Midea MCH2U-18PHH2, MCH3U-27PHH2, MCH5U-48PHH2, MCH4U-36PHH2 Service Manual

1
MULTI OUTDOOR UNITS
SERVICE MANUAL
Multi zone
CONDENSING UNITS
Revision C: ODMI-E-1606
Model Numbers:
MCH2U-18PHH2 MCH3U-27PHH2 MCH4U-36PHH2
MCH5U-48PHH2
WARNING
Installation MUST conform with local building codes or, in the absence of local
codes, with the National Electrical Code NFPA70/ANSI C1-1993 or current edition and Canadian Electrical Code Part1 CSA C.22.1.
The information contained in the manual is intended for use by a qualified service
technician familiar with safety procedures and equipped with the proper tools and test instruments
Installation or repairs made by unqualified persons can result in hazards to you
and others.
Failure to carefully read and follow all instructions in this manual can result in
equipment malfunction, property damage, personal injury and/or death.
Table of Contents
1. Indoor Unit Combination
2. Suggested Indoor Unit Model Numbers
3. Dimension Of Outdoor Unit
4. Refrigerant Cycle Diagram
5. Installation Details
6. Electronic Function
7. Wiring Diagrams
8. Trouble Shooting
9. Disassembly Instructions
2
CONTENTS
1. Indoor Unit Combination .................................................................................................................................... 4
2. Dimension Of Outdoor Unit ................................................................................................................................ 6
3. Refrigerant Cycle Diagram .................................................................................................................................. 7
4. Installation Details ............................................................................................................................................ 10
4.1 Wrench torque sheet for installation .......................................................................................................... 10
4.2 Connecting the cables ................................................................................................................................. 10
4.3 Pipe length and the elevation ..................................................................................................................... 10
4.4 First-Time Installation ................................................................................................................................. 11
4.5 Adding Refrigerant after Long-Term System Operation ............................................................................... 12
4.6 Procedure when servicing the indoor unit refrigeration circuit. ................................................................... 12
4.7 Evacuation after servicing the outdoor unit refrigeration circuit ................................................................. 14
6. Electronic Function ........................................................................................................................................... 15
6.1 Abbreviation ............................................................................................................................................... 15
6.2 Electric Control Working Environment. ....................................................................................................... 15
6.3 Main Protection .......................................................................................................................................... 15
6.4 Control and Functions ................................................................................................................................. 17
