
Operation
Maintenance Manual
MKA/MKB/MKC/MKT/MKT2
200CFM~1500CFM
(50Hz/60Hz)
Fan Coil Unit
Cassette and Ceiling Concealed Series

Content MCAC-KTSM-2007-2
i Content
Introduction…………………………………………………………………………………………..1
Part 1 General Information………………………………………………………………………...2
Part 2 Indoor Unit……………………………………………………………………......................7
Part 3 Installation………………………………….……………………………........................127

MCAC-KTSM-2007-2 Introduction
Introduction 1
Introduction
Fan coil unit is a kind of compound device which assemble fan and surface-type coil heating-exchanger
together. Fan coil with fresh air supply system is a main type of center air-conditioner system, so it is an
important component of AC devices. Fan coil has horizontal type, vertical type, etc. A cooling (heating)
supply system usually consists of fan coil terminals and chilled water system (heated water system).
Midea
®
commercial AC fan coil is designed and manufactured on the base of advanced technology, and
utilize qualified galvanized iron as material. Due to its supper-thin design, it has such advantages: beautiful
outlook, space saving, easy installation, etc. And the most obvious advantage is that it can decrease the
outlet air Temp-difference as low as possible to make room more comfortable, as well as don’t decrease
cooling capacity output. For the large air flow volume design, it can increase room ventilation frequency,
supply more flesh air, and balance room temperature distribution. Benefiting from adoption of advanced
material and technology, it can effectively decrease the running noise and keep running smoothly. With the
advantages above, it can be widely applied in market, hospital, office building, hotel airport, etc.

General information MCAC-KTSM-2007-2
2 General Information
Part 1
General Information
1. Model Names of Fan Coil…………......................................3
2. External Appearance……………………………………........4
3. Nomenclature…………………………………………………..5
4. Features…………………………………………….….………..6

MCAC-KTSM-2007-2 Model Names of Fan Coil
General Information 3
1. Model Names of Fan Coil
Compact cassette type fan coil
One way cassette type fan coil

External Appearance MCAC-KTSM-2007-2
4 General Information
2. External Appearance
Compact four way cassette type
Duct type
Four way cassette type
One way cassette type

MCAC-KTSM-2007-2 Nomenclature
General Information 5
3. Nomenclature
KM
Nominal Air Volume(CFM)
Midea
Chilled Water Fan coil unit
-- 12Pa Static Pressure H 30Pa Static Pressure
F3 Concealed Flood-stand Type
F2 Exposed Flood-stand Type (below air intake)
Type Code
T2 2nd Generation Duct Type
A 4 Way Cassette B 4 Way Cassette (Compact)
C One Way Cassette T Duct
F1 Exposed Floor-stand Type (side air intake)
T1 127v 60 Hz Duct Type

Features MCAC-KTSM-2007-2
6 Indoor Units
4. Features
Chilled water/Hot water (2 pipes)
Low height for easy installation
Low noise fan direct driven by single phase, 3 speed permanent split capacitor motor.
Copper tube/aluminum fin coils
Hydrophilic aluminum fin coils coated (optional)
Unit constructed by electrostatic galvanized sheet, providing maximum protection against corrosion
Heavy gauge zinc coated steel drainage pan with good insulation processing, avoiding sweating and
corrosion
Unit tested performance comply with GB4706.32-2004、JB9063-1999 and JB/T4283-1991.

MCAC-KTSM-2007-2 Indoor Units
Indoor Units 7
Part 2
Indoor Units
Four Way Cassette Type …….................................................6
Compact Four Way Cassette Type.......................................25
Duct Type...............................................................................38
One Way Cassette Type ……..............................................106

Four Way Cassette Type MCAC-KTSM-2007-2
8 Indoor Units
Four Way Cassette Type
1. Features…………………………………….......……………………….............. 9
2. Specification……………………………………………………………............ 10
3. Dimensions………………………………………………………………...........12
4. Service Space……………………………………………………………...........13
5. Wiring Diagrams…………………………………………………………..........14
6. Capacity Tables……………………………………………………………........15
7. Sound Levels……………………………………………………………...........22
8. Explored View……………………………………………………………..........23

MCAC-KTSM-2007-2 Features
Four Way Cassette Type 9
1. Features
(1) Low operation noise
---Streamline plate ensures quietness
---Creates natural and comfortable environment
(2) Efficient cooling
---Equal, fast and wide—range cooling
(3) The adoption of the most advanced 3- Dimensional Screw fan
---Reduces the air resistance passing through
---Smoothes the air flow
---Makes air speed distribution to the heat exchange uniform
(4) Fresh air makes life healthier and more comfortable.

