1.2 Products list .................................................................................................................................................................... 3
1.4 Features ......................................................................................................................................................................... 5
1.10 Electric Characteristics ............................................................................................................................................... 17
1.11 Outlook drawing: MGBT-F25W/RN1, MGBT-D25W/RN1, MGBT-D30W/RN1, MGBT-F30W/RN1 .............................. 18
1.12 Outlook drawing: MGBT-F60W/RN1 .......................................................................................................................... 19
1.13 Outlook drawing: MGBT-D60W/RN1.......................................................................................................................... 20
1.14 Outlook drawing: MGBT-F120W/RN1 ........................................................................................................................ 21
1.15 Outlook drawing: MGBT-F180W/RN1 ........................................................................................................................ 22
1.16 Outlook drawing: MGBT-F250W/RN1 ........................................................................................................................ 24
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Mode
Outlet water temp.
Cooling(S5
address)
Normally(OFF)
5~17℃
Low water temp.(ON)
0~17℃
Heating(S4
address)
Normally(OFF)
40~50℃
Low water temp. (ON)
22~50℃
Max 8 units
Picture2
2000kW
250kW
250kW
1.4 Features
1). Wide range of outlet water temp. (For MGBT-D60W/RN1, MGBT-F250W/RN1)
Cooling: 5~17˚C (7˚C set in factory), 0~17˚C can be available by switch the S5 on PCB, the antifreeze must be
put into pipeline.
Heating: 40~50˚C (45˚C set in factory), 22~50˚C can be available by switch the address.
2).Humanization remote control (For MGBT-D60W/RN1, MGBT-F250W/RN1)
S7 address on PCB should be switched to ON to realize remote
control, which including: Remote ON/OFF, remote heating and
cooling mode selection, remote alarm. The customer can simply
and conveniently control the module and acquire the running
information on real time in door.
3).Digital scroll technique,new type air-cooled modular chiller system.
Capacity output is controlled depending on controlling compressor to on/off in traditional modular air-cooled
chiller system control. The precision of the control mode is not very good, and the compressor is frequently on
and off, which is very bad for the compressor’s life.
Digital scroll modular air-cooled chiller system breaks traditional design, which is inconceivably designed with
digital scroll compressor and constant scroll compressor parallel connection. The system can achieve linear
capacity output within 0.5%-100% after modules combined, the scope is widest in industry. When the system
operates at the part-load, the system can accurately adjust cooling and heating capacity output basing on
actual requirement of the indoor room.
4). Easy and fast installation
The unit adopts modular design, which can make more units connect together. The unit can combine 16
separate module(equal and less than 65kW) or 8 module(250kW).Cooling(heating) capacity can increase
step by step by 5KW per each time within 15kW-2000kW,meanwhile every separate module can operate as
main unit, also each module can be a slave unit with modules combination, more convenient for design and
installation.
The maximum combination of the system consists of 1 main unit and 15 slave units for 25kW&30kW&60kW
module,1 main unit and 7 slave units for 120kW module, 1 main unit and 4 slave units for 180kW module, 1
main unit and 7 slave units for 250kW module.
5
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Wired controller
Three-core shielding
twisted pair
Three-core shielding
twisted pair
Water outlet temp.
Water outlet temp.
Water outlet temp.
Total water outlet temp.
(Just for master unit)
Total water outlet temp.
(Just for master unit)
Total water outlet temp.
(Just for master unit)
Easily connect between main unit and slave units.
All the units can be connected together with a wired controller in series type. Using three-core shielded
twisted wire as communication wire.
5).Environmental care
R410a— the environmental refrigerant.
Chlorine-free and environmental friendly refrigerant, zero ozone depletion potential.
High density refrigerant, therefore, less refrigerant required.
Leak-tight refrigerant circuit, Brazed refrigerant connections for increased leak-tightness.
6). Economical operation
New design adopts electronic expansion valve precise refrigerant control in wider range. Electronic
expansion valve allows operation at lower condensing pressure, the adjustment can be made fast linear
response, making the system more stable output, the indoor temp. more uniform, and enhanced human
comfortable.
7). Compact structure
The structure of air-cooled modular chiller is compact, light weight. The system adopts double-pipe or shell
and tube heat exchanger, which not only greatly enhanced the transfer performance, but also reduced the
unit weight, the lightest single module has only 380kg.
8). Back up function
6
When unit is failure
If master unit fails, all the units will stop.
If one slave unit fails, this unit will stop but the others will keep running.
When the master unit fails, any of the slave one can be set as the master unit by manual setting.
When unit is under protection
If master unit’s protection occurs, this unit will stop but the others will keep running.
If slave unit’s protection occurs, this unit will stop but the others will keep running.
( Except PE, P9 protection happen)
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
MasterSlave
MasterSlave
Mode
Ambient temp. range
Water outlet temp. range
Cooling
10˚C ~52˚C
5˚C ~17˚C (7˚C is default)
10˚C ~46˚C
0~17˚C(0˚C must add antifreeze)
Heating
-10˚C ~21˚C
45˚C ~50˚C (45˚C is default)
22˚C ~50˚C
9).Strong micro-computer intelligent control and monitor function.
Optimizing the design of system and using varieties of protection devices, to make the system more safe and
reliable.
10). Superior reliability
System will be more reliable with new type efficient heat exchanger.
Evaporator of 25KW and 30KW module adopt double pipe heat exchanger,evaporator of 60kW ,120kW and
180kW modules adopt shell and tube heat exchanger.
Double pipe heat exchanger Shell and tube heat exchanger
11) Applicable temp. range
7
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Model
Mode
Compressor
quantity
Refrigerant
Refrigeration
system
Electrical
controller no.
Maximum
combinations
Digital
Constant
MGBT-D25W/RN1
Cooling & Heating
1 1 R410A 2 1
16
MGBT-F25W/RN1
Cooling & Heating
0 2 R410A 2 1
16
MGBT-D30W/RN1
Cooling & Heating
1 1 R410A 2 1
16
MGBT-F30W/RN1
Cooling & Heating
0 2 R410A 2 1
16
MGBT-F60W/RN1
Cooling & Heating
0 2 R410A 2 1
16
MGBT-D60W/RN1
Cooling & Heating
1 2 R410A 3 1
16
MGBT-F120W/RN1
Cooling & Heating
0 4 R410A 4 2
8
MGBT-F180W/RN1
Cooling & Heating
0 6 R410A 6 3
5
MGBT-F250W/RN1
Cooling & Heating
0 8 R410A 4 2
8
-15˚C
Ambient temp. range
-10˚C
-5˚C
0˚C
5˚C
10˚C
15˚C
20˚C
25˚C
30˚C
35˚C
40˚C
45˚C
50˚C
Cooling range
10˚C
52˚C
Heating range
-10˚C
21˚C
Water outlet temp. range
5˚C
17˚C
50˚C
5˚C
17˚C
Heating range
Cooling range
45˚C
22˚C
0˚C
45˚C
50˚C
Cooling range
0˚C
17˚C
Heating range
22˚C
50˚C
Chilled outlet water temp. can be adjusted by wired controller according to customer’s requirement.
1.5 Capacity lineup
8
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Model
MGBT-F25W/RN1
MGBT-D25W/RN1
Cooling Capacity (*1)
kW
28
Btu/h
95,500
Cooling Capacity (*2)
kW
24.9
Btu/h
85,000
Heating Capacity
kW
29.5
EER(*1)
kW/ kW
3.01
EER(*2)
kW/ kW
2.20
COP
kW/ kW
3.21
Power supply
V/Ph/Hz
380~415/3/50
Power supply
Manual switch
A
50
Fuse
A
36
Compressor
Type
Scroll (fixed speed)
Digital Scroll + Fixed speed
Brand
Copeland
Copeland
Model
ZP61KCE-TFD-522
ZPD61KCE-TFD-532/
ZP61KCE-TFD-522
Quantity
Pieces
2
1+1
Power input
Cooling (*1)
kW
9.3
Cooling rated current (*1) A 14.6
Cooling (*2)
kW
11.16
Cooling rated current (*2) A 17.52
Heating
kW
9.2
Heating rated current
A
14.3
Max. Input consumption
kW
12.6
12.5
Rated Current
A
19
19
Refrigerant
Type
R410A
Refrigerant control
EXV
Weight
kg
3.1×2
Condenser
(Air side)
Air side heat-exchanger type
Fin-coil
Quantity of fan motor
Pieces
1
Air flow volume
×103m3/h
12
Fan motor model
YDK400-8-YA
Fan motor rated current
A
2.95
Fan motor input
kW
0.65
Evaporator
(Water side)
Water side heat-exchanger type
Double-pipe
Water pressure drop
kPa
60
Volume
L
10
Water inlet/outlet pipeline
inside normal diameter
inch
1-1/2”
Water flow volume
m3/h
4.8
Max. Pressure
MPa
1
Evaporator volume
L
10
Water pipe connection type
Flexible joint
Dimension
Net(W×H×D)
mm
1514×1865×841
1.6 Specification: MGBT-F25W/RN1, MGBT-D25W/RN1
9
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
inch
59.6×73.4×33.1
Packing size(W×H×D)
mm
1590×2065×995
inch
62.6×81.3×39.2
Weight
Net weight
kg
380
Gross weight
kg
400
Connection wire
Power wire
mm2×No.
10×4+6×1
Signal wire
mm2×No.
0.75×3-core with shielding
Control type
Wired controller
Safety protection device
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-freezing protection in cooling mode.
5) Anti-freezing protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temp. difference protection.
9) Compressor discharge temp. protection.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
12) Low-temperature protection of shell and tube heat
exchanger.
