Midea MSX-09HRN1-QC2, MSX-12HRN1-QC2, MSX-18HRN1-QC2, MSX-21HRN1-QB8W, MSX-24HRN1-QB8W Service Manual

...
Page 1
XSEU-A-12
02
SERVICE MANUAL
MIDEA AIRCONDITIONER
EUROPE MARKET
X ON-OFF SERIES
Page 2
CONTENTS
1. Precaution .............................................................................................................................................. 1
1.1 Safety Precaution .......................................................................................................................... 1
1.2 Warning ......................................................................................................................................... 1
2. Function .................................................................................................................................................. 6
3. Dimension............................................................................................................................................... 9
3.1 Indoor Units ................................................................................................................................... 9
3.2 Outdoor Units .............................................................................................................................. 11
4. Refrigerant Cycle Diagram ................................................................................................................... 12
5. Wiring Diagram ..................................................................................................................................... 13
5.1 Indoor Units ................................................................................................................................. 13
5.2 Outdoor Units .............................................................................................................................. 15
6. Installation details ................................................................................................................................ 19
6.1 Wrench torque sheet for installation ........................................................................................... 19
6.2 Connecting the cables ................................................................................................................. 19
6.3 Pipe length and the elevation ...................................................................................................... 20
6.4 Installation for the first time ......................................................................................................... 22
6.5 Adding the refrigerant after running the system for many years ................................................. 25
6.6 Re-installation while the indoor unit need to be repaired ............................................................ 26
6.7 Re-installation while the outdoor unit need to be repaired ......................................................... 28
7. Operation characteristics .................................................................................................................... 31
8. Electronic function ............................................................................................................................... 32
8.1 Abbreviation ................................................................................................................................. 32
8.2 Display function ........................................................................................................................... 32
8.3 Main Protection ........................................................................................................................... 34
9. Troubleshooting ................................................................................................................................... 47
9.1 Indoor unit error display .............................................................................................................. 47
9.2 Diagnosis and Solution ............................................................................................................... 48
Page 3
1
1. Precaution
1.1 Safety Precaution
n To prevent injury to the user or other people and property damage, the following
instructions must be followed.
n Incorrect operation due to ignoring instruction will cause harm or damage. n Before service unit, be sure to read this service manual at first.
1.2 Warning
Ø Installation
n Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated
circuit.
There is risk of fire or electric shock.
n For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized
service center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
n Always ground the product.
There is risk of fire or electric shock.
n Install the panel and the cover of control box securely.
There is risk of fire of electric shock.
n Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fore or electric shock.
n Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
n Do not modify or extend the power cable.
There is risk of fire or electric shock.
n Do not install, remove, or reinstall the unit by yourself(customer).
There is risk of fire, electric shock, explosion, or injury.
n Be caution when unpacking and installing the product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the
Page 4
2
condenser and evaporator.
n For installation, always contact the dealer or an Authorized service center.
There is risk of fire, electric shock, explosion, or injury.
n Do not install the product on a defective installation stand.
It may cause injury, accident, or damage to the product.
n Be sure the installation area does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
n Do not let the air conditioner run for a long time when the humidity is very high and a
door or a window is left open.
Moisture may condense and wet or damage furniture.
n Take care to ensure that power cable could not be pulled out or damaged during
operation.
There is risk of fire or electric shock.
n Do not place anything on the power cable.
There is risk of fire or electric shock.
n Do not plug or unplug the power supply plug during operation.
There is risk of fire or electric shock.
n Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
n Do not place a heater or other appliance near the power cable.
There is risk of fire and electric shock.
n Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric shock.
n Do not store or use flammable gas or combustible near the product.
There is risk of fire or failure of product.
n Do not use the product in a tightly closed space for a long time.
Oxygen deficiency could occur.
n When flammable gas leaks, turn off the gas and open a window for ventilation before
turn the product on.
Do not use the telephone or turn switches on or off.
Page 5
3
There is risk of explosion or fire.
n If strange sounds, or small or smoke comes from product. Turn the breaker off or
disconnect the power supply cable.
There is risk of electric shock or fire.
n Stop operation and close the window in storm or hurricane. If possible, remove the
product from the window before the hurricane arrives.
There is risk of property damage, failure of product, or electric shock.
n Do not open the inlet grill of the product during operation. (Do not touch the electrostatic
filter, if the unit is so equipped.)
There is risk of physical injury, electric shock, or product failure.
n When the product is soaked (flooded or submerged), contact an Authorized service
center.
There is risk of fire or electric shock.
n Be caution that water could not enter the product.