Specification MCAC-KTSM-2007-2
10 Four Way Cassette Type
2. Specification
Tube pitch(a)x row pitch(b)
Tube outside dia.and type
Coil length x height x width
Low noise 3 speed fan motor
wired controller(optional), remote controller (standard)
Water-return pipe RC3/4” internal thread
Condensation water-outlet pipe
EVA+LDPE 3/4” external thread
Remark: 1. All performance data above is based upon 0Pa ambient static pressure.
2. Cooling capacity test condition: air inlet Temp. : 27DB℃/19.5WB℃, water inlet Temp. 7℃,
water Temp. difference 5℃.
3. Heating capacity test condition:
Air inlet Temp. 21DB℃, water inlet Temp. 60 DB℃
The volume of air and water is same as cooling.
4. Noise level is tested in full-anechoic room.

MCAC-KTSM-2007-2 Specifications
Four Way Cassette Type 11
Remark: 1. All performance data above is based upon 0Pa ambient static pressure.
2. Cooling capacity test condition: air inlet Temp. : 27DB℃/19.5WB℃, water inlet Temp. 7℃,
water Temp. difference 5℃.
3. Heating capacity test condition:
Air inlet Temp. 21DB℃, water inlet Temp. 60 DB℃
The volume of air and water is same as cooling.
4. Noise level is tested in full-anechoic room.
2 Tube pitch(a)x row pitch(b)
Tube outside dia.and type
Coil length x height x width
Low noise 3 speed fan motor
wired controller(optional) ,
remote controller (standard)
Water-inlet pipe RC3/4” internal thread
Condensation water-outlet pipe
EVA+LDPE 3/4” external thread

Dimensions MCAC-KTSM-2007-2
12 Four Way Cassette Type
3. Dimensions
MKA-600、MKA-750
Gas side
E-parts box
Liquid side
4-install hanger
Drain hole
Pump
inspect hole
MKA-850、MKA-950、MKA-1200、MKA-1500
310
4-install
hanger
Gas side
liquid side
E-parts box
Pump
inspect hole
Drain hole

MCAC-KTSM-2007-2 Service Space
Four Way Cassette Type 13
4. Service Spaces
MKA-600、MKA-750、MKA-850、MKA-950、MKA-1200、MKA-1500

Wring Diagram MCAC-KTSM-2007-2
14 Four Way Cassette Type
5. Wiring Diagram
MKA-600、MKA-750、MKA-850、MKA-950、MKA-1200、MKA-1500
XS1
XP1
R
POWER:220V-240V
MAINBOARD
XT1
L
T4
K3
INDOOR DRAWING
POWER:220V-240V~
50Hz
FAN1
BE
N
N1L1
PUMP
Y/G
CAP1
Y/G
XS1-XS2
Rt3
XT1
XP1-XP2
T4
K3
Rt2
FAN1
2CON10
DISPLAY
CAP1
CONNECTORS
6-WAY
TERMINAL
TRANSFORMER
PIPE TEMPERATURE SENSOR
PUMP WATER PUMP
CODE
WATER
LEVLE
INDOOR FAN
INDOOR FAN
PART
CAPACITOR
SWITCH
CN8
CN11 CN10
CN5
CN7
CN3
CN2
CN12
CN1 CN14 CN16
CN15
RT2
RT3
M
R Y
XS2
XP2
CONNECTORS
TO WIRE CONTROLER
(CHOICE)
REMARK:

MCAC-KTSM-2007-2 Capacity Tables
Four Way Cassette Type 15
6. Capacity Tables
Remark:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)

Capacity Tables MCAC -KTSM-2007-2
16 Four Way Cassette Type
Remark:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)

Capacity Tables MCAC -KTSM-2007-2
Four Way Cassette Type 17
Remark:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)

Capacity Tables MCAC -KTSM-2007-2
18 Four Way Cassette Type
Remark:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)

MCAC-KTSM-2007-2 Capacity Tables
Four Way Cassette Type 19
Remark:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)

Capacity Tables MCAC-KTSM-2007-2
20 Four Way Cassette Type
Remark:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)

MCAC-KTSM-2007-2 Capacity Tables
Four Way Cassette Type 21
Heating Capacity Table:
Hydraulic
Pressure
Drop (kPa)
Air inlet condition DB18℃
Remark:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp.
TH: Total heat SH: Sensible heat
2. Table above is based on normal type fan coil high speed air-flow volume; heating capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)

Sound Levels MCAC-KTSM-2007-2
22 Four Way Cassette Type
7. Sound Levels
FOUR-WAY CASSETTE TYPE
Microphone
1.0m

MCAC-KTSM-2007-2 Explored View
Four Way Cassette Type 23
8. Exploded View
MKA-600、MKA-750、MKA-850、MKA-950、MKA-1200、MKA-1500
Pipe Temperature Sensor Assembly