Sound level(semi-anechoic )
dB(A)
65
Operation water temp.
℃
Cooling:5~17 Heating:45~50
Ambient temp.
℃
Cooling:10~52 Heating:-10~21
Note: Specifications are based on the following conditions:
Cooling : (*1) chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 35°C (117℉) DB.
(*2) chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 46˚C(140℉) DB.
Heating : warm water inlet/outlet: 40˚C / 45˚C, and outdoor ambient temp. 7˚C DB/6°CWB.
Water side fouling factor: 0.086m2˚C /kW.
10
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Model
MGBT-F30W/RN1
MGBT-D30W/RN1
Cooling Capacity (*1)
kW
30
Btu/h
102,300
Cooling Capacity (*2)
kW
25.8
Btu/h
88,030
Heating Capacity
kW
32
EER(*1)
kW/ kW
3.00
EER(*2)
kW/ kW
2.15
COP
kW/ kW
3.27
Power supply
V/Ph/Hz
380~415/3/50
Power supply
Manual switch
A
50
Fuse
A
36
Compressor
Type
Scroll (fixed speed)
Digital Scroll + Fixed speed
Brand
Copeland
Copeland
Model
ZP61KCE-TFD-522
ZPD61KCE-TFD-532/
ZP61KCE-TFD-522
Quantity
Pieces
1+1
1+1
Power input
Cooling (*1)
kW
10.0
Cooling rated current (*1)
A
16.3
Cooling (*2)
kW
12
Cooling rated current (*2) A 19.56
Heating
kW
9.8
Heating rated current
A
16.0
Max. Input consumption
kW
12.6
12.5
Rated Current
A
21.1
21.1
Refrigerant
Type
R410A
Refrigerant control
EXV
Weight
kg
3.1×2
Condenser
(Air side)
Air side heat-exchanger type
Fin-coil
Quantity of fan motor
Pieces
1
Air flow volume
×103m3/h
12
Fan motor model
YDK400-8-YA
Fan motor rated current
A
2.95
Fan motor input
kW
0.65
Evaporator
(Water side)
Water side heat-exchanger type
Double-pipe
Water pressure drop
kPa
60
Volume
L
10
Water inlet/outlet pipeline
inside normal diameter
mm
DN40
inch
1-1/2”
Water flow volume
m3/h
5.2
Max. Pressure
MPa
1
Evaporator volume
L
10
Water pipe connection type
Flexible joint
Dimension
Net(W×H×D)
mm
1514×1865×841
inch
59.6×73.4×33.1
1.7 Specification: MGBT-F30W/RN1, MGBT-D30W/RN1
11
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Packing (W×H×D)
mm
1590×2065×995
inch
62.6×81.3×39.2
Weight
Net weight
kg
380
Gross weight
kg
415
Connection wire
Power wire
mm2×No.
10×4+6×1
Signal wire
mm2×No.
0.75×3-core with shielding
Control type
Wired controller
Safety protection device
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-frozen protection in cooling mode.
5) Anti-frozen protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temp. difference protection.
9) Compressor discharge temp. protection.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
12) Low-temperature protection of shell and tube heat
exchanger.
Sound level(semi-anechoic )
dB(A)
65
Operation water temp.
℃
Cooling:5~17 Heating:45~50
Ambient temp.
℃
Cooling:10~52 Heating:-10~21
Note: Specifications are based on the following conditions:
Cooling : (*1) chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 35°C (117℉) DB.
(*2) chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 46˚C (140℉)DB
Heating : warm water inlet/outlet: 40˚C / 45˚C, and outdoor ambient temp. 7˚C DB/6°CWB.
Water side fouling factor: 0.086m2˚C /kW.
12
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Model
MGBT-F60W/RN1
MGBT-D60W/RN1
MGBT-F120W/RN1
Cooling Capacity (*1)
kW
60
120
Btu/h
204,700
409,400
Cooling Capacity (*2)
kW
51.6
103.2
Btu/h
176,100
352,100
Heating Capacity
kW
64
65
128
EER(*1)
kW/ kW
3.11
3.09
3.12
EER(*2)
kW/ kW
2.20
2.22
2.23
COP
kW/ kW
3.23
3.19
3.08
Power supply
V/Ph/Hz
380~415/3/50
Power supply
Manual switch
A
100
200
Fuse
A
70
150
Compressor
Type
Scroll (fixed speed)
Digital Scroll + Fixed
speed
Scroll (fixed speed)
Brand
Copeland
Copeland
Copeland
Model
ZP137KCE-TFD-522
ZP137KCE-TFD-522
/ZPD72KCE-TFD-433
/ ZP67KCE-TFD-420
ZP137KCE-TFD-522
Quantity
Pieces 2 1+1+1
4
Power input
Cooling (*1)
kW
19.3
19.4
38.5
Cooling rated current (*1)
A
33.6
33.6
68.8
Cooling (*2)
kW
23.16
23.28
46.2
Cooling rated current (*2)
A
40.32
40.32
82.56
Heating
kW
19.8
20.4
41.5
Heating rated current
A
34.3
35.1
71.8
Max. Input consumption
kW
29.5
29
55.5
Rated Current
A
51.5
51.5
130
Refrigerant
Type
R410A
R410A
R410A
Refrigerant control
EXV+ capillary
Weight
kg
6.0×2
6.5×2
6.0×4
Condenser
(Air side)
Air side heat-exchanger type
Fin-coil
Quantity of fan motor
Pieces 2 2
4
Air flow volume
×103m3/h
24
24
48
Fan motor model
YS700-6F
YDK550-6E
YS700-6F
Fan motor rated current
A
1.8×2
4.0×2
1.8×4
Fan motor input
kW
0.9×2
0.865×2
0.9×4
Evaporator
(Water side)
Water side heat-exchanger type
Shell and tube
Shell and tube
Shell and tube
Water pressure drop
kPa
15
15
25
Volume L 42
42
64
Water inlet/outlet pipeline
inside normal diameter
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
inch
78.7×74×35.4
78.7×74×35.4
78.7×66.3×82.3
Packing (W×H×D)
mm
2090×2095×985
2090×2095×985
2090×1755×2240
inch
82.3×82.5×38.8
82.3×82.5×38.8
82.3×69×88.2
Weight
Net weight
kg
580
600
1150
Gross weight
kg
650
640
1200
Connection
wire
Power wire
mm2×No.
25×4+16 ×1
16×4+10×1
35×3+16 ×2
Signal wire
mm2×No.
0.75×3-core with shielding
Control type
Wired controller
Safety protection device
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-frozen protection in cooling mode.
5) Anti-frozen protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temp. difference protection.
9) Compressor discharge temp. protection.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
12) Low-temperature protection of shell and tube heat exchanger.
Sound level(semi-anechoic )
dB(A)
65
67
70
Operation water temp.
℃
Cooling:5~17
Heating:45~50
Cooling:0~17(5℃
must add antifreeze)
Heating:22~50
Cooling:5~17
Heating:45~50
Ambient temp.
℃
Cooling:10~52
Heating:-10~21
Cooling:10~52
Heating:-10~21
Cooling:10~52
Heating:-10~21
Note: Specifications are based on the following conditions:
Cooling : (*1) chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 35°C (117℉) DB.
(*2) chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 46˚C (140℉)DB
Heating : warm water inlet/outlet: 40˚C / 45˚C, and outdoor ambient temp. 7˚C DB/6°CWB.
Water side fouling factor: 0.086m2˚C /kW.
14
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Model
MGBT-F180W/RN1
MGBT-F250W/RN1
Cooling Capacity (*1)
kW
180
250
Btu/h
614,100
830000
Cooling Capacity (*2)
kW
155.8
216
Btu/h
528,200
737000
Heating Capacity
kW
195
270
EER(*1)
kW/ kW
3.11
3.19
EER(*2)
kW/ kW
2.66
2.50
COP
kW/ kW
3.28
3.38
Power supply
V/Ph/Hz
380~415/3/50
380~415/3/50
Power supply
Manual switch A 300
450
Fuse
A
200
300
Compressor
Type
Scroll (fixed speed)
Scroll (fixed speed)
Brand
Copeland
Copeland
Model
ZP137KCE-TFD-522
SH120A4ALC
Quantity
Pieces 6 8
Power input
Cooling (*1)
kW
57.9
78.3
Cooling rated current (*1)
A
100.8
141.9
Cooling (*2)
kW
58.5
86.3
Cooling rated current (*2)
A
121
170.3
Heating
kW
59.4
80
Heating rated current
A
102.9
146
Max. Input consumption
kW
78.3
104.9
Rated Current A 155.1
200
Refrigerant
Type
R410A
R410A
Refrigerant control
EXV+ capillary
EXV+ capillary
Weight
kg
6.0×6
15×4
Condenser (Air
side)
Air side heat-exchanger type
Fin-coil
Fin-coil
Quantity of fan motor
Pieces 6 8
Air flow volume
×103m3/h
72
96
Fan motor model
YS700-6F/ YS700-6F-1
YS700-6F-1/YS700-6F-2
Fan motor rated current
A
1.8×6
1.8×8
Fan motor input
kW
0.9×6
0.9×8
Evaporator
(Water side)
Water side heat-exchanger type
Shell and tube
Shell and tube
Water pressure drop
kPa
30
40
Volume
L
90
131
Water inlet/outlet pipeline
inside normal diameter
mm
DN80
DN100
inch
3”
4”
Water flow volume
m3/h
31
43
Max. Pressure
MPa 1 1
Evaporator volume L 90
131
Water pipe connection type
Flexible joint
Flexible joint
Dimension
Net(W×H×D)
mm
2850×2000×2110
3800×2130×2000
inch
112.2×78.7×83.1
149.6×83.86×78.74
1.9 Specification: MGBT-F180W/RN1, MGBT-F250W/RN1
15
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Packing size(W×H×D)
mm
2980×2135×2260
3900×2200×2100
inch
117.3×84.1×89
153.54×86.61×82.68
Weight
Net weight
kg
1730
2450
Gross weight
kg
1780
2500
Connection wire
Power wire
mm2×No.