There is risk of fire, electric shock, or product damage.
n Ventilate the product from time to time when operating it together with a stove, etc.
There is risk of fire or electric shock.
n Turn the main power off when cleaning or maintaining the product.
There is risk of electric shock.
n When the product is not be used for a long time, disconnect the power supply plug or
turn off the breaker.
There is risk of product damage or failure, or unintended operation.
n Take care to ensure that nobody could step on or fall onto the outdoor unit.
This could result in personal injury and product damage.
Ø CAUTION
n Always check for gas (refrigerant) leakage after installation or repair of product.
Low refrigerant levels may cause failure of product.
n Install the drain hose to ensure that water is drained away properly.
A bad connection may cause water leakage.
n Keep level even when installing the product.
Page 6
4
It can avoid vibration of water leakage.
n Do not install the product where the noise or hot air from the outdoor unit could damage
the neighborhoods.
It may cause a problem for your neighbors.
n Use two or more people to lift and transport the product.
Avoid personal injury.
n Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Ø Operational
n Do not expose the skin directly to cool air for long periods of time. (Do not sit in the
draft).
This could harm to your health.
n Do not use the product for special purposes, such as preserving foods, works of art, etc.
It is a consumer air conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
n Do not block the inlet or outlet of air flow.
It may cause product failure.
n Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
n Do not touch the metal parts of the product when removing the air filter. They are very
sharp.
There is risk of personal injury.
n Do not step on or put anything on the product. (outdoor units)
There is risk of personal injury and failure of product.
n Always insert the filter securely. Clean the filter every two weeks or more often if
necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
n Do not insert hands or other object through air inlet or outlet while the product is
Page 7
5
operated.
There are sharp and moving parts that could cause personal injury.
n Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
n Use a firm stool or ladder when cleaning or maintaining the product.
Be careful and avoid personal injury.
n Replace the all batteries in the remote control with new ones of the same type. Do not
mix old and mew batteries or different types of batteries.
There is risk of fire or explosion.
n Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
They may burn of explode.
n If the liquid from the batteries gets onto your skin or clothes, wash it well with clean
water. Do not use the remote of the batteries have leaked.
The chemical in batteries could cause burns or other health hazards
The designs, and information in this book are subject to change without notice for product improvement.
Page 8
6
2. Function
Model Names of Indoor/Outdoor Units
Series Capacity Indoor units Outdoor units
On-Off
7k
MSX-07HRN1-QC2 MOA-07HN1-QC2
9k
MSX-09HRN1-QC2 MOA-09HN1-QC2 MSX-09HRN1-QC2 MOA1-09HN1-QC2
12k
MSX-12HRN1-QC2 MOB1-12HN1-QC2 MSX-12HRN1-QC2 MOB-12HN1-QC2
18k
MSX-18HRN1-QC2 MOF-18HN1-QC2
21k
MSX-21HRN1-QB8W MOF1-21HN1-QB8W
24k MSX-24HRN1-QB8W MOF3-24HN1-QB8W
Page 9
7
The louver can be set at the desired position
or swing up and down automatically
The function is usually used in rainy
days in springtime or damp areas.
The unit wil
l decide the louver direction according
to operation mode.
Turbo wind, high, med, low, breeze.
Prevent the water being fr
ozen
on evaporator by
checking the evaporator pipe temperature
Indoor units
Operation by remote controller.
Anti-freezing control in cooling
Time Delay Safety control
Indoor fan speed control
Two-direction air vane
Sleep mode auto control
Independent dehumidification
Air flow Direction
Auto mode
Temp. Compensation
Flexible wiring connection
Auto defrost
Anti-cold function
Self-diag. function
Auto-restart
Ionizer/Plasma(optional)
Prevent the cold wind at the
beginning of unit start.
Follow me
Golden fin (Optional)
LCD display
Page 10
8
It protects the valves and prevents water from dr
ipping.
Outdoor units
Power relay control
Valve protection cover
Made from electrolytic zinc steel sheet and anti
-
rust coated components.
