Midea MGB-F25W/RN1, MGB-F30W/RN1, MGCSL-D30W/RN1, MGB-F60W/RN1, MGB-F55W/RN1 User Manual

...
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
2
Content
1 General information ................................................................................ 3
2. Features ................................................................................................... 5
3. Specification ........................................................................................... 9
4 Dimension .............................................................................................. 21
5 Refrigeration system drawing .............................................................. 33
6. Piping diagram ...................................................................................... 36
7 Wiring diagrams..................................................................................... 42
8 Electric characteristics ......................................................................... 56
9 Capacity tables ...................................................................................... 58
10 Exploded view ...................................................................................... 74
11 Troubleshooting ................................................................................... 96
12 Installation .......................................................................................... 108
13 Commissioning .................................................................................. 132
14 Maintenance ....................................................................................... 135
15 Control system .................................................................................. 137
Appendix ................................................................................................. 174
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
1 General information
1.1Nomenclature
M G C T S L - D 60 W / R N1 - A
Design Serial Number Refrigerant type
N1:R410A Omit for R22
Power Supply
R: 380~415V, 50Hz, 3N D: 220V, 60Hz, 3N
Outdoor Unit Rated cooling capacity (kw) The special function code
D: Digital scroll F: Constant feed V: Inverter system
The special function code
S: Hydraulic mole L: Low temperature cooling H: Heat recovery Omit for 10 - 46C T: 10 - 52C
The heat exchanger type
A: Plate heat exchanger B: Tube and shell C: Tube in tube heat exchanger
Light chiller system MDV
1.2 Product schedule
No Model Power supply
1 MGB-F25W/RN1 380~415V/3ph/50Hz Tube in tube 16 400 KJR-08B/BE
2 MGB-D25W/RN1 380~415V/3ph/50Hz Tube in tube 16 400 KJR-08B/BE
3 MGB-F30W/RN1 380~415V/3ph/50Hz Tube in tube 16 480 KJR-08B/BE
4 MGB-D30W/RN1 380~415V/3ph/50Hz Tube in tube 16 480 KJR-08B/BE
5 MGCSL-F30W/RN1
6 MGCSL-D30W/RN1
7 MGB-F55W/RN1 380~400V/3ph/50Hz Tube and shell 16 880 KJR-08B/BE
8 MGB-F60W/RN1 380~400V/3ph/50Hz Tube and shell 16 960 KJR-08B/BE
9 MGB-F65W/RN1 380~400V/3ph/50Hz Tube and shell 16 1040 KJR-08B/BE
10 MGB-D65W/RN1 380~415V/3ph/50Hz Tube and shell 16 1040 KJR-120A/MBE
11 MGB-F130W/RN1 380~400V/3ph/50Hz Tube and shell 8 1040 KJR-08B/BE
12 MGB-F185W/RN1 380~400V/3ph/50Hz Tube and shell 5 1000 KJR-08B/BE
13 MGBT-F250W/RN1 380~400V/3ph/50Hz Tube and shell 8 2000 KJR-120A/MBE
380~415V/3ph/50Hz
380~415V/3ph/50Hz
Heat
exchanger type
Tube in tube 1 30 KJR-120A/MBE
Tube in tube 1 30 KJR-120A/MBE
Maximum
combinations
Maximum
capacity(kw)
Wired controller
3
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
1.3 External appearance:
New 30KW module
25/30KW module
55/60/65KW module 130KW module
185KW module
250KW module
4
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
2. Features
1). Low ambient temperature cooling function (Only for MGCSL-F30W/RN1 and MGCSL-D30W/RN1)
The ambient temperature is down to -10 in cooling mode, the cooling operating temperature up to 52˚C in tropical model and heating down to -10˚C ambient by added one board (see picture1). Wide ambient temperature range is selectable by adjustable address between different conditions to meet different requirements.
Mode Ambient temp.
NormallyS8 address OFF
Cooling
T condition
Low temp. (S8 address ON)
Heating
2). Wide range of outlet water temperature (For MGCSL-F(D)30W/RN1 ,MGB-D65W/RN1, MGB-F250W/RN1)
Cooling: 5~17˚C (Set in factory), 0~17˚C can be available by switch the S5 on PCB, the antifreeze must be put into pipeline.
10~46 10~52
-10~46
-10~21
Picture1
Heating: 40~50˚C (Set in factory), 22~50˚C can be available by switch the address.
Mode Outlet water temp.
Cooling(S5 address)
Heating(S4 address)
Normally(OFF) Low water temp.(ON)
Normally(OFF) Low water temp. (ON)
5~17 0~17
45~50 22~50
Picture2
3).Built-in hydraulic module (Only for MGCSL-F30W/RN1 and MGCSL-D30W/RN1)
The unit built-in hydraulic module to simplified installation, save space and beautification appearance, simultaneous effectively reduce installation costs and covering area.
auto-air exchanse valve
2-way valve
Expansion tank
Double
-pipe heat exchanger
Water pump
Safety valve
Y-shaped filiter
Water-flow valve
Water replenishing valve
1.5kg<Water replenishing pres<6kg
Flexible joint
Flexible joint
Aux. heater
Thermometer
Cutoff valve
Manometer
Flexible joint
2-way valve
Flexible joint
Fan coil unit
Fan coil unit
Fan coil unit
Fan coil unit
This figure for reference purpose only, please in terms of the design rule for field installation.
5
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
4).Humanization remote control (For MGCSL-F(D)30W/RN1 ,MGB-D65W/RN1, MGB-F250W/RN1)
S7 address on PCB should be switched to ON to realize remote control, here are reliable: Remote ON/OFF, remote heating and cooling mode selection, remote alarm. The customer can simply and conveniently control the module and acquire the running information on real time in door.
5)Digital scroll techniquenew type modular air-cooled chiller system.
Capacity output is controlled depending on controlling compressor to on/off in traditional modular air-cooled chiller system control. The precision of the control mode is not very good, and the compressor is frequently on and off, which is very bad for the compressor’s life.
Digital scroll modular air-cooled chiller system breaks traditional design, which is inconceivably designed with digital scroll compressor and constant scroll compressor parallel connection. the system can achieve linear capacity adjustment within 0.5%-100%,the scope is widest in industry. When the system operates at the part-load, the system can accurately adjust cooling and heating capacity output basing on actual requirement of the indoor room.
6).Modular design, flexible combination, more convenient for design and installation.
The unit adopt modular design, which can makes more unit connect together. The unit can combine 16 separate module(25,30.55.60.65KW module) or 8 module(250KW module).Cooling(heating) capacity can increase step by step by 5KW per each time within 25kW-2000kW,meanwhile every separate module can operate as main unit, also each module can be a slave unit with modules combination, more convenient for design and installation.
Max 8 modules
250KW
250KW
2000KW
7).The maximum combination of the system consists of 1 main unit and 15 slave units for 25,30.55.60 and 65KW module, 1 main unit and 7 slave units for 130KW module, 1 main unit and 4 slave units for 200KW module1 main unit and 7 slave units for 250KW module.
Easy connection between main unit and slave units. All the units can be connected together with a wired controller in series type. Using three-core shielded twisted wire as communication wire.
Wa te r outlet temp.
Wa te r outlet temp.
Wa te r outlet temp.
Wired c on troller
6
Total w a te r o u tlet te mp. (Just fo r m a s te r u n it)
Thre e - c o re s hielding twisted pair
Total w a te r o u tlet te mp. (Just for m a s te r u n it)
Three-core shielding twisted pair
Total w a te r o u tlet te mp. (Just fo r maste r unit)
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
8).Environmental care
Ecological R410A refrigerant.
Chlorine-free and environmental friendly refrigerant, zero ozone depletion potential.
High density refrigerant, therefore, less refrigerant required.
Leak-tight refrigerant circuit, Brazed refrigerant connections for increased leak-tightness.
9) Economical operation
New design adopts electronic expansion valve precise refrigerant control in wider range. Electronic expansion valve allows operation at lower condensing pressure, adjustment can be made fast linear response, making the system more stable output, the indoor temperature more uniform, and enhance human comfortable.
10).Compact structure
Air cooled modular chiller structure are compact, light weight. The system adopts tube in tube, shell and tube heat exchanger, not only greatly enhanced the transfer performance, but also reduce the unit weight, the lightest single module only has 380kg.
The characteristic of unit decided cooling tower is not needed, not only reduced installation costs, but also resolved the cooling tower generated noise when running.
11).Back up function
When unit is failure
If master unit fails, all the units will stop. If one slave unit fails, this unit will stop but the others will keep running. When the master unit fails, any of the slave one can be set as the master unit by manual setting.
When unit is under protection
If master unit’s protection occurs, this unit will stop but the others will keep running. If slave unit’s protection occurs, this unit will stop but the others will keep running. ( Except PE, P9
Master Slave
protection happen
)
Master Slave
12).Strong micro-computer intelligent control and monitor function.
Optimizing the design of system and using varieties of protection devices, to make the system more safe and reliable.
13). Superior reliability
System will be more reliable with new type efficient heat exchanger.
7
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
Coo
ge
C
Evaporator of 25KW and 30KW module adopts tube in tube heat exchanger,evaporator of 60kw ,120kw and 180kw modules adopt Shell and tube heat exchanger.
Tube in tube heat exchanger Shell and tube heat exchanger
14). Applicable temperature range
Mode
Cooling
Heating -10˚C ~21˚C
Ambient temperature
range
10˚C ~46˚C
-10˚C ~46˚C 5˚C ~17˚C Only for MGCSL-F(D)30W/RN1
Water outlet temperature range Application module
5˚C ~17˚C (7˚C is default) The module with KJR-08B/BE
0~17˚C(0˚C must add antifreeze)
45˚C ~50˚C (45˚C is default) The module with KJR-08B/BE
22˚C ~50˚C
For MGCSL-F(D)30W/RN1,MGBT-D65W/RN1,
MGBT-F250W/RN1
For MGCSL-F(D)30W/RN1,MGBT-D65W/RN1,
MGBT-F250W/RN1
Ambient temperature range
Cooling range-10˚C
46˚C
-10˚C 21˚C
Heating range
10˚
ling ran
46˚C
-15˚C
-10˚C -5˚C 0˚C 5˚C 10˚C 15˚C
20˚C
30˚C 35˚C 40˚C
25˚C
45˚C
Chilled outlet water temperature can be adjusted by wire controller according to customer’s demand.
Water outlet temperature range
0˚C
8
5˚C
0˚C
5˚C
Cooling range
Cooling range
17˚C
17˚C
17˚C
22˚C
22˚C
Heating range
45˚C
45˚C
Heating range
50˚C
50˚C
50˚C
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
3. Specification
Model MGB-F25W/RN1 MGB-F30W/RN1
Cooling Capacity
Heating Capacity kW 29.5 32
Power supply V/Ph/Hz 380-415/3/50
Manual switch A 50
Power supply
Fuse A 36
Type Scroll (constant speed)
Quantity Pieces 2
Model ZP67KCE-TFD-522
Brand Copeland
Compressor
Capacity W 16200×2
Input W 5200×2
Rate current(RLA) A 9.1×2
Locked rotor Amp(LRA) A 74×2
Cooling kW 9.3 10.0
Cooling rated current A 14.6 16.3
Power input
Heating kW 9.2 9.8
kW 28 30
Btu/h 95,500 102,300
Heating rated current A 14.3 16
Max. Input consumption A 12.6
Max. Current A 21.8
Type R410a
Refrigerant
Condenser (Air side)
Evaporator (Water side)
Weight kg 3.5×2
Refrigerant control EXV+ capillary throttle
Air side heat-exchanger type Copper-fin-coil
Quantity of fan motor Pieces 1
Air flow volume ×103m3/h 12
Fan motor input kW 0.3
Water side heat-exchanger type Tube in tube
Water resistance loss kPa 60
Water inlet/outlet pipeline inside normal diameter
Water flow volume m3/h 4.4 5.2
Max. Pressure MPa 1
Water pipe connection type Flexible joint
mm DN40
inch 1-1/2”
Net(W×H×D)
mm
inch
Dimension
mm
Packing(W×H×D)
inch
Weight Net weight kg 380
1514×1865×841
59.6×73.4×33.1
1590×2065×995
62.6×81.3×39.2
9
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
Operation weight kg 400
Power wire mm
2
×No. 10×4+10×1
Connection wire
Signal wire mm2×No. 0.75×3-core
Control type Wired controller
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-frozen protection in cooling mode.
5) Anti-frozen protection in Winter.
Safety protection device
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temperature difference protection.
9) Compressor discharge temp. protection.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
Noise level(semi-anechoic ) dB(A) 65
Operation water temp Cooling:5~17 Heating:45~50
Ambient temp
Cooling1046
Heating-1021
Note: Please refer to the water flow volume in the above table strictly to design and install. All the above data is measured base on the following working condition:
1. cooling mode under normal working condition: water flow 0.172 m
3
/(h•kW), outlet water temperature of chilled water is
7,air inlet temperature of condenser is 35;
2. heating mode under normal working condition: water flow 0.172 m3/(h•kW), outlet water temperature of chilled water is 45,air inlet temperature of condenser is DB/WB 7/6.
10
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
Model MGB-D25W/RN1 MGB-D30W/RN1
Cooling Capacity
Heating Capacity kW 29.5 32
Power supply V/Ph/Hz 380-415/3/50
Power supply
Compressor
Power input
Max. Input consumption A 12.5
Max. Current A 21.5
Refrigerant
Condenser (Air side)
Evaporator (Water side)
Dimension
Weight
Connection wire
Manual switch A 50
Fuse A 36
Type Constant Speed Scroll + Digital Scroll
Quantity Pieces 1+1
Model
Brand Copeland
Capacity W 16200+16200
Input W 5200+5260
Rate current(RLA) A 9.1+9.3
Locked rotor Amp(LRA) A 74+74
Cooling kW 9.3 10.0
Cooling rated current A 14.6 16.3
Heating kW 9.2 9.8
Heating rated current A 14.3 16
Type R410a
Weight kg 3.5×2
Refrigerant control EXV+ capillary throttle
Air side heat-exchanger type Copper-fin-coil
Quantity of fan motor Pieces 1
Air flow volume ×103m3/h 12
Fan motor input kW 0.3
Water side heat-exchanger type Double-pipe heat exchanger
Water resistance loss kPa 60
Water inlet/outlet pipeline inside normal diameter
Water flow volume m3/h 4.4 5.2
Max. Pressure MPa 1
Water pipe connection type Flexible joint
Net(W×H×D)
Packing(W×H×D)
Net weight kg 380
Operation weight kg 400
Power wire mm2×No. 10×4+10×1
Signal wire mm2×No. 0.75×3-core
kW 28 30
Btu/h 95,500 102,300
ZP67KCE-TFD-522+
ZPD67KCE-TFD-532
mm DN40
inch 1-1/2”
mm
inch
mm
inch
1514×1865×841
59.6×73.4×33.1
1590×2065×995
62.6×81.3×39.2
Control type Wired controller
11
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-frozen protection in cooling mode.
5) Anti-frozen protection in Winter.
Safety protection device
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temperature difference
protection
9) Compressor discharge temp. protection.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
Noise level(semi-anechoic ) dB(A) 65
Operation water temp Cooling:5~17 Heating:45~50
Ambient temp Cooling:10~46 Heating:-10~21
Note: Please refer to the water flow volume in the above table strictly to design and install. All the above data is measured base on the following working condition:
1. cooling mode under normal working condition: water flow 0.172 m
3
/(h•kW), outlet water temperature of chilled water is
7,air inlet temperature of condenser is 35;
2. heating mode under normal working condition: water flow 0.172 m3/(h•kW), outlet water temperature of chilled water is 45,air inlet temperature of condenser is DB/WB 7/6.