70×3+35×2
185×4+70×1
Signal wire
mm2×No.
0.75×3-core with shielding
0.75×3-core with shielding
Control type
Wired controller
Wired controller Wiredcontroller
Safety protection device
1) Protection for over-high discharge pressure.
2) Protection for over-low suction pressure.
3) Power supply phase sequence protection.
4) Anti-frozen protection in cooling mode.
5) Anti-frozen protection in Winter.
6) Protection for compressor over current.
7) Protection for compressor overload.
8) Outlet and inlet water temp. difference protection.
9) Compressor discharge temp. protection.
10) Water flow cut-off protection.
11) Sensor malfunction protection.
12)Low-temp. protection of shell-and-tube heat exchanger.
Sound level(semi-anechoic )
dB(A)
74
74
Operation water temp.
℃
Cooling:5~17
Heating:45~50
Cooling:0~17(5℃ must
add antifreeze)
Heating:22~50
Ambient temp.
℃
Cooling:10~52
Heating:-10~21
Cooling:10~52
Heating:-10~21
Note: Specifications are based on the following conditions:
Cooling : (*1) chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 35°C (117℉) DB.
(*2) chilled water inlet/outlet: 12˚C / 7˚C, and outdoor ambient temp. of 46˚C (140℉)DB
Heating : warm water inlet/outlet: 40˚C / 45˚C, and outdoor ambient temp. 7˚C DB/6°CWB.
Water side fouling factor: 0.086m2˚C /kW.
16
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Model
Outdoor Unit
Application
Power
Supply
Compressor
OFM
Hz
VOL
Ph
Min.
Max.
TOCA
MFA
LRA
RLA
Qty
KW
FLA
Qty
MGBT-F25W/RN1
50
380-415
3
342
456
25
36
64
10.9
2
0.65
2.95
1
MGBT-D25W/RN1
50
380-415
3
342
456
25
36
64/64
10.9/10.9
2
0.65
2.95
1
MGBT-F30W/RN1
50
380-415
3
342
456
25
36
64
10.9
2
0.65
2.95
1
MGBT-D30W/RN1
50
380-415
3
342
456
25
36
64/64
10.9/10.9
2
0.65
2.95
1
MGBT-F60W/RN1
50
380-415
3
342
456
52
100
118
20.7
2
0.9x2
1.8x2
2
MGBT-D60W/RN1
50
380-415
3
342
456
52
100
118/82.4/74
20.7/12.7/11.8
3
0.865x2
4.0x2
2
MGBT-F120W/RN1
50
380-415
3
342
456
90
200
118
20.7
4
0.9x4
1.8x4
4
MGBT-F180W/RN1
50
380-415
3
342
456
135
300
118
20.7
6
0.9x6
1.8x6
6
MGBT-F250W/RN1
50
380-415
3
342
456
191
300
142
20.7
8
0.9x8
1.8x8
8
Voltage imbalance between phases to be <2%.
1.10 Electric Characteristics
Remark:
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
LRA: Locked Rotor Amps. (A)
RLA: Rated Load Amps. (A)
OFM: Outdoor Fan Motor.
FLA: Full Load Amps. (A)
KW: Rated Motor Input (KW)
17
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Model
Unit
A B C D E
F
MGBT-F(D)25W/RN1
MGBT-F(D)30W/RN1
mm
1514
841
1865
115
315
172
inch
59.6
33.11
73.43
4.53
12.4
6.77
No.
Name
1
Top cover
2
Air outlet
3
Air inlet
4
Water outlet
5
Water inlet
6
Electric control box
1.11 Outlook drawing: MGBT-F25W/RN1, MGBT-D25W/RN1, MGBT-D30W/RN1,
MGBT-F30W/RN1
Front view
Top view
18
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Model
Unit
A B C D E F G H I J K
MGBT-F60W/RN1
mm
2000
900
1880
350
1420
225
1500
506
530
930
450
inch
78.74
35.4
74
13.78
55.91
8.86
59.06
19.92
20.87
36.61
17.72
No.
Name
1
Top cover
2
Air outlet
3
Air inlet
4
Water outlet
5
Compressor
6
Electric control box
7
Water inlet
1.12 Outlook drawing: MGBT-F60W/RN1
Front view
Top view
19
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Model
unit A B C D E F G H I J
K
MGBT-D60W/RN1
mm
2000
900
1880
350
1420
225
1500
506
530
930
450
inch
78.74
35.43
74
13.78
55.9
8.86
59.05
19.92
28.87
36.61
17.72
3
1
2
4
5
6
7
1.13 Outlook drawing: MGBT-D60W/RN1
20
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
No.
Name
No.
Name
1
Top cover
5
Compressor
2
Air outlet
6
Electric control box
3
Air inlet
7
Water inlet
4
Water outlet
Model
Unit
A B C D E F G
H
MGBT-F120W/RN1
mm
2000
1685
2080
350
1420
506
1550
1586
inch
78.74
66.34
81.89
13.78
55.91
19.92
61.02
62.44
1.14 Outlook drawing: MGBT-F120W/RN1
Front view Side view
Top view Anchor hole
:
21
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
No.
Name
No.
Name
1
Top cover
5
Electric control box Air inlet
2
Condenser
6
Water outlet
3
Compressor
7
Water inlet
4
Evaporator
8
Compressor
1.15 Outlook drawing: MGBT-F180W/RN1
22
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Model
unit A B C D E F G H
MGBT-F180W/RN1
Mm
2850
2000
2110
3470
2156
506
1888
2388
inch
112.2
78.74
83.07
136.61
84.88
19.92
74.33
94.02
No.
Name
No.
Name
1
Top cover
5
Electric control box
2
Compressor
6
Water inlet
3
Evaporator
7
Condenser
Front view
23
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
4
Water outlet
Front view
E
A
C
F
D
Left view
B
Bottom view
HH
G
A
Hole for anchor boltΦ15
Model
unit A B C D E F G H
MGBT-F250W/RN1
Mm
3800
2000
2130
1235
2156
573
1888
1551
inch
149.6
78.74
83.86
48.62
84.88
22.56
74.33
61.06
1.16 Outlook drawing: MGBT-F250W/RN1
24
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
1
Air outlet
Air outlet
Air outlet
Air outlet
Air inlet
2
8
4
5
6
7
3
A
i
r
i
n
l
e
t
A
i
r
i
n
l
e
t
A
i
r
i
n
l
e
t
A
i
r
i
n
l
e
t
No.
Name
No.
Name
1
Top cover
5
Electric control box
2
Compressor
6
Water inlet
3
Evaporator
7
Condenser
4
Water outlet
8
Transportation guard plate (Be removed off
after installation)
25
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
2.7 Remote control ..........................................................................................................................................................109
2.8 Control software ........................................................................................................................................................110
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Chilled water
outlet temp.
Ambient temp.(℃)
21.00
25.00
30.00
35.00
40.00
46.00
52.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
5.00
31.35
8.19
29.52
8.44
27.85
8.71
26.32
8.97
24.66
9.42
22.69
9.89
20.42
10.39
6.00
32.41
8.32
30.49
8.58
28.73
8.84
27.13
9.11
25.45
9.57
23.44
10.05
21.12
10.55
7.00
33.54
8.49
31.52
8.75
29.68
9.02
28.00
9.30
26.29
9.77
24.24
10.25
21.87
10.77
8.00
34.57
8.74
32.46
9.01
30.54
9.29
28.78
9.58
27.06
10.06
24.97
10.56
22.55
11.09
9.00
35.55
8.83
33.35
9.10
31.34
9.38
29.51
9.67
27.77
10.16
25.66
10.66
23.20
11.20
10.00
36.90
8.96
34.58
9.24
32.47
9.52
30.54
9.82
28.77
10.31
26.62
10.82
24.09
11.36
11.00
37.93
9.05
35.51
9.33
33.31
9.62
31.31
9.91
29.52
10.41
27.34
10.93
24.77
11.48
12.00
38.79
9.18
36.29
9.46
34.01
9.76
31.93
10.06
30.15
10.56
27.95
11.09
25.35
11.64
13.00
39.49
9.25
36.90
9.54
34.55
9.84
32.41
10.14
30.63
10.65
28.43
11.18
25.81
11.74
14.00
40.47
9.32
37.79
9.61
35.35
9.90
33.13
10.21
31.34
10.72
29.11
11.26
26.46
11.82
15.00
40.99
9.36
38.23
9.65
35.73
9.95
33.46
10.26
31.68
10.77
29.47
11.31
26.81
11.88
1. Capacity tables
1.1MGBT-F25W/RN1,MGBT-D25W/RN1
Cooling:
Note:
The inlet/outlet water temperature difference is 5℃.
75
Heating:
Hot water
outlet temp.