Low noise air flow system
Anti-rust cabinet
Page 11
9
3. Dimension
3.1 Indoor Units
Figure 1:
Figure 2:
Page 12
10
Figure 3:
Figure 4:
Figure Models
W D H
Figure 1
MSX-07HRN1-QC2
710 195 250
MSX-09HRN1-QC2
Figure 2
MSX-12HRN1-QC2 790 195 265
Figure 3 MSX-18HRN1-QC2 850 225 305
Figure 4
MSX-21HRN1-QB8W
998 235 322
MSX-24HRN1-QB8W
Page 13
11
3.2 Outdoor Units
More than 30cm
More than 60cm
More than 70cm
More than 30cm
More than 60cm (Service space
Fence or
obstacles
Model W D H W1 A B
MOA-07HN1-QC2
700 240 540 757 458 250 MOA1-09HN1-QC2
MOA-09HN1-QC2
MOB1-12HN1-QC2
780 250 540 843 549 276
MOB-12HN1-QC2 MOF-18HN1-QC2
845 320 700 908 560 335 MOF1-21HN1-QB8W
MOF3-24HN1-QB8W
Page 14
12
4. Refrigerant Cycle Diagram
For heat pump models:
INDOOR
OUTDOOR
LIQUID SIDE
GAS SIDE
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
COMPRESSOR
2-WAY VALVE
3-WAY VALVE
CHECK VALVE (Heating Model only)
CAPILIARY TUBE
REVERSING VALVE (Heating Model only)
COOLING HEATING
ACCUMULATOR
Page 15
13
5. Wiring Diagram
5.1 Indoor Units
MSX-07HRN1-QC2 MSX-09HRN1-QC2 MSX-12HRN1-QC2 MSX-18HRN1-QC2
Page 16
14
MSX-21HRN1-QB8W, MSX-24HRN1-QB8W
Page 17
15
5.2 Outdoor Units
MOA-07HN1-QC2
Page 18
16
MOA1-09HN1-QC2 MOA-09HN1-QC2 MOB1-12HN1-QC2 MOB-12HN1-QC2
Page 19
17
MOF-18HN1-QC2
Page 20
18
MOF1-21HN1-QB8W
MOF3-24HN1-QB8W
Page 21
19
6. Installation details
6.1 Wrench torque sheet for installation
Outside diameter Torque Additional tightening torque
mm inch N.cm N.cm
Ф6.35 1/4 1500(153kgf.cm) 1600(163kgf.cm) Ф9.52 3/8 2500(255kgf.cm) 2600(265kgf.cm) Ф12.7 1/2 3500(357kgf.cm) 3600(367kgf.cm)
Ф16 5/8 4500(459kgf.cm) 4700(479kgf.cm) Ф19 3/4 6500(663kgf.cm) 6700(683kgf.cm)
6.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Rated current of appliance Nominal cross-sectional area (mm²)
>3 and 6 0.75
>6 and 10 1.0 >10 and 16 1.5 >16 and 25 2.5
The cable size and the current of the fuse or switch are determined by the maximum current indicated on the nameplate which located on the side panel of the unit. Please refer to the nameplate before selecting the cable, fuse and switch.
Page 22
20
6.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model Connective pipe length Air purging
Additional amount of
refrigerant All Less than 5m Use vacuum pump -----------------­MSX-07HRN1-QC2
More than 5m Use vacuum pump (Pipe length – 5) × 20g/m
MSX-09HRN1-QC2 MSX-12HRN1-QC2 MSX-18HRN1-QC2 MSX-21HRN1-QB8W
More than 5m Use vacuum pump (Pipe length – 5) × 40g/m
MSX-24HRN1-QB8W
Model
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
MSX-07HRN1-QC2
5 8 20 MSX-09HRN1-QC2 MSX-12HRN1-QC2 MSX-18HRN1-QC2
5 10 25 MSX-21HRN1-QB8W
MSX-24HRN1-QB8W
Page 23
21
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the system reliability. The oil trap should be installed per 5-7 meters.
Page 24
22
6.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested
and evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles come out, the pipes have leakage.
1. Air purging with vacuum pump
1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the 2-way and
3-way valves are set to the closed position.
2) Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If
(Indoor unit)
(Liquid side)
(Gas side)
Vacuum
pump
Vacuum pump
Lo
Hi
Handle Hi
Two-way valve
Close
Manifold valve
Compound meter
Pressure
gauge
20Pa
Handle Lo
Charge hose
Charge hose
(Outdoor unit)
Close
Three-way valve
Page 25
23
the pressure cant achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump. Confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a little higher than the atmosphere pressure. Then remove the charge hose from the 3 way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve.
2. Air purging by refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve.
3). Air purging Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45 for 3 seconds then closing it for 1 minute; repeat 3 times. After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage Check the flare connections for gas leakage.
5). Discharge the refrigerant Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the
Page 26
24
2-way valve approximately 45 until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open position. Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap Be sure to use a torque wrench to tighten the service port cap to a torque 18N·m.
Be sure to check the gas leakage.
3. Adding the refrigerant if the pipe length >5m
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve. Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure the liquid charge.
2). Purge the air from the charge hose Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose
Electronic scale
Page 27
25
from the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.