12
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
Model MGCSL-F30W/RN1 MGCSL-D30W/RN1
Cooling Capacity
Heating Capacity kW 32 32
Power supply V/Ph/Hz 380-415/3/50
Power supply
Compressor
Power input
Max. Input consumption A 13.4
Max. Current A 22.5
Refrigerant
Condenser (Air side)
Evaporator (Water side)
Dimension
Weight
Connection wire
Manual switch A 50
Fuse A 36
Type Fixed speed Digital Scroll + Fixed speed
Quantity Pieces 1+1 1+1
Model ZP67KCE-TFD-522
Brand Copeland
Capacity W 16200×2
Input W 5200×2
Rate current(RLA) A 9.1×2
Locked rotor Amp(LRA) A 74×2
Cooling kW 10 10
Cooling rated current A 16.3 16.3
Heating kW 9.8 9.8
Heating rated current A 16 16
Type R410A
Weight kg 3.5×2
Refrigerant control EXV
Air side heat-exchanger type Fin-coil
Quantity of fan motor Pieces 1
Air flow volume ×103m3/h 12
Fan motor input kW 0.55
Water side heat-exchanger type Double-pipe
Water resistance loss kPa /
Water inlet/outlet pipeline inside normal diameter
Water flow volume m3/h 5.2 5.2
Max. Pressure MPa 1
Water pipe connection type Flexible joint
Net(W×H×D)
Packing(W×H×D)
Net weight kg 430
Operation weight kg 450
Power wire mm2×No. 10×4+6×1
Signal wire mm2×No. 0.75×3-core with shielding
kW 30 30
Btu/h 102,300 102,300
ZPD67KCE-TFD-532/
ZP67KCE-TFD-522
mm DN40
inch 1-1/2”
mm
inch
mm
inch
1514×1865×841
59.6×73.4×33.1
1590×2065×995
62.6×81.3×39.2
Control type Wired controller
13
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-frozen protection in cooling mode.
5) Anti-frozen protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
Safety protection device
8) Outlet and inlet water temperature difference
protection.
9) Compressor discharge temp. protection.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
12) Low ambient temperature drive-up protection
13) Low-temperature protection of shell-and-tube heat
exchanger.
Noise level(semi-anechoic ) dB(A) 67
Operation water temp
Ambient temp
Cooling:0~17(0 must add antifreeze)
Heating:22~50
Cooling-1046 Heating-1021
Note: Please refer to the water flow volume in the above table strictly to design and install. All the above data is measured base on the following working condition:
1. cooling mode under normal working condition: water flow 0.172 m
3
/(h•kW), outlet water temperature of chilled water is
7,air inlet temperature of condenser is 35;
2. heating mode under normal working condition: water flow 0.172 m3/(h•kW), outlet water temperature of chilled water is 45,air inlet temperature of condenser is DB/WB 7/6.
14
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
Model MGB-F55W/RN1 MGB-F60W/RN1 MGB-F65W/RN1
Cooling Capacity
Heating Capacity kW 59 64 69
Power supply V/Ph/Hz 380-400/3/50
Power supply
Compressor
Power input
Manual switch A 125
Fuse A 100
Type Fixed speed Scroll
Quantity Pieces 2
Model SH140A4ALC
Brand Danfoss
Capacity W 34700×2
Input W 10860×2
Rate current(RLA) A 21.4×2
Locked rotor Amp(LRA) A 147×2
Cooling kW 17.5 19.3 20.4
Cooling rated current A 30.5 33.6 36.5
Heating kW 18.3 19.8 21.5
kW 55 60 65
Btu/h 187,660 204,700 221,780
Heating rated current A 31.5 34.3 37.2
Max. Input consumption A 28.2
Max. Current A 47.6
Type R410a
Refrigerant
Condenser (Air side)
Evaporator (Water side)
Weight kg 7×2
Refrigerant control EXV+ capillary throttle
Air side heat-exchanger type Copper-fin-coil
Quantity of fan motor Pieces 2
Air flow volume ×103m3/h 24
Fan motor input kW 0.65
Water side heat-exchanger type Shell and tube
Water resistance loss kPa 15
Water inlet/outlet pipeline inside normal diameter
Water flow volume m3/h 9.4 10.3 11.2
Max. Pressure MPa 1
Water pipe connection type Flexible joint
mm DN100
inch 4”
Dimension
Weight
Net(W×H×D)
mm
inch
mm
Packing(W×H×D)
inch
Net weight kg 580
Operation weight kg 650
2000×1880×900
78.7×74×35.4
2090×2055×985
82.3×80.9×38.8
15
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
2
Connection wire
Control type Wired controller
Safety protection device
Noise level(semi-anechoic ) dB(A) 67
Power wire mm
Signal wire mm2×No. 0.75×3-core
×No. 16×4+10 ×1
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-frozen protection in cooling mode.
5) Anti-frozen protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temperature difference protection.
9) Compressor discharge temp. protection.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
Operation water temp
Ambient temp Cooling:10~46 Heating:-10~21
Cooling517 Heating4550
Note: Please refer to the water flow volume in the above table strictly to design and install. All the above data is measured base on the following working condition:
1. cooling mode under normal working condition: water flow 0.172 m 7,air inlet temperature of condenser is 35;
2. heating mode under normal working condition: water flow 0.172 m3/(h•kW), outlet water temperature of chilled water is 45,air inlet temperature of condenser is DB/WB 7/6.
3
/(h•kW), outlet water temperature of chilled water is
16
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
Model
MGB-D65W/RN1
MBG-F130W/R(S)N1
MGB-F185W/R(S)N1
Cooling Capacity
kW 65 130 185
Btu/h 221,780 443,560 631,220 Heating Capacity kW 69 138 200 Power supply V/Ph/Hz 380-415/ 3/50 380-400/3/50 380-400/3/50
Power supply
Manual switch A 150 250 400 Fuse A 100 200 300
Type Scroll (fixed speed+digital scroll) Fixed speed Scroll Fixed speed Scroll Quantity Pieces 3 4 6
ZP144KCE-TFD-522 /
Model
ZPD72KCE-TFD-433 /
SH140A4ALC SH140A4ALC
ZP67KCE-TFD-420
Compressor
Brand Copeland Danfoss Danfoss Capacity kW 36 17 16.3 34.7×4 34.7×6 Input kW 10.8 5.75 5.2 10860×4 10860×6 Rate current(RLA) A 18.7 9.8 9.1 21.4×4 21.4×6 Locked rotor Amp(LRA) A 144 82.4 74 147× 4 147×6 Cooling kW Cooling rated current A
Power input
Heating kW
Heating rated current A Max. Input consumption A Max. Current A
20.4
36.5
21.5
37.2
28.2 55.5 78.3
47.6 93.8 133.4
40.8 63 73 110
43.0 61
74.4 107
Type R410a R410a R410a
Refrigerant
Condenser (Air side)
Evaporator (Water side)
Dimension
Weight kg 7×2 7×4 7×6
Refrigerant control EXV+ capillary throttle
EXV+ capillary
throttle
EXV+ capillary
throttle Air side heat-exchanger type Copper-fin-coil Copper-fin-coil Copper-fin-coil Quantity of fan motor Pieces 2 4 6 Air flow volume ×103m3/h 24 48 72 Fan motor input kW 0.55×2 1.3 1.3 Water side heat-exchanger type Shell and tube Shell and tube Shell and tube Water resistance loss kPa 15 25 30
Water inlet/outlet
mm DN100 DN65 DN80
pipeline inside normal diameter
inch 4’’ 2-1/2” 3” Water flow volume m3/h 11.2 22.4 31.8 Max. Pressure MPa 1 1 1 Water pipe connection type Flexible joint Flexible joint Flexible joint
Net(W×H×D)
mm 2000×1880×900
inch 78.7×74×35.4
mm 2090×2020×985 Packing(W×H×D)
inch 82.3×80.9×38.8
2000×2090×1685 2850×2110×2000
78.7×82.3×66.3 112.2×83.1×78.7
2090×2240×1755 2980×2260×2135
82.3×88.2×69 117.3×89×84.1
17
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
Weight
Control type Wired controller Wired controller
Safety protection device
Noise level(semi-anechoic ) dB(A) 67 70 74
Net weight kg 600 1150 Operation weight kg 670 1270 Power wi re mm2×No. 25×4+16×1 35×3+16×2 75×3+35 ×2 Signal wire mm2×No. 0.75×3-core 0.75×3-core
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-frozen protection in cooling mode.
5) Anti-frozen protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temperature difference protection.
9) Compressor discharge temp. protection.
10) Water flow cut-off protection.
11)Sensor malfunction protection.
12)Low ambient temperature drive-up protection
13)Low-temperature protection of shell-and-tube heat exchanger.
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-frozen protection in cooling mode.
5) Anti-frozen protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temperature difference protection.
9) Compressor discharge temp. protection.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
1730 2000
Cooling:0~17(0 must add
Operation water temp
Ambient temp Cooling:1046 Heating:-1021 Cooling1046 Heating-1021
Note: Please refer to the water flow volume in the above table strictly to design and install. All the above data is measured base on the following working condition:
1. cooling mode under normal working condition: water flow 0.172 m3/(h•kW), outlet water temperature of chilled water is 7,air inlet temperature of condenser is 35;
2. heating mode under normal working condition: water flow 0.172 m3/(h•kW), outlet water temperature of chilled water is 45,air inlet temperature of condenser is DB/WB 7/6.
antifreeze)
Heating2250
Cooling:5~17 Heating4550
18
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
Model MGBT-F250W/RN1
Cooling Capacity
Heating Capacity kW 270
Power supply V/Ph/Hz 380-400/3/50
Power supply
Compressor
Power input
Max. Input consumption A
Max. Current A
Refrigerant
Condenser (Air side)
Evaporator (Water side)
Dimension
Weight
Connection wire
Manual switch A 450
Fuse A 350
Type Scroll (fixed speed)
Quantity Copeland 8
Model SH120A4ALC
Brand
Capacity W
Input W
Rate current(RLA) A
Locked rotor Amp(LRA) A
Cooling kW
Cooling rated current A
Heating kW
Heating rated current A
Type R410A
Weight kg 15×4
Refrigerant control EXV+ capillary throttle
Air side heat-exchanger type Fin-coil
Quantity of fan motor Pieces 8
Air flow volume ×103m3/h 96
Fan motor input kW 5.6
Water side heat-exchanger type Shell-tube
Water resistance loss kPa 40
Water inlet/outlet pipeline inside normal diameter
Water flow volume m3/h 43
Max. Pressure MPa 1
Water pipe connection type Flexible joint
Net(W×H×D)
Packing(W×H×D)
Net weight kg 2450
Operation weight kg 2600
Power wire mm2×No. 185×4+70×1
Signal wire mm2×No. 0.75×3-core with shielding
kW
Btu/h
mm DN100
inch 4”
mm
inch
mm
inch
149.6×83.86×78.74
153.54×86.61×82.68
250
830,000
Copeland
111231
10275
20.88
177
78.3
141.9
80
146
104.9
194.6
3800×2130×2000
3900×2200×2100
Control type Wired controller
19
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-frozen protection in cooling mode.
5) Anti-frozen protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
Safety protection device
8) Outlet and inlet water temperature difference
protection.
9) Compressor discharge temp. protection.
10) Water flow cut-off protection.
11)Sensor malfunction protection.
12)Low ambient temperature drive-up protection
13)Low-temperature protection of shell-and-tube heat
exchanger.
Noise level(semi-anechoic ) dB(A) 74
Operation water temp
Ambient temp
Cooling:0~17(0 must add antifreeze)
Heating:22~50
Cooling1052
Heating-1021
Note: Please refer to the water flow volume in the above table strictly to design and install. All the above data is measured base on the following working condition:
1. cooling mode under normal working condition: water flow 0.172 m
3
/(h•kW), outlet water temperature of chilled water is
7,air inlet temperature of condenser is 35;
2. heating mode under normal working condition: water flow 0.172 m3/(h•kW), outlet water temperature of chilled water is 45,air inlet temperature of condenser is DB/WB 7/6.
20
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
4 Dimension
25/30kw module
Front view
Top view
Model
MGB-F(D)25W/RN1 MGB-F(D)30W/RN1
Unit
mm
A B C D E F
1514 841 1865 115 315 172
inch 59.6 33.11 73.43 4.53 12.4 6.77
21
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
No. Name
1 Top cover
2 Air outlet
3 Air inlet
4 Water outlet
5 Water inlet
6 Electric control box
22
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
30KW new module
(Only for MGCSL-F30W/RN1 and MGCSL-D30W/RN1)
1865
874
317
Front view
Left view
Top view
23
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
1
3
4
2
1
NO.
NAME
5
6
12 3 4
Air outletAir inlet Water outlet DrainWater inlet
Make-up
water inlet
5
6
24
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
55/60/65KW module
Model
Unit
Front view
Top view
A B C D E F G H I J K
MGB-F55W/RN1 MGB-F60W/RN1 MGB-F65W/RN1 MGB-D65W/RN1
mm
inch 78.74 35.4 74 13.78 55.91 8.86 59.06 19.92 20.87 36.61 17.72
2000 900 1880 350 1420 225 1500 506 530 930 450
25
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
No. Name
1 Top cover
2 Air outlet
3 Air inlet
4 Water outlet
5 Compressor
6 Electric control box
7 Water inlet
26
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
130KW module
Front view Side view
MGB-F130W/RN1
Model
Top view Anchor hole
A B C D E F G H
Unit
2000 1685 2080 350 1420 506 1550 1586
mm
inch 78.74 66.34 81.89 13.78 55.91 19.92 61.02 62.44
27
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
No. Name
1 Top cover
2 Condenser
3 Compressor
4 Evaporator
5 Electric control box Air inlet
6 Water outlet
7 Water inlet
8 Compressor
28
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
185KW module
Model unit A B C D E F G H
Mm 2850 2000 2110 3470 2156 506 1888 2388
MGB-F185W/RN1
inch 112.2 78.74 83.07 136.61 84.88 19.92 74.33 94.02
29
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
No. Name
1 Top cover
2 Compressor
3 Evaporator
4 Water outlet
5 Electric control box
6 Water inlet
7 Condenser
30
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
H
H
G
250KW module
C
F
D
A
Front view
E
B
Left view
A
Hole for anchor boltΦ15
Bottom view
Model unit A B C D E F G H
Mm 3800 2000 2130 1235 2156 573 1888 1551
MGB-F250W/RN1
inch 149.6 78.74 83.86 48.62 84.88 22.56 74.33 61.06
31
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
A
Air outlet
Air outlet
Air outlet
Air outlet
1
A
i
r
i
n
l
e
ir inlet
A
i
r
i
n
l
e
t
t
e
l
n
i
r
i
A
A
i
r
i
n
l
e
t
t
7
6
5
2
No. Name
1 Top cover
2 Compressor
3 Evaporator
4 Water outlet
5 Electric control box
6 Water inlet
7 Condenser
8
Transportation guard plate (Be removed off after installation)
8
4
3
32
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
5 Refrigeration system drawing
5.1 25/30KW module refrigeration system sketch drawing
Each module has two compressors with two separate units, one double-pipe evaporator for two systems.
Fan
4-way valve A
Discharge pipe
Compressor A
Suction pipe
Low pressure cylinder A
4-way valve B
Compressor B
Water outlet
Low pressure cylinder B
Water inlet
Evaporator (Double-pipe heat exchanger)
Condenser
Filter A
throttle parts A
throttle parts B
Filter B
5.2 55/60/65KW module refrigeration system sketch drawing(Fixed speed)
Each module has two compressors with two separate units, one shell and tube evaporator for two systems.
Compressor B
Compressor A
low pressure cylinder B
4-Way valve B
Fan A
Condenser
4-Way valve A
low pressure cylinder A
Fan B
Capillary
Capillary
4"
Water flow direction
EXV
Dry type evaporator
EXV
33
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
65KW digital module refrigeration system sketch drawing (MGB-D65W/RN1)
Each module has three compressors with two separate units, one shell and tube evaporator for two systems.