Ambient temp.(℃)
-10
-6
-2 2 7
10
13
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
39.00
18.34
5.76
22.92
6.54
26.97
7.27
29.96
7.90
32.57
8.32
36.47
8.82
41.95
9.52
41.00
17.72
5.87
22.18
6.67
26.12
7.42
29.06
8.06
31.62
8.49
35.35
8.99
40.58
9.71
42.00
17.21
5.99
21.56
6.81
25.43
7.57
28.32
8.23
30.85
8.66
34.42
9.18
39.45
9.91
43.00
16.79
6.12
21.07
6.95
24.88
7.72
27.73
8.39
30.24
8.84
33.69
9.37
38.54
10.12
44.00
16.47
6.24
20.69
7.09
24.45
7.88
27.29
8.57
29.80
9.02
33.13
9.56
37.84
10.32
45.00
16.23
6.37
20.41
7.24
24.16
8.04
26.99
8.74
29.50
9.20
32.75
9.75
37.33
10.53
46.00
15.91
6.43
20.04
7.31
23.74
8.12
26.56
8.83
29.06
9.29
32.20
9.85
36.64
10.64
47.00
15.44
6.56
19.47
7.46
23.10
8.28
25.87
9.00
28.33
9.48
31.33
10.05
35.60
10.85
48.00
14.83
6.76
18.73
7.68
22.24
8.53
24.93
9.27
27.34
9.76
30.18
10.35
34.23
11.18
49.00
14.02
7.03
17.73
7.99
21.08
8.87
23.66
9.65
25.97
10.15
28.62
10.76
32.40
11.62
50.00
13.12
7.38
16.61
8.39
19.77
9.32
22.22
10.13
24.41
10.66
26.86
11.30
30.35
12.20
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Note:
The inlet/outlet water temperature difference is 5℃.
76
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Chilled water
outlet temp.
Ambient temp.(℃)
21.00
25.00
30.00
35.00
40.00
46.00
52.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
5.00
33.59
8.81
31.63
9.08
29.84
9.36
28.20
9.65
26.42
10.13
24.31
10.64
21.88
11.17
6.00
34.72
8.94
32.66
9.22
30.79
9.51
29.07
9.80
27.27
10.29
25.11
10.80
22.63
11.34
7.00
35.93
9.13
33.77
9.41
31.80
9.70
30.00
10.00
28.17
10.50
25.97
11.03
23.43
11.58
8.00
37.04
9.40
34.78
9.69
32.72
9.99
30.84
10.30
28.99
10.82
26.76
11.36
24.16
11.92
9.00
38.09
9.49
35.73
9.79
33.58
10.09
31.62
10.40
29.75
10.92
27.49
11.47
24.85
12.04
10.00
39.53
9.63
37.05
9.93
34.79
10.24
32.73
10.56
30.83
11.08
28.52
11.64
25.81
12.22
11.00
40.63
9.73
38.05
10.03
35.69
10.34
33.54
10.66
31.63
11.19
29.29
11.75
26.54
12.34
12.00
41.56
9.87
38.88
10.18
36.44
10.49
34.22
10.82
32.30
11.36
29.94
11.92
27.16
12.52
13.00
42.31
9.95
39.54
10.26
37.02
10.58
34.73
10.90
32.82
11.45
30.46
12.02
27.65
12.62
14.00
43.36
10.02
40.48
10.33
37.87
10.65
35.49
10.98
33.58
11.53
31.19
12.10
28.35
12.71
15.00
43.92
10.07
40.97
10.38
38.29
10.70
35.85
11.03
33.95
11.58
31.57
12.16
28.73
12.77
1.2 MGBT-F30W/RN1, MGBT-D30W/RN1
Cooling:
Note:
The inlet/outlet water temperature difference is 5℃.
77
Heating:
Hot water outlet
temp.
Ambient temp.(℃)
-10
-6
-2 2 7
10
13
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
39.00
19.89
6.13
24.86
6.97
29.25
7.74
32.50
8.42
35.33
8.86
39.57
9.39
45.50
10.14
41.00
19.22
6.26
24.06
7.11
28.34
7.90
31.52
8.59
34.30
9.04
38.34
9.58
44.02
10.35
42.00
18.67
6.38
23.39
7.26
27.58
8.06
30.72
8.76
33.46
9.22
37.34
9.78
42.79
10.56
43.00
18.22
6.52
22.86
7.40
26.98
8.23
30.08
8.94
32.80
9.41
36.54
9.98
41.81
10.77
44.00
17.86
6.65
22.44
7.55
26.53
8.39
29.61
9.12
32.32
9.60
35.94
10.18
41.04
10.99
45.00
17.60
6.78
22.14
7.71
26.21
8.57
29.28
9.31
32.00
9.80
35.52
10.39
40.49
11.22
46.00
17.26
6.85
21.74
7.79
25.76
8.65
28.81
9.40
31.52
9.90
34.92
10.49
39.74
11.33
47.00
16.75
6.99
21.12
7.94
25.06
8.82
28.06
9.59
30.73
10.10
33.99
10.70
38.61
11.56
48.00
16.09
7.20
20.31
8.18
24.13
9.09
27.05
9.88
29.66
10.40
32.74
11.02
37.13
11.90
49.00
15.21
7.49
19.23
8.51
22.87
9.45
25.67
10.27
28.17
10.81
31.05
11.46
35.15
12.38
50.00
14.23
7.86
18.02
8.93
21.45
9.92
24.10
10.79
26.48
11.36
29.13
12.04
32.92
13.00
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Note:
The inlet/outlet water temperature difference is 5℃.
78
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Chilled water
outlet temp.
Ambient temp.(℃)
21.00
25.00
30.00
35.00
40.00
46.00
52.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
5.00
67.17
17.61
63.25
18.16
59.67
18.72
56.40
19.30
52.85
20.27
48.62
21.28
43.76
22.34
6.00
69.44
17.89
65.33
18.44
61.57
19.01
58.14
19.60
54.54
20.58
50.23
21.61
45.25
22.69
7.00
71.87
18.25
67.54
18.82
63.60
19.40
60.00
20.00
56.34
21.00
51.95
22.05
46.85
23.15
8.00
74.09
18.80
69.57
19.38
65.44
19.98
61.68
20.60
57.98
21.63
53.51
22.71
48.32
23.85
9.00
76.18
18.98
71.46
19.57
67.16
20.18
63.24
20.80
59.51
21.84
54.99
22.93
49.71
24.08
10.00
79.06
19.27
74.10
19.86
69.58
20.48
65.45
21.11
61.66
22.17
57.03
23.28
51.61
24.44
11.00
81.27
19.46
76.09
20.06
71.38
20.68
67.09
21.32
63.27
22.39
58.58
23.51
53.08
24.68
12.00
83.13
19.74
77.76
20.35
72.88
20.98
68.43
21.63
64.60
22.71
59.88
23.85
54.31
25.04
13.00
84.61
19.90
79.08
20.52
74.04
21.15
69.46
21.81
65.64
22.90
60.91
24.04
55.31
25.24
14.00
86.72
20.04
80.97
20.66
75.74
21.30
70.99
21.96
67.15
23.05
62.38
24.21
56.71
25.42
15.00
87.83
20.14
81.93
20.76
76.57
21.40
71.70
22.06
67.90
23.17
63.14
24.33
57.46
25.54
1.3 MGBT-F60W/RN1
Cooling:
Note:
The inlet/outlet water temperature difference is 5℃.
79
Heating:
Hot water outlet
temp.
Ambient temp.(℃)
-10
-6
-2 2 7
10
13
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
39.00
40.40
12.51
50.50
14.22
59.41
15.80
66.02
17.17
71.76
18.08
80.37
19.16
92.42
20.70
41.00
39.04
12.77
48.87
14.51
57.56
16.12
64.02
17.52
69.67
18.45
77.89
19.55
89.41
21.12
42.00
37.92
13.03
47.51
14.81
56.03
16.45
62.39
17.88
67.97
18.82
75.85
19.95
86.93
21.55
43.00
37.00
13.30
46.42
15.11
54.81
16.79
61.10
18.25
66.63
19.21
74.23
20.36
84.92
21.99
44.00
36.28
13.57
45.58
15.42
53.88
17.13
60.14
18.62
65.65
19.60
73.00
20.78
83.37
22.44
45.00
35.76
13.84
44.98
15.73
53.23
17.48
59.48
19.00
65.00
20.00
72.15
21.20
82.25
22.90
46.00
35.06
13.98
44.15
15.89
52.32
17.65
58.52
19.19
64.03
20.20
70.94
21.41
80.73
23.12
47.00
34.02
14.26
42.90
16.21
50.90
18.01
56.99
19.57
62.42
20.60
69.04
21.84
78.43
23.59
48.00
32.68
14.69
41.26
16.69
49.01
18.55
54.94
20.16
60.24
21.22
66.50
22.50
75.42
24.30
49.00
30.90
15.28
39.07
17.36
46.45
19.29
52.13
20.97
57.23
22.07
63.06
23.40
71.39
25.27
50.00
28.91
16.04
36.60
18.23
43.57
20.25
48.95
22.02
53.79
23.17
59.17
24.57
66.87
26.53
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Note:
The inlet/outlet water temperature difference is 5℃.
80
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Chilled water
outlet temp.