6.5 Adding the refrigerant after running the system for many years
Procedure:
1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3-way valve. Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low
Electronic scale
Page 28
26
side), disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.
6.6 Re-installation while the indoor unit need to be repaired
1. Collecting the refrigerant into the outdoor unit
Procedure
1). Confirm that both the 2-way and 3-way valves are set to the opened position. Remove the valve stem caps and confirm that the valve stems are in the opened position. Be sure to use a hexagonal wrench to operate the valve stems.
2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose Open the handle Lo valve of the manifold valve slightly to purge air from the charge hose for 5 seconds and then close it quickly.
4). Set the 2-way valve to the close position.
5). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
Page 29
27
6). Set the 3-way valve to the closed position immediately. Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa. Disconnect the charge set, and tighten the 2-way and 3-way valve’s stem nuts. Use a torque wrench to tighten the 3-way valves service port cap to a torque of 1.8 kgf.m. Be sure to check for gas leakage.
2. Air purging by the refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve. Leave the valve on the charging cylinder closed.
3). Air purging Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45 for 3 seconds then closing it for 1 minute; repeat 3 times. After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage Check the flare connections for gas leakage.
5). Discharge the refrigerant Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the
Page 30
28
2-way valve approximately 45 until the gauge indicates 0.3 to 0.5 Mpa.
6). Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open position. Be sure to use a hexagonal wrench to operate the valve stems.
7). Mount the valve stems nuts and the service port cap. Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
Be sure to check the gas leakage.
6.7 Re-installation while the outdoor unit need to be repaired
1. Evacuation for the whole system
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the opened position.
2). Connect the vacuum pump to 3-way valve’s service port.
3). Evacuation for approximately one hour Confirm that the compound meter indicates -0.1Mpa.
4). Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the vacuum pump.
Page 31
29
2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve. Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4). Open the valves (Low side) on the charge set and charge the system with liquid refrigerant. If the system cannot be charge with the specified amount of refrigerant, or can be charged with a little at a time (approximately 150g each time) , operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure.
5).When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way valve’s service port immediately. If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose.
6). Mounted the valve stem caps and the service port
Electronic scale
Page 32
30
Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.
Page 33
31
7. Operation characteristics
CAUTION:
1. If air conditioner is used outside of the above conditions, certain safety protection features may
come into operation and cause the unit to function abnormally.
2. Room relative humidity less than 80%. If the air conditioner operates in excess of this figure, the surface of the air conditioner may attract condensation. Please set the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode.
3. Optimum performance will be achieved within this operating temperature.
Page 34
32
8. Electronic function
8.1 Abbreviation
T1: Indoor ambient temperature T2: Coil temperature of indoor heat exchanger T3: Coil temperature of outdoor heat exchanger T4: Outdoor ambient temperature T5: Compressor discharge temperature
8.2 Display function
Icon explanation on indoor display board.
ON/OFF indicator
This indicator illuminates when the air conditioner is in operation.
PRE.-DEF. Indicator (For Cooling & Heating models only)
This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air control feature is activated in heating mode.
Auto Mode This indicator illuminates when the air conditioner is in Auto Mode.
Turbo indicator This indicator illuminates when the air conditioner is in turbo operation.
TEMPERATURE indicator
Usually it displays the temperature settings.
TIMER indicator
This indicator illuminates when TIMER is set ON/OFF.
FAN SPEED indicator
This indicator illuminates when change the fan speed.
Page 35
33
Ionizer ( Plasma ) function indicator This indicator illuminates when Ionizer ( Plasma ) function is on.
Page 36
34
8.3 Main Protection
8.3.1 Time Delay at restart for compressor.
8.3.2 Fan Speed is out of control. (only for MSX-07HRN1-QC2, MSX-09HRN1-QC2, MSX-12HRN1-QC2, MSX-18HRN1-QC2 models)
----When Indoor Fan Speed keeps too low or too high for certain time, the unit will stop and the LED will display the failure
8.3.3 Current protection
I3SEC
I5MIN
A
B
C
Resume
IFAN
IRESTORE
A zone : The current exceeds I
3SEC
for 5 seconds, the compressor and outdoor fan will shut off.
B zone: The current exceeds I
5min
for 5 minutes, the compressor and outdoor fan will shut off.
C zone: The current exceeds I
FAN
, the outdoor fan will shut off if AC is in heating mode. If AC is in cooling mode, the indoor fan will run at low speed. I
3SEC
=7.0A, I
5min
=6.0A, I
FAN
=5.0A, I
RESTORE
=6.5A for MSX-07HRN1-QC2 model.
