ambient kit, it can control the outdoor unit’s fan and cooling can be
performed throughout the year for computer rooms, banquet halls, etc. Wide operation range covers outdoor temperatures as low as -15 for cooling.
4.6 Indoor & outdoor unit’s power supply is separate.
4.7 All indoor units have network control function.
4.8 All indoor units have Auto-restart function.
General Information 5
Indoor Units MLCAC-UTSM-2010-06
Part 2
Indoor Units
Four-way Cassette Type ....................................................... 7
Duct Type ............................................................................. 20
Ceiling & Floor Type ........................................................... 31
6 Indoor Units
MLCAC-UTSM-2010-10 Four-way Cassette Type
Four-way Cassette Type
1. Features ........................................................................... 8
2. Dimensions .................................................................... 11
3. Service Space ................................................................ 12
4. Wiring Diagrams ........................................................... 13
5. Air Velocity and Temperature Distributions ............... 14
6. Electric Characteristics ................................................ 15
7. Sound Levels ................................................................ 15
8. Accessories ................................................................... 16
9. The Specification of Power .......................................... 17
10. Field Wiring ................................................................... 18
Four-way Cassette Type 7
Features MLCAC-UTSM-2010-10
1. Features
(1) Low operation noise
—Streamline plate ensures quietness —Creates natural and comfortable environment
(2) Efficient cooling——Equal, fast and wide range cooling
(3) Excellent performance. The optimal evaporator & sufficient airflow volume guarantees the excellent
capacity
(4) The adoption of the most advanced 3- Dimensional Screw fan
—Reduces the air resistance passing through —Smoothes the air flow —Makes air speed distribution to the heat exchange uniform
(5) Fresh air makes life healthier and more comfortable.
(6) Drainage pump can take up the condenser water to 750mm.
(7) Ultra thin machine body to easy installation and maintenance. 18K~24K:230mm, 36~48K:300mm.
8 Four-way Cassette Type
MLCAC-UTSM-2010-10 Features
(8) Different color panels for choose: White、Gray、Blue、Black
(9) Swing angle of louver
1) Add one more swing motor, one motor driving two louvers. Controlling the interspace of each part, minimizing the angle loss.
2) The swing angle of the first louver are 40~42 degrees and the second louver are 37~38 degrees. New evaporator and inner configuration designed can acquire high heat-exchanger effect.
(10) More strengthening rib design around the panel, preventing the distortion for the panel.
(11) New outlet frame design to make the phenomena of coagulation great improvement: prevent the
condensing water from damaging the air guide strip.
(12) Adding rib on the panel of fan outlet, which can avoid the air outlet direct flow to people.
(13) 4 speeds available, optional super high fan speed design suitable for the large building over 3m high.
(14) Adding digital tube displaying on the display board. LED can display the Error Code to make the
malfunction checking easier.
Four-way Cassette Type 9
Features MLCAC-UTSM-2010-10
(15) Reserve spaces for air side-outlet, it is available to connect duct pipe hence air supplying from the four
sides to nearby small room..
(16) The connecting pipe and drop height is higher. Max. pipe length up to 50m(refer to ①), and Max. drop height up to 30mrefer to ②).
(17) Optimal design, smaller Control Box, Space saving and convenient for wiring, Using fire resistance galvanized steel for E-box material. Metal box make the control part more stable and prevent damaging.
(18) 360°air flow panel : 360°air flow delivery ensures uniform airflow distribution(optional)
10 Four-way Cassette Type
MLCAC-UTSM-2010-10 Dimensions
2. Dimensions
Unit: mm
MODEL(Btu/h) A B C H 36000 300 Ф15.9 Ф9.5 >330 48000 300 Ф15.9 Ф9.5 >330
Four-way Cassette Type 11
Service Space MLCAC-UTSM-2010-10
3. Service Space
12 Four-way Cassette Type
MLCAC-UTSM-2010-10 Wiring Diagrams
4. Wiring Diagrams
MCC-36HRDN1MCC-48HRDN1
Four-way Cassette Type 13
Air Velocity and Temperature Distributions MLCAC-UTSM-2010-10
5. Air Velocity and Temperature Distributions
Airflow velocity
High pressure switch
T5
Discharge temp. sensor
Oil s epar ator
Filter
Compressor
Low pressure
Condenser
Ambient temp. sensor
4-way valve
Oil return Capillary
Filter
Low pressure l iqui d accumulator
switch
Condenser temp. sensor
T3
Filter
T4
Outdoor unit
Electronic expansion valve
Capillary
Filter
Evaporator
Evaporator temp. se nsor
Room temp. sensor
Indoor uni t
T2
T1
14 Four-way Cassette Type
MLCAC-UTSM-2010-10 Electric Characteristics
6. Electric Characteristics
Power
Supply
Model
MCC-36HRDN1 50 220-240 198 254 15 MCC-48HRDN1 50 220-240 198 254 15
Remark: MFA: Max. Fuse Amps. (A)
Indoor Unit
Hz Voltage Min Max MFA
7. Sound Levels
Model
MCC-36HRDN1 44 42 41 MCC-48HRDN1 44 42 41
H M L
Noise level dB(A)
Four-way Cassette Type 15
Accessories MLCAC-UTSM-2010-10
8. Accessories
Name Shape Quantity
INSTALLATION FITTINGS
Tubing & Fittings
Installation paper board
Soundproof / insulation sheath
Connecting pipe group 1
1
2
Drainpipe Fittings
Remote controller & Its Frame
Others
Installation accessory (The product you have might not be provided the following accessories
Out-let pipe sheath
Out-let pipe clasp 1
Drain joint 1
Seal ring 1
Remote controller & Its Frame
Remote controller holder 1
Mounting screw(ST2.9×10-C-H) 2
Alkaline dry batteries (AM4)
Owner's manual 1
Installation manual 1
Expansible hook
Installation hook
Orifice
1
1
2
4
4
1
16 Four-way Cassette Type
MLCAC-UTSM-2010-10 The Specification of Power
9. The Specification of Power
Four-way Cassette Type 17
Field Wiring MLCAC-UTSM-2010-10
10. Field Wiring
Wiring chart
18 Four-way Cassette Type
MLCAC-UTSM-2010-10 Field Wiring
Four-way Cassette Type 19
Duct Type MLCAC-UTSM-2010-10
Duct Type
1. Features ......................................................................... 21
2. Dimensions .................................................................... 22
3. Service Space ................................................................ 23
4. Wiring Diagrams ........................................................... 24
5. Static Pressure .............................................................. 25
6. Electric Characteristics ................................................ 25
7. Sound Levels ................................................................ 26
8. Accessories ................................................................... 27
9. The Specification of Power .......................................... 28
10. Field Wiring ................................................................... 29
20 Duct Type
MLCAC-UTSM-2010-10 Features
1. Features
New structure design.