Ambient temp.(℃)
21.00
25.00
30.00
35.00
40.00
46.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
kW
KW
kW
KW
kW
KW
kW
KW
kW
KW
kW
5.00
72.77
17.97
68.52
18.52
64.64
19.10
61.10
19.69
57.25
20.67
52.67
21.70
6.00
75.23
18.25
70.77
18.81
66.70
19.39
62.99
19.99
59.08
20.99
54.41
22.04
7.00
77.85
18.62
73.17
19.19
68.90
19.79
65.00
20.40
61.04
21.42
56.27
22.49
8.00
80.26
19.18
75.36
19.77
70.90
20.38
66.82
21.01
62.81
22.06
57.97
23.17
9.00
82.52
19.36
77.41
19.96
72.76
20.58
68.51
21.22
64.47
22.28
59.57
23.39
10.00
85.65
19.65
80.27
20.26
75.38
20.89
70.91
21.53
66.80
22.61
61.79
23.74
11.00
88.04
19.85
82.44
20.46
77.33
21.09
72.68
21.75
68.54
22.83
63.47
23.98
12.00
90.06
20.14
84.24
20.76
78.95
21.40
74.13
22.06
69.98
23.17
64.87
24.33
13.00
91.66
20.30
85.67
20.93
80.21
21.57
75.25
22.24
71.11
23.35
65.99
24.52
14.00
93.94
20.44
87.72
21.07
82.05
21.72
76.90
22.40
72.75
23.52
67.58
24.69
15.00
95.15
20.54
88.76
21.18
82.95
21.83
77.67
22.51
73.55
23.63
68.41
24.81
1.4 MGBT-D60W/RN1
Cooling
Note:
The inlet/outlet water temperature difference is 5℃.
81
Heating:
Hot water
outlet temp.
Ambient temp.(℃)
-10
-6
-2 2 7
10
13
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
kW
KW
kW
KW
kW
KW
kW
KW
kW
KW
kW
KW
kW
39.00
42.89
13.45
53.61
15.29
63.07
16.99
70.08
18.46
76.17
19.43
85.31
20.60
98.11
22.25
41.00
41.45
13.73
51.87
15.60
61.10
17.33
67.96
18.84
73.95
19.83
82.68
21.02
94.92
22.70
42.00
40.25
14.01
50.44
15.92
59.48
17.69
66.23
19.22
72.15
20.24
80.52
21.45
92.28
23.17
43.00
39.28
14.29
49.28
16.24
58.18
18.05
64.86
19.62
70.74
20.65
78.80
21.89
90.15
23.64
44.00
38.52
14.58
48.39
16.57
57.20
18.42
63.84
20.02
69.69
21.07
77.50
22.33
88.50
24.12
45.00
37.96
14.88
47.75
16.91
56.51
18.79
63.14
20.43
69.00
21.50
76.59
22.79
87.31
24.61
46.00
37.22
15.03
46.87
17.08
55.54
18.98
62.12
20.63
67.97
21.72
75.31
23.02
85.70
24.86
47.00
36.12
15.33
45.54
17.42
54.03
19.36
60.50
21.04
66.27
22.15
73.29
23.48
83.26
25.36
48.00
34.69
15.79
43.80
17.95
52.02
19.94
58.32
21.67
63.95
22.81
70.60
24.18
80.06
26.12
49.00
32.80
16.42
41.47
18.66
49.31
20.74
55.34
22.54
60.75
23.73
66.95
25.15
75.78
27.16
50.00
30.69
17.24
38.85
19.60
46.25
21.77
51.96
23.67
57.10
24.91
62.81
26.41
70.98
28.52
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Note:
The inlet/outlet water temperature difference is 5℃.
82
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Chilled water
outlet temp.
Ambient temp.(℃)
21.00
25.00
30.00
35.00
40.00
46.00
52.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
5.00
134.35
34.35
126.50
35.41
119.34
36.51
112.80
37.64
105.69
39.52
97.24
41.49
87.51
43.57
6.00
138.88
34.88
130.65
35.96
123.14
37.07
116.28
38.22
109.07
40.13
100.45
42.14
90.51
44.24
7.00
143.73
35.59
135.09
36.70
127.20
37.83
120.00
39.00
112.68
40.95
103.89
43.00
93.71
45.15
8.00
148.17
36.66
139.13
37.80
130.88
38.96
123.36
40.17
115.96
42.18
107.03
44.29
96.65
46.50
9.00
152.35
37.02
142.92
38.16
134.32
39.34
126.48
40.56
119.02
42.59
109.97
44.72
99.41
46.95
10.00
158.13
37.57
148.20
38.74
139.15
39.93
130.91
41.17
123.31
43.23
114.07
45.39
103.23
47.66
11.00
162.54
37.94
152.19
39.12
142.77
40.33
134.18
41.57
126.53
43.65
117.17
45.84
106.15
48.13
12.00
166.26
38.50
155.53
39.69
145.76
40.92
136.86
42.18
129.20
44.29
119.77
46.51
108.63
48.83
13.00
169.22
38.81
158.15
40.01
148.08
41.24
138.92
42.52
131.28
44.65
121.82
46.88
110.62
49.22
14.00
173.43
39.08
161.94
40.28
151.48
41.53
141.97
42.82
134.31
44.96
124.77
47.20
113.42
49.56
15.00
175.66
39.27
163.86
40.48
153.14
41.74
143.39
43.03
135.79
45.18
126.29
47.44
114.92
49.81
1.5 MGBT-F120W/RN1
Cooling:
Note:
The inlet/outlet water temperature difference is 5℃.
83
Heating:
Hot water outlet
temp.
Ambient temp.(℃)
-10
-6
-2 2 7
10
13
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
39.00
80.80
25.03
101.00
28.44
118.83
31.60
132.03
34.35
143.51
36.16
160.73
38.33
184.85
41.39
41.00
78.09
25.54
97.73
29.02
115.11
32.25
128.05
35.05
139.33
36.89
155.77
39.11
178.83
42.24
42.00
75.83
26.06
95.03
29.61
112.06
32.90
124.79
35.77
135.93
37.65
151.70
39.91
173.85
43.10
43.00
74.00
26.59
92.85
30.22
109.62
33.58
122.21
36.50
133.27
38.42
148.46
40.72
169.84
43.98
44.00
72.57
27.13
91.17
30.83
107.76
34.26
120.27
37.24
131.30
39.20
146.01
41.55
166.74
44.88
45.00
71.52
27.69
89.96
31.46
106.46
34.96
118.95
38.00
130.00
40.00
144.30
42.40
164.50
45.79
46.00
70.12
27.97
88.31
31.78
104.63
35.31
117.04
38.38
128.05
40.40
141.88
42.82
161.46
46.25
47.00
68.05
28.52
85.81
32.41
101.79
36.02
113.99
39.15
124.85
41.21
138.08
43.68
156.86
47.17
48.00
65.36
29.38
82.52
33.39
98.01
37.10
109.88
40.32
120.48
42.44
133.01
44.99
150.83
48.59
49.00
61.80
30.56
78.13
34.72
92.90
38.58
104.27
41.93
114.46
44.14
126.13
46.79
142.78
50.53
50.00
57.82
32.08
73.19
36.46
87.14
40.51
97.90
44.03
107.59
46.35
118.35
49.13
133.73
53.06
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Note:
The inlet/outlet water temperature difference is 5℃.
84
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Chilled water
outlet temp.
Ambient temp.(℃)
21.00
25.00
30.00
35.00
40.00
46.00
52.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
5.00
201.52
51.52
189.75
53.12
179.01
54.76
169.20
56.45
158.54
59.28
145.86
62.24
131.27
65.35
6.00
208.32
52.32
195.98
53.94
184.71
55.61
174.42
57.33
163.61
60.20
150.68
63.21
135.76
66.37
7.00
215.60
53.39
202.63
55.04
190.80
56.75
180.00
58.50
169.02
61.43
155.84
64.50
140.56
67.72
8.00
222.26
54.99
208.70
56.69
196.33
58.45
185.04
60.26
173.94
63.27
160.54
66.43
144.97
69.75
9.00
228.53
55.53
214.38
57.24
201.48
59.01
189.72
60.84
178.53
63.88
164.96
67.08
149.12
70.43
10.00
237.19
56.36
222.30
58.10
208.73
59.90
196.36
61.75
184.97
64.84
171.10
68.08
154.84
71.49
11.00
243.81
56.92
228.28
58.68
214.15
60.49
201.27
62.36
189.80
65.48
175.75
68.75
159.23
72.19
12.00
249.38
57.75
233.29
59.53
218.64
61.38
205.29
63.27
193.80
66.44
179.65
69.76
162.94
73.25
13.00
253.84
58.21
237.23
60.01
222.13
61.87
208.37
63.78
196.91
66.97
182.74
70.32
165.92
73.83
14.00
260.15
58.61
242.91
60.43
227.23
62.30
212.96
64.22
201.46
67.43
187.15
70.81
170.12
74.35
15.00
263.49
58.90
245.79
60.72
229.71
62.60
215.09
64.54
203.69
67.77
189.43
71.15
172.38
74.71
1.6 MGBT-F180W/RN1
Cooling:
Note:
The inlet/outlet water temperature difference is 5℃.
85
Heating:
Hot water outlet
temp.
Ambient temp.(℃)
-10
-6
-2 2 7
10
13
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
KW
39.00
121.21
37.54
151.51
42.66
178.24
47.40
198.05
51.52
215.27
54.24
241.10
57.49
277.27
62.09
41.00
117.13
38.31
146.60
43.53
172.67
48.37
192.07
52.57
209.00
55.34
233.66
58.66
268.24
63.36
42.00
113.75
39.09
142.54
44.42
168.09
49.36
187.18
53.65
203.90
56.47
227.56
59.86
260.78
64.65
43.00
111.00
39.89
139.27
45.33
164.43
50.36
183.31
54.74
199.90
57.62
222.69
61.08
254.76
65.97
44.00
108.85
40.70
136.75
46.25
161.64
51.39
180.41
55.86
196.95
58.80
219.01
62.33
250.11
67.31
45.00
107.28
41.53
134.94
47.20
159.69
52.44
178.43
57.00
195.00
60.00
216.45
63.60
246.75
68.69
46.00
105.18
41.95
132.46
47.67
156.95
52.96
175.56
57.57
192.08
60.60
212.82
64.24
242.19
69.37
47.00
102.07
42.79
128.71
48.62
152.69
54.02
170.98
58.72
187.27
61.81
207.12
65.52
235.29
70.76
48.00
98.04
44.07
123.79
50.08
147.02
55.64
164.82
60.48
180.72
63.67
199.51
67.49
226.25
72.89
49.00
92.70
45.83
117.20
52.08
139.35
57.87
156.40
62.90
171.68
66.21
189.19
70.19
214.17
75.80
50.00
86.73
48.12
109.79
54.69
130.70
60.76
146.86
66.05
161.38
69.52
177.52
73.70
200.60
79.59
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Note:
The inlet/outlet water temperature difference is 5℃.