I
3SEC
=10.0A, I
5min
=7.5A, I
FAN
=6.0A, I
RESTORE
=5.0A for MSX-09HRN1-QC2 model.
I
3SEC
=12.0A, I
5min
=8.5A, I
FAN
=7.5A, I
RESTORE
=6.5A for MSX-12HRN1-QC2 model.
I
3SEC
=19.5A, I
5min
=17.0A, I
FAN
=15.0A, I
RESTORE
=13.0A for MSX-18HRN1-QC2 model.
I
3SEC
=22.0A, I
5min
=20.0A, I
FAN
=16.0A, I
RESTORE
=14.0A for MSX-21HRN1-QB8W model.
I
3SEC
=26.0A, I
5min
=24.0A, I
FAN
=19.0A, I
RESTORE
=17.0A for MSX-24HRN1-QB8W model.
8.3.4 Zero crossing detection error protection (only for MSX-07HRN1-QC2, MSX-09HRN1-QC2, MSX-12HRN1-QC2, MSX-18HRN1-QC2 models)
If AC can not detect zero crossing signal for 4 minutes or the zero crossing signal time interval is not correct, the unit will stop and the LED will display the failure. The correct zero crossing signal time interval should be between 6-13ms.
Page 37
35
8.3.5 Indoor / outdoor units communication protection(only for MSX-21HRN1-QB8W, MSX-24HRN1-QB8W model)
If the indoor units can not receive the feedback signal from the outdoor units for 2 minutes, the AC will stop and display the failure.
Page 38
36
8.4 Operation Modes and Functions
8.4.1 Fan mode.
(1) Outdoor fan and compressor stop. (2) Temperature setting function is disabled, and no setting temperature is displayed. (3) Indoor fan can be set to high/med/low/auto. (4) The louver operates same as in cooling mode.
(5) Auto fan:
8.4.2 Cooling Mode
8.4.2.1 Compressor running rules:
Once the compressor starts up, it will follow the below rules: When indoor room temp.T1 is lower than Tn, the compressor and outdoor fan will shut off. When T1 is higher than Tm, the compressor and outdoor fan will start up.
Tm=Ts ,Tn=Ts-2 for MSX-07HRN1-QC2, MSX-09HRN1-QC2, MSX-12HRN1-QC2, MSX-18HRN1-QC2 models. Tm=Ts+1, Tn=Ts for MSX-21HRN1-QB8W, MSX-24HRN1-QB8W model.
8.4.2.2 Outdoor fan running rules:
The On-off outdoor units have single fan speed. The outdoor fan will run following the compressor except when AC is in evaporator high temp. protection in heating mode ,condenser high temp.
Page 39
37
protection in cooling mode, defrosting mode and the current protection.
8.4.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto. The auto fan:
8.4.2.4 Evaporator low temperature T2 protection.
When the evaporator coil temp.T2 keeps lower than TE5 for 5 minutes, the compressor and outdoor fan will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart up. While TE5=4, TE6=10for MSX-07HRN1-QC2, MSX-09HRN1-QC2(2T0032300007 2T0032300007), MSX-12HRN1-QC2(2T0032500006), TE5=2 , TE6= 7℃ for MSX-09HRN1-QC2(2T0032300534), MSX-12HRN1-QC2(2T0032500185), MSX-18HRN1-QC2 models; TE5=2 , TE6= 12℃ for MSX-21HRN1-QB8W, MSX-24HRN1-QB8W models.
Page 40
38
8.4.2.5 Condenser high temperature T3 protection.(only for MSX-21HRN1-QB8W, MSX-24HRN1-QB8W model)
T3
TE10
Off
On
TE11
When T3TE10, the compressor will shut off. When T3TE11,the compressor will restart. TE10=65, TE11=55.
8.4.3 Heating Mode
8.4.3.1 Compressor running rules:
Every time, the compressors start up, they will keep running for t minutes (protections are active) and then follow the below rules. (While t=7.) When indoor room temp.T1 is higher than Tj, the compressor and outdoor fan will shut off. When T1 is lower than Tk, the compressor and outdoor fan will start up.
Tj=Ts+6 Tk=Ts+4. for MSX-07HRN1-QC2, MSX-09HRN1-QC2, MSX-12HRN1-QC2, MSX-18HRN1-QC2 models. Tj=Ts+3 Tk=Ts+2.for MSX-21HRN1-QB8W, MSX-24HRN1-QB8W models.
8.4.3.2 Outdoor fan running rules:
The outdoor units have single fan speed. The outdoor fan will run following the compressor except when AC is in evaporator high temp. protection in heating mode , condenser high temp. protection in
Page 41
39
cooling mode ,defrosting mode and the current protection.