Pressure switch
low pressure cylinder B
Compressor B
Discharge switch
Com. A1 digital
Pressure switch
Pressure switch
Com. A2
4-Way valve B
Pressure switch
Fan A
Fan B
Condenser
Pressure switch
T3B
Capillary
T3A
Capillary
Water flow direction
EXV
Dry type evaporator
EXV
Discharge switch
Pressure switch
4-Way valve A
low pressure cylinder A
5.3 130KW module refrigeration system sketch drawing
Each module has four compressors with two separate units, one shell and tube evaporator for four systems
low pressure cylinder B
Unit 2
Compressor B
4-Way valve B
Fan A
Condenser
Fan B
Capillary
Capillary
Water flow direction
EXV
Dry type evaporator
EXV
2-1/2"
Compressor A
34
4-Way valve A
Unit 1
low pressure cylinder A
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
5.4 185KW module refrigeration system sketch drawing
Each module has six compressors with three separate units, one shell and tube evaporator for six systems.
low pressure cylinder B
Unit 2
Compressor B
Compressor A
4-Way valve B
Fan A
Condenser
4-Way valve A
Fan B
Capillary
Capillary
Water flow direction
EXV
Dry type evaporator
EXV
3"
Unit 3
Unit 1
low pressure cylinder A
5.5 250KW module refrigeration system sketch drawing
Each module has eight compressors with two separate units, one shell and tube evaporator for four systems
low pressure cylinder B
Unit 2
Compressor B2
Compressor B1
Compressor A2
4-Way valve B
Fan A
Condenser
Fan B
Capillary
Capillary
4"
Water flow direction
EXV
Dry type evaporator
EXV
Compressor A1
4-Way valve A
Unit 1
low pressure cylinder A
35
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
6. Piping diagram
6.1 25/30KW module water pipeline sketch drawing
The table below describes the symbols.
Symbol Symbol explanation Symbol Symbol explanation
Stop valve
Pressure gauge
Water flow switch
Gate valve
Flexible joint
Y-shaped filter
Thermometer
Circulating pump
Check valve
Automatic discharge valve
36
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
30KW module water pipeline sketch drawing
auto-air exchanse valve
Water pump
Expansion tank
Y-shaped filiter
Water-flow valve
Water replenishing valve
1.5kg<Water replenishing pres<6kg
Double
-pipe heat exchanger
Safety valve
Flexible joint
Flexible joint
This figure for reference purpose only, please in terms of the design rule for field installation.
The table below describes the symbols.
Aux. heater
Thermometer
2-way valve
Flexible joint
2-way valve
Flexible joint
Cutoff valve
Manometer
Fan coil unit
Fan coil unit
Fan coil unit
Fan coil unit
Symbol Symbol explanation Symbol Symbol explanation
Safety valve
Y-shaped filter
Pressure gauge
Water flow switch
Cut off valve
Manometer
Thermometer
Water pump
Expansion tank
Water replenishing valve
37
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
6.2 55/60/65kw&(65kw digital) module water pipeline sketch drawing
DN100
The table below describes the symbols.
Symbol Symbol explanation Symbol Symbol explanation
Stop valve
Pressure gauge
Water flow switch
Gate valve
Flexible joint
Y-shaped filter
Thermometer
Circulating pump
Check valve
Automatic discharge valve
38
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
6.3 130KW module water pipeline sketch drawing
The table below describes the symbols.
Symbol Symbol explanation Symbol Symbol explanation
Stop valve
Pressure gauge
Water flow switch
Gate valve
Flexible joint
Y-shaped filter
Thermometer
Circulating pump
Check valve
Automatic discharge valve
39
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
6.4 185KW module water pipeline sketch drawing
The table below describes the symbols.
Symbol Symbol explanation Symbol Symbol explanation
Stop valve
Pressure gauge
Water flow switch
Gate valve
Flexible joint
Y-shaped filter
Thermometer
Circulating pump
Check valve
Automatic discharge valve
40
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
6.5 250KW module water pipeline sketch drawing
Expansion tank
Main unit
The table below describes the symbols.
Water replenishing
Differential pressure by-pass valve
Drain valve
Auxiliary electric heater
Dirt discharge valve
Te rm i na l
Two-way valve
Three-way valve
Symbol Symbol explanation Symbol Symbol explanation
Stop valve
Pressure gauge
Water flow switch
Gate valve
Flexible joint
Y-shaped filter
Thermometer
Circulating pump
Check valve
Automatic discharge valve
41
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
7 Wire Diagrams
7.1 Chiller wiring diagram
25/30KW module
Attached Drawing (I) Electric Drawing of Main Unit and Auxiliary Unit
42
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
30KW new module (Only for MGCSL-F30W/RN1 and MGCSL-D30W/RN1)
XT4
MIDDLE
WIRE JOINT
BLAC K
Y&G
FAN CAP
T3A2
WHITE
RED
CN2
COLD MOD ULE
BLUE
8
LOW
BLUE
BLUE
BLACK
BLUE
BLUE
CN1
RED
RED
RED
2
6
4
RELAY
KM1
HIGH
BROWN
BLUE
Y&G
U
HEAT_A
PUMP
RED
PUMP
W
V
WHITE
BLUE
BLACK
2
6
4
A2
22
3
5
21
A1
RELAY
YEL LOW
BROWN
AC CONTACTOR
RED
BLU E
WHIT E
Y&G
T1(U)
RED
CRANK
WHITE
BLACK
A2
A1
COMPRESSOR A
COMP A
T3(W)
T2(V)
BLUE
2
6
4
22
3
5
21
AC CONTACTOR
RED
RED
RED
BLUE
WHITE
HEAT_B
) C N ( ) M O C ( ) O N (
POWER PROTECTOR
Y&G
T1(U)
RED
CRANK
E U
D
L
E
B
R
COMPR ESSO RB
COMP B
T3(W)
T2(V)
BLUE
WHITE
BLACK
2
6
4
A2
22
3
1
5
A1
21
RED
E
D
U
E
L
R
B
ORANGE
PWM PRESSURE
RELIF VALVE
RED
RED
XT7
MIDDLE
WIRE JOINT
AC CONTACTOR
RED
BLACK
RED
S.V(A)
4-VALVE A
XT5
MIDDLE
WIRE JOINT
BLUE
BLUE
BLUE
BLACK
BLACK
BLACK
BLACK
S.V(A)
4-VALVE B
BLACK
XT6
MIDDLE
WIRE JOINT
PURPLE
BLACK
MARK:NORMA L MO DU LE S DO N 'T INC LU DE
Y&G
202090191055
BROKEN LINE AND THEIR J OINT WIRES
OUTDOO R W IRIN G DIAGRAM
BLACK
BLACK
BLACK
CN8
CN7
CN6
CN5
L3 L4
CURRENT BOARD
L1 L2
CN4
XS9
XP9
T
4
WHITE
TEMP B
CONDENSER
RED BLACK
TE MP A
CONDENSER
BLACK
BLACK
XS8
XP8
3
B
T
A
3
T
XS7
XP7
ANTI-FREEZING TEMP SENSOR
UNIT OUT-LET WATER TEMP
IN-LET WATER TEMPSENSOR
TOTAL OUT-LET WATER TEMP
PWM(B)
PWM(A)
CURRENT(A2)
TRANS
CN19(WHIT E)
TRANS OUT
5V
CN15
CN14
T3A T3B T4
CN26
CN21
CN22
MAIN BOARD
CN10
CN1(WHIT E)
PMV(A)
CN2(RED)
PMV(B)
ON/OFF
RED
ORANGE
YELLOW
H_PRO(A)
H_PRO(B)
HIGH PRESSURE
PROTECTOR A
K1(A)
TEMP PROTECTOR
SWITCH A
CURRENT( B2)
L_PRO(1A)
HIGH PRESSURE
PROTECTOR B
K1(B)
TEMP PROTECTOR
SWITCH B
RED
BLUE
BLACK
WHITE
PWM
POWER
CN18(WHITE)
S9
ON
OFF
S7 S8
SW3
S1
S4 S5
ON
OFF
S2 S3
SW2
CHECK
CN6
CN25
CN5
H&L_PRO
PURPLE
L_PRO(1B)
LOW PRESSURE
PROTECTOR 1B
LOW PRESSURE
PROTECTOR 1A
COM(I)
COM(O)
PURPLE
BLUE
CN17
FAN_B
CN31
FAN_A
CN30
BLUE
RED
PURPLE
CN11(BLACK )
ORANGE
YELLOW
P2
CN24
PUMP
(YELLOW)(RED)
RED
P1
BLUE
BLUE
HEAT
(BLUE)
RED
L_PRO(2B)
L_PRO(2A)
BLACK
BLUE
WHITE
RED
XT1
4-WAY TERMINA L
ON
OFF
1 2 3
SW3
FIXED
3 4
1 2
SW2
ON
OFF
S7 ON:REMOT E CONTROL OFF:WIR E CONTROL
S8 ON:LOW T EMP.MODE OFF:NOR M AL
S9 ON:30KW OFF:65/ 1 30/200/2 60KW
ON
ADDRE SS
DAIL SWITCH
S1
S2 ON:COOL ONLY OFF :R&C
S3 ON:DIGIT AL OFF : FIXED
SW2/S W3 FUCT ION DEFIN ATION
16-WA Y DAI L SWITC H FUNCTI ON
2-WAY
BLUE
BLUE
R
E
D
D
E
R
K
C
A
L
B
N
W
O
R
B
E
U
L
B
D
E
R
Y
A
R
G
Y
A
R
G
K
C
A
L
B
GRAY
W
O
L
L
E
Y
11-WAY
OFF
1 2 3
SW3
DIGIT AL
3 4
1 2
SW2
ON
OFF
S4 ON:H-EEP ROM OFF : NORMAL
S5 ON:C-EEP ROM OFF : NORMAL
DEFA ULT SETT I NG
XT3
TERMINAL
H2
H1
ALA R M
ON/ OF F
NC
W1 W2
PQ E
TERMINAL
FLOW
CO M
(E)
Q
P
XT2
POWER I N
OFF
ON
REMOT E TURN OFF
S2 S3 S4 S5 S7 S8 S9
REMOT E HEAT
ON OFF
ON OFF
REMOT E COOL
S2 S3 S4 S5 S7 S8 S9
S7
ON/OFF
REMOT E FUCTI ON SETTING
HEAT
EFFEC T ON NO. 0 MODUL E)
(ON/OFF SIGNAL!)
PROVI DE
BY USER
PROVI DE
BY USER
(ON/OFF SIGNAL!)
FLOW
SWTICH
LOW VOLTAGE SIGNAL
DON'T CONNECT HIGH VOLTAGE!
Attached picture (I) Electric Drawing of Main Unit and Auxiliary Unit
43
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
55/60/65KW module
Attached picture (I) Electric Drawing of Main Unit and Auxiliary Unit
44
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
65KW digital module(Only for MGB-D65W/RN1)
BLACK
Y&G
T1
(U)
HEAT_A1
RED
COMP A1
(W)
(V)
COMPRESSOR A1
T2
CRANK
T3
BLUE
WHITE
4
6
2
A2
22
BLACK
A1
5
21
3
AC CONTACTOR
RED
RED
RED
BLUE
WHITE
Y&G
T1
(U)
HEAT_A2
RED
COMP A2
(W)
(V)
COMPRESSOR A2
T2
T3
CRANK
ORANGE
BLUE
WHITE
4
6
2
A2
22
BLACK
A1
5
21
3
RED
RED
BROWN
BLUE
WHITE
Y&G
T1
(U)
HEAT_B
RED
COMP B
(W)
(V)
T2
CRANK
WHITE
ORANGE
4
6
2
A2
BLACK
A1
1
5
3
AC CONTACTOR
RED
BLUE
ORANGE
WHITE
Y&G
FAN A
COMPRESSOR B
T3
BLUE
ORANGE
22
21
RED
AC CONTACTOR
WHITE RED
BLACKBLACK
BLUE
LOW
BLUE
HIGH
BROWN
Y&G
RED
FAN B
WHITE
BLUE
BLACK
HIGH
BROWN B LUE
BROWN
BLUE
RED
RED
RED
XT7
MIDDLE
WIRE JOINT
RED
S.V(B)
4-VALVE B
S.V(A)
4-VALVE A
MIDDLE
WIRE JOINT
XT6
BLUE
BLACK
BROWN
XT5
MIDDLE
WIRE JOINT
PURPLE
OUTDOOR WIRING DIAGRAM
L1
L2
L3
L2L3L4 L1
CN4
CURRENT BOARD
CN6
CN7
CN8
CN5
RED
BLUE
BLACK
WHITE
ICOMP-B2
ICOMP-A2ICOMP-A1 ICOMP-B1
CN11(RED)
POWER OUT
CN19(WHITE)
T
4
XP9XP9
XS9
WHITE
T
3
B
XP8
XS8
TEMP B
CONDENSER
T
A
3
XP7
XS7
RED BLACK
TEMP A
CONDENSER
CN14
T3A T3B T4
ANTI-FREEZING TEMP. SENSOR
RT4
IN-LET WATER TEMP. SENSOR
RT5
CN21 CN26 CN33 CN35CN34
UNIT OUT-LETWATER TEMP.
R
T
6
TOTAL OUT-LETWATER TEMP.
7
T
R
TRANS OUT
MAIN BOARD
POWER
CN18(WHITE)
ON
123
SW3
34
ON
12
SW2
S2 S3 S4 S5 S7 S8 S9
QUERY
S1
CN27 CN10 CN22 CN32
COM(O)
CN2(RED)
CN23(WHITE)
PMV(B)
CN28(RED)
HEAT/COOL
ON/OFF
YELLOW
PMV(A)
CURRENT(A1)
CURRENT(A2)
CN6
COM(I)
PMV(B)
VALVE(B)
ELECTRIC EXPANSIVE
CN5
H&L_PRO
CN1(WHIITE)
PMV(A)
RED
ORANGE
H_PRO(A)
H_PRO(B)
HIGH PRESSURE
PROTECTOR B
HIGH PRESSURE
PROTECTOR A
L_PRO(1A)
LOW PRESSURE
K1(A1)
TEMP PROTECTOR
K1(A2)
TEMP PROTECTOR
PROTECTOR1A
K1(B)
TEMP PROTECTOR
SWITCH B1
SWITCHA1
SWITCH A2
CURRENT(B1)
PWM
CN17
CN20(RED)
TRANS IN
COMP.A1 S.V(A)
CN15(WHITE)
BLUE
RED
FANB
CN31
FANA
CN30
PURPLE
CN12(BLACK)
ORANGE
COMP.B1 S.V(B)
BROWN
CN9(WHIT E)
COMP.B2 COMP.A2
YELLOW
CN24
PUMP
YELLOW
(YELLOW)
BLUE
CN7
HEAT
BLUEBLUEBLUE
(BLUE)
CN16
ALARM
(RED)
CN8(WHITE)
ANTI-FREEZING
CN3(YELLOW)
PH_PRO
CN4(RED)
WATER_PRO
RED
PURPLE
L_PRO(1B)
PURPLE
LOW PRESSURE
PROTECTOR 1B
LOW PRESSURE
PROTECTOR 2B
L_PRO(2A)
L_PRO(2B)
LOW PRESSURE
PROTECTOR2A
S7 ON:REMOTE CONTROL OFF:WIRE CONTROL
S8 ON:LOW TEMP.MODE OFF:NORMAL
S9 ON:30KW OFF:65/130/200/260KW
ADDRESS
DAIL SWITCH S1
16-WAY DAIL SWITCH FUNCTION
S2 ON:COOL ONLY OFF:R&C
S3 ON:DIGITAL OFF:FIXED
S4 ON:H-EEPROM OFF:NORMAL
S5 ON:C-EEPROM OFF:NORMAL
SW2/SW3 FUCTION DEFINATION
PWM PRESSURE
RELIF VALVE
XT1
Y&G
4-WAY TERMINAL
Y&G
BLUE
WHITE
RED
BLUE
BLUEBLUEBL UE
R
E
D
D
E
R
K
C
A
L
B
N
W
O
R
B
E
U
L
B
D
E
R
GRAY
Y
A
R
G
K
C
A
L
B
W
O
L
L
GRAY
OFF
ON
REMOTE TURN OFF
REMOTE HEAT
OFF
123
34
12
OFF
ON OFF
ON OFF
REMOTE COOL
S2 S3 S4 S5 S7 S8 S9
S7
ON/OFF
REMOTE FUCTION SETTING
ON
SW3
SW2
ON
DEFAULT SETTING
BLACK
BLUE
WHITE
POWER IN
RED
XT4
4-WAY
TERMINAL
YELLOW
YELLOW
E
Y
PUMP
H2 P1 P2H1
HEAT
EFFECT ON NO.0 MODULE)
(ON/OFF SIGNAL!)