Explored View MCAC-KTSM-2007-2
24 Four Way Cassette Type
Switch cover, air inlet grille
Hanger for panel, assembly
Fixing hanger, Evaporator
Fixing hanger, Evaporator

MCAC-KTSM-2007-2 Compact Four Way Cassette Type
Compact Four Way Cassette Type 25
Compact Four Way Cassette Type
1. Features..........……………………………………………………………............26
2. Specification……………………………………………………………............27
3. Dimensions………………………………………………………………...........28
4. Service Space……………………………………………………………............29
5. Wiring Diagrams…………………………………………………………..........30
6. Capacity Tables……………………………………………………………........31
7. Sound Levels……………………………………………………………..........35
8. Explored View……………………………………………………………..........36

Features MCAC-KTSM-2007-2
26 Compact Four Way Cassette Type
1. Features
(1) Low operation noise
---Streamline plate ensures quietness
---Creates natural and comfortable environment
(2) Efficient cooling
---Equal, fast and wide—range cooling
(3) The adoption of the most advanced 3- Dimensional Screw fan
---Reduces the air resistance passing through
---Smoothes the air flow
---Makes air speed distribution to the heat exchange uniform
(4) Fresh air makes life healthier and more comfortable.
(4) Improvement for easy installation and maintenance (only available for small four-way cassette)
---Little space is required for installation into a shallow ceiling
---Because of the compactness and weight reduction of the main unit and panel, all models can be
installed without a hoist
The sketch map of installation (compact type)

MCAC-KTSM-2007-2 Specification
Compact Four Way Cassette Type 27
2. Specification
Tube pitch(a)x row pitch(b)
Fin type Hydrophilic aluminium
Tube outside dia.and type
Type Low noise 3 speed fan motor
wired controller(optional) , remote controller
(standard)
Condensation water-outlet pipe
EVA+LDPE 3/4” external thread
Remark: 1. All performance data above is based upon 0Pa ambient static pressure.
2. Cooling capacity test condition: air inlet Temp. : 27DB℃/19.5WB℃, water inlet Temp. 7℃,
water Temp. difference 5℃.
3. Heating capacity test condition:
air inlet Temp. 21DB℃, water inlet Temp. 60 DB℃
the volume of air and water is same as cooling.
4. Noise level is tested in full-anechoic room.

Dimensions MCAC-KTSM-2007-2
28 Compact Four Way Cassette Type
3. Dimensions
MKB-300、MKB-400、MKB-450、MKB-500
580(Body)
67
600(Ceiling hole)
650(Panel)
401(Hook-location)
611(Hook-location)
580(Body)
422 28.5
600(Ceiling hole)
650(Panel)
Drain side and
Tubing side
A
600
Hook
265
Panel
Chart 4
Body
Nut
Ceiling

MCAC-KTSM-2007-2 Service Space
Compact Four Way Cassette Type 29
4. Service Space

Wring Diagram MCAC-KTSM-2007-2
30 Compact Four Way Cassette
5. Wiring Diagram
CN7
CN 11 C N1 0
CN2
CN 19
CN1
CN5
CN 12
CN4 CN8 CN9
CN 17
T O CON T R OL E R
5
CN3
2
Y
BL

MCAC-KTSM-2007-2 Capacity Tables
Compact Four Way Cassette Type 31
6. Capacity Tables
Remark:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)

Capacity Tables MCAC-KTSM-2007-2
32 Compact Four Way Cassette Type
Remark:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)

MCAC-KTSM-2007-2 Capacity Tables
Compact Four Way Cassette Type 33
Remark:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)

Capacity Tables MCAC-KTSM-2007-2
34 Compact Four Way Cassette Type
Remark:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)

MCAC-KTSM-2007-2 Sound Levels
Compact Four Way Cassette Type 35
7. Sound Levels
FOUR-WAY CASSETTE TYPE
Microphone
1.0m

Explored View MCAC-KTSM-2007-2
36 Compact Four Way Cassette Type
8. Explored View
MKB-300、MKB-400、MKB-450、MKB-500
Collect Water Pan ,Assembly
Switch cover, air inlet grille
Evaporator Fixture Board Assembly
Liquid Position Sensor Assembly

MCAC-KTSM-2007-2 Explored View
Compact Four Way Cassette Type 37
Install cover, swing motor
Sealing board, pipe out I

The Installation of MKA MCAC-KTSM-2007-2
142 The Installation of MKA
The Installation of MKA
1. Before Installation …………………………………………………................143
2. Install the Main Body...…………………………………………………...........144
3. Install the Panel...…………………………………………………..............146
4. Install the Drain Pipe...…………………………………………………...........148
5. Wiring...…………………………………………………...................................150

MCAC-KTSM-2007-2 Before Installation
The Installation of MKA 143
1. Before Installation
Please check whether the accessories are of full scope. If there are some fittings free from use, please
restore them carefully.