86
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
Chilled
water
outlet
temp.
Ambient temp.(℃)
21.00
25.00
30.00
35.00
40.00
46.00
52.00
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
kW
KW
kW
KW
kW
KW
kW
KW
kW
KW
kW
KW
kW
5.00
279.89
68.96
263.55
71.09
248.63
73.29
235.00
75.56
220.20
79.34
202.58
83.30
182.32
87.47
6.00
289.34
70.03
272.19
72.20
256.54
74.43
242.25
76.73
227.23
80.57
209.28
84.60
188.56
88.83
7.00
299.44
71.46
281.43
73.67
265.00
75.95
250.00
78.30
234.75
82.22
216.44
86.33
195.23
90.64
8.00
308.70
73.61
289.86
75.88
272.68
78.23
257.00
80.65
241.58
84.68
222.98
88.92
201.35
93.36
9.00
317.40
74.32
297.75
76.62
279.84
78.99
263.50
81.43
247.95
85.50
229.11
89.78
207.11
94.27
10.00
329.43
75.44
308.75
77.77
289.90
80.17
272.72
82.65
256.90
86.79
237.64
91.13
215.06
95.68
11.00
338.62
76.18
317.06
78.53
297.43
80.96
279.54
83.47
263.61
87.64
244.10
92.02
221.15
96.62
12.00
346.37
77.29
324.01
79.68
303.66
82.15
285.13
84.69
269.16
88.92
249.52
93.37
226.31
98.04
13.00
352.55
77.91
329.49
80.32
308.51
82.81
289.41
85.37
273.49
89.64
253.80
94.12
230.45
98.82
14.00
361.32
78.45
337.37
80.88
315.59
83.38
295.78
85.96
279.80
90.26
259.94
94.77
236.28
99.51
15.00
365.96
78.84
341.38
81.28
319.05
83.79
298.73
86.38
282.90
90.70
263.10
95.24
239.42
100.00
1.7 MGBT-F250W/RN1
Cooling:
Note:
The inlet/outlet water temperature difference is 5℃.
87
Heating
Hot
water
outlet
temp.
Ambient temp.(℃)
-10.00
-6.00
-2 2 7
10
13
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
(℃)
KW
kW
KW
kW
KW
kW
KW
kW
KW
kW
KW
kW
KW
kW
39.00
167.82
50.06
209.78
56.88
246.80
63.20
274.22
68.70
298.07
72.31
333.83
76.65
383.91
82.78
41.00
162.18
51.08
202.98
58.04
239.08
64.49
265.94
70.10
289.38
73.79
323.53
78.22
371.41
84.47
42.00
157.50
52.12
197.36
59.23
232.74
65.81
259.18
71.53
282.33
75.30
315.08
79.81
361.08
86.20
43.00
153.69
53.18
192.84
60.44
227.67
67.15
253.82
72.99
276.79
76.83
308.34
81.44
352.75
87.96
44.00
150.72
54.27
189.35
61.67
223.81
68.52
249.79
74.48
272.70
78.40
303.24
83.10
346.30
89.75
45.00
148.54
55.38
186.84
62.93
221.11
69.92
247.05
76.00
270.00
80.00
299.70
84.80
341.66
91.58
46.00
145.63
55.93
183.41
63.56
217.31
70.62
243.08
76.76
265.95
80.80
294.67
85.65
335.34
92.50
47.00
141.33
57.05
178.22
64.83
211.41
72.03
236.74
78.30
259.30
82.42
286.79
87.36
325.79
94.35
48.00
135.75
58.76
171.40
66.77
203.56
74.19
228.21
80.64
250.23
84.89
276.25
89.98
313.27
97.18
49.00
128.36
61.11
162.27
69.44
192.95
77.16
216.56
83.87
237.71
88.28
261.96
93.58
296.54
101.07
50.00
120.09
64.17
152.02
72.92
180.97
81.02
203.34
88.06
223.45
92.70
245.80
98.26
277.75
106.12
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Note:
The inlet/outlet water temperature difference is 5℃.
88
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
13
12
14
15
16
17
22
29
23
18
19
20
21
24
25
26
27
28
11 10 9 8 7 6 54 321
No
Detail information
1
Detection of current of the compressor B (protection code P5)
2
Detection of current of the compressor A (protection code P4)
Current is not detected within the initial 5 seconds after the compressor is started up. When the current of the
compressor is detected to exceed protective value set (18A), it will be shut down and re-started after 3 min.
3
T4: outdoor ambient temp. sensor (fault code E7)
T3B: pipe temp. sensor of the condenser B (fault code E6 and protection code P7)
T3A: pipe temp. sensor of the condenser A (fault code E5 and protection code P6)
1) T4: if there is one system that requires starting outdoor fans, the fans are started through electric control of the unit.
Outdoor fans set high wind, low wind two respectively, and control the unit through T4.
2) T3B and T3A: when the electric control of the modular unit detects the temp. of the outdoor pipe T3A or T3B of the
system exceeds the protective temp. 65℃, the corresponding system will be shut down. And it will be re-started up,
after the temp. drops below the recovery temp. 60℃. Another system will be not affected.
3) T4, T3B and T3A: when the temp. sensor is detected to suffer open circuit or short circuit, fault alarm will occur.
● When the main unit suffer fault of temp. sensor: the main unit and subordinate units will be shut down.
● When the subordinate unit suffer fault of temp. sensor: the unit will be shut down, but other subordinate units will not
be affected.
4
System A digital compressor exhaust temp. sensor(fault code E8, protection codeP8),Only the digital modular is
valid, and the constant speed modular are invalid.
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
5
Unit outlet water temp. sensor (fault code E4)
Under cooling mode and heating mode, conduct adjustment according to the magnitude of unit outlet water temp..
6
Total outlet water temp. sensor (fault code E3)
Only the main unit is valid, and the subordinate units are invalid.
Under refrigerating mode and heating mode, conduct adjustment according to the magnitude of total outlet water temp..
Adjustment range: shut-down, 40%, 60%, 80% and 100%.
7
Spot check. The operating status of outdoor system can be observed through spot check, and specific display contents
are as shown in the following figure:
Normal display
Operating mode Operating capability of the compressor B Number of online units Outdoor ambient temp. Temp. of the condenser A
T61 frost-proof temp Unitoutlet water temp Unit outlet-water tempeTemp. of the condenser B
TXV openingA TXV opening BOperating current of system AOperating currentof system BThe last failure
●Display contents of “number of online units”: the main unit can display the number of online units, and the
subordinate unit displays 0.
8
Selection code of the compressor
9
10
COM (O) 485 communication port (fault code E2)
11
COM (I) 485 communication port (fault code E2)
COM (O) is interconnected with P, Q and E of COM (I), used for RS-485 communication.
1) If faults occur between the wired controller and the main unit module, all modules will be shut down.
2) If faults occur between the main unit and subordinate units, the subordinate unit module suffering communication
fault will be shut down. Less units will be detected by the wired controller, which may display EA, and in the meanwhile,
the indicator lamp of the wired controller will flash.
Restart 3 minutes later after malfunction be removed.
12
High-pressure protection of the system A and discharge temp. switch protection (protection code P0);
High-pressure protection of the system B and discharge temp. switch protection (protection code P2);
Low-pressure protection of the system A (protection code P1);
Low-pressure protection of the system B (protection code P3);
1) Constant speed compressor: connection of discharge temp. switch and high-pressure switch of the system in series.
2) Digital compressor: With dual-protection from Air Exhaust Temp. Switch and Air Exhaust Temp. Sensor. The Switch
tandem connects with the Hi-pressure switch in the system, while the Sensor enjoys an exclusive connector.
The Air Exhaust Temp. Sensor at Digital Compressor: Air exhaust temp. value (DLT) protects the compressor (Fixed
frequency compressor doesn’t inspect this port). When DLT work in normal (no air exhaust temp. sensor error, if does,
The diagram denotes
selection of digital
compressor
The diagram denotes
selection of constant
speed compressor.
Each unit has the same electric control function, and the main
unit and subordinate units can be set through address code
on the electric control board. The address code 0 # is provided
as the main unit. The priority of being the main unit is given to
the unit with digital compressor, and other addresses are
subordinate units. Only the unit is chosen as the main unit, its
electric control can activate such functions as direct
communication with the wired controller, refrigerating and
heating capability adjustment, pump control, auxiliary electric
heater control, total effluent temp. detection and water flow
switch detection.
When the address is
1,2,3……F, it serves
as the subordinate
unit 1,2,3……15.
8
9
A
B
C
D
E
F
8
7
6
5
4
3
2
1
0
0
1
2
3
4
5
6
7
8
F
E
D
C
B
A
9
8
ADDRRSS
When the
address is 0, it
serves as the
main unit.