PROVIDE
BY USER
PROVIDE
BY USER
(ON/OFF SIGNAL!)
W1 W2
(E)
(E)
Q
Q
P
P
XT2
7-WAY
TERMINAL
LOW VOLTAGE SIGNAL
DON'T CONNECT HIGH VOLTAGE!
Attached picture (I) Electric Drawing of Main Unit and Auxiliary Unit
45
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
130KW module
Attached picture (I) Electric Drawing of Main Unit and Auxiliary Unit
46
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
185KW module
2SNART
T
4
-
T
-
4
2
1SNART
4
T
-
1
1PAC
2PAC
)E(
Q
P
3TX
3
3SNART
C B A
C
AB
C B A
C
AB
C
AB
C
AB
KM6
KM5
KM4
KM3
KM2
KM1
G/YG/YG/YG/YG/Y
B3PMOCA3PMOCB2PMOCA2PMOCB1PMOC
W
V
U
W
V
U
W
V
U
W
V
U
W
V
U
G/Y
A1PMOC
W
V
U
B3taeH
A3taeH
B2taeH
A2taeH
B1taeH
A1taeH
Attached Drawing (I) Electric Drawing of Main Unit and Auxiliary Unit
2TX
A
50Hz
~
3N
C
B
N
380-400V
47
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
250KW module
48
Attached Drawing (I) Electric Drawing of Main Unit and Auxiliary Unit
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
7.2 Networking communication schematic of main unit and auxiliary unit
25/30KW module
49
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
m m
30KW new module(Only for MGCSL-F30W/RN1 and MGCSL-D30W/RN1)
RVV-300/500 4*10+1*6
H2 P1 P2H1
H2 P 1 P2H1
120Ω
RVV-300/500 4*10+1*6m
Please choose such accessory as power
Thewiringdiagramof auxiliaryheaterand
Notes
pump is justfor reference ,please follow the
instructions ofcorresponding auxiliary
heater products.
wire , switch of auxiliaryheateraccording to
the actual parameter of productsand national
N C
AB
Black
100Ω
RVV-300/500 4*10+1*6mm
H2 P1 P2H1
The length of wire
shouldbeshorter
than 500m
Gray
Yel lo w
Query
Fault
Attached picture (II) Networking Communication Schematic of Main Unit and Auxiliary Unit
50
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
55/60/65KW module
51
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
m
m
m
65KW digital Mmodule(Only for MGB-D65W/RN1)
H2 P1 P2H1
atic of Main Unit and Auxiliary Unit
H2 P1 P2H1
120Ω
Please choose such acces sory aspower
The wiring diagramof auxiliaryheater and
Notes
pump is just for reference,please follow the
instructions of corresponding auxiliary
heater products.
wire,switchofauxiliaryheateraccordingto
the actual paramet er ofproducts and national
N C
AB
unication Sche
Attached picture (II) Networking Co
52
100Ω
Black
Gray
Yellow
H2 P1 P2H1
The length of wire
should be shorter
than 500m
Query
Fault
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
130KW module
53
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
185KW module
Attached Drawing (II) Networking Communication Schematic of Main Unit and Auxiliary Unit
54
kcalB
yarG
w o
lleY
yreuQ
tluaF
ylppuSrewoP
rotcennoC
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
m
m
m
250KW module
H2 P1 P2H1
atic of Main Unit and Auxiliary Unit
H2 P1 P2H1
120Ω
Please ch oose such accessory as power
The wiringdiagram of auxiliary heaterand
Notes
pump is justfor reference,please follow the
instructions of corresponding auxiliary
heater products.
wire , swit ch of auxiliary heater according to
the actual parameter ofproducts and national
N C
AB
unication Sche
Attached Drawing (II) Networking Co
Black
Gray
Yell ow
H2 P1 P2H1
The length of wire
should be shorter
than 500m
55
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
8 Electric Characteristics
Model
MGB-F25W/RN1 50 380-415 342 456 21.3 36 74(×2) 9.1(×2) 0.67 3.1 MGB-D25W/RN1 50 380-415 342 456 21.3 36 74(×2) 9.1(×2) 0.67 3.1
MGB-F30W/RN1 50 380-415 342 456 22.6 36 74(×2) 9.1(×2) 0.67 3.1
MGB-D30W/RN1 50 380-415 342 456 22.6 36 74(×2) 9.1(×2) 0.67 3.1
MGCSL-F30W/RN1 50 380-415 342 456 25.3 25 74(×2) 11.8(×2) 0.55 4
MGCSL-D30W/RN1 50 380-415 342 456 25.3 25 74(×2) 11.8(×2) 0.55 4
MGB-F55W/RN1 50 380-400 342 440 49.8 100 110(×2) 17.6 (×2) 0.65(×2) 3.0(×2)
MGB-F60W/RN1 50 380-400 342 440 51.7 100 110(×2) 17.6(×2) 0.65(×2) 3.0(×2) MGB-F65W/RN1 50 380-400 342 440 54.5 100 110(×2) 17.6 (×2) 0.65(×2) 3.0(×2)
MGB-D65W/RN1 50 380-415 342 456
MGB-F130W/RN1 50 380-400 342 440
MGB-F185W/RN1 50 380-400 342 440 160 180 110(×6) 17.6 (×6) 0.88(×6) 4.0(×6)
MGBT-F250W/RN1 50 380-400 342 440 191 280 177(×8) 20.8(×8) 5.6(×8) 14.4(×8)
Remark:
TOCA: Total Over-current Amps. (A) MFA: Max. Fuse Amps. (A) LRA: Locked Rotor Amps. (A) RLA: Rated Locked Amps. (A) OFM: Outdoor Fan Motor. KW: Rated Motor Input (KW) FLA: Full Load Amps.
Hz Voltage Min. Max. TOCA MFA LRA RLA KW FLA
Outdoor Unit Power Supply Compressor OFM
52 70 118/74/82.4 17.8/9.1/9.8 0.55(×2) 4.5(×2)
130 200 110(×4) 17.6 (×4) 0.88(×4) 4.0(×4)
56
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
9 Capacity Tables
9.1 MGB-F(D)25W/RN1
Cooling:
Ambient temp.(℃)
Chilled water outlet
temp.
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
() KW KW KW KW KW KW KW KW KW KW KW KW
5.00 31.35 8.19 29.52 8.44 27.85 8.71 26.32 8.97 24.66 9.42 22.69 9.89
6.00 32.41 8.32 30.49 8.58 28.73 8.84 27.13 9.11 25.45 9.57 23.44 10.05
7.00 33.54 8.49 31.52 8.75 29.68 9.02 28.00 9.30 26.29 9.77 24.24 10.25
8.00 34.57 8.74 32.46 9.01 30.54 9.29 28.78 9.58 27.06 10.06 24.97 10.56
9.00 35.55 8.83 33.35 9.10 31.34 9.38 29.51 9.67 27.77 10.16 25.66 10.66
21.00 25.00 30.00 35.00 40.00 46.00
58
10.00 36.90 8.96 34.58 9.24 32.47 9.52 30.54 9.82 28.77 10.31 26.62 10.82
11.00 37.93 9.05 35.51 9.33 33.31 9.62 31.31 9.91 29.52 10.41 27.34 10.93
12.00 38.79 9.18 36.29 9.46 34.01 9.76 31.93 10.06 30.15 10.56 27.95 11.09
13.00 39.49 9.25 36.90 9.54 34.55 9.84 32.41 10.14 30.63 10.65 28.43 11.18
14.00 40.47 9.32 37.79 9.61 35.35 9.90 33.13 10.21 31.34 10.72 29.11 11.26
15.00 40.99 9.36 38.23 9.65 35.73 9.95 33.46 10.26 31.68 10.77 29.47 11.31
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
Heating:
Ambient temp.(℃)
Hot water outlet
temp.
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
() KW KW KW KW KW KW KW KW KW KW KW KW KW KW
39.00 18.34 5.76 22.92 6.54 26.97 7.27 29.96 7.90 32.57 8.32 36.47 8.82 41.95 9.52
41.00 17.72 5.87 22.18 6.67 26.12 7.42 29.06 8.06 31.62 8.49 35.35 8.99 40.58 9.71
42.00 17.21 5.99 21.56 6.81 25.43 7.57 28.32 8.23 30.85 8.66 34.42 9.18 39.45 9.91
43.00 16.79 6.12 21.07 6.95 24.88 7.72 27.73 8.39 30.24 8.84 33.69 9.37 38.54 10.12
44.00 16.47 6.24 20.69 7.09 24.45 7.88 27.29 8.57 29.80 9.02 33.13 9.56 37.84 10.32
45.00 16.23 6.37 20.41 7.24 24.16 8.04 26.99 8.74 29.50 9.20 32.75 9.75 37.33 10.53
46.00 15.91 6.43 20.04 7.31 23.74 8.12 26.56 8.83 29.06 9.29 32.20 9.85 36.64 10.64
-10 -6 -2 2 7 10 13
47.00 15.44 6.56 19.47 7.46 23.10 8.28 25.87 9.00 28.33 9.48 31.33 10.05 35.60 10.85
48.00 14.83 6.76 18.73 7.68 22.24 8.53 24.93 9.27 27.34 9.76 30.18 10.35 34.23 11.18
49.00 14.02 7.03 17.73 7.99 21.08 8.87 23.66 9.65 25.97 10.15 28.62 10.76 32.40 11.62
50.00 13.12 7.38 16.61 8.39 19.77 9.32 22.22 10.13 24.41 10.66 26.86 11.30 30.35 12.20
59
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
9.2 MGB-F(D)30W/RN1
Cooling:
Chilled water
outlet temp.
Ambient temp.(℃)
21.00 25.00 30.00 35.00 40.00 46.00
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
()
5.00 33.59 8.81 31.63 9.08 29.84 9.36 28.20 9.65 26.42 10.13 24.31 10.64
6.00 34.72 8.94 32.66 9.22 30.79 9.51 29.07 9.80 27.27 10.29 25.11 10.80
7.00 35.93 9.13 33.77 9.41 31.80 9.70 30.00 10.00 28.17 10.50 25.97 11.03
8.00 37.04 9.40 34.78 9.69 32.72 9.99 30.84 10.30 28.99 10.82 26.76 11.36
9.00 38.09 9.49 35.73 9.79 33.58 10.09 31.62 10.40 29.75 10.92 27.49 11.47
10.00 39.53 9.63 37.05 9.93 34.79 10.24 32.73 10.56 30.83 11.08 28.52 11.64
11.00 40.63 9.73 38.05 10.03 35.69 10.34 33.54 10.66 31.63 11.19 29.29 11.75
12.00 41.56 9.87 38.88 10.18 36.44 10.49 34.22 10.82 32.30 11.36 29.94 11.92
KW KW KW KW KW KW KW KW KW KW KW KW
13.00 42.31 9.95 39.54 10.26 37.02 10.58 34.73 10.90 32.82 11.45 30.46 12.02
14.00 43.36 10.02 40.48 10.33 37.87 10.65 35.49 10.98 33.58 11.53 31.19 12.10
15.00 43.92 10.07 40.97 10.38 38.29 10.70 35.85 11.03 33.95 11.58 31.57 12.16
60
Heating:
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
Hot water outlet
temp.
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
() KW KW KW KW KW KW KW KW KW KW KW KW KW KW
39.00 19.89 6.13 24.86 6.97 29.25 7.74 32.50 8.42 35.33 8.86 39.57 9.39 45.50 10.14
41.00 19.22 6.26 24.06 7.11 28.34 7.90 31.52 8.59 34.30 9.04 38.34 9.58 44.02 10.35
42.00 18.67 6.38 23.39 7.26 27.58 8.06 30.72 8.76 33.46 9.22 37.34 9.78 42.79 10.56
43.00 18.22 6.52 22.86 7.40 26.98 8.23 30.08 8.94 32.80 9.41 36.54 9.98 41.81 10.77
44.00 17.86 6.65 22.44 7.55 26.53 8.39 29.61 9.12 32.32 9.60 35.94 10.18 41.04 10.99
45.00 17.60 6.78 22.14 7.71 26.21 8.57 29.28 9.31 32.00 9.80 35.52 10.39 40.49 11.22
46.00 17.26 6.85 21.74 7.79 25.76 8.65 28.81 9.40 31.52 9.90 34.92 10.49 39.74 11.33
47.00 16.75 6.99 21.12 7.94 25.06 8.82 28.06 9.59 30.73 10.10 33.99 10.70 38.61 11.56
48.00 16.09 7.20 20.31 8.18 24.13 9.09 27.05 9.88 29.66 10.40 32.74 11.02 37.13 11.90
-10 -6 -2 2 7 10 13
Ambient temp.(℃)
49.00 15.21 7.49 19.23 8.51 22.87 9.45 25.67 10.27 28.17 10.81 31.05 11.46 35.15 12.38
50.00 14.23 7.86 18.02 8.93 21.45 9.92 24.10 10.79 26.48 11.36 29.13 12.04 32.92 13.00
61
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
9.3 MGB-F55W/RN1
Cooling:
Chilled water
outlet temp.
Ambient temp.(℃)
21.00 25.00 30.00 35.00 40.00 46.00
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
() Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW
5.00 61.58 15.41 57.98 15.89 54.70 16.38 51.70 16.89 48.44 17.73 44.57 18.62
6.00 63.65 15.65 59.88 16.14 56.44 16.64 53.30 17.15 49.99 18.01 46.04 18.91
7.00 65.88 15.97 61.91 16.47 58.30 16.98 55.00 17.50 51.65 18.38 47.62 19.29
8.00 67.91 16.45 63.77 16.96 59.99 17.48 56.54 18.03 53.15 18.93 49.06 19.87
9.00 69.83 16.61 65.50 17.12 61.56 17.65 57.97 18.20 54.55 19.11 50.40 20.07
10.00 72.48 16.86 67.92 17.38 63.78 17.92 60.00 18.47 56.52 19.40 52.28 20.37
11.00 74.50 17.03 69.75 17.55 65.43 18.10 61.50 18.66 57.99 19.59 53.70 20.57
12.00 76.20 17.28 71.28 17.81 66.81 18.36 62.73 18.93 59.22 19.87 54.89 20.87
13.00 77.56 17.41 72.49 17.95 67.87 18.51 63.67 19.08 60.17 20.03 55.84 21.04
14.00 79.49 17.53 74.22 18.08 69.43 18.64 65.07 19.21 61.56 20.17 57.19 21.18
15.00 80.51 17.62 75.10 18.17 70.19 18.73 65.72 19.31 62.24 20.27 57.88 21.29
62
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
Heating:
Ambient temp.(℃)
Hot water
outlet temp.