Install The Main Body MCAC-KTSM-2007-2
144 The Installation of MKA
2. Install the Main Body
A. The existing ceiling (to be horizontal)
a. Please cut a quadrangular hole of 880 880mm in the ceiling according to the shape of the installation
paper board. (Refer to Chart3, 4)
The center of the hole should be at the same position of that of the air conditioner body.
Determine the lengths and outlets of the connecting pipe, drain pipe and cables.
To balance the ceiling and to avoid vibration, please enforce the ceiling when necessary.
b. Please select the position of installation hooks according to the hook holes on the installation board.
Drill four holes of Ø12mm, 50~55mm deep at the selected positions on the ceiling. Then embed the
expansible hooks (fittings).
Face the concave side of the installation hooks toward the expansible hooks. Determine the length of the
installation hooks from the height of ceiling, and then cut off the unnecessary part.
If the ceiling is extremely high, please determine the length of the installation hook according to facts.
Cut the installation hook open in the middle position, and then use appropriate length of reinforcing rod (Ø12)
to weld together.
The length could be calculated from Chart5:
Length=H-181+L (in general, L=100mm and is half of the whole length of the installation hook).
c. Please adjust the hexangular nuts on the four installation hooks evenly, to ensure the balance of the body.
1. The transparent hose filled with water to check the lever of the main body from the four sides or diagonal
line direction, the lever indicator also can check the lever from four sides of the main body Refer to chart 6)
2. The drainpipe is awry, leakage will be caused by the malfunction of the water-level switch.
Adjust the position to ensure the gaps between the body and the four sides of ceiling are even.
3. The body's lower part should sink into the ceiling for 10~12mm (Refer to chart5).
Locate the air conditioner firmly by wrenching the nuts after having adjusted the body's position well.

MCAC-KTSM-2007-2 Install The Main Body
The Installation of MKA 145
B. New built houses and ceilings
a. In the case of new built house, the hook can be embedded in advance (refer to the A.b mentioned above).
But it should be strong enough to bear the indoor unit and will not become loose because of concrete
shrinking.
b. After installing the body, please fasten the installation paper board onto the air conditioner with bolts (M6
16) to determine in advance the sizes and positions of the hole opening on ceiling.
Please first guarantee the flatness and horizontal of ceiling when installing it.
Refer to the A.a mentioned above for others.
c. Refer to the A.c mentioned above for installation.
d. Remove the installation paper board.

Install The Panel MCAC-KTSM-2007-2
146 The Installation of MKA
3. Install the Panel
(1) Remove the inlet grid.
Cat ion
Never put the panel face down on floor or against the wall, or on bulgy objects.
Never crash or strike it.
a. Slide two grid switches toward the middle at the same time, and then pull them up. (Refer to chart 9)
b. Draw the grid up to an angle of about 45o, and remove it. (Refer to chart 10)
(2)Remove the installation covers at the four corners.
Wrench off the bolts, loose the rope of the installation covers, and remove them. (Refer to chart 11)
(3) Install the panel
a. Align the swing motor on the panel to the tubing joints of the body properly. (Refer to chart 12)
b. Fix hooks of the panel at swing motor and its opposite sides to the hooks of corresponding water receiver.
(Refer to chart 12) Then hang the other two panel hooks onto corresponding hangers of the body. (Refer to
chart 12)
Cautions
Do not coil the wiring of the swing motor into the seal sponge.
c. Adjust the four panel hook screws to keep the panel horizontal, and screw them up to the ceiling evenly.
(Refer to chart 12)
d. Regulate the panel in the direction of the arrow in Chart12 slightly to fit the panel's center to the center of
the ceiling's opening. Guarantee that hooks of four corners are fixed well.
e. Keep fastening the screws under the panel hooks, until the thickness of the sponge between the body and
the panel's outlet has been reduced to about 4~6mm. The edge of the panel should contact with the ceiling
well. (Refer to chart 13)
Malfunction described in Chart14 can be caused by inappropriate tightness the screw.
If the gap between the panel and ceiling still exists after fastening the screws, the height of the indoor unit
should be modified again. (Refer to chart 15-left)
You can modify the height of the indoor unit through the openings on the panel's four corners; if the lift of the
indoor unit and the drainpipe is not influenced (refer to chart 15-right).
(4) Hang the air-in grid to the panel, and then connect the lead terminator of the swing motor and that of the
control box with corresponding terminators on the body respectively.
(5) Relocate the air-in grid in the procedure of reversed order.
(6) Relocate the installation cover.
a. Fasten the rope of installation cover on the bolt of the installation cover. (Refer to chart 16-left)
b. Press the installation cover into the panel slightly. (Refer to chart 16-right)