8.4.3.3 Indoor fan running rules:
When the compressor is off because off the room temperature rising or the protection, the indoor fan will run at breeze. When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold wind function has the priority.
Anti-cold wind function:
When evaporator coil temp.T2 is getting higher, T2>TE2, the indoor fan will run at setting speed. TE1<T2<TE2, the indoor fan will run at low speed. When T2 is getting lower, TE4<T2<TE3,the indoor fan will run at low speed. T2<TE4, the indoor fan will shut off.
While TE1=28,TE2=3 8 ,TE3=30,TE4=2℃℃0 for MSX-07HRN1-QC2, MSX-09HRN1-QC2 models. TE1=31 ,TE2=36,TE3=30,TE4=20℃℃℃℃ for MSX-12HRN1-QC2 model(2T0032500185) TE1=31,TE2=36,TE3=30,TE4=22 for MSX-12HRN1-QC2 model(2T0032500006) TE1=34 ,TE2=3 7 ,TE3=30,TE4=20 for ℃℃℃MSX-18HRN1-QC2 model. TE1=25,TE2=32,TE3=30,TE4=20 for MSX-21HRN1-QB8W, MSX-24HRN1-QB8W models.
Auto fan action:
Page 42
40
When T1-Ts>2,the indoor fan will run at low speed. When T1-Ts0, the indoor fan will run at medium speed.
8.4.3.4 Defrosting mode For MSX-07HRN1-QC2,MSX-09HRN1-QC2, MSX-12HRN1-QC2, MSX-18HRN1-QC2 models:
l Condition of defrosting:
AC will enter defrosting mode if any of the following items &is satisfied: AC meets A+B1 or A+B2.
A: The cumulative compressor running time is over 42 minutes. B1: The cumulative compressor running time is between 42~120 minutes. Meanwhile the T2-T1 meet the below table.
T2T1
High speed TH
DEFROST
Medium speed TM
DEFROST
Low speed TL
DEFROST
Breeze/off No need to compare the T2 and T1 B2: The cumulative compressor running time is over 120 minutes. Meanwhile the T2-T1 meet the below table.
T2T1
High speed TH
DEFROST
+2
Medium speed TM
DEFROST
+2
Low speed TL
DEFROST
+2
Breeze/off No need to compare the T2 and T1
After the last defrosting, the time that the outdoor fan is off but the compressor is on in high T2 protection cumulates up to 90 minutes. While TH
DEFROST
=14, TM
DEFROST
=16, TL
DEFROST
=17 for MSX-07HRN1-QC2 model.
TH
DEFROST
=15, TM
DEFROST
=17, TL
DEFROST
=19 for MSX-09HRN1-QC2 model.
TH
DEFROST
=14, TM
DEFROST
=15, TL
DEFROST
=16 for MSX-12HRN1-QC2 model.
TH
DEFROST
=17, TM
DEFROST
=18, TL
DEFROST
=19 for MSX-18HRN1-QC2 model.
l Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to normal heating mode.
Page 43
41
(1) The defrosting time is reached to the setting value. (2) The compressor current reaches or exceeds I
DEFROST
for 7 seconds.
I
DEFROST
=3.5A for MSX-07HRN1-QC2 model, I
DEFROST
=4.5A for MSX-09HRN1-QC2 model,
I
DEFROST
=5.0A for MSX-12HRN1-QC2 model. I
DEFROST
=8.5A for MSX-18HRN1-QC2 model.
About the setting defrosting time: condition runtime(minute Defrosting time(minute
Case 1 AB1 runtime60 DT1 Case 2 AB1 60runtime≤80 DT1+1 Case 3 AB1 80runtime≤95 DT1+2 Case 4 AB1 95runtime110 DT1+3 Case 5 AB1 110runtime≤120 DT1+4 Case 6 AB2 DT1+5 Case 7 DT1+5
Note:
Ø From case1 to case 5, If case B happens before case A and lasts till case A happens, the setting
defrosting time will be 10 minutes.