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
() Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW
39.00 40.40 11.45 45.84 13.01 53.93 14.46 59.92 15.71 65.13 16.54 72.95 17.53 83.89 18.94
41.00 35.44 11.68 44.36 13.28 52.24 14.75 58.11 16.04 63.24 16.88 70.70 17.89 81.16 19.32
42.00 34.42 11.92 43.13 13.55 50.86 15.05 56.63 16.36 61.69 17.22 68.85 18.26 78.90 19.72
43.00 33.58 12.17 42.14 13.82 49.75 15.36 55.46 16.70 60.48 17.58 67.38 18.63 77.08 20.12
44.00 32.94 12.41 41.38 14.11 48.91 15.67 54.58 17.04 59.59 17.93 66.26 19.01 75.67 20.53
45.00 32.46 12.67 40.83 14.39 48.32 15.99 53.99 17.39 59.00 18.30 65.49 19.40 74.66 20.95
46.00 31.82 12.79 40.08 14.54 47.49 16.15 53.12 17.56 58.12 18.48 64.39 19.59 73.28 21.16
47.00 30.88 13.05 38.94 14.83 46.20 16.48 51.73 17.91 56.66 18.85 62.67 19.98 71.19 21.58
48.00 29.66 13.44 37.45 15.27 44.48 16.97 49.87 18.45 54.68 19.42 60.37 20.58 68.45 22.23
-10 -6 -2 2 7 10 13
49.00 28.05 13.98 35.46 15.89 42.16 17.65 47.32 19.19 51.95 20.19 57.24 21.41 64.80 23.12
50.00 26.24 14.68 33.22 16.68 39.55 18.53 44.43 20.14 48.83 21.20 53.71 22.48 60.69 24.28
63
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
9.4 MGB-F60W/RN1
Cooling:
Ambient temp.(℃)
Chilled water
outlet temp.
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
() Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW
5.00 67.17 17.00 63.25 17.52 59.67 18.07 56.40 18.62 52.85 19.56 48.62 20.53
6.00 69.44 17.26 65.33 17.80 61.57 18.35 58.14 18.91 54.54 19.86 50.23 20.85
7.00 71.87 17.61 67.54 18.16 63.60 18.72 60.00 19.30 56.34 20.27 51.95 21.28
8.00 74.09 18.14 69.57 18.70 65.44 19.28 61.68 19.88 57.98 20.87 53.51 21.92
9.00 76.18 18.32 71.46 18.89 67.16 19.47 63.24 20.07 59.51 21.08 54.99 22.13
10.00 79.06 18.59 74.10 19.17 69.58 19.76 65.45 20.37 61.66 21.39 57.03 22.46
11.00 81.27 18.78 76.09 19.36 71.38 19.96 67.09 20.57 63.27 21.60 58.58 22.68
12.00 83.13 19.05 77.76 19.64 72.88 20.25 68.43 20.87 64.60 21.92 59.88 23.01
21.00 25.00 30.00 35.00 40.00 46.00
13.00 84.61 19.20 79.08 19.80 74.04 20.41 69.46 21.04 65.64 22.09 60.91 23.20
14.00 86.72 19.34 80.97 19.94 75.74 20.55 70.99 21.19 67.15 22.25 62.38 23.36
15.00 87.83 19.43 81.93 20.03 76.57 20.65 71.70 21.29 67.90 22.36 63.14 23.47
64
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
Heating
Ambient temp.(℃)
Hot water
outlet temp.
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
() Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW
39.00 39.78 12.39 49.73 14.08 58.50 15.64 65.00 17.00 70.65 17.90 79.13 18.97 91.00 20.49
41.00 38.44 12.64 48.11 14.37 56.67 15.96 63.04 17.35 68.59 18.26 76.69 19.36 88.04 20.91
42.00 37.33 12.90 46.78 14.66 55.17 16.29 61.43 17.70 66.92 18.64 74.68 19.75 85.59 21.33
43.00 36.43 13.16 45.71 14.96 53.97 16.62 60.16 18.07 65.61 19.02 73.09 20.16 83.61 21.77
44.00 35.73 13.43 44.88 15.26 53.05 16.96 59.21 18.43 64.64 19.40 71.88 20.57 82.09 22.21
45.00 35.21 13.71 44.29 15.57 52.41 17.31 58.56 18.81 64.00 19.80 71.04 20.99 80.99 22.67
46.00 34.52 13.84 43.48 15.73 51.51 17.48 57.62 19.00 63.04 20.00 69.85 21.20 79.49 22.89
47.00 33.50 14.12 42.24 16.05 50.11 17.83 56.12 19.38 61.46 20.40 67.98 21.62 77.22 23.35
48.00 32.18 14.54 40.63 16.53 48.25 18.36 54.09 19.96 59.31 21.01 65.48 22.27 74.26 24.05
-10 -6 -2 2 7 10 13
49.00 30.43 15.12 38.46 17.19 45.74 19.10 51.33 20.76 56.35 21.85 62.09 23.16 70.29 25.01
50.00 28.47 15.88 36.03 18.05 42.90 20.05 48.20 21.80 52.97 22.94 58.26 24.32 65.84 26.26
65
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
9.5 MGB-F65W/RN1, MGB-D65W/RN1
Cooling
Ambient temp.(℃)
Chilled water
outlet temp.
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
() Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW
5.00 72.77 17.97 68.52 18.52 64.64 19.10 61.10 19.69 57.25 20.67 52.67 21.70
6.00 75.23 18.25 70.77 18.81 66.70 19.39 62.99 19.99 59.08 20.99 54.41 22.04
7.00 77.85 18.62 73.17 19.19 68.90 19.79 65.00 20.40 61.04 21.42 56.27 22.49
8.00 80.26 19.18 75.36 19.77 70.90 20.38 66.82 21.01 62.81 22.06 57.97 23.17
9.00 82.52 19.36 77.41 19.96 72.76 20.58 68.51 21.22 64.47 22.28 59.57 23.39
10.00 85.65 19.65 80.27 20.26 75.38 20.89 70.91 21.53 66.80 22.61 61.79 23.74
11.00 88.04 19.85 82.44 20.46 77.33 21.09 72.68 21.75 68.54 22.83 63.47 23.98
21.00 25.00 30.00 35.00 40.00 46.00
12.00 90.06 20.14 84.24 20.76 78.95 21.40 74.13 22.06 69.98 23.17 64.87 24.33
13.00 91.66 20.30 85.67 20.93 80.21 21.57 75.25 22.24 71.11 23.35 65.99 24.52
14.00 93.94 20.44 87.72 21.07 82.05 21.72 76.90 22.40 72.75 23.52 67.58 24.69
15.00 95.15 20.54 88.76 21.18 82.95 21.83 77.67 22.51 73.55 23.63 68.41 24.81
66
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
Heating:
Ambient temp.(℃)
Hot water
outlet temp.
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
() Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW
39.00 42.89 13.45 53.61 15.29 63.07 16.99 70.08 18.46 76.17 19.43 85.31 20.60 98.11 22.25
41.00 41.45 13.73 51.87 15.60 61.10 17.33 67.96 18.84 73.95 19.83 82.68 21.02 94.92 22.70
42.00 40.25 14.01 50.44 15.92 59.48 17.69 66.23 19.22 72.15 20.24 80.52 21.45 92.28 23.17
43.00 39.28 14.29 49.28 16.24 58.18 18.05 64.86 19.62 70.74 20.65 78.80 21.89 90.15 23.64
44.00 38.52 14.58 48.39 16.57 57.20 18.42 63.84 20.02 69.69 21.07 77.50 22.33 88.50 24.12
45.00 37.96 14.88 47.75 16.91 56.51 18.79 63.14 20.43 69.00 21.50 76.59 22.79 87.31 24.61
46.00 37.22 15.03 46.87 17.08 55.54 18.98 62.12 20.63 67.97 21.72 75.31 23.02 85.70 24.86
47.00 36.12 15.33 45.54 17.42 54.03 19.36 60.50 21.04 66.27 22.15 73.29 23.48 83.26 25.36
48.00 34.69 15.79 43.80 17.95 52.02 19.94 58.32 21.67 63.95 22.81 70.60 24.18 80.06 26.12
-10 -6 -2 2 7 10 13
49.00 32.80 16.42 41.47 18.66 49.31 20.74 55.34 22.54 60.75 23.73 66.95 25.15 75.78 27.16
50.00 30.69 17.24 38.85 19.60 46.25 21.77 51.96 23.67 57.10 24.91 62.81 26.41 70.98 28.52
67
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
9.6 MGB-F130W/RN1
Cooling:
Ambient temp.(℃)
Chilled water
outlet temp.
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
21.00 25.00 30.00 35.00 40.00 46.00
() kW kW kW
5.00 145.54 35.93 137.04 37.05 129.29 38.19 122.20 39.37 114.50 41.34 105.34 43.41
6.00 150.46 36.49 141.54 37.62 133.40 38.78 125.97 39.98 118.16 41.98 108.83 44.08
7.00 155.71 37.24 146.34 38.39 137.80 39.58 130.00 40.80 122.07 42.84 112.55 44.98
8.00 160.52 38.35 150.72 39.54 141.79 40.76 133.64 42.02 125.62 44.13 115.95 46.33
9.00 165.05 38.73 154.83 39.92 145.52 41.16 137.02 42.43 128.94 44.55 119.14 46.78
10.00 171.31 39.31 160.55 40.52 150.75 41.78 141.82 43.07 133.59 45.22 123.57 47.48
11.00 176.08 39.69 164.87 40.92 154.66 42.19 145.36 43.49 137.08 45.67 126.93 47.95
12.00 180.11 40.28 168.49 41.52 157.91 42.81 148.27 44.13 139.97 46.34 129.75 48.65
13.00 183.33 40.60 171.33 41.85 160.42 43.15 150.49 44.48 142.22 46.71 131.98 49.04
14.00 187.89 40.88 175.43 42.14 164.11 43.45 153.80 44.79 145.50 47.03 135.17 49.38
15.00 190.30 41.08 177.52 42.35 165.90 43.66 155.34 45.01 147.11 47.26 136.81 49.63
kW
kW
kW
kW
kW
kW
kW
kW
kW
68
Heating:
Hot water
outlet temp.
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
Ambient temp.(℃)
-10 -6 -2 2 7 10 13
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
() kW kW kW
39.00 85.78 26.91 107.22 30.57 126.14 33.97 140.16 36.93 152.34 38.87 170.63 38.33 196.22 41.39
41.00 82.89 27.45 103.75 31.20 122.20 34.66 135.93 37.68 147.91 39.66 165.36 39.11 189.83 42.24
42.00 80.50 28.01 100.87 31.83 118.96 35.37 132.47 38.45 144.30 40.47 161.04 39.91 184.55 43.10
43.00 78.55 28.59 98.56 32.48 116.37 36.09 129.73 39.23 141.47 41.30 157.60 40.72 180.29 43.98
44.00 77.03 29.17 96.78 33.15 114.39 36.83 127.67 40.03 139.38 42.14 154.99 41.55 177.00 44.88
45.00 75.92 29.76 95.49 33.82 113.01 37.58 126.27 40.85 138.00 43.00 153.18 45.58 174.63 49.23
46.00 74.43 30.06 93.74 34.16 111.07 37.96 124.24 41.26 135.93 43.43 150.61 46.04 171.39 49.72
47.00 72.23 30.66 91.09 34.85 108.05 38.72 121.00 42.08 132.53 44.30 146.58 46.96 166.52 50.71
48.00 69.38 31.58 87.60 35.89 104.04 39.88 116.64 43.35 127.89 45.63 141.19 48.37 160.11 52.23
49.00 65.61 32.85 82.94 37.33 98.62 41.47 110.69 45.08 121.50 47.45 133.89 50.30 151.56 54.32
50.00 61.38 34.49 77.70 39.19 92.50 43.55 103.93 47.33 114.21 49.83 125.63 52.81 141.96 57.04
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
69
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
9.7 MGB-F185W/RN1
Cooling:
Chilled water
outlet temp.
(℃)
5.00
6.00
7.00
8.00
9.00
10.00
11.00
12.00
13.00
14.00
15.00
Kw
173.90
179.27
185.00
190.18
194.99
196.36
201.27
205.29
208.37
212.96
215.09
35.00
Power
kW
60.80
61.74
63.00
64.89
65.52
66.50
67.16
68.14
68.69
69.16
69.50
Capacity
Kw
162.94
168.15
173.72
178.77
183.49
184.97
189.80
193.80
196.91
201.46
203.69
40.00
Power
kW
63.83
64.83
66.15
68.13
68.80
69.83
70.52
71.55
72.12
72.62
72.98
46.00
Capacity
Kw
149.91
154.87
160.17
165.00
169.54
171.10
175.75
179.65
182.74
187.15
189.43
Power
kW
67.03
68.07
69.46
71.54
72.24
73.32
74.04
75.13
75.73
76.25
76.63
Ambient temp.(℃)
21.00
Capacity
Kw
207.12
214.11
221.59
228.44
234.87
237.19
243.81
249.38
253.84
260.15
263.49
Power
kW
55.49
56.35
57.50
59.22
59.80
60.70
61.29
62.19
62.69
63.12
63.43
Capacity
Kw
195.03
201.42
208.26
214.49
220.33
222.30
228.28
233.29
237.23
242.91
245.79
25.00
Power
kW
57.20
58.09
59.28
61.06
61.65
62.57
63.19
64.11
64.63
65.08
65.40
30.00
Capacity
Kw
183.99
189.84
196.10
201.78
207.08
208.73
214.15
218.64
222.13
227.23
229.71
Power
kW
58.97
59.89
61.11
62.94
63.55
64.51
65.14
66.10
66.63
67.09
67.42
Capacity
70
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
Heating:
Ambient temp.(℃)
Hot water outlet
temp.
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
() Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW
39.00 124.31 38.17 155.39 43.37 182.81 48.19 203.13 52.38 220.79 55.14 247.28 58.45 284.38 63.12
41.00 120.14 38.95 150.36 44.26 177.10 49.18 197.00 53.45 214.36 56.26 239.65 59.64 275.12 64.41
42.00 116.66 39.74 146.19 45.16 172.40 50.18 191.98 54.54 209.13 57.41 233.39 60.86 267.46 65.73
43.00 113.85 40.55 142.84 46.08 168.65 51.20 188.01 55.66 205.03 58.58 228.40 62.10 261.29 67.07
44.00 111.64 41.38 140.26 47.02 165.79 52.25 185.03 56.79 202.00 59.78 224.62 63.37 256.52 68.44
45.00 110.03 42.22 138.40 47.98 163.79 53.31 183.00 57.95 200.00 61.00 222.00 64.66 253.08 69.83
46.00 107.87 42.65 135.86 48.46 160.97 53.85 180.06 58.53 197.00 61.61 218.28 65.31 248.40 70.53
47.00 104.69 43.50 132.01 49.43 156.60 54.92 175.36 59.70 192.08 61.81 212.43 66.61 241.33 71.94
48.00 100.55 44.80 126.96 50.91 150.78 56.57 169.04 61.49 185.35 63.67 204.63 68.61 232.05 74.10
-10 -6 -2 2 7 10 13
49.00 95.08 46.60 120.20 52.95 142.93 58.83 160.41 63.95 176.08 66.21 194.05 71.36 219.66 77.06
50.00 88.96 48.93 112.61 55.60 134.05 61.78 150.62 67.15 165.52 69.52 182.07 74.92 205.74 80.92
71
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
9.8 MGBT-F250W/RN1
Cooling:
Chilled
water outlet temp.
() Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW
5.00 279.89 68.96 263.55 71.09 248.63 73.29 235.00 75.56 220.20 79.34 202.58 83.30 182.32 87.47
6.00 289.34 70.03 272.19 72.20 256.54 74.43 242.25 76.73 227.23 80.57 209.28 84.60 188.56 88.83
7.00 299.44 71.46 281.43 73.67 265.00 75.95 250.00 78.30 234.75 82.22 216.44 86.33 195.23 90.64
8.00 308.70 73.61 289.86 75.88 272.68 78.23 257.00 80.65 241.58 84.68 222.98 88.92 201.35 93.36
9.00 317.40 74.32 297.75 76.62 279.84 78.99 263.50 81.43 247.95 85.50 229.11 89.78 207.11 94.27
10.00 329.43 75.44 308.75 77.77 289.90 80.17 272.72 82.65 256.90 86.79 237.64 91.13 215.06 95.68
11.00 338.62 76.18 317.06 78.53 297.43 80.96 279.54 83.47 263.61 87.64 244.10 92.02 221.15 96.62
12.00 346.37 77.29 324.01 79.68 303.66 82.15 285.13 84.69 269.16 88.92 249.52 93.37 226.31 98.04
13.00 352.55 77.91 329.49 80.32 308.51 82.81 289.41 85.37 273.49 89.64 253.80 94.12 230.45 98.82
14.00 361.32 78.45 337.37 80.88 315.59 83.38 295.78 85.96 279.80 90.26 259.94 94.77 236.28 99.51
15.00 365.96 78.84 341.38 81.28 319.05 83.79 298.73 86.38 282.90 90.70 263.10 95.24 239.42 100.00
21.00 25.00 30.00 35.00 40.00 46.00 52.00
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
Ambient temp.(℃)
72
Heating
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
Hot water outlet
temp.
() Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW Kw kW
39.00 167.82 50.06 209.78 56.88 246.80 63.20 274.22 68.70 298.07 72.31 333.83 76.65 383.91 82.78
41.00 162.18 51.08 202.98 58.04 239.08 64.49 265.94 70.10 289.38 73.79 323.53 78.22 371.41 84.47
42.00 157.50 52.12 197.36 59.23 232.74 65.81 259.18 71.53 282.33 75.30 315.08 79.81 361.08 86.20
43.00 153.69 53.18 192.84 60.44 227.67 67.15 253.82 72.99 276.79 76.83 308.34 81.44 352.75 87.96
44.00 150.72 54.27 189.35 61.67 223.81 68.52 249.79 74.48 272.70 78.40 303.24 83.10 346.30 89.75
45.00 148.54 55.38 186.84 62.93 221.11 69.92 247.05 76.00 270.00 80.00 299.70 84.80 341.66 91.58
46.00 145.63 55.93 183.41 63.56 217.31 70.62 243.08 76.76 265.95 80.80 294.67 85.65 335.34 92.50
47.00 141.33 57.05 178.22 64.83 211.41 72.03 236.74 78.30 259.30 82.42 286.79 87.36 325.79 94.35
48.00 135.75 58.76 171.40 66.77 203.56 74.19 228.21 80.64 250.23 84.89 276.25 89.98 313.27 97.18
49.00 128.36 61.11 162.27 69.44 192.95 77.16 216.56 83.87 237.71 88.28 261.96 93.58 296.54 101.07
50.00 120.09 64.17 152.02 72.92 180.97 81.02 203.34 88.06 223.45 92.70 245.80 98.26 277.75 106.12
-10.00 -6.00 -2 2 7 10 13
Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power Capacity Power
Ambient temp.(℃)
73
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
10 Exploded View
10.1 MGB-F25W/RN1 MGB-F30W/RN1
74
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
No. Part Name Quantity No. Part Name Quantity
Rear—front net
1
2 Condenser right seal board ass'y 1 25 underpan bracket 1
3 Double-pipe heat exchanger 1 26 Reinforcement bracket 6
4 Condenser right seal board ass'y 1 27 E-part box ass'y 1
5 Input pipe ass'y of B unit 1 27.1 Main control board ass'y 1
5.1 Electronic expansion valve 1 27.2 Relay 2
6 Input pipe ass'y of A unit 1 27.3 Contactor 1
6.1 Filter 1 27.4 Contactor 1
7 Input pipe ass'y of A unit 1 27.5 Transformer 1
7.1 Electronic expansion valve 1 27.6 Wire joint 2
8 Output pipe ass'y of B unit 1 27.7 Wire joint 1
8.1 Pressure controller 1 27.8 Wire joint 4
9 Output pipe ass'y of A unit 1 27.9 Wire joint 1
9.1 Pressure controller 1 27.10 Comp capacitor 1
10 4-Way valve ass'y of A unit 1 28 Drainage pan bracket 2
10.1 4-Way valve 1 29 E-part box cover board 1
10.2 4-Way valve solenoid 1 30 Drainage pan 1
10.3 Muffler 1 31 Prevent water box 1
10.4 Filter 1 32 Condenser of A unit 1
10.5 Pipe joint 1 33
10.6 Pressure controller 1 34 Condenser left seal board ass'y 2
11 Input pipe ass'y of B unit 1 35 Condenser of B unit 1
11.1 Filter 1 36 Motor bracket 2
12 4-Way valve ass'y of B unit 1 37 Side seal board 4
12.1 4-Way valve 1 38 Side bracket 2
12.2 4-Way valve solenoid 1 39 Motor bracket 2
12.3 Muffler 1 40
12.4 Filter 1 41 Motor 1
12.5 Pipe joint 1 42 Axial flow fan 1
12.6 Pressure controller 1 43 Top cover 1
13 Suction pipe ass'y of A unit 1 44 Partition board 1
13.1 Pressure controller 1 45 Top cover 1
14 Suction pipe ass'y of A unit 1 46 Seal partition board 1
14.1 Pressure controller 1 47 Rear cover board 1
15 Rear-below and front below bracket 2 48
16 front-below cover board 1 49
17 comp cover board 2 50 R410a 7Kg
18 Small underpan bracket ass'y 2 51 EEV solenoid 2
19 Small underpan bracket ass'y 2 52 Ambient temp sensor 1
20 Small underpan 1 53 Discharge temp controller 2
21 Separator 2 54 Comp electric heater 2
22 Compressor 2 55 Pipe sensor 6
23 underpan bracket 1 56 Pipe sensor wire 3
2 24 underpan parts 1
Rearbelow cover board
Rearfront cover board
Rearfront cover board Leftright side board
1
2
1
2
75
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
10.2 MGB-D25W/RN1 MGB-D30W/RN1
76
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
No. Part Name Quantity No. Part Name Quantity
1 Rear—front net
2
Condenser right seal board ass'y
3
Double-pipe heat exchanger
4
Condenser right seal board ass'y
5
Input pipe ass'y of B unit
5.1
Electronic expansion valve
6
Input pipe ass'y of A unit
6.1 Filter
7 Input pipe ass'y of A unit
7.1 Electronic expansion valve
8 Output pipe ass'y of B unit
8.1 Pressure controller
9 Output pipe ass'y of A unit
9.1 Pressure controller
10 4-Way valve ass'y of A unit
10.1 4-Way
10.2 4-Way solenoid
10.3 Muffler
10.4 Filter
10.5 Pipe joint
10.6 Pressure controller
11 Input pipe ass'y of B unit
11.1 Filter
12 4-Way ass'y of B unit
12.1 4-Way
12.2 4-Way solenoid
12.3 Muffler
12.4 Filter
12.5 Pipe joint
12.6 Pressure controller
13 Suction pipe ass'y of A unit
13.1 Pressure controller
14 Suction pipe ass'y of B unit
14.1 Pressure controller
14.2 Filter
14.3 Reducing valve
15 Rearbelow and frontbelow bracket 16 Frontbelow cover board
17 comp cover board
18 small underpan bracket ass‘y
19 small underpan bracket ass‘y
20 small underpan
21 Accumulater cylinder
22 compressor
23 Underpan bracket
2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 2 2 2 1 2 1 1
24 Underpan
25 Underpan bracket
26 reinforcement bracket
27 E-part box ass'y
27.1 Main control board ass'y
27.2 Relay
27.3 Contactor
27.4 Contactor
27.5 Transformer
27.6 Wire joint
27.7 Wire joint
27.8 Wire joint
27.9 Wire joint
27.10 Compressor capacitor
28 Compressor
29 Drainage pan bracket
30 E-part box cover board
31 Drainage pan
32 Preventing water box
33 Condenser of A unit
34 Rear-below cover board
35 Left seal board ass'y of condenser
36 Condenser of B unit
37 Motor bracket
38 side seal board
39 Side bracket
40 Motor bracket
Rear-above and front-above cover
41
42 Motor
43 Axial flow fan
44 Top cover board
45 Partition board
46 Top cover board
47 Seal partition board
48 Rear cover board
49 Rear-front cover board
50 Left-right side board
51 R410a
52 EEV solenoid
53 Ambient sensor
54 Discharge temp sensor
55 Comp electric heater
56 Pipe sensor
57 Pipe sensor wire
58 Comp electric heater
1 1 6 1 1 2 1 1 1 2 1 4 1 1 1 2 1 1 1 1 1 2 1 2 4 2 2 2 1 1 1 1 1 1 1 1 2
7Kg
2 1 2 1 6 3 1
77
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
MGCSL-F30W/RN1
78
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
No. Part Name Qty BOM code
1
2
3
4
5
6
7
8
9
10
11
12
12.1
13
14
14.1
15
16
16.1
16.2
16.3
16.4
16.5
16.6
17
17.1
17.2
17.3
17.4
17.5
18
Right seal plate condenser components D
A condenser components
Motor holder
Cover C components of the left seal plate condenser
Part B condenser A seal plate condenser components of the right
Supporting board
Cover board
Cover
Drainage pan holder
Suction pipe ass'y A
Pipe joint
Accumulator cylinder
Suction pipe ass'y B
Pipe joint
Compressor
A unit four-way valve ass'y
4-way valve
4-Ways valve solenoid
Muffler
Strainer
Pipe joint
Pressure controller
B unit 4-way valve ass'y
4-way valve
4-Ways valve solenoid
Muffler
Strainer
Pipe joint
Base ass'y
1 201290190122 20
1 201590190014 21
2 201295010078 22
2 201295300100 23
1 201290190124 23.1
1 201590190012 24
1 201290190125 24.1
2 201290190204 25
2 201295300101 26
1 201295300098 26.1
2 201275900027 26.2
1 201690191112 27
1 201601200004 27.1
2 201601010504 28
1 201690191111 28.1
1 201601200004 28.2
2 201401410020 29
1 201690191405 30
1 201600600111 31
1 201600600103 32
1 201601000031 33
1 201600900056 34
3 201601200004 35
1 202301800835 36
1 201690191151 37
1 201600600111 37.1
1 201600600103 37.2
1 201601000031 38
1 201600900056 39
3 201601200004 40
1 201290190056 41
No.
The door welding part of electrical box The welding part of small baseplate
Base Output pipe ass'y of A unit double-pipe
Pressure controller
Input pipe ass'y II of A unit
Strainer Input pipe fixed base of double pipe
Input pipe ass'y of A unit
Electronic expansion valve
Strainer
Input pipe ass'y II of B unit
Strainer
Input pipe ass'y I of B unit
Electronic expansion valve
Strainer
Safety valve
Double pipe heat exchanger
Replenishing pipe's fixed base
Water pump
Installation beam of pump Welding support of hydraulic module Connection part of hydraulic module support
Stainless steel corrugated pipe
Inlet pipe ass'y of pump
Y shape filter
Water charge valve
Target flow-volume controller Outlet pipe welding ass'y of pump
Expansion vessel
Welding parts water tray
Part Name Qty BOM code
1 201290190224
1 201290190233
1 201290190103
1 201690191407
1 202301800835
1 201690191414
1 201600900040
1 201290190288
1 201690191416
1 201601300018
1 201600900040
1 201690191409
1 201600900040
1 201690191411
1 201601300018
1 201600900040
1 201604100114
1 201700202000
1 201290190210
1 202400600824
2 201290190211
1 201290190212
1 201290190209
1 201290190286
1 201690191422
1 201600900815
1 201601600104
1 202301820013
1 201690191418
1 201601300517
1 201290190119
79
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
No. Part Name
19
19.1
19.2
19.3
19.4
19.5
19.6
19.7
19.8
19.9
19.10
19.11
19.12
19.13
19.14
19.15
Electrical box ass'y
Electronic installation board
Dual Relay
Compressor capacitor Low temp. cooling module ass'y
Relay
Contactor
Contactor Three-phase power protection devices
Wire joint
Wire joint
Wire joint
Wire joint,11p
Outdor main board ass'y
Transformer Outdoor current detection board ass'y
Qty BOM code No. Part Name Qty BOM code
1 203390190029 42
1 201290190227 43
1 202300830544 44
1 202401000410 45
1 201390190028 46
1 202300800003 47
2 202300850043 48
1 202300800110 49
1 202301600518 50
4 202301450122 51
1 202301450110 52
1 202301450132 53
1 202301400365 54
1 201390190026 55
1 202300900109 56
1 201390190020 57
Cover
Left-side board ass'y
Rear cover
Front cover
Top cover Maintenance window in the bulkhead cover Welding part of middle separation board
Outlet pipe fixed base
Net
Clapboard supporting board
About clapboard
Top cover B components of the left seal plate condenser
Axial flow fan
Motor
Motor bracket bonding parts
1 201295300096
1 201290190232
1 201290190223
1 201290100235
1 201290140111
1 201290501495
1 201290190205
1 201290190287
2 201290190118
3 201295010094
1 201295500014
1 201195300051
1 201290190123
1 201200300013
1 202400401168
2 201290590191
80
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
MGCSL-D30W/RN1
81
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
No. Part Name Qty BOM code No. Part Name Qty BOM code
1 2
3 4
5 6 7 8
9 10 11 12
12.1 13 14
15 16
16.1
16.2
16.3
16.4
16.5
16.6 17
17.1
17.2
17.3
17.4
82
Right seal plate condenser components D
A condenser components Motor holder Cover
C components of the left seal plate condenser
Part B condenser A seal plate condenser components of the right
Supporting board Cover board Cover Drainage pan holder Suction pipe ass'y A Pipe joint Accumulator cylinder Compressor
Digital compressor A unit four-way valve ass'y 4-way valve
4-Ways valve solenoid Muffler Strainer
Pipe joint Pressure controller B unit 4-way valve ass'y 4-way valve
4-Ways valve solenoid Muffler Strainer
1 201290190122 23 1 201590190014 23.1
2 201295010078 24 2 201295300100 24.1
1 201290190124 25 1 201590190012 26 1 201290190125 26.1 2 201290190204 26.2
2 201295300101 27 1 201295300098 27.1 2 201275900027 28 1 201690191112 28.1 1 201601200004 28.2 2 201601010504 29 1 201401410020 30
1 201401400280 31 1 201690191405 32
1 201600600111 33 1 201600600103 34
1 201601000031 35 1 201600900056 36
3 201601200004 37 1 202301800835 37.1 1 201690191151 37.2 1 201600600111 38
1 201600600103 39 1 201601000031 40
1 201600900056 41
Output pipe ass'y of A unit double-pipe
Pressure controller Input pipe ass'y II of A unit Strainer
Input pipe fixed base of double pipe
Input pipe ass'y of A unit Electronic expansion valve
Strainer Input pipe ass'y II of B unit Strainer Input pipe ass'y I of B unit Electronic expansion valve Strainer Safety valve Double pipe heat exchanger
Replenishing pipe's fixed base
Water pump Installation beam of pump
Welding support of hydraulic module Connection part of hydraulic module support Stainless steel corrugated pipe
Inlet pipe ass'y of pump Y shape filter Water charge valve Target flow-volume controller
Outlet pipe welding ass'y of pump
Expansion vessel Welding parts water tray
1 201690191407 1 202301800835
1 201690191414 1 201600900040
1 201290190288 1 201690191416 1 201601300018 1 201600900040
1 201690191409 1 201600900040 1 201690191411 1 201601300018 1 201600900040 1 201604100114 1 201700202000
1 201290190210 1 202400600824
2 201290190211 1 201290190212
1 201290190209 1 201290190286
1 201690191422 1 201600900815 1 201601600104 1 202301820013
1 201690191418 1 201601300517
1 201290190119
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
No. Part Name
17.5 18 19
19.1
19.2
19.3
19.4
19.5
19.6
19.7
19.8
19.9
19.10
19.11
19.12
19.13
19.14
19.15 20 21
22
Pipe joint Base ass'y Electrical box ass'y Electronic installation board Dual Relay
Compressor capacitor Low temp. cooling module ass'y
Relay Contactor Contactor
Three-phase power protection devices
Wire joint Wire joint
Wire joint Wire joint,11p
Outdor main board ass'y Transformer
Outdoor current detection board ass'y The door welding part of electrical box The welding part of small baseplate
Base
Qty BOM code No. Part Name Qty BOM code
3 201601200004 42 1 201290190056 43 1 203390190029 44 1 201290190227 45 1 202300830544 46
1 202401000410 47 1 201390190028 48
1 202300800003 49 2 202300850043 50 1 202300800110 51
1 202301600518 52 4 202301450122 53 1 202301450110 54 1 202301450132 54.1 1 202301400365 55 1 201390190026 55.1
1 202300900109 55.2 1 201390190020 56
1 201290190224 57 1 201290190233 58
1 201290190103 59
Cover Left-side board ass'y Rear cover Front cover Top cover
Maintenance window in the bulkhead cover Welding part of middle separation board
Outlet pipe fixed base Net Clapboard supporting board
About clapboard Top cover
D machine back to the tube components
Pipe joint D machines take over the assembly solenoid valve
Pressure-relief-valve Strainer
B components of the left seal plate condenser
Axial flow fan Motor
Motor bracket bonding parts
1 201295300096 1 201290190232 1 201290190223 1 201290100235 1 201290140111
1 201290501495 1 201290190205
1 201290190287 2 201290190118 3 201295010094
1 201295500014 1 201195300051 1 201690191306 1 201601200004 1 201690101464 1 201600600501
1 201600900040 1 201290190123
1 201200300013 1 202400401168
2 201290590191
83
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
10.3 MGB-F55W/RN1 MGB-F60W/RN1 MGB-F65W/RN1
84
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
No. Part Name Qty BOM code No. Part Name Qty BOM code
1 2
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
21.1
21.2
A combination of pieces of fixed plate condenser