MCAC-KTSM-2007-2 Install The Panel
The Installation of MKA 147

Connect Drain Pipe MCAC-KTSM-2007-2
148 The Installation of MKA
4. Connect the Drain Pipe
Install the drainpipe of the indoor unit
You can use a polyethylene tube as the drainpipe (out-dia. 37~39mm, in-dia. 32mm). It could be bought at
local market or from your dealer.
Set the mouth of the drainpipe onto the root of the body's pump-pipe, and clip the drainpipe and the out-let
pipe sheath (fittings) together firmly with the out-let pipe clasp (fitting).
Cautions: Use your strength carefully to prevent the pump-pipe from breaking. The body's pump pipe and
the drainpipe (especially the indoor part) should be covered evenly with the out-let pipe sheath (fittings) and
be bound tightly with the constrictor to prevent condensation caused by entered air.
To prevent water from flowing backwards into the air conditioner while the air conditioner stops, please lean
the drainpipe down toward outdoor (outlet-side) at a degree of over 1/50. And please avoid any bulge or
water deposit. (Refer to Chart 17.a)
Do not drag the drainpipe violently when connecting to prevent the body from being pulled. Meanwhile, one
support-point should be set every 1~1.5m to prevent the drainpipe from yielding (Refer to Chart 17.b). Or
you can tie the drainpipe with the connecting pipe to fix it. (Refer to Chart 17.c) In the case of prolonged
drainpipe, you had better tighten its indoor part with a protection tube to prevent it from loosing.
If the outlet of the drainpipe is higher than the body's pump joint, the pipe should be arranged as vertically as
possible. And the lift distance must be less than 200mm, otherwise the water will overflow when the air
conditioner stops. (Refer to Chart 18) The end of the drainpipe should be over 50mm higher than the ground
or the bottom of the drainage chute, and do not immerse it in water. If you discharge the water directly into
sewage is sure to make a U-form aqua seal by bending the pipe up to prevent the smelly gas entering the
house through the drain pipe.
Cautions: All the joints of the drain system must be sealed to prevent water leakage.
2. Drainage test
Check whether the drainpipe is unhindered
New built house should have this test done before paving the ceiling.
Remove the test cover, and stow water of about 2000ml to the water receiver through the stow tube. (Refer
to Chart 19)

MCAC-KTSM-2007-2 Connect Drain Pipe
The Installation of MKA 149
Turn on the power, and operate the air conditioner under the "COOLING" mode. Listen to the sound of
the drain pump. Check whether the water is discharged well (a lag of 1min is allowed before
discharging, according to the length of the drain pipe), and check whether water leaks from the joints.
Cautions:
1. If there is any malfunction, please resolve it immediately.
2. Stop the air conditioner for there minutes, check if everything is ok. If the drain hose is located
unreasonable, water overflow will cause the Alarm indicator lamp flashing (For both cooling and heating
type or cooling only type), even the water leak out from the water receiver.
3. Check the drain pump whether drain water immediately when alarm sound for the high water lever. If
the water lever can't come down below to the limited water lever, the air conditioner will stop. Restart it
until turn off the power and drain off all the water.
Turn off the power, drain the water away.
The drain plug is used to empty the water-receiver for maintenance of the air conditioner. Please stuff it
imposition at all times during operation to avoid leakage.

Wring MCAC-KTSM-2007-2
150 The Installation of MKA
5. Wiring
Caution:
1. The air conditioner should use separate power supply with rated voltage; the voltage of power supply
must be within90%~110% of rated value.
2. The wiring work should be done by qualified persons according to circuit drawing.
3. A disconnection device having an air gap contact separation in all active conductors should
incorporated in the fixed wiring according to the National wiring regulation.
4. Be sure to locate the power wiring and the signal wiring well to avoid cross-disturbance and their
contact with connecting pipe or stop valve body.
5. The wiring (5-core shield cable) attached between the signal receiving board and the wire controller
is not more than 2m. Be sure to prolong it with wiring of the same type and proper length if necessary.
Generally, do not twist two wiring together unless the joint is soldered well and covered with insulator
tape.
6. Do not turn on the power until you have checked carefully after wiring.
7. The yellow and green wire can only be used to link to the ground wiring.