Built-in drainage pump (Optical).
Two air intake ways: from below or rear (standard).
Wire controller is standard.
Three speeds indoor unit.
Fresh air inlet hole is reserved.
Duct Type 21
Dimensions MLCAC-UTSM-2010-10
2. Dimensions
Capacity
(KBtu)
MTB-36HWDN1 1140 270 775 710 65 933 35 179 1035 260 20 1180 490
MTB-48HWDN1 1200 300 865 800 80 968 40 204 1094 288 45 1240 500
22 Duct Type
Outline
dimension(mm)
A B C D E F G H I J K L M
Air outlet o
pening size
Air return
opening size
Size of outline dimension mounted
plug
MLCAC-UTSM-2010-10 Service Space
3. Service Space
Ensure enough space required for installation and maintenance.
All the indoor units reserve the hole to joint the fresh air pipe. The hole size as following:
Duct Type 23
Wiring Diagrams MLCAC-UTSM-2010-10
4. Wiring Diagrams
MTB-36HWDN1 MTB-48HWDN1
D M
Y/G
TR
XS1 XP1
BLAC K
BLUE
RED
L
IND OOR POWE R
CN 11
CN 1
C N13
CN2
P3
P2
CH
BR OWN
BLAC K
N
WHIT E
NOT E:PL EASE USE SHI ELDE R WI RE F OR C OMM .BUS WIR E,
202070390385
CODE
FM DM CS H/P2 CH /P3
T1
T2B
T2 XP 1-4 XS 1-4 TR
ENC 2
' 0F' o f t he E NC2 an d 'O N/ OFF '
respectively.
respectivel y.
ENC1
T ITLE
FAN MOTO R
PU MP MOTOR
WATER L EVEL SWI TCH HIGH FAN
SUPER HI GH FAN R OOM TEMP . O UTER PIP E TE MP.
MIDDLE P IPE TEMP .
CON NECT ORS
TRANSFOR MER
FUNCTION OF SWITCH
SWITCH
SWITCH
SWITCH NUMBER
4
5 7 8
9
(FOR INDOOR UNIT ADDRESS)
(FOR CCM UNIT ADDRESS)
(FOR POWER)
PO W E R
5300W 5600W 7100W 9000W
10500W 140 00W 160 00W
SW 1
of t he Sw1 m ean th e add res se s
of the different units,
S1 S2
'0F' of t he S2 and 'ON/OFF'
of the S1 mean the addresses of the different net units,
S3
WHITE
ENC1
SW1
MAIN BOARD
CN 4
XP4 X S4
Y/G
FM
ENC2
BLA CK
DIS PLAY BOAR D
CN1 0
CN9
S2
S1
33CN
C S
BLA CK
CN1 7
CN7
CN 6
23CN
CN5
E RROR O UTPU T
CN5
CN 3
W HITE
T1
ON/OFF
REMOTE CONTROL
BLAC K
XP3 XS3
T2
CN2CN 4
XY
TO CCM CO MM.BUS
XS2
XP2
T2B
CN 1
EPQ
TO OUTD OOR COM M.BU S
TO WIRE CONTROLLER
EALARM
24 Duct Type
MLCAC-UTSM-2010-10 Static Pressure
5. Static Pressure
MTB-36HWDN1 MTB-48HWDN1
Pa
90
80
70
60
50
40
External static pressure (Pa)
30
20
10
1200
1100
Super high speed
High speed
1800
Air volume(m
Mid speed
Low speed
2000
3
/h)
220016001400
2400
Pa
120
110
100
90
80
70
60
50
40
External static pressure (Pa)
30
20
10
1000
1300
19001600
Air vo lume(m
Super high speed
High speed
Mid speed
Low speed
2500
2200
3
/h)
2800
3100
6. Electric Characteristics
Model
MTB-36HWDN1 50 220-240 207 253 15
MTB-48HWDN1 50 220-240 207 253 15
Remark:
MFA: Max. Fuse Amps. (A)
Hz Voltage Min. Max. MFA
Indoor Unit Power Supply
Duct Type 25