Ø If AC enter defrosting mode continuously three times from case 1 to case 5, the fourth defrosting time will
be DT1 +5 minutes
Ø At the beginning 6.5 minutes of compressor running, AC will not enter the defrosting mode
l Defrosting action
For MSX-21HRN1-QB8W,MSX-24HRN1-QB8W model:
l Condition of defrosting:
Page 44
42
AC will enter defrosting mode if any of the following items is satisfied. (1) When T3TC1 , if the compressor keeps running over 45 minutes and T3TC3 for 3
minutes. While TC1= 0 , ℃ TC3=3 . (2) After the last defrosting, the time that the outdoor fan is off but the compressor is on in high T2 protection cumulates up to 90 minutes.
l Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to normal heating mode. (1) T3 rises to be higher than TC2. TC2= 20. (2) The machine has run for 10 minutes in defrosting.
l Defrosting action
8.4.3.5 High evaporator coil temp.T2 protection: For MSX-07HRN1-QC2 model, MSX-09HRN1-QC2, MSX-12HRN1-QC2, MSX-18HRN1-QC2 models:
While TE7=63,TE8=53,TE9=51 for MSX-07HRN1-QC2 model
Page 45
43
TE7=63,TE8=56,TE9=52 for MSX-09HRN1-QC2 model, TE7=63,TE8=53,TE9=52 for MSX-12HRN1-QC2 model. TE7=63,TE8=53,TE9=50 for MSX-18HRN1-QC2 model.
For MSX-21HRN1-QB8W, MSX-24HRN1-QB8W models:
While TE7=63,TE8=54,TE9=50,TE15=53.
8.4.4 Auto-mode The machine will choose cooling, heating or fan-only mode according to ΔT (ΔT =T1-Ts).
For MSX-07HRN1-QC2, MSX-09HRN1-QC2, MSX-12HRN1-QC2, MSX-18HRN1-QC2 models:
ΔT=T1-Ts Running mode ΔT2
Cooling
-3≤ΔT≤2 Fan-only ΔT<-3 Heating(for cooling only models, they will
run at fan-only mode)
For MSX-21HRN1-QB8W, MSX-24HRN1-QB8W models:
ΔT=T1-Ts Running mode ΔT2
Cooling
-1<ΔT2 Fan-only ΔT-1 Heating(for cooling only models ,they will
run at fan-only mode)
AC will run in auto mode in the below cases:
1Press the forced auto button. 2If AC is off, it will run in auto mode when timer on function is active. 3After setting the mode, AC will run in auto mode if the compressor keeps not running for 20
(15 minutes for MSX-21HRN1-QB8W,MSX-24HRN1-QB8W models).
Page 46
44
8.4.5 Drying mode For MSX-07HRN1-QC2, MSX-09HRN1-QC2, MSX-12HRN1-QC2, MSX-18HRN1-QC2 models:
8.4.5.1 The indoor fan will run following the compressor. If the compressor is on ,the indoor fan will run at low speed. If the compressor is off, the indoor fan will run at breeze. Running rules:
No Condition Indoor fan Compressor and outdoor fan
1 T1 TS+2
Low
Breeze
ON 6 minutes OFF 4 minutes
2 TS T1TS+2
Low
Breeze
ON 5 minutes OFF 5 minutes
3 T1 TS
Low
Breeze
ON 4 minutes OFF 6 minutes
8.4.5.2 In drying mode, if room temperature is lower than 10, the indoor fan will run at breeze while the compressor and outdoor fan will stop and not resume until room temperature exceeds 13.
8.4.5.3 System protection is active in this mode. For MSX-21HRN1-QB8W, MSX-24HRN1-QB8W models:
8.4.5.4 The indoor fan will keep running at low speed.
8.4.5.5 The outdoor fan, compressor and all the protections are the same with cooling mode.
8.4.6 Forced operation function
Press the touch button continually, the AC will run as below sequence:
Forced auto Forced cooling Off
Forced cooling mode: The compressor and outdoor fan keep running and the indoor fan runs at low speed. After running for 30 minutes, AC will turn to auto mode with 24 setting temperature. Forced auto mode: The action of forced auto mode is the same as normal auto mode with 24 setting temperature.
l When AC receives signals, such as switch on, switch off, timer on, timer off, mode setting ,fan
speed setting ,sleeping mode setting ,follow me setting, it will quit the forced operation.
Page 47
45
l The forced operation function can not be memorized if power off.
8.4.7 Timer function
8.4.7.1 Timing range is 24 hours.
8.4.7.2 Timer on. The machine will turn on automatically when reaching the setting time.
8.4.7.3 Timer off. The machine will turn off automatically when reaching the setting time.
8.4.7.4 Timer on/off. The machine will turn on automatically when reaching the setting on time, and then turn off automatically when reaching the setting off time.
8.4.7.5 Timer off/on. The machine will turn off automatically when reaching the setting off time, and then turn on automatically when reaching the setting “on time.
8.4.7.6 The timer function will not change the AC current operation mode. Suppose users set the timer off function and AC is off now, the AC will keep the current running mode and then turn off when reaching the setting time.