MCAC-KTSM-2007-2 The Installation of MKB
The Installation of MKB 151
The Installation of MKB
1. Before Installation …………………………………………………...............152
2. Install the Main Body...…………………………………………………...........153
3. Install the Panel...…………………………………………………...............155
4. Install the Drain Pipe...…………………………………………………...........158
5. Wiring...…………………………………………………...................................160

Before Installation MCAC-KTSM-2007-2
152 The Installation of MKB
1. Before Installation
Please check whether the accessories are of full scope. If there are some fittings free from use, please
restore them carefully.
Select the location
Install the connecting pipe
Install the indoor unit
Connect the drain pipe
Install the outdoor unit
Wiring
Test operation

MCAC-KTSM-2007-2 Install The Main Body
The Installation of MKB 1 53
2. Install the Main Body
A. The existing ceiling (to be horizontal)
a. Please cut a quadrangular hole of 600×600mm in the ceiling according to the shape of the installation
paper board. (Refer to Chart3, 4)
The center of the hole should be at the same position of that of the air conditioner body.
Determine the lengths and outlets of the connecting pipe, drain pipe and cables.
To balance the ceiling and to avoid vibration, please enforce the ceiling when necessary.
b. Please select the position of installation hooks according to the hook holes on the installation board.
Drill four holes of Ø12mm, 50~55mm deep at the selected positions on the ceiling. Then embed the
expansible hooks (fittings).
Face the concave side of the installation hooks toward the expansible hooks. Determine the length of the
installation hooks from the height of ceiling, and then cut off the unnecessary part.
If the ceiling is extremely high, please determine the length of the installation hook according to facts.
Cut the installation hook open in the middle position, and then use appropriate length of reinforcing rod (Ø12)
to weld together.
The length could be calculated from Chart5:
Length=210+L (in general, L is half of the whole length of the installation hook)

Install The Main Body MCAC-KTSM-2007-2
154 The Installation of MKB
c. Please adjust the hexangular nuts on the four installation hooks evenly, to ensure the balance of the body.
Use the transparent hose filled with water to check the lever of the main body from the four sides or diagonal
line direction, the lever indicator also can check the lever from four sides of the main body (Refer to chart 6)
If the drainpipe is awry, leakage will be caused by the malfunction of the water-level switch.
Adjust the position to ensure the gaps between the body and the four sides of ceiling are even.
The body's lower part should sink into the ceiling for 10~12mm (Refer to chart5).
Locate the air conditioner firmly by wrenching the nuts after having adjusted the body's position well.
B. New built houses and ceilings
a. In the case of new built house, the hook can be embedded in advance (refer to the A.b mentioned above).
But it should be strong enough to bear the indoor unit and will not become loose because of concrete
shrinking.
b. After installing the body, please fasten the installation paper board onto the air conditioner with bolts
(M5×16) to determine in advance the sizes and positions of the hole opening on ceiling. Please first
guarantee the flatness and horizontal of ceiling when installing it. Refer to the A. a mentioned above for
others.
c. Refer to the A.c mentioned above for installation.
d. Remove the installation paper board.

MCAC-KTSM-2007-2 Install The Panel
The Installation of MKB 155
3. Install the Panel
Caution:
Never put the panel face down on floor or against the wall, or on bulgy objects.
Never crash or strike it.
a. Slide two grid switches toward the middle at the same time, and then pull them up. (Refer to chart 9)
b. Draw the grid up to an angle of about 30o, and remove it. (Refer to chart 10)
Grid switch
Chart9 Chart 10
(2) Install the panel
a. Align the swing motor on the panel to the water receiver of the body properly. (Refer to chart 11)
b. Hang the four fixed rope of the main body to the installation cover and the other three covers of the swing
motor: (Refer to chart 11① and11②)
Caution:
The installation cover of the swing motor must sink into the corresponding water receiver.
c. Install the panel on the main body with bolt (M5×16) and washer. (Refer to chart 11④)
d. Adjust the four panel hook screws to keep the panel horizontal, and screw them up to the ceiling evenly.
e. Regulate the panel in the direction of the arrow in Chart 11③ slightly to fit the panel's center to the center
of the ceiling's opening. Guarantee that hooks of four corners are fixed well.
f. Keep fastening the screws under the panel hooks, until the thickness of the sponge between the body and
the panel's outlet has been reduced to about 4~6mm. The edge of the panel should contact with the ceiling
well. (Refer to chart 12) Malfunction described in Chart 13 can be caused by inappropriate tightness the
screw.
If the gap between the panel and ceiling still exists after fastening the screws, the height of the indoor unit
should be modified again. You can modify the height of the indoor unit through the openings on the panel's
four corners; if the lift of the indoor unit and the drainpipe is not influenced (refer to chart 14-right).
(3) Hang the air-in grid to the panel, and then connect the lead terminator of the swing motor and that of the
control box with corresponding terminators on the body respectively.
(4) Relocate the air-in grid in the procedure of reversed order; install the air-in grid.
Cover
Steel rope
Swing motor side
Swi ng motor installation cover
Drain side
Chart 11
Bolt, washer
1
2
4
3
Body
Panel foam2Ceiling
Panel foam
Air plate
Panel Panel f oam1
Panel sealing foam
Inlet air
Outlet air
Chart 12

