2. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB, 24°CWB; Equivalent refrigerant piping: 7.5m (horizontal).
3. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB, 15°CWB; Outdoor temp: 7°CDB, 6°CWB; Equivalent refrigerant piping: 7.5m (horizontal).
6
Direct/ Single
YDK300-4X
720*2
MCAC-UTSM-12
Model
MDTA-120HRN2
Code
220070900151
Power supply - 220~240V-1N-50Hz
Rated input power
W
18000
18000
Rated current A 28.7
28.7
Cooling
Capacity
Btu/h
116,000
116,000
W
34000
34000
Input
W
11900
11900
EER
W/W
2.86
2.86
Heating
Capacity
Btu/h
——
139900
W
——
41000
Input
W
——
12600
COP
W/W
——
3.25
Indoor air flow
m3/h
6800
6800
Indoor external static pressure
150
Indoor noise level
56
Refrigerant
Type
Control
Capillary
Fan
Type
Centrifugal fan
Fan model
SYZ9-9MD
Dimension
Φ307
Drive type/ Motor
step
Direct/ Single
Motor model
YDK300-4X
Motor Input * No.
720*3
Motor speed
rpm
1040/930/825
1040/930/825
Coil
Type
-
Copper tube and
aluminum fin
Copper tube and
aluminum fin
Tube size
mm
Ф7
Ф7
No. of rows - 4
4
Fin per inch
FPI
17
17
Length* height
mm
1602*588
1602*588
Controller
-
Remote controller
Drain pipe size
mm
Ф41
Ф41
Connection
wiring
Power wiring
mm2
3*2.5
3*2.5
Signal wiring
mm2
2*1.0
4*1.0
Indoor unit
Dimension
(W*H*D)
mm
1828*638*858
1828*638*858
Packing
(W*H*D)
mm
2095*689*929
2095*689*929
Net/Gross weight
kg
188/220
188/220
MDTA-120CRN2
220070900161
Pa 150
dB(A) 56
-
- Capillary
- Centrifugal fan
- SYZ9-9MD
mm Φ307
R407CR407C
- Direct/ Single
- YDK300-4X
W 720*3
Notes:
1. ESP: external static pressure
2. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB, 24°CWB; Equivalent refrigerant piping: 7.5m (horizontal).
3. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB, 15°CWB; Outdoor temp: 7°CDB, 6°CWB; Equivalent refrigerant piping: 7.5m (horizontal).
If any of the following malfunctions occur, stop operation of the air conditioner immediately. Turn off the power
switch, and contact the local after sales service center of manufacturer:
The RUN lamp flashes quickly (2 flash per second).
After turning off the power switch and then turning it on again, the RUN lamp still flashes quickly.
The receiving function of the remote controller fails, or the start/ shutdown operation is abnormal.
The fuse blows out frequently, or the circuit breaker protection occurs frequently.
Obstacles or water enter the air conditioner.
Condensing water leaks from indoor unit.
Other malfunctions occur.
24
MCAC-UTSM-12
Symptoms
Causes
Handling methods
The unit does not
work
Power supply fails.
Operate after power resumes.
Power switch is not connected.
Connect the power supply properly.
Fuse blows out or circuit breaker snaps off.
Replace the fuse or check whether
electric leakage occurs.
The remote controller or the wire controller
fails.
Check the remote controller or wire
controller.
Air flowing
normally but
completely can’t
cooling
Temperature setting is improper.
Temperature setting is higher than the
room temperature in cooling mode. Or
temperature setting is lower than the
room temperature in heating mode.
3-minute protection of compressor.
Waiting for 3 minutes.
The unit starts or
stops frequently
The system is lack of refrigerant. Or there is
too much refrigerant in the system.
Fix the leakage places, and charge the
proper quantity of refrigerant.
Air or non-condensable gas exists in the
refrigerant system.
Vacuum the system and charge
refrigerant again.
Compressor fails.
Repair or replace the compressor.
The voltage is too high or too low.
Install a voltage regulator.
The refrigerant pipe is obstructed.
Locate and replace that part.
Poor cooling effect
The heat exchanger of outdoor unit or indoor
unit is too dirty.
Clean the heat exchanger.
The filter is too dirty.
Clean the filter.
Air inlet or air outlet of the indoor/ outdoor
unit is blocked.
Remove obstacles to keep well
ventilating.
Doors or windows of the room are open.
Close all the windows and doors.
Directly exposed to sunlight.
Use curtain to obstruct sunlight.
Too many heat sources in the room.
Reduce the heat sources.
The outdoor ambient temperature is too
high.
The cooling effect is poor but normal.
The system is lack of refrigerant.
Fix the leakage places, and charge the
proper quantity of refrigerant.
Poor heating
effect
The outdoor ambient temperature is lower
than -7℃.
Use an assistance heating device.
If the air conditioner fails and does not meet the above phenomena, check the system as the following table:
25
Doors or windows of the room are not closed
tightly.
Close the doors and windows properly.
The system is lack of refrigerant.
Fix the leakage places, and charge the
proper quantity of refrigerant.
Symptoms
Causes
Handling methods
The fan speed
cannot be
changed
Check whether the mode marked on the
screen is “AUTO”.
When the “AUTO” mode is selected, the
unit will change the fan speed
automatically.
Check whether the mode marked on the
screen is “DEWET”.
When the “DEWET” mode is selected,
the unit will change the fan speed
automatically. The fan speed can be
selected in “COOLING”,”HEATING”
and ”SUPPLY AIR” mode.
The “ON/OFF”
button of remote
controller do not
work
Check whether the batteries of remote
controller are exhausted.
Replace the batteries.
The “ON/OFF”
lamp extinguishes
Check whether the time set on the timer has
expired.
Restart the unit.
The “TIMER ON”
lamp extinguishes
Check whether the time set on the timer has
expired.
It comes to the setting time and the unit
stat running automatically.
No receiving
sounds from the
indoor unit even
when the
“ON/OFF” button
is pressed
Check whether the signal transmitter of the
remote controller is properly directed to the
infrared signal receiver of the indoor unit
when the “ON/OFF” button is pressed.
Directly transmit the signal transmitter of
the remote controller to the infrared
signal receiver of the indoor unit, and
then push the “ON/OFF” button twice.
The buttons of the
remote controller
do not work
Check whether the settings are locked.
Push the “LOCK” button again.
MCAC-UTSM-12
26
MCAC-UTSM-12
No
No
Yes
All lamps flashing at 5Hz
Judge 1: The PRO terminal on PCB of indoor unit without connecting to grounding wire
Validate: Check whether the PRO terminal on PCB of indoor
unit without connected to grounding wire.
Connect it to grounding wire.
Judge 2: Optical coupler on PCB malfunction
Validate: Check whether the Optical coupler is normal.
Replace optical coupler
Replace indoor PCB.
Operation lamp flashes:
Yes
27
MCAC-UTSM-12
Timer lamp flashing at 5Hz
Room temperature sensor malfunction
Judge 1: Check the room temperature sensor
Is break off.
Connects it well.
Judge 2: Check the room temperature sensor
is abnormal.
Validate: Check whether the resistance of the
temperature sensor is correct according to Annex 1.
Replace temperature sensor
Replace indoor PCB.
No
Yes
No
Operation lamp flashes:
Yes
28