90
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
will display the error code E8), three temp. areas protections will be conducted: Safety Area, Yellow Area and Red
Area. In case of DLT temp. lower than 125℃, there is no protection will perform; in case of DLT higher than 125℃, after
10 minutes continual operation, it will enter to Yellow Area, the capacity output from the digital compressor will
decrease to 40%, once the temp. reduce to 100℃, it will go back to the Safety Area, and compressor stop down, error
be released, system will restart after 3 minutes .
13
Water inlet temp sensorT62 (TBH2) (fault code EF)
14
Frost-proof sensorT61 (TBH1) (fault code Eb)
15
Water flow detection (fault code of the main unit E0) is only valid for the main unit but invalid for subordinate units.
1) Main unit: if abnormal water flow occurs for the first and second time, the main unit board will display fault code E9. If
abnormal water flow occurs the third time, the main unit board will display fault code E0 (off-power recovery is needed),
and the wired controller will display fault code E0 (fault is displayed only after 3 detection).
2) Subordinate unit: (Joint this terminal with short-connective wires,water flow detection will not be done).
16
Electronic expansion valve of the system B
17
Electronic expansion valve of the system A
Electronic expansion valve is used to control refrigerant flow under different operating modes and different loads.
18
Auxiliary electric heater
Attention: the control port value of auxiliary electric heater actually detected is ON/OFF but not 220-240V control power
supply, so special attention should be paid when installing the auxiliary electric heater.
Attention!
Under heating mode, when the main unit board detects total water outlet temp. to be lower than 45℃, the switch will be
closed, and the auxiliary electric heater will begin to work; when the total water outlet temp. is higher than 50℃, the
switch will be opened, and the auxiliary electric heater will stop working.
19
PUMP.
Attention: the control port value of the pump actually detected is ON/OFF but not 220-240V control power supply, so
special attention should be paid when installing the pump.
1) After receiving start-up instruction, the pump will be started up instantly, and will maintain start-up state always in the
process of operation.
2) In case of refrigerating or heating shutdown, the pump will be shut down 2 minutes after all modules stop operating.
3) In case of shutdown under the pump mode, the pump can be directly shut down.
20
Compressor of the system B;
Zero line;
Four-way valve of the system B;
Zero line.
21
Digital pipe.
1) In case of stand-by, the address of the module is displayed;
2) In case of normal operation, 10. is displayed (10 is followed by dot).
3) In case of fault or protection, fault code or protection code is displayed.
22
Compressor of the system A;
Zero line;
Four-way valve of the system A;
Zero line.
23
Outdoor fan high wind , controlled by T4.
24
Outdoor fan low wind, controlled by T4.
25
PMW , For the main unit's ability to adjust the digital compressor .( Only the digital modular is valid)
26
Input of transformer, 220-240V AC current. (only valid for the main unit)
27
Input of three-phase four-wire power supply (fault code E1)
Three phases L1, L2 and L3 of power supply should exist simultaneously, and the difference of phase angle should be
120º among them. If the conditions are not met, fault of phase sequence or phase lack may occur, and fault code will be
displayed. When the power supply returns to normal condition, fault is removed. Attention: phase lace and phase
dislocation of power supply are detected only in the early period after the power supply is connected, and they are not
detected while the unit is in operation.
In case of phase sequence error, please switchover to the two of L1, L2 orL3 power cable.
28
Output of transformer
29
ON/OFF control interface
Faults
When the main unit suffers faults, the main unit stops operating, and all other units also stop running. When
the subordinate unit suffers faults, only the unit stops operating, and other units are not affected.
Protection
When the main unit is under protection, only the unit stops operating, and other units keep running.
When the subordinate unit is under protection, only the unit stops operating, and other units are not affected..
91
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
13
111098 765 4321
19
202122
23
242526
12
14
15
16
27
28
29
17
18
13
No
Detail information
1
Detection of current of the compressor B (protection code P5)
2
Detection of current of the compressor A (protection code P4)
Current is not detected within the initial 5 seconds after the compressor is started up. When the current of the
compressor is detected to exceed protective value set (33A for constant speed compressor), it will be shut down and
re-started after 3 min.
3
T4: outdoor ambient temp. sensor (fault code E7)
T3B: pipe temp. sensor of the condenser B (fault code E6 and protection code P7)
T3A: pipe temp. sensor of the condenser A (fault code E5 and protection code P6)
1) T4: if there is one system that requires starting outdoor fans, the fans are started through electric control of the unit.
Start outdoor fan A only, start A and B gears, and control the unit through T4.
2) T3B and T3A: when the electric control of the modular unit detects the temp. of the outdoor pipe T3A or T3B of the
system exceeds the protective temp. 65。C, the corresponding system will be shut down. And it will be re-started up,
after the temp. drops below the recovery temp. 60。C. Another system will be not affected.
3) T4, T3B and T3A: when the temp. sensor is detected to suffer open circuit or short circuit, fault alarm will occur.
● When the main unit suffer fault of temp. sensor: the main unit and subordinate units will be shut down.
● When the subordinate unit suffer fault of temp. sensor: the unit will be shut down, but other subordinate units will not
be affected.
4
(reserved)
5
Unit outlet water temp. sensor (fault code E4)
Under refrigeration mode and heating mode, conduct adjustment according to the magnitude of unit outlet water temp..
Adjustment range of constant speed capability: ON and OFF.
6
Total outlet water temp. sensor (fault code E3)
Only the main unit is valid, and the subordinate units are invalid.
Under refrigerating mode and heating mode, conduct adjustment according to the magnitude of total outlet water temp..
Adjustment range: Load, stabilize, unload, Emergency Stop.
2.2 MGBT-F60W/RN1
92
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
7
Spot check. The operating status of outdoor system can be observed through spot check, and specific display contents
are as shown in the following figure:
Normal display
Operating mode Operating capability of the compressor B Number of online units Outdoorambienttemp. Temp. of the condenserA
T61 frost-proof temp Unit outlet water temp Unit outlet-water tempeTemp. of the condenser B
TXV openingA TXV opening BOperating current of system AOperating current of system BThe last failure
● Display contents of “number of online units”: the main unit can display the number of online units, and the
subordinate unit displays 0.
8
Selection code of the compressor
9
10
COM (O) 485 communication port (fault code E2)
11
COM (I) 485 communication port (fault code E2)
COM (O) is interconnected with P, Q and E of COM (I), used for RS-485 communication.
1) If faults occur between the wired controller and the main unit module, all modules will be shut down.
2) If faults occur between the main unit and subordinate units, the subordinate unit module suffering communication
fault will be shut down. Less units will be detected by the wired controller, which may display EA, and in the meanwhile,
the indicator lamp of the wired controller will flash.
Restart 3 minutes later after malfunction be removed.
12
High-pressure protection of the system A and discharge temp. switch protection (protection code P0);
High-pressure protection of the system B and discharge temp. switch protection (protection code P2);
Low-pressure protection of the system A (protection code P1);
Low-pressure protection of the system B (protection code P3);
Constant speed compressor: connection of discharge temp. switch and high-pressure switch of the system in series.
13
Inlet water temp. sensor T62 (TBH2) (fault code EF)
Water flow detection (fault code of the main unit E0) is only valid for the main unit but invalid for subordinate units.
1) Main unit: if abnormal water flow occurs for the first and second time, the main unit board will display fault code E9. If
abnormal water flow occurs the third time, the main unit board will display fault code E0 (off-power recovery is needed),
and the wired controller will display fault code E0 (fault is displayed only after 3 detection).
2) Subordinate unit: (water flow detection will not be done).
16
(reserved port)
17
Electronic expansion valve of the system B
Reserved DIP switch
state
The diagram denotes
selection of constant
speed compressor
Each unit has the same electric control function, and the main
unit and slave units can be set through address code on the
electric control board. The address code 0 # is provided as the
main unit. The priority of being the main unit is given to the
unit with digital compressor, and other addresses are slave
units. Only the unit is chosen as the main unit, its electric
control can activate such functions as direct communication
with the wired controller, refrigerating and heating capability
adjustment, pump control, auxiliary electric heater control,
total effluent temperature detection and water flow switch
detection.
When the address is
1,2,3……F, it serves
as the subordinate
unit 1,2,3……15.
8
9
A
B
C
D
E
F
8
7
6
5
4
3
2
1
0
0
1
2
3
4
5
6
7
8
F
E
D
C
B
A
9
8
ADDRRSS
When the
address is 0, it
serves as the
main unit.
93
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
18
Electronic expansion valve of the system A
Electronic expansion valve is used to control refrigerant flow under different operating modes and different loads.
19
Auxiliary electric heater
Attention: the control port value of auxiliary electric heater actually detected is ON/OFF but not 220-230V control power
supply, so special attention should be paid when installing the auxiliary electric heater.
Attention!
Under heating mode, when the main unit board detects total water outlet temp. to be lower than 45℃, the switch will be
closed, and the auxiliary electric heater will begin to work; when the total water outlet temp. is higher than 50℃, the
switch will be opened, and the auxiliary electric heater will stop working.
20
PUMP.
Attention: the control port value of the pump actually detected is ON/OFF but not 220-230V control power supply, so
special attention should be paid when installing the pump.
1) After receiving start-up instruction, the pump will be started up instantly, and will maintain start-up state always in the
process of operation.
2) In case of refrigerating or heating shutdown, the pump will be shut down 2 minutes after all modules stop operating.
3) In case of shutdown under the pump mode, the pump can be directly shut down.
21
Compressor of the system B;
Neutral wire;
Four-way valve of the system B;
Neutral wire.