7. Wiring Diagrams ............................................................................................................................................... 23
8. Troubleshooting ............................................................................................................................................... 33
8.1Safety .......................................................................................................................................................... 33
8.2 Indoor Unit Error Display ............................................................................................................................. 34
8.3 Outdoor Unit Display .................................................................................................................................. 37
8.4 Diagnosis and Solution ................................................................................................................................ 42
8.5 Trouble Criterion Of Main Parts. ................................................................................................................. 91
9. Disassembly Instructions ................................................................................................................................ 103
 MCH2U-18PHH2 (WCA30 metal plate) .............................................................................................. 103
 MCH3U-27PHH2 (WD30 metal plate) ................................................................................................. 110
3
 MCH4U-36PHH2 (WD30 metal plate) ................................................................................................. 118
 MCH5U-48PHH2 (WE30 metal plate) ................................................................................................. 125
4
1. Indoor Unit Combination
Multi DC
Outdoor
Unit
Nominal capacity
Suggested
Combination
Limit
1drive 2 5.2kW
12
None
9+9
9+12
12+12
Multi DC
Outdoor
Unit
Nominal capacity
Suggested
Combination
Limit
1 drive 5 14kW
18+18
None
18+24
24+24
9+9+18
9+9+24
9+12+12
9+12+18
9+12+24
9+18+18
9+18+24
9+24+24
12+12+12
12+12+18
12+12+24
12+18+18
12+18+24
12+24+24
18+18+18
18+18+24
9+9+9+9
9+9+9+12
9+9+9+18
9+9+9+24
9+9+12+12
Multi DC
Outdoor
Unit
Nominal capacity
Suggested
Combination
Limit
1drive 3 7.8kW
9+9
None
9+12
9+18
12+12
12+18
18+18
9+9+9
9+9+12
9+9+18
9+12+12
9+12+18
12+12+12
Multi DC
Outdoor
Unit
Nominal capacity
Suggested
Combination
Limit
1 drive 4 10.5kW
9+18
None
12+12
12+18
18+18
9+9+9
9+9+12
9+9+18
9+12+12
9+12+18
9+18+18
12+12+12
12+12+18
12+18+18
9+9+9+9
9+9+9+12
9+9+9+18
9+9+12+12
9+9+12+18
9+12+12+12
12+12+12+12
5
9+9+12+18
9+9+12+24
9+9+18+18
9+9+18+24
9+12+12+12
9+12+12+18
9+12+12+24
9+12+18+18
9+18+18+18
12+12+12+12
12+12+12+18
12+12+12+24
12+12+18+18
9+9+9+9+9
9+9+9+9+12
9+9+9+9+18
9+9+9+9+24
9+9+9+12+12
9+9+9+12+18
9+9+9+18+18
9+9+12+12+12
9+9+12+12+18
9+12+12+12+12
9+12+12+12+18
12+12+12+12+12
6
2. Dimension Of Outdoor Unit
Model
Unit
W D H W1 A B
MCH2U-18PHH2
mm
845 363 702 923 540 350
inch
33.3
14.3
27.6
36.0
21.3
13.8
MCH3U-27PHH2
mm
946 410 810 1034 673 403
inch
37.2
16.5
31.9
40.6
26.5
15.9
MCH4U-36PHH2
mm
946 410 810 1034 673 403
inch
37.2
16.5
31.9
40.6
26.5
15.9
MCH5U-48PHH2
mm
952 415 1333 1060 634 404
inch
37.5
16.3
52.5
41.7
25.0
15.9
A
B
D
7
3. Refrigerant Cycle Diagram
3.1 Refrigeration circuit drawing of inverter 1 drive 2 type
LIQUID VALVE A
GAS VALVE A
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
Compressor
4-WAY VALVE
COOLING
HEATING
T2 Evaporator temp. sensor middle
T1 Room temp. sensor
T3 Condenser temp. sensor
T5 Discharge temp. sensor
T4 Ambient temp. sensor
INDOOR OUTDOOR
EXV A
CAPILIARY A
CHECK VALVE
CAPILIARY TUBE
EXV B CAPILIARY B
LIQUID VALVE B
GAS VALVE B
Accumulator
T2B-A
Evaporator
temp. sensor outlet
T2B-B
3.2 Refrigeration circuit drawing of inverter 1 drive 3 type
LIQUID VALVE A
GAS VALVE A
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
Compressor
4-WAY VALVE
COOLING
HEATING
T2 Evaporator temp. sensor middle
T1 Room temp. sensor
T3 Condenser temp. sensor
T5 Discharge temp. sensor
T4 Ambient temp. sensor
INDOOR OUTDOOR
EXV A CAPILIARY A
CHECK VALVE
CAPILIARY TUBE
EXV B
CAPILIARY B
LIQUID VALVE B
GAS VALVE B
EXV C
CAPILIARY C
LIQUID VALVE C
GAS VALVE C
Accumulator
T2B-A
Evaporator
temp. sensor outlet
T2B-B
T2B-C
8
3.3 Refrigeration circuit drawing of inverter 1 drive 4 type
LIQUID VALVE A
GAS VALVE A
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
Compressor
4-WAY VALVE
COOLING
HEATING
T2 Evaporator temp. sensor middle
T1 Room temp. sensor
T3 Condenser temp. sensor
T5 Discharge temp. sensor
T4 Ambient temp. sensor
INDOOR OUTDOOR
EXV A
CAPILIARY A
CHECK VALVE
CAPILIARY TUBE
EXV B CAPILIARY B
LIQUID VALVE B
GAS VALVE B
EXV C
CAPILIARY C
LIQUID VALVE C
GAS VALVE C
EXV D CAPILIARY D
LIQUID VALVE D
GAS VALVE D
Accumulator
High pressure switch
Low pressure switch
T2B-A
Evaporator
temp. sensor outlet
T2B-B
T2B-C
T2B-D
3.4 Refrigeration circuit drawing of inverter 1 drive 5 type
9
LIQUID VALVE A
GAS VALVE A
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
COOLING
HEATING
T2 Evaporator temp. sensor
T1 Room temp. sensor
T3 Condenser temp. sensor
T4 Ambient temp. sensor
INDOOR OUTDOOR
EXV A CAPILIARY A
CHECK VALVE
CAPILIARY TUBE
EXV B CAPILIARY B
LIQUID VALVE B
GAS VALVE B
EXV C
CAPILIARY C
LIQUID VALVE C
GAS VALVE C
EXV D
CAPILIARY D
LIQUID VALVE D
GAS VALVE D
EXV E
CAPILIARY E
LIQUID VALVE E
GAS VALVE E
Compressor
4-WAY VALVE
T5 Discharge temp. sensor
Accumulator
High pressure switch
Low pressure switch
T2B-A
Evaporator
temp. sensor outlet
T2B-B
T2B-C
T2B-D
T2B-E
10
4. Installation Details
4.1 Wrench torque sheet for
installation
Outside
Torque
Additional
mm inch
N.cm N.cm
Ф6.35 1/4 1500(153kgf.cm) 1600(163kgf.cm)
Ф9.52 3/8 2500(255kgf.cm) 2600(265kgf.cm)
Ф12.7 1/2 3500(357kgf.cm) 3600(367kgf.cm)
4.2 Connecting the cables
The power cord connection should be selected according to the following specifications sheet.
Unit
AWG
1 drive 2 type (18K outdoor unit) 14
1 drive 3 type (27K outdoor unit). 14
1 drive 4 type (36K outdoor unit) 12
1 drive 5 type (48K outdoor unit) 10
For indoor unit and outdoor unit connection line, 16AWG is ok for all.
4.3 Pipe length and the elevation
Maximum piping length and height difference
1 drive 2 1 drive 3 1 drive 4 1 drive
5 Max. length for all rooms (m)
40
(131ft)
60
(197ft)
80
(262ft)
80
(262ft)
Max. length for one IU (m)
25
(82ft)
30
(98ft)
35
(115ft)
35
(115ft)
Max. height difference between IU and OU (m)
15
(49.2ft)
15
(49.2ft)
15
(49.2ft)
15
(49.2ft)
Max. height difference between IUs (m)
10
(33ft)
10
(33ft)
10
(33ft)
10
(33ft)
Additional refrigerant charge
1 drive 2 1 drive 3 1 drive 4 1 drive
5 Pre-charge pipe length
(m)
15
(49.2ft)
22.5
(73.8ft)
30
(98.4ft)
37.5
(123ft)
Additio
nal
refriger
ant
charge
g 15 x
(length
for all
rooms -
15)
15 x
(length
for all
rooms
– 22.5)
15 x
(length
for all
rooms -
30)
15 x
(length
for all
rooms
– 37.5)
oz 0.161
x(lengt
h for all
rooms
– 49.2)
(0.161 x(lengt
h for all
rooms
– 73.8)
0.161x( length
for all
rooms
– 98.4)
.0.161x
(length
for all
rooms
–123)
Caution:
Refrigerant pipe diameter is different
according to indoor unit to be connected. When using the extension pipe, refer to the tables below.
When refrigerant pipe diameter is
different from that of the outdoor unit connector (18K indoor unit) an additional adapter is required.
Indoor unit
Extension pipe
diameter (mm/inch)
Model
Pipe diameter
(mm/inch)
9K
Liquid 6.35(1/4) Liquid 6.35(1/4) Gas 9.52(3/8) Gas 9.52(3/8)
12K 18K
Liquid 6.35(1/4) Liquid 6.35(1/4) Gas 12.7(1/2) Gas 12.7(1/2)
24K
Liquid 9.52 (3/8) Liquid 9.52 (3/8) Gas 15.9(5/8) Gas 15.9(5/8)
Outdoor unit union diameter (mm/inch)
1 drive 2
Liquid
6.35(1/4)
*2
Gas
9.52(3/8)
*2
1 drive 3
Liquid
6.35(1/4)
*3
Gas
9.52(3/8)
*3
1 drive 4
Liquid
6.35(1/4)
*4
Gas
9.52(3/8)
*3
12.7(1/2) *1
1 drive 5
Liquid
6.35(1/4)
*5
Gas
9.52(3/8)
*3
12.7(1/2) *2
11
4.4 First-Time Installation
Air and moisture in the refrigerant system cause the following problems:
Increases in system pressure
Increases in operating current
Decreases in cooling and heating
efficiency
Blocks in capillary tubing caused by
moisture in the refrigerant circuit freezing
Corrosion of parts in the refrigerant
system caused by water
The indoor units and the pipes between indoor and outdoor units must be tested for leakages and evacuated to remove gas and moisture from the system.
Gas leak check with soap water:
Apply soap water or a liquid neutral detergent on the connections with a soft brush to check for leakage in the pipe connecting points. If bubbles emerge, the pipes are leaking.
1. Air Purging Using the Vacuum Pump
1. Completely tighten the flare nuts on the
indoor and outdoor units. Confirm that both the2-way and 3-way valves are set to the closed position.
2. Connect the charge hose with the push
pin of the Handle Lo to the 3-way valve gas service port.
3. Connect the charge hose of the Handle Hi to the vacuum pump.
4. Fully open the Handle Lo of the manifold valve.
5. Turn on the vacuum pump to begin evacuation.
6. Conduct a 30-minute evacuation. Check whether the compound meter indicates -
0.1Mpa(14.5Psi). If the meter does not indicate -0.1Mpa(14.5Psi) after 30 minutes has elapsed, continue evacuation for 20 more minutes. If the pressure does not reach -
0.1Mpa(14.5Psi) after 50 minutes has elapsed, check if there are any leaks.
Fully close the Handle Lo valve of the manifold valve and turn off the vacuum pump. After 5 minutes, confirm that the gauge needle is not moving.
7. Turn the flare nut on the 3-way valve45° counterclockwise for 6-7 seconds. Once gas begins to come out, tighten the flare nut. Make sure the pressure display on the pressure indicator is higher than atmospheric pressure. Then remove the charge hose from the 3-way valve.
8. Fully open the 2-wayand 3-way valves and securely tighten the cap on the 3­way valve.
2. Adding refrigerant if the pipe length
exceeds chargeless pipe length
Procedure:
12
1)
Connect the charge hose to the charging cylinder and open the 2-way and 3-way valves.
With the charge hose you disconnected from the vacuum pump, connect it to the valve at the bottom of the cylinder.
If the refrigerant is R410A, place the cylinder bottom-up to ensure liquid charging is possible.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set (be careful of the liquid refrigerant).
3) Place the charging cylinder onto the electronic scale and record the weight.
4) Turn on the air conditioner in cooling mode.
5) Open the valves (Low side) on the charge set. Charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port
Use a torque wrench to tighten the service port cap to a torque of 18N.m(13.27 ft·lbs).
Be sure to check for gas leaks.
4.5 Adding Refrigerant after Long-
Term System Operation
Procedure
1)
Connect the charge hose to the 3-way service port and open the 2-way and 3-way valve.
Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, place the cylinder bottom-up to ensure liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Place the charging cylinder onto the electronic scale and record the weight.
4) Turn on the air conditioner in cooling mode.
5) Open the valves (Low side)on the charge set and charge the system with liquid refrigerant.
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low side), disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port.
Use torque wrench to tighten the service port cap to a torque of 18N.m(13.27 ft·lbs).
Be sure to check for gas leaks.
4.6 Procedure when servicing the
indoor unit refrigeration circuit.
1. Collecting the refrigerant into the outdoor unit
13
Procedure
1). Confirm that both the 2-way and 3-way valves are set to the opened position Remove the valve stem caps and confirm that the valve stems are in the opened position. Be sure to use a hexagonal wrench to operate the valve stems.
2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose. Open the handle Lo valve of the manifold valve slightly to purge air from the charge hose for 5 seconds and then close it quickly.
4). Set the 2-way valve to the close position.
5). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates
0.1MPa.
6). Set the 3-way valve to the closed position immediately Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa. Disconnect the charge set, and tighten the 2­way and 3-way valve’s stem nuts. Use a torque wrench to tighten the 3-way valves service port cap to a torque of 18N.m. Be sure to check for gas leakage.
2. Air purging with vacuum pump
1) Completely tighten the flare nuts of the
indoor and outdoor units, confirm that both the 2-way and 3-way valves are set to the closed position.
2) Connect the charge hose with the push
pin of handle lo to the 3-way valves gas service port.
3) Connect the charge hose of handle hi
connection to the vacuum pump.
4) Fully open the handle Lo of the manifold
valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and
check whether the compound meter indicates -0.1Mpa. If the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If the pressure can’t achieve -
0.1Mpa after pumping 50 minutes, please check if there are some leakage points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump. Confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
7) Turn the flare nut of the 3-way valves
about 45° counterclockwise for 6 or 7seconds after the gas
coming out, then tighten the flare nut again. Make sure the pressure display in the
14
pressure indicator is a little higher than the atmosphere pressure. Then remove the charge hose from the 3 way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve.
4.7 Evacuation after servicing the
outdoor unit refrigeration circuit
1. Evacuation of the complete
refrigeration circuit, Indoor and outdoor unit.
Procedure:
1). Confirm that both the 2-way and 3-way
valves are set to the opened position.
2). Connect the vacuum pump to 3-way
valve’s service port.
3). Evacuation for approximately one hour.
Confirm that the compound meter indicates -
0.1Mpa (500 Microns / 29.9 in,hg).
4). Close the valve (Low side) on the charge
set, turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the
vacuum pump.
2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve. Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4). Open the valves (Low side) on the charge set and charge the system with liquid refrigerant If the system cannot be charge with the specified amount of refrigerant, or can be charged with a little at a time (approximately 150g each time) , operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure.
5).When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way valve’s service port immediately If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose.
6). Mounted the valve stem caps and the service port. Use torque wrench to tighten the service port cap to a torque of 18N·m (13.27 ft·lbs). Always leak check after servicing the
15
refrigerant system.
For MCH3U-27PHH2/MCH4U­36PHH2/MCH5U-48PHH2 There are one low-pressure centralized valve and one high-pressure centralized valve, it will be more time saving when vacuum and recycle refrigerant. But refer to the previous instruction when vacuum and recycle refrigerant.
6. Electronic Function
6.1 Abbreviation
T1: Indoor ambient temperature
T2: Middle indoor heat exchanger coil temperature
T2B: Indoor heat exchanger exhaust coil temperature (located on the outdoor unit)
T3: Outdoor heat exchanger pipe temperature
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
6.2 Electric Control Working
Environment.
6.2.1 Input voltage: 230V.
6.2.2 Input power frequency: 60Hz.
6.2.3 Indoor fan standard working amp.: <1A
6.2.4 Outdoor fan standard working amp.: <1.5A.
6.2.5 Four-way valve standard amp.: <1A.
6.3 Main Protection
6.3.1 Compressor Restart Delay
---- The compressor takes 1 minute to start up the first time. Further restarts take 3 minutes.
6.3.2 Temperature Protection of Compressor Discharge.
When the discharge temperature of the compressor rises, the running frequency is limited according to the following rules:
----If 105 (221 )T5<110 (230 ), maintain the current frequency.
16
----If the temperature increase and T5110
(230 ), decrease the frequency to a lower level every 2 minutes till to F1.
---If T5115 (239 ) for 10 seconds, the
compressor stops and then restart untill T5<90 (194 ).
6.3.3 Fan Speed Malfunction
---- If outdoor fan speed is lower than
100RPM or higher than 2400RPM for 60
seconds or more, the unit stops and LED displays E8 failure code.
6.3.4 Inverter Module Protection.
---- The inverter protection module ensures
that faults related to current, voltage, or temperature does not damage the inverter.
If these protections are triggered, the A/C unit stops and the LED displays the failure code.
The unit restarts 3 minutes after the protection mechanism has turned off.
6.3.5 Low Voltage Protection
V O LT A G E
N o l im it
V O L T _ LT M _F R EQ 1_ A D D
V O L T _L T M _F R EQ 2_ A D D
Note: If low voltage protection triggers and voltage is not restored to normal within 3 minutes, the protection remains active even after a machine restart.
6.3.6 Compressor Current Limit
Protection
The temperature interval for the current limit is the same as the range of the T4 frequency limit.
Cooling mode:
CoolReturnI The difference between
current limit and shutdown current
CoolT4Zone5I
Cooling T450 current limit value
CoolT4Zone4I
Cooling 49T445
current limit value
CoolT4Zone3I
Cooling 44T441 current limit value
CoolT4Zone2I
Cooling 40T433 current limit value
CoolT4Zone1I
Cooling 32T4current limit value
CoolStopI Cooling stop protection
current value
Heating mode:
CoolT4Zone5I
50
49
45
CoolT4Zone4I
44
41
40
CoolT4Zone3I
33
32
CoolT4Zone2I
17
15 14 HeatT4Zone4I
10
9 HeatT4Zone3I
6 5 HeatT4Zone2I
HeatT4Zone1I
HeatReturnI The difference between
current limit and shutdown current
HeatT4Zone4I
Heating
T415
current
limit value
HeatT4Zone3I
Heating
14T410
current limit value
HeatT4Zone2I
Heating
9T46
current limit value
HeatT4Zone1I
Heating
5T4
current limit
value
HeatStopI Heating stop protection
current value
6.3.7 Indoor / Outdoor Units
Communication Protection
If the indoor units do not receive the feedback signal from the outdoor units for 2 consecutive minutes, the unit stops. The unit displays the failure code.
6.3.8 High Condenser Coil Temp.
Protection
6.3.9 Outdoor Unit Anti-Freezing Protection
When T2<4 for 250seconds or T2<0, the indoor unit capacity demand is zero and resumes normal operation when T2>8 and the protection time is no less than 3 minutes.
6.3.10 Oil Return
Rules for Operation
1. If the compressor frequency continues to be lower than the frequency set for setting time, the unit raises the frequency to the frequency set for setting time and then resumes with the former frequency.
2. The EXV continues at 300p while indoor units maintain their operation.
If the outdoor ambient temperature is higher than the set frequency during oil return, the unit stops the oil return process.
6.3.11 Low Outdoor Ambient Temperature Protection
When the compressor is off and T4 is lower than -35 for 10 seconds, the unit stops and displays LP.
When the compressor is on and T4 remains lower than -40 for 10 seconds, the unit stops and displays LP.
When T4 is no lower than -32 for 10 seconds, the unit exits protection.
6.4 Control and Functions
6.4.1 Capacity Request Calculation
Cooling Mode:
T3
Resume
Off
Decrease
Hold
18
T1 Ts
3
1
1
e
c
a
4
2
0
2
3
0
1
f
d
b
Capacity area a b c d e f
Norm code
(N)
3 2 1.5 1 0.5 0
Model 9K 12K 18K 24K
HP 1.0 1.2 1.5 2.5
Note: The final result is an integer.
Use the following table and final capacity request to confirm the operating frequency.
Frequency (Hz)
0
CO
OL_
F1
CO
OL_
F2
… …
COO L_F2
4
CO
OL_
F25
Amendatory
capacity
demand.
0 1 2
… …
24 25
The maximum running frequency is adjusted according to the outdoor ambient
temperature
55 54 Fmax=
T4FREMAXC0
51.5
50.5 Fmax= T4FREMAXC1
45.5
44.5 Fmax= T4FREMAXC2 39 38 Fmax= T4FREMAXC3 33 32 Fmax= T4FREMAXC4 30 29 Fmax= T4FREMAXC5 22 20 Fmax= T4FREMAXC6 10
8 Fmax= T4FREMAXC7 0
-2 Fmax= T4FREMAXC8
-10
-12 Fmax= T4FREMAXC9
Fmax= T4FREMAXC10
Heating Mode
T1 Ts
4
0
a
3
1
-1
3
1
2
0
b
c
d
e
f
2
Capacity area a b c d e f
Norm code (N) 3 2 1.5 1 0.5 0
Model 9K 12K 18K 24K
HP 1.0 1.2 1.5 2.5
Note: The final result is an integer.
19
Then modify it according to a T2 average (correction):
Note:Average value of T2Sum T2 value of all indoor units)/ (indoor units number
T2 average
Decrease frequency
47
Keep frequency
40 Increase frequency
Use the following table and final capacity request to confirm the operating frequency.
Frequency (Hz) 0
HEA
T_F
1
HEA
T
_F2
HEA
T
_F24
HEA
T
_F2
5
Amendatory
capacity
demand.
0 1 2 … 24 25
The maximum running frequency is adjusted according to the outdoor ambient temperature
℃ 34 33 Standby 28 27 Fmax=T4FREHEATMAX1 25 24 Fmax=T4FREHEATMAX2 22 21 Fmax=T4FREHEATMAX3 19 18 Fmax=T4FREHEATMAX4 17 16 Fmax=T4FREHEATMAX5 15 14 Fmax=T4FREHEATMAX6 12 11 Fmax=T4FREHEATMAX7
6 5 Fmax=T4FREHEATMAX8 1 0 Fmax=T4FREHEATMAX9
-3
-4 Fmax=F21
-7
-8 Fmax=F22
-11
-12 Fmax=F23
-15
-16 Fmax=F24
Fmax=F25
6.4.2 Defrosting Control
Conditions for Defrosting:
After the compressor starts and enters normal operation, mark the minimum value of T3 from the 10th to 15th minute as T30.
If any one of the following conditions is satisfied, the unit enters defrosting mode:
1) If the compressor’s cumulative running time reaches 29 minutes and T3< TCDI1 and T3T30SUBT3ONET30.
20
2) If the compressor cumulative running time reaches 35 minutes and T3< TCDI2 and T3T30SUBT3TWOT30.
3) If the compressor cumulative running time reaches 40 minutes and T3< -24C for 3 minutes.
4) If the compressor cumulative running time reaches 120 minutes and T3<-15.
Defrost Stop Conditions
If any one of the following conditions is satisfied, defrosting ends and the unit returns to normal heating mode:
----T3 rises above than TCDE1.
----T3 remains at TCDE2 or above for 80 seconds.
----The machine runs for 10 consecutive minutes in defrosting mode.
Defrosting Action
off on
Cool-F9
10S 30S
TimeA
10S
4-way valve
defrosting Defrosting over
compressor
Indoor fan
Outdoor fan
EXV open
frequency
Max 10 minutes
frequency
Compressor stops
off
Anti-cold control
off
480P 480P for 240s
Condition of ending defrosting:
If any one of following items is satisfied, defrosting will stop and the machine will turn to normal heating mode.
T3 > TempQuitDefrost_ADD ℃;.
The defrosting time achieves 10min.
Turn to other modes or off.
6.4.3 Outdoor Fan Control
6.4.3.1 Cooling Mode
Under normal operating conditions, the system chooses the running fan speed according to the ambient temperature:
O
utdoor temperature
℃ 45 43 Supper high fan speed 28 26 High fan speed 25 23 Middle fan speed 22 20 Low fan speed 