Install The Panel MCAC-KTSM-2007-2
156 The Installation of MKB
3. Install the drainage pipe
Check whether the height drop between the indoor unit and outdoor unit, the length of refrigerant pipe, and
the number of the bends meet the following requirements:
The max height drop ................................................................................................... 20m
(If the height drop is more than 10m, you had better put the outdoor unit over above the indoor unit.)
The length of refrigerant pipe ...................................................................... less than 30m
The number of bends ..................................................................................... less than 15
The standard length of connecting pipe is no more than 8m; choose appropriate position for both indoor and
outdoor unit to make the connecting pipe as short as possible.
Do not let air, dust, or other impurities fall in the pipe system during the time of installation.
The connecting pipe should not be installed until the indoor and outdoor units have been fixed already.
Keep the connecting pipe dry, and do not let moisture in during installation.
The procedure of connecting pipe
1. Locate the Pipe
a) Measure the necessary length of the connecting pipe.
b) Drill a hole in the wall (suitable just for the size of the wall conduit, 90mm in general), then set on the
fittings such as the wall conduit and its cover.
c) Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will
cause water leakage by condensation.
d) Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to
do no damage to the tubing.
2. Connect the pipes.
a) Connect the indoor unit at first, then the outdoor unit.
Bend the tubing in proper way. Do not harm them.
Cautions:
Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds with hands
before fasten the flare nuts. (Refer to chart 15).Be sure to use two wrenches simultaneously when you
connect or disconnect the pipes.
Use frozen oil Bend the pipe with thumb
Make the end straight
min-radius 100mm
Chart 15 Chart 16 Chart 17
b) The stop valve of the outdoor unit should be closed absolutely (as original state). Every time you connect
it, first loosen the nuts at the part of stop valve, and then connect the flare pipe immediately (in 5 minutes). If
the nuts have been loosened for a long time, dusts and other impurities may enter the pipe system and may
cause malfunction later. So please expel the air out of the pipe with refrigerant (R407C) before connection.
Expel the air (refer to the "Expel the Air") after connecting the refrigerant pipe with the indoor unit and the
outdoor unit. Then fasten the nuts at the repair-points.

MCAC-KTSM-2007-2 Install The Panel
The Installation of MKB 1 57
Notices for bendable notices
The bending angle should not exceed 90°.
Bending position is preferably in the bendable pipe. The larger the better it is.
Do not bend the pipe more than three times.
Bend the connecting pipe of small wall thickness
Cut out a desired concave at the bending part of the insulating pipe. Then expose the pipe (cover it with
tapes after bending).
To prevent collapsing or deforming, please bend the pipe at its biggest radius.
Use bender to get a small radius pipes.
Use the market brass pipe
Be sure use the same insulating materials when you buy the brass pipe. (Thickness over 9mm in general)
3. Then, open the stem of stop valves of the outdoor unit to make the refrigerant pipe connecting the indoor
unit with the outdoor unit in fluent flow.
4. be sure of no leakage by checking it with leak detector or soap water.
5. Necessary refrigerant capacity:
When the piping is less than 8m, is no need to add refrigerant;
When the piping is longer than 8m, then add 0.03kg/m refrigerant.
Please record and reserve well the refrigerant stow capacity of your air conditioner for later maintenance.
6. Cover the joint of the connecting pipe to the indoor unit with the soundproof insulating sheath (fittings),
and bind it well with the tapes to prevent leakage.
Pipe connecting
Fasten the nut
Put the connecting tubing at the proper position, wrench the nuts with hands then fasten it with a
wrench. (Refer to chart 18)
The selection of the torque sees Table 2.