Condenser side board Condenser ass'y A Condenser ass'y B Mid horizontal support Fixed board Mid upright support Pipe fixing clamp Evaporator input pipe ass'y Evaporator input pipe ass'y Cover Cover Triangle reinforcement ass'y Reinforcement board Base Compressor Cover Wiring terminal fixing board Cover Cover E-part box ass'y
Air-cooled module control board components
Transformer
1 201290108627 21.9 Wire joint 2 201290108624 21.10
1 201590100023 21.11 1 201590100024 22 2 201290100219 23 2 201290100233 24 2 201290100211 25 2 201252600035 26 1 201690191273 27 1 201690191272 28 1 201290100241 29 1 201290100246 30 8 201290100218 31 4 201290100247 32 1 201290100042 33 2 201402300130 34 1 201290100243 35 1 201290100193 36 1 201290100244 37 1 201290100245 38 1 203390190018 39
1 201390190006 40 Motor 2 202400400399 1 202300900109 41
Wire joint, 3p E-part box Wiring slot separator Shell and tube evaporator Cover Pole E-part box door Suction pipe ass'y A Suction pipe ass'y B 4-way valve ass'y A 4-way valve ass'y B Drainage pan ass'y Middle partition plate Net Net Top upright support Condenser seal connector Top cover Axial flow fan
Mid horizontal support
1 202301450130 2 202301450044
1 201290100212
0.5 201119900945 2 201601100072 1 201790190017 1 201290100242 4 201290108623 1 201290100194 1 201690191276 1 201690191274 1 201690191279 1 201690191278 1 201290100195 2 201290100248 2 201290100240 4 201290100237 2 201290100191 1 201290108626 2 201195300051 2 201200300013
2 201290100223
85
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
No. Part Name
Three-phase protection
21.3
21.4
21.5
21.6 AC contactor 2 202300850050 45
21.7
21.8
device signal output line group
Relay Compressor capacitor
Wire joint Wire joint
Qty BOM code No. Part Name Qty BOM code
1 2024901A0004 42 Motor bracket ass'y 4 201290100005
2 202300800003 43 2 202401000410 44
3 202301450122 46 1 202301450110
Condenser seal connector Coil temp. sensor ass'y
Room temp sensor ass'y T41
Wired controller
1 201290108625 2 202301300401
1 202301300403 1 203355100210
86
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
MGB-D65W/RN1
87
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
No. Part Name Qty BOM code No. Part Name Qty BOM code
1
2
3 Condenser ass'y A 1 201590100023 28
A combination of pieces of fixed plate condenser
Condenser side board
1 201290108627 26 Pole
2 201290108624 27
Electronic control box door A machine back to the tube components
4 201290108623
1 201290190139
1 201690191335
88
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
No. Part Name
3.1
3.2 Fluted pipe ass'y A 1 201690101439 29
3.3
4 Condenser ass'y B 1 201590100024 30
4.1 Condenser ass'y of B 1 201590100031 30.1 4-way valve 1 201600600110
4.2 Fluted pipe ass'y B 1 201690101440 30.2 Pressure controller 1 202301820014
4.3
5 Mid horizontal support 2 201290100219 30.4 Pipe joint 2 201601200004
6 Fixed board 2 201290100233 31 Four-way valve ass'y of A 1 201690191390
7 Mid upright support 2 201290100211 31.1 4-way valve 1 201600600110
8 Pipe fixing clamp 2 201252600035 31.2 Pressure controller 1 202301820014
9 Evaporator input pipe ass'y 1 201690191273 31.3 Pressure controller 1 202301800840
9.1 Electronic expansion valve 1 201601300018 31.4 Pipe joint 2 201601200004
9.2 Strainer 2 201600910001 32 Drainage pan ass'y 1 201290100195
10
10.1 Electronic expansion valve 1 201601300018 34 Net 2 201290100240
10.2 Strainer 2 201600910001 35 Net 4 201290100237
11 Cover 1 201290100241 36 Top upright support 2 201290100191
12 Cover 1 201290100246 37 Condenser seal connector 1 201290108626
13 Triangle reinforcement ass'y 8 201290100218 38 Top cover 2 201195300051
14 Reinforcement board 4 201290100247 39 Axial flow fan 2 201200300013
15 Base 1 201290190198 40 Discharge pipe ass'y of A 1 201690191381
16
17 Cover 1 201290100243 42 Mid horizontal support 2 201290100223
18 Wiring terminal fixing board 1 201290100193 43 Motor bracket ass'y 4 201290100005
19 Cover 1 201290100244 44 Condenser seal connector 1 201290108625
20 Cover 1 201290100245 45 Unload valve ass'y 1 201690191392
21 Outdoor electric box ass'y 1 203390190028 45.1 Pressure-relief-valve 1 201600600501
21.1
21.2 Electronic installing board 1 201290190196 47 EEV solenoid coil 2 201601300516
21.3 Outdoor main board ass'y 1 201390190017 48 Discharge temp sensor 3 202301610027
21.4
21.5 Relay 3 202300800003 50 Coil temp. sensor ass'y 2 202301300401
21.6 Contactor 2 202300850043 51 Temp.sensor ass'y 1 202301300083
21.7 AC contactor 1 202300850050 52 Coil temp sensor ass'y 3 202301300081
21.8 Transformer 1 202300900109 53 Compressor electric heater 1 202403100031
21.9 Wire joint,11p 1 202301400365 54 Compressor electric heater 2 202403100254
21.10 Wire joint,4p 1 202301450003 55 4-Ways valve solenoid 2 201600600103
21.11 Wire joint 1 202301450110 56 R410A 14 200500100003
21.12 Wire joint 3 202301450122 57 Compressor 1 201401400740
21.13
21.14 Compressor capacitor 2 202401000410 59 Compressor 1 201401420030
22 Wiring trough 0.5 201119900945 60
23 Vapor-liquid separator 2 201601100111 61 Oil balance pipe ass'y 1 201690191385
24 Shell and tube evaporator 1 201790190017 62
25 Cover 1 201290100242 63
Condenser ass'y of A
The condenser splitter assemblies A
The condenser splitter assemblies B
Evaporator input pipe ass'y of A
Supporting ass'y of compressor
Welding together pieces of electronic control box
Outdoor current detection board ass'y
Three-phase power protection devices
Qty BOM code No. Part Name Qty BOM code
1 201590100030 28.1
1 201690101393 29.1 Pressure controller 1 202301820073
1 201690101392 30.3 Pressure controller 1 202301800840
1 201690191395 33 Middle partition plate 2 201290100248
2 201290190199 41 Motor 2 202400401168
1 201290190144 46
1 201390190024 49 Room temp sensor ass'y T41 1 202301300403
1 202301600518 58 Compressor 1 201401420040
Pressure controller A machine back to the tube ass'y
A four-way valve assembly machine
Fixed plate with the condenser B
Gas balance pipe of compreesor
Total water temperature mouth components Accessory- wired controller(English)
1 202301820073
1 201690191377
1 201690191339
1 201290108629
1 201690191384
1 201690101220
1 203355100572
89
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
10.4 MGB-F130W/RN1
90
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
No. Part Name Qty BOM code No. Part Name Qty BOM code
1 2 3 4 5 6 7
8 9 10 11 Cover 1 201290100242 42 Motor bracket bonding parts 8 201290100284 12
12.3
12.4 Wire joint 5 202301450122 45
12.5 Relay 4 202300800003 46
12.6 Compressor capacitor 4 202401000410 46.1
12.7 Transformer 2 202300900109 46.2
12.8 Wire joint 1 202301450130 46.3
12.9 Wire joint, 5p 1 202301450037 47
12.10 AC contactor 4 202300850050 47.1
12.11 Wire joint 1 202301450104 48
12.12 13
14
15 Cover 1 201290100244 49
16
The top beam The condenser seal fittings. II Iron nets fixed plate. II Protect net around pole Trough fixation plate Left right panel by. II
Iron nets fixed board I Protect network and In the frame beams
Air-cooled electronic control box assembly module Outdoor control board assembly
Three-phase power protection devices
Control box door Cover
Cover
2 201290100258 35.3 2 201290100260 36 2 201290100429 37 4 201290100433 38 4 201290100427 39 4 201290100266 40 1 201290100269 40.1
2 201290100430 40.2 4 201290100432 40.3 2 201290100255 41
1 203390190019 43 Motor 4 202400400399 1 201390100013 44 Axial flow fan 4 201200300013
2 202301600518 48.1 4-way valve 1 201600600110 1 201290100280 48.2
1 201290100241 48.3
1 201290100243 49.1
Pipe joint Fixed plate Pipe fixing clamp Welding parts water tray Seal plate condenser A condenser components Condenser ass'y of A
A flute-shaped tube assembly machine The condenser splitter assemblies A A combination of pieces of fixed plate condenser
Fixed plate with the condenser B
B condenser components Condenser ass'y of B
B-flute-shaped tube assemblies The condenser splitter assemblies B A1 machine to take over the evaporator component four-way valve
Pressure controller B2 four-way valve assembly machine
Pressure controller Pipe joint
B2 machines take over the four-way valve assembly evaporator
Pressure controller
2 201601200004 4 201290100297 6 201252600035 2 201290100431 4 201290100428 2 201590100025 1 201590100030
1 201690101436 1 201690101393 2 201290108627
2 201290108629 2 201590100026
1 201590100031 1 201690101437
1 201690101392
1 201690191296
1 202301800842 1 201690191350
1 202301800843 2 201601200004
1 201690191297
1 202301800842
91
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
No. Part Name
17 18 19
20 21 Reinforcement board 4 201290100247 52
22 23 24 25
26 27
28 29
30
30.1 Electronic expansion valve 1 201601300018 59 31
31.1 32
32.1 Electronic expansion valve 1 201601300018 66 33
33.1 34
34.1
34.2
34.3
34.4 Pipe joint 2 201601200004 73 35
35.1 4-way valve 1 201600600110 81
35.2
Base weld parts Compressor
Storage tank bottom II weld installation Compressor installed base II weld
Triangle reinforcement ass'y Piping support-unit Vapor-liquid separator Shell and tube evaporator
Storage tank bottom I weld parts installation Compressor installed base I weld
Vertical beams in the frame I left panel
B2 machine evaporator inlet pipe assembly
A2 machine evaporator inlet pipe assembly Electronic expansion valve to take over B1 Evaporator inlet pipe assembly machine
A1 machine evaporator inlet pipe assembly
Electronic expansion valve B1 machine four-way valve assembly
4-way valve Pressure controller Pressure controller
A1 Machine four-way valve assembly
Pressure controller
Qty BOM code No. Part Name Qty BOM code
1 201290100286 50 4 201402300130 50.1 1 201290100264 51
1 201290100273 51.1 Pressure controller 1 202301800844
8 201290100218 52.1 2 201290100272 52.2 4 201601100111 52.3 1 201790190019 52.4
1 201290100265 53 1 201290100274 54
2 201290100256 55 3 201290100270 56
1 201690191293 57 Vertical beam roof rack 2 201290100287
1 201690191291 61 1 201690101166 63 1 201690191295 64 Room temp sensor ass'y T41 2 202301300403
1 201690191294 67 1 201601300018 68 1 201690191354 69 Four-way valve coil 2 201600600237 1 201600600110 70
1 202301800842 71 1 202301800841 72
1 201690191356 76 Coil temp sensor ass'y 4 202301300400
1 202301800841
A2 machine back to the tube components
Pressure controller B1 machine back to the tube components
A2 four-way valve assembly machine
4-way valve Pressure controller Pressure controller Pipe joint
I sealed connector condenser Roof rack beams II
Top cover I beam roof rack
Total water temperature mouth components
Coil temp sensor ass'y Pipe temperature sensor assemblies
Discharge temperature controller Electrical heating belt compression
Four-way valve coil
Electronic expansion valve coil Refrigerant Wire controller
Pipe temperature sensor assemblies
Pipe temperature sensor assemblies
1 201690191373 1 202301800845 3 201690191375
1 201690191352 1 201600600110
1 202301800842 1 202301800843 2 201601200004
2 201290100261 1 201290100276
4 201195300051 1 201290100277
1 201690101220 2 202301300081 1 202301300082
4 202301610049 4 202403101357
2 201600600235
4 201601300544
28 200500100021
1 203355100210 3 202301300097
1 202301300478
92
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
10.5 MGB-F185W/RN1
93
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
No. Part Name Qty BOM code No. Part Name Qty BOM code
1 Column 4 201290100384 41.1 2 About the protective screen 4 201290100347 41.2 3 Network Rail fixed plate II 2 201290100349 41.3
4 Vertical beam in the frame 2 201290100386 42 5 Roof rack crossbar 2 201290100377 42.1 6 I sealed connector condenser 3 201290100378 43 7 Vertical beam roof rack 2 201290100383 43.1 8 Condenser sealed connector II 3 201290100381 44 9 Roof rack beam welding parts 2 201290100359 44.1 10 Top cover 6 201195300051 45 11 Rear Panel II 1 201290100366 46
12 Condenser output tube II 3 201690101357 47 13 In lane bridge I 2 201290100353 48
14 15
16 Rear Panel I 1 201290100367 51 Trunking II 1 201290100361 17
18 Electric door 2 201290100374 53 19
19.1
19.2 94
Block I installed electronic control box Block III electronic control box installed
Block II Electronic Control Box Installation
Air-cooled electronic control box assembly module Welding together pieces of electronic control box
Electrical mounting plate I
2 201290100364 49 Panel fasteners II 8 201290100372 2 201290100362 50 Triangular reinforcement 12 201290100387
2 201290100363 52 II trunking cover 1 201290100360
1 203390190012 53.1 Electronic expansion valve 1 201601300018 1 201290100390 54
1 201290100388 54.1
4-way valve Pressure controller Pipe joint
Evaporator tube assembly output
Pressure controller Evaporator tube assembly output
Pressure controller Evaporator tube assembly output
Pressure controller Welding together pieces of the base
Left panel II Strengthened beams II I left panel
Enter the evaporator tube assembly
Enter the evaporator tube assembly
Electronic expansion valve
1 201600600110 1 202301800843 2 201601200004
1 201690191322 1 202301800842 1 201690191323 1 202301800842 1 201690191321 1 202301800842 1 201290100376 1 201290100365
2 201290100370 3 201290100369
1 201690191313
1 201690191312 1 201601300018
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
No. Part Name
19.3
19.4
19.5
19.6 AC contactor 6 202300830520 57
19.7 Transformer 3 202300900109 58
19.8
19.9
19.10
19.11
19.12
19.13 A Terminal Block 3 202301400231 64
19.14
20
21
21.1
22
22.1
23
24
25
26
27
28 Motor 5 202400400399 73
29
30
31
32
33 Tube fixed plate II 2 201290100355 76
34
35
36 Tube fixed plate III 12 201290100354 78
37
37.1 Pressure controller 1 202301800842 80 Coil temp sensor ass'y 9 202301300081
38
38.1 Pressure controller 1 202301800842 82
39
39.1 Pressure controller 1 202301800842 84
40 I four-way valve assembly 1 201690191309 85
40.1 4-way valve 1 201600600110 86
40.2
40.3
41
Electrical component mounting plate II
Main control board ass'y
Relay
Wire joint, 5p
Wire joint
Wire joint
Compressor capacitor Three-phase power protection devices
A Terminal Block
Seal plate condenser Components of the compressor back to the trachea
Pressure controller I return to the trachea compressor components
Pressure controller
Condenser inlet pipe II I enter the tube condenser components
Part B condenser B fixed plate with pieces of condenser
Axial flow fan
Induction motor
Motor bracket bonding parts A fixed plate with pieces of condenser
A machine Condenser Parts
Welding parts water tray
In lane bridge II
Evaporator tube assembly output
Evaporator tube assembly output
Evaporator tube assembly output
Pressure controller
Pipe joint
Four-way valve assembly III
Qty BOM code No. Part Name Qty BOM code