8.4.7.7 The setting time is relative time.
8.4.8 Sleep function mode
8.4.8.1 Operation time in sleep mode is 7 hours. After 7 hours, the AC quits this mode and turns off.
8.4.8.2. Operation process in sleep mode is as follow: After pressing ECONOMIC or SLEEP button on controller, the machine will turn into sleep mode. When cooling, the setting temperature rises 1(be lower than 30) every one hour,℃℃ 2 hours later the setting temperature stops rising and indoor fan is fixed as low speed. When heating, the setting temperature decreases 1(be higher than 17) every one hour, 2 hours ℃℃ later the setting temperature stops rising and indoor fan is fixed as low speed.(Anti-cold wind function has the priority)
8.4.8.3 Timer setting is available.
8.4.8.4 When user uses timer off function in sleep mode(or sleep function in timer off mode), if the timing is less than 7 hours, sleep function will be cancelled when reaching the setting time. If the timing is more than 7 hours, the machine will not stop until reaches the setting time in sleep mode.
8.4.9 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In case of a sudden power failure, the module memorizes the setting conditions before the power failure. The unit will resume the previous operation setting (not including Swing function)
Page 48
46
automatically after 3 minutes when power returns. If the memorization condition is forced cooling mode, the unit will run in cooling mode for 30 minutes and then turn to auto mode as 24 setting temp.
Page 49
47
9. Troubleshooting
9.1 Indoor unit error display
For MSX-07HRN1-QC2, MSX-09HRN1-QC2, MSX-12HRN1-QC2, MSX-18HRN1-QC2 models:
LED Failure
E1
EEPROM error
E2
Zero crossing detection error
E3
Indoor fan speed has been out of control
E4
Over current protection occurs 4 times.
E5
The T1 sensor is open circuit or short circuit
E6
The T2 sensor is open circuit or short circuit
For MSX-21HRN1-QB8W, MSX-24HRN1-QB8W models:
LED Failure
E1
EEPROM error
E4
Over current protection occurs 4 times.
E5
The T1 sensor is open circuit or short circuit
E6
The T2 sensor is open circuit or short circuit
E7
The T3 sensor is open circuit or short circuit
E9
Indoor / outdoor units communication error
Page 50
48
9.2 Diagnosis and Solution
9.2.1 Indoor fan speed out of control diagnosis and solution
Is the fan motor connector and connection good?
The unit does not work normally
Turn off the unit, rotate the cross fan. Does it rotate freely?
No
Disassemble the connection between the fan and the motor, check if the bearing is normal. If not, change the bearing. If yes, follow the below step.
Yes
The problem is not resolved.
Yes
Shut off the power supply and turn
on it 5s later
Replace the outdoor fan motor
Replace the outdoor PCB
Page 51
49
9.2.2 Open or short circuit of temperature sensor diagnosis and solution.
9.2.3 Over current protection occurs 4 times.
Yes
Disconnect with the power and replace the main PCB
No
Check if the operation condition is normal, especially the outdoor unit?
Check if the compressor is normal
Yes
Yes
Turn on the units and check if the problem remains
Yes
Check if the voltage of the power supply is too low
No
No
Replace the compressor
Yes
Check if the capillary is blocked
Yes
No
There is some air mixed inside the refrigerant system
Evacuate the refrigerant system and recharge gas
Repair the power supply
Correct the operation condition
Replace the capillary
Yes
Replace the PCB
Yes
Check the connections between the sensors and the PCB. Are the connections good?
Replace the sensor and check if the errors happen again?
Page 52
50
9.2.4 EEPROM parameter error diagnosis and solution
9.2.5 Zero crossing detection error
When such failure occurs, the main control board must have fault.
Shut off the power supply and turn on it 5s later
The problem comes out again
Is the EEPROM chip plugged in indoor PCB well?
No
Correct the connection
Replace the main PCB of indoor unit
Page 53
51
9.2.6 Indoor / outdoor units communication error diagnosis and solution
Yes
No
No
Change the indoor PCB
Change the outdoor PCB
Power on. Is the error extinguished after 3 minutes?
Yes
Power on. Is the error extinguished after 3 minutes?
Change the outdoor PCB
Yes
Change the indoor PCB
Yes
Power off, then power on the A/C by the breaker.(reconnect the power wire). Is the error extinguished?
Check the wiring on the outdoor terminal and indoor terminal following the wiring diagram. Is all the connecting correctly?
-24V<Vs<+24V? (Vs is the voltage between S and N
of outdoor unit
.)
No
Is the wiring to the outdoor PCB connecting correctly?
Is the wiring to the indoor PCB connecting correctly?
No