Install The Drain Pipe MCAC-KTSM-2007-2
158 The Installation of MKB
4. Install The Drain Pipe
Install the drainpipe of the indoor unit
You can use a polyethylene tube as the drainpipe (out-dia. 31~32mm, in-dia. 25mm). It could be bought at
local market or from your dealer.
Set the mouth of the drainpipe onto the root of the body's pump-pipe, and clip the drainpipe and the out-let
pipe sheath (fittings) together firmly with the out-let pipe clasp (fitting).
The body's pump pipe and the drainpipe (especially the indoor part) should be covered evenly with the
out-let pipe sheath (fittings) and be bound tightly with the constrictor to prevent condensation caused by
entered air.
To prevent water from flowing backwards into the air conditioner while the air conditioner stops, please lean
the drainpipe down toward outdoor (outlet-side) at a degree of over 1/50. And please avoid any bulge or
water deposit. (Refer to Chart 24.a)
Do not drag the drainpipe violently when connecting to prevent the body from being pulled.
Meanwhile, one support-point should be set every 1~1.5m to prevent the drainpipe from yielding (Refer to
Chart 24.b). Or you can tie the drainpipe with the connecting pipe to fix it. (Refer to Chart 24.c)
In the case of prolonged drainpipe, you had better tighten its indoor part with a protection tube to prevent it
from loosing.
If the outlet of the drainpipe is higher than the body's pump joint, the pipe should be arranged as vertically as
possible. And the lift distance must be less than 200mm, otherwise the water will overflow when the air
conditioner stops. (Refer to Chart 25)
The end of the drainpipe should be over 50mm higher than the ground or the bottom of the drainage chute,
and do not immerse it in water. If you discharge the water directly into sewage be sure to make a U-form
aqua seal by bending the pipe up to prevent the smelly gas entering the house through the drain pipe.
Cautions:
All the joints of the drain system must be sealed to prevent water leakage.
a
c
b
Lean over 1/50
Lean over 1/50
Pump-pipe clasp
(the fitti ngs)
1-1.5m
1-1.5m
>1.5m
>200mm
<200mm
223mm
Constrict here
Lean over 1/50
Drainpipe
Connecting pipe
Chart 24
Chart 25
Drainage test
Check whether the drainpipe is unhindered
New built house should have this test done before paving the ceiling.
Remove the test cover, and stow water of about 1500ml to the water receiver through the stow tube. (Refer
to Chart 26)

MCAC-KTSM-2007-2 Install The Drain Pipe
The Installation of MKB 1 59
Chart 26
Stow
Body
Drain pipe
Drain plug
Mater pan
Water receiver
Stow tube
Turn on the power, and operate the air conditioner under the "COOLING" mode. Listen to the sound of the
drain pump. Check whether the water is discharged well (a lag of 1min is allowed before discharging,
according to the length of the drain pipe), and check whether water leaks from the joints.
Cautions: If there is any malfunction, please resolve it immediately.
Stop the air conditioner for there minutes, check if everything is ok. If the drain hose is located unreasonable,
water overflow will cause the Alarm indicator lamp flashing (For both cooling and heating type or cooling only
type), even the water leak out from the water receiver.
Check the drain pump whether drain water immediately when alarm sound for the high water lever. If the
water lever can't come down below to the limited water lever, the air conditioner will stop. Restart it until turn
off the power and drain off all the water.
Turn off the power, drain the water away.
The drain plug is used to empty the water-receiver for maintenance of the air conditioner. Please stuff it
imposition at all times during operation to avoid leakage.

Wring MCAC-KTSM-2007-2
160 The Installation of MKB
5. Wring
1. The air conditioner should use separate power supply with rated voltage; the voltage of power supply
must be within90%~110% of rated value.
2. The wiring work should be done by qualified persons according to circuit drawing.
3. A disconnection device having an air gap contact separation in all active conductors should incorporated
in the fixed wiring according to the National wiring regulation.
4. be sure to locate the power wiring and the signal wiring well to avoid cross-disturbance and their contact
with connecting pipe or stop valve body.
5. The wiring (5-core shield cable) attached between the signal receiving board and the wire controller is not
more than 2m. Be sure to prolong it with wiring of the same type and proper length if necessary. Generally,
do not twist two wiring together unless the joint is soldered well and covered with insulator tape.
6. Do not turn on the power until you have checked carefully after wiring.
7. The yellow and green wire can only be used to link to the ground wiring.
Indoor Unit
Electric Con trolling
Box
Elect ric Controlling Box抯 Plu g Cn10
Main Bo ard
Wire Termin al Group
Signal
Receiving
Boa rd
Co nnecting
to wire con troller
Wire Termin al Group
Conne cting Extended
Figure
Grounding
10-c ore
Connecting
Wire Group
5-core Connect ing Group
5-cor e Shield Cable 5x0. 5mm
Wire Con troller
Plane of Indo or Unit
Signal Reciver
Power:220V-240V~ 50H
3 core 3x1.0mm

GD Midea Refrigeration Equipment Co., Ltd.
Have received ISO 9001 certification for quality
assurance.
Certificate Numer. CC 454
GD Midea Refrigeration Equipment Co., Ltd.
Have received environmental management system
Standard ISO 14001 certification
Certificate Numer. CC 1417
GD Midea Air-conditioning Equipment
Add: Penglai Road,Beijiao,Shunde,Foshan,
Guangdong China
Tel: +86-757-26338538
Fax:+86-757-26339337
Web Site: http://www.mideaaircon.com
Please note that the data in this book may be changed without notice for further improvement on quality and performance,.