1 201290100389 55
3 201390100009 55.1
6 202300800003 56
1 202301450037 59
10 202301450122 60
1 202301450130 61
6 202401000410 62
3 202301600518 63 I fixed plate tube 4 201290100356
1 202301400232 64.1
6 201290100382 64.2
5 201690191311 64.3 Pipe joint 2 201601200004
1 202301800845 65 separator 6 201601100072
1 201690191330 66 The beams in the 2 201290100385
1 202301800845 67 Front Panel 4 201290100368
3 201690101354 68 Strengthen the beam I 4 201290100371
3 201690101362 69 Network Rail fixed plate I 4 201290100350
3 201590100022 70
3 201290108635 71
6 201200300013 72
1 202400400564 73.1
12 201290100375 74
3 201290108634 75
3 201590100021 75.1
3 201290100398 76.1
2 201290100352 77
1 201690191318 79 Wired controller 1 203355100210
1 201690191319 81 Coil temp sensor ass'y 6 202301300400
1 201690191320 83 Room temp sensor ass'y T41 3 202301300403
1 202301800843 87
2 201601200004 88
2 201690191325 89
Enter the evaporator tube assembly
Electronic expansion valve
I output tube condenser Output tube condenser (C drive) transition tube assemblies Condenser output tube (D drive) transition tube assemblies
Shell and tube evaporator
Duct I
I cover trunking
I panel fasteners
Four-way valve assembly II
4-way valve
Pressure controller
Front grille Welding parts mounting base compressors
Compressor Enter the evaporator tube assembly
Electronic expansion valve
I fixed plate throttle parts Enter the evaporator tube assembly
Electronic expansion valve Enter the evaporator tube assembly
Electronic expansion valve
Target flow-volume controller Total water temperature mouth components
Pipe temperature sensor assemblies
Discharge temperature controller Electrical heating belt compression Electronic expansion valve coil
Four-way valve coil
Four-way valve coil
R410A
1 201690191314
1 201601300018
3 201690101358
1 201690101405
1 201690101408
1 201790190020
1 201290100392
1 201290100391
10 201290100373
3 201690191310
1 201600600110
1 202301800843
6 201290100348
6 201290100351
6 201402300130
1 201690191317
1 201601300018
2 201290100358
1 201690191315
1 201601300018
1 201690191316
1 201601300018
1 202301820013
1 201690101220
1 202301300097
6 202301610049
6 202403100066
6 201601300544
4 201600600239
2 201600600235
42 200500100003
95
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
10.6 MGB-F250W/RN1
96
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
69.5 69.9 69.8 69.4
69.1 69.1
69.15
69.6
69.14
69.10 69.1 69.7
No. Part Name Qty BOM code No. Part Name Qty BOM code
1
Triangular reinforcement
2
Left panel II
3
Vertical beam in the frame
4
Strengthened beams II
5
I panel fasteners
6
I left panel Inputting pipe ass'y of A unit
7
evaporator
7.1
Electronic expansion valve
7.2
Strainer
8
Discharging pipe ass'y Inputting pipe II of B unit
9
evaporator Inputting pipe ass'y of B unit
10
evaporator
10.1
Electronic expansion valve
10.2
Strainer
11
Column
12 Base welding parts 1 201290190241 69.4
13 Base guard board 10 201290190257 69.5
Inputting pipe ass'y of C unit
14
evaporator
14.1 Electronic expansion valve 1 201601300021 69.7 AC contactor 8 202300850046
14.2 Strainer 2 201600900078 69.8 AC contactor 8 202300850050 15 Guard board welding parts 4 201290190253 69.9 Transformer 2 202300900109 16 Four-way valve ass'y I 3 201690191473 69.10 A Terminal Block 1 202301400253
Outlet pipe ass'y I of
17
condenser Inputting pipe ass'y of D unit
18
evaporator
18.1 Electronic expansion valve 1 201601300021 69.13
18.2 Strainer 2 201600900078 69.14 19 Four-way valve ass'y II 1 201690191465 70
20 Pipe support VI 1 201290190258 71
21 Cover of wire casing III 1 201290190285 72
22
Wire casing III
12 201290100387 56
1 201290100365 58 2 201290100386 59 2 201290100370 60
10 201290100373 61
3 201290100369 62
1 201690191460 63 Pipe fixing clamp 20 201252600035
1 201601300021 64 Reinforcing board I 1 201290190244 2 201600900078 65 Pipe support III 1 201290190261 8 201690191435 67 Pipe preforming 9 201286900040
1 201690191451 68 Pipe support VII 8 201290190273
1 201690191429 69
1 201601300021 69.1 Installation board II ass'y 1 201290190265 2 201600900078 69.2 Installation board I ass'y 1 201290190267 4 201290100384 69.3 Electrical box welding parts 1 201290190269
1 201690191453 69.6 Relay 6 202300800003
3 201690191447 69.11 Wire joint,11p 1 202301400365
1 201690191457 69.12 Wire joint, 1P 3 202301400419
1 201290190260 73
Top cover Front panel II Fixed part of panel Bottom pillar I Pipe support IV Front panel I
Electrical box ass'y of air modular
Currrent detction board ass'y of outdoor unit Main board ass'y of outdoor unit
Wire joint,4p Wire joint Reinforcing board II
Three-phase asynchronous motor Back support board of electric box
Pipe support V
8 201195300051 1 201290190282 1 201290190281 1 201290190245 1 201290190274 1 201290190283
1 203390190031
2 201390100024
2 201390190031
1 202301450003 7 202301450122 3 201290190242
6 202400800834
1 201290190272
3 201290190259
97
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
No. Part Name
Outlet pipe ass'y II of
24
condenser
25
Wire casing I
26
Cover of wire casing I
27
Shell-tube heat exchanger Installation base welding
28
parts of compressor
29
Inclined support II
30 Pipe support I 1 201290190263 80
31 Pipe support II 2 201290190262 81
32 Grille fixed board I 4 201290190251 82 33 Front grille 8 201290100348 83 34 Fixed board II of grille 2 201290190250 84
35 Compreesor 8 201402300210 85
37 Liquid separator 4 201601100165 86
38 Bottom column 4 201290190247 87
39 Beam 2 201290190246 88
40 Front Panel 5 201290100368 89
41 Wire casing 1 201290190277 90
42 Cover of wire casing II 1 201290190278 91
43
Fixed board of drainage
45
Panel fasteners II
46
Inclined support I
47
Wire support
48
Wiring bridge I sealed connector
49
condenser Condenser sealed connector
50
II
52
About the protective screen
53
Upper beam Roof rack beam welding
54
parts
55
Vertical beam roof rack
Qty BOM code No. Part Name Qty BOM code
1 201690191445 74 Seal plate condenser 8 201290100382
1 201290190279 75 Motor 2 202400800952 1 201290190280 76 Axial flow fan 8 201200300013 1 201790190021 77 Motor bracket bonding parts 16 201290100375
4 201290190255 78 Part B condenser 4 201590100022
1 201290190249 79
8 201290190243 92 8 201290100372 93 1 201290190248 94 3 201290190270 95 3 201290190264 96
4 201290100378 97 Four-way valve coil 4 201600600517
4 201290100381 99
4 201290100347 100
2 201290190252 101
3 201290100359 102
2 201290100383
A machine Condenser Parts B fixed plate with pieces of condenser A fixed plate with pieces of condenser
Welding parts water tray Cover II of electrical box Cover I of electrical box
Support board of electrical box
Output pipe of evaporator Output pipe ass'y of evaporator(A) Output pipe ass'y of evaporator(B) Output pipe ass'y of evaporator(C) Output pipe ass'y of evaporator(D) Suction pipe ass'y of compressor
Suction pipe III Oil balance pipe ass'y I Reinforcing board Refrigerant Oil balance pipe ass'y II
Electronic expansion valve coil Total water temperature mouth components
Target flow-volume controller Electrical heating belt compression
4 201590100021
4 201290108635
4 201290108634
4 201290100398 1 201290190275 1 201290190276
2 201290190271
1 201690191452
1 201690191443
1 201690191441
1 201690191439
1 201690191437
4 201690191462
4 201690191450 4 201690191477 1 201290190284
60 200500100021
4 201690191478
4 201601300544
1 201690101220
1 202301820013
8 202403100066
98
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
11 Troubleshooting
11.1 Failure & Protection Codes of the Module
25/30kw module
No
Code Trouble
1 E0 Water flow detection error (The third time)
2 E1 Power phase sequence error
3 E2 Communication error
4 E3 Total water outlet temperature sensor error
5 E4 Outlet water temperature sensor in Shell and tube exchanger error
6 E5 Pipe temperature sensor in condenser A error
7 E6 Pipe temperature sensor in condenser B error
8 E7 Outdoor ambient temperature sensor error
9 E8 System A is air discharge temperature sensor in digital compressor error
10 E9 Water flow detection error (The first and second times)
11 EA Main unit detect that auxiliary unit’s quantity have decreased
12 EB Freeze-proof temperature sensor 1 in shell and tube exchanger error
13 EC Wire control did not found out any on-line module unit
14 ED Wire control and module unit communication error
15 Ed 1-hour consecutive 4-times PE protection
16 EE Wire control and computer communication error
17 EF Inlet water temperature sensor error
18 P0 High pressure or air discharge temperature protection error in system A
19 P1 Low pressure protection system A
20 P2 High pressure or air discharge temperature protection in system B
21 P3 Low pressure protection System B
22 P4 Current protection in system A
23 P5 Current protection in system B
24 P6 Condenser high pressure protection in system A
25 P7 Condenser high pressure protection in system B
26 P8 System A is air discharge temperature sensor in digital compressor
27 Pb System freeze-proof protection
28 PE Low-temperature protection of double-pipe heat exchanger
29 F1 EEPROM failure
30 F2
Failure of reduction of wired controller number at parallel connection of multiple wired controller (reserved) parallel connection of multiple wired controller
99
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
New 30kw module
For MGCSL-F30W/RN1 and MGCSL-D30W/RN1 only)
(
No
Code Trouble
1 E0 Error of outdoor EEPROM
2 E1 Power phase sequence error
3 E2 Communication error
4 E3 Error of total outlet water.temp sensor(Be valid for main unit)
5 E4 Error of unit outlet water.temp sensor
6 E5 Pipe temperature sensor in condenser A error
7 E6 Pipe temperature sensor in condenser B error
8 E7 Outdoor ambient temperature sensor error
9 E8 Output of the power protector error
10 E9 Water flow detection error(manual recovery)
11 EA (Reserved failure code)
12 Eb Freeze-proof temperature sensor in shell and tube exchanger error
13 EC Wire control detect that the units on-line have decreased.
14 Ed (Reserved failure code)
15 EF Error of inlet water temperature sensor
16 P0 High pressure or air discharge temperature protection error in system A (manual recovery)
17 P1 Low pressure protection System A (manual recovery)
18 P2 High pressure or air discharge temperature protection in system B (manual recovery)
19 P3 Low pressure protection System B (manual recovery)
20 P4 Current protection in system A (manual recovery)
21 P5 Current protection in system B (manual recovery)
22 P6 Condenser high temperature protection in system A
23 P7 Condenser high temperature protection in system B
24 P8 (Reserved failure code)
25 P9 Protection of outlet and inlet water temperature difference
26 PA Low ambient temperature drive-up protection
27 Pb System anti-frozen protection
28 PC Anti-freezing pressure protection of the system A (manual recovery)
29 Pd Anti-freezing pressure protection of the system B (manual recovery)
30 PE Low-temperature protection of evaporator (manual recovery)
100
MCAC-ATSM-2011-12 Air-cooled modular chiller unit 50Hz
55/60/65kw module (Fixed speed)
No
Code Trouble
1 E0 Water flow detection error (The third time)
2 E1 Power phase sequence error
3 E2 Communication error
4 E3 Total water outlet temperature sensor error
5 E4 Outlet water temperature sensor in Shell and tube exchanger error
6 E5 Pipe temperature sensor in condenser A error
7 E6 Pipe temperature sensor in condenser B error
8 E7 Outdoor ambient temperature sensor error
9 E8 System A is air discharge temperature sensor in digital compressor error
10 E9 Water flow detection error (The first and second times)
11 EA Main unit detect that auxiliary unit’s quantity have decreased
12 EB Freeze-proof temperature sensor 1 in shell and tube exchanger error
13 EC Wire control did not found out any on-line module unit
14 ED Wire control and module unit communication error
15 Ed 1-hour consecutive 4-times PE protection
16 EE Wire control and computer communication error
17 EF Inlet water temperature sensor error
18 P0 High pressure or air discharge temperature protection error in system A
19 P1 Low pressure protection system A
20 P2 High pressure or air discharge temperature protection in system B
21 P3 Low pressure protection System B
22 P4 Current protection in system A
23 P5 Current protection in system B
24 P6 Condenser high pressure protection in system A
25 P7 Condenser high pressure protection in system B
26 P8 System A is air discharge temperature sensor in digital compressor
27 P9 Protection of outlet and inlet water temperature difference
28 PA Starting protection of low-temp cooling
29 Pb System freeze-proof protection
30 PC (Reserved failure code)
31 PE Low-temperature protection of shell-and-tube heat exchanger
32 F1 EEPROM failure
33 F2
Failure of reduction of wired controller number at parallel connection of multiple wired controller (reserved) parallel connection of multiple wired controller
101
Air-cooled modular chiller unit 50Hz MCAC-ATSM-2011-12
65kw digital module (Only for MGB-D65W/RN1)
No
Code Trouble
1 E0 EEPROM error
2 E1 Power phase sequence error
3 E2 Communication error
4 E3 Total water outlet temperature sensor error
5 E4 Outlet water temperature sensor in heat exchanger error
6 E5 Pipe temperature sensor in condenser A error
7 E6 Pipe temperature sensor in condenser B error
8 E7 Outdoor ambient temperature sensor error or power supply protection
9 E8 Output error of the power protector
10 E9 Water flow detection error
11 EA (Reserved failure code)
12 Eb Freeze-proof temperature sensor 1 in shell and tube exchanger error
13 EC Wire control detect that the units on-line have decreased.
14 Ed (Reserved failure code)
15 EF Inlet water temperature sensor error
16 P0 High pressure or air discharge temperature protection error in system A
17 P1 Low pressure protection System A
18 P2 High pressure or air discharge temperature protection in system B
19 P3 Low pressure protection System B
20 P4 Current protection in system A
21 P5 Current protection in system B
22 P6 Condenser high pressure protection in system A
23 P7 Condenser high pressure protection in system B
24 P8 (Reserved failure code)
25 P9 Protection of outlet and inlet water temperature difference
26 PA Low ambient temperature drive-up protection
27 Pb System freeze-proof protection
28 Pc Anti-freezing pressure protection of the system A
29 Pd Anti-freezing pressure protection of the system B
30 PE Low-temperature protection of shell-and-tube heat exchanger
102