22
Numerical code tube.
1) In case of stand-by, the address of the module is displayed;
2) In case of normal operation, 10. is displayed (10 is followed by dot).
3) In case of fault or protection, fault code or protection code is displayed.
23
Compressor of the system A;
Neutral wire;
Four-way valve of the system A;
Neutral wire.
24
Outdoor fan A, controlled by T4.
25
Outdoor fan B, controlled by T4.
26
(reserved port)
27
Input of transformer, 220-230V AC current. (only valid for the main unit)
28
Input of three-phase four-wire power supply (fault code E1)
Three phases A, B and C of power supply should exist simultaneously, and the difference of phase angle should be
120º among them. If the conditions are not met, fault of phase sequence or phase lack may occur, and fault code will be
displayed. When the power supply returns to normal condition, fault is removed. Attention: phase lace and phase
dislocation of power supply are detected only in the early period after the power supply is connected, and they are not
detected while the unit is in operation.
29
Output of transformer
Faults
When the main unit suffers faults, the main unit stops operating, and all other units also stop running. When
the subordinate unit suffers faults, only the unit stops operating, and other units are not affected.
Protection
When the main unit is under protection, only the unit stops operating, and other units keep running.
When the subordinate unit is under protection, only the unit stops operating, and other units are not affected.
94
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
No.
Detail information
1
Detection of current of the compressor A1 (protection code P4)
2
Detection of current of the compressor B1 (protection code P5)
Current is not detected within the initial 5 seconds after the compressor is started up. When the current of the compressor is
detected to exceed protective value set (33A for constant speed compressor), it will be shut down and re-started after 3 min.
3
T4: outdoor ambient temp. sensor (fault code E7)
T3B: pipe temp. sensor of the condenser B (fault code E6 and protection code P7)
T3A: pipe temp. sensor of the condenser A (fault code E5 and protection code P6)
1) T4: if there is one system that requires starting outdoor fans, the fans are started through electric control of the unit. Start
outdoor fan A only, start A and B gears, and control the unit through T4.
2) T3B and T3A: when the electric control of the modular unit detects the temp. of the outdoor pipe T3A or T3B of the system
exceeds the protective temp. 65。C, the corresponding system will be shut down. And it will be re-started up, after the temp.
drops below the recovery temp. 60。C. Another system will be not affected.
3) T4, T3B and T3A: when the temp. sensor is detected to suffer open circuit or short circuit, fault alarm will occur.
● When the main unit suffer fault of temp. sensor: the main unit and subordinate units will be shut down.
● When the subordinate unit suffer fault of temp. sensor: the unit will be shut down, but other subordinate units will not be
affected.
4
Detection of current of the compressor A2 (protection code P4)
5
Unit outlet water temp. sensor (fault code E4)
Under refrigeration mode and heating mode, conduct adjustment according to the magnitude of unit outlet water temp..
2.3 MGBT-D60W/RN1
95
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Adjustment range of constant speed capability: ON and OFF. Adjustment range of constant speed capability: ON and OFF.
6
Total outlet water temp. sensor (fault code E3)
Only the main unit is valid, and the subordinate units are invalid.
Under refrigerating mode and heating mode, conduct adjustment according to the magnitude of total outlet watertemp..
Adjustment range: Load, stabilize, unload, Emergency Stop.
7
Spot check. The operating status of outdoor system can be observed through spot check, and specific display contents are
as shown in the following figure:
Normal display
Operating mode Operating capability of the compressor B Number of online units Outdoor ambient temp. Temp. of the condenserA
T61 frost-proof temp Unit outlet water temp Unit outlet-water tempe Temp. of the condenser B
TXV opening A TXV opening B Operating current of systemA Operating current of system BThe last failure
● Display contents of “number of online units”: the main unit can display the number of online units, and the slave unit
displays 0.
8
Factory setting
9
10
COM (O) 485 communication port (fault code E2)
11
COM (I) 485 communication port (fault code E2)
COM (O) is interconnected with P, Q and E of COM (I), used for RS-485 communication.
1) If faults occur between the wired controller and the main unit module, all modules will be shut down.
2) If faults occur between the main unit and subordinate units, the subordinate unit module suffering communication fault will
be shut down. Less units will be detected by the wired controller, which may display EA, and in the meanwhile, the indicator
lamp of the wired controller will flash, restart 3 minutes later after malfunction be removed.
8
9
A
BCDEF
8
7
654
321
0
01234
5
6
7
8FE
D
CBA
9
8ADDRRSS
When the address
is 1,2,3……
F
, it
serves as the
subordinate unit
1,2,3……15.
When the
address is 0, it
serves as the
main unit.
Each unit has the same electric control function, and
the main unit and slave units can be set through
address code on the electric control board. The
address code 0 # is provided as the main unit. The
priority of being the main unit is given to the unit with
digital compressor, and other addresses are slave
units. Only the unit is chosen as the main unit, its
electric control can activate such functions as direct
communication with the wired controller, refrigerating
and heating capability adjustment, pump control,
auxiliary electric heater control, total effluent
temperature detection and water flow switch
detection.
96
MCAC-ATSM-2014-09 Aqua tempo power series tropical air-cooled scroll chiller 50Hz
12
High-pressure protection of the system A and discharge temp. switch protection (protection code P0);
High-pressure protection of the system B and discharge temp. switch protection (protection code P2);
Low-pressure protection of the system A (protection code P1);
Low-pressure protection of the system B (protection code P3);
Constant speed compressor: connection of discharge temp. switch and high-pressure switch of the system in series.
13
Inlet water temp. sensor (fault code EF)
14
Shell and tube low-temp. ant-freeze sensor (fault code Eb)
15
Water flow detection (fault code of the main unit E0) is only valid for the main unit but invalid for subordinate units.
1) Main unit: if abnormal water flow occurs for the first and second time, the main unit board will display fault code E9. If
abnormal water flow occurs the third time, the main unit board will display fault code E0 (off-power recovery is needed), and
the wired controller will display fault code E0 (fault is displayed only after 3 detection).
2) Subordinate unit: (water flow detection will not be done).
16
Power phase detection(fault code E8)
17
Electronic expansion valve of the system B
18
Electronic expansion valve of the system A
Electronic expansion valve is used to control refrigerant flow under different operating modes and different loads.
19
Auxiliary electric heater
Attention: the control port value of auxiliary electric heater actually detected is ON/OFF but not 220-230V control power
supply, so special attention should be paid when installing the auxiliary electric heater.
Attention!
Under heating mode, when the main unit board detects total water outlet temp. to be lower than 45℃, the switch will be
closed, and the auxiliary electric heater will begin to work; when the total water outlet temp. is higher than 50℃, the switch will
be opened, and the auxiliary electric heater will stop working.
20
PUMP.
Attention: the control port value of the pump actually detected is ON/OFF but not 220-230V control power supply, so special
attention should be paid when installing the pump.
1) After receiving start-up instruction, the pump will be started up instantly, and will maintain start-up state always in the
process of operation.
2) In case of refrigerating or heating shutdown, the pump will be shut down 2 minutes after all modules stop operating.
3) In case of shutdown under the pump mode, the pump can be directly shut down.
21
One compressor of the system B(B1);
Neutral wire;
Four-way valve of the system B;
Neutral wire.
22
Numerical code tube.
1) In case of stand-by, the address of the module is displayed;
2) In case of normal operation, 10. is displayed (10 is followed by dot).
3) In case of fault or protection, fault code or protection code is displayed.
23
One compressor of the system A(A1);
Neutral wire;
Four-way valve of the system A;
Neutral wire.
24
Outdoor fan A, controlled by T4.
25
Outdoor fan A, controlled by T4.
26
PWM pressure relif valve control(for digital compressor)
27
Input of transformer, 220-230V AC current. (only valid for the main unit)
28
Input of three-phase four-wire power supply (fault code E1)
97
Aqua tempo power series tropical air-cooled scroll chiller 50Hz MCAC-ATSM-2014-09
Three phases A, B and C of power supply should exist simultaneously, and the difference of phase angle should be 120º
among them. If the conditions are not met, fault of phase sequence or phase lack may occur, and fault code will be displayed.
When the power supply returns to normal condition, fault is removed. Attention: phase lace and phase dislocation of power
supply are detected only in the early period after the power supply is connected, and they are not detected while the unit is in
operation.
29
Output of transformer
30
Output of transformer
31
One compressor of the system B(B2);
Neutral wire;
One compressor of the system A(A2) ;
Neutral wire.
32
The alarm signal output of the unit(ON/OFF signal)
33
Anti-freezing pressure protection of the system A(protection code Pc)
Anti-freezing pressure protection of the system B(protection code Pd)
34
Remote control port(ON/OFF signal, effect on NO.0 unit)
1、Dial the code S7 in the main control board to the “ON” position and enter to the remote control mode
(the wired controller is invalid)
2、If the port is closed, the unit is turned on, else, the unit is turned off.
35
Remote mode control port(ON/OFF signal effect on NO.0 unit)
1、Dial the code S7 in the main control board to the “ON” position and enter to the remote control mode
(the wired controller is invalid)
2、First, the ON/OFF port is closed. Second, if this port is closed, the unit enters the heating mode, else, the unit enters
the cooling mode.
CAUTION
1. Faults
When the main unit suffers faults, the main unit stops operating, and all other units also stop running;
When the subordinate unit suffers faults, only the unit stops operating, and other units are not affected.
2. Protection
When the main unit is under protection, only the unit stops operating, and other units keep running;
When the subordinate unit is under protection, only the unit stops operating, and other units are not affected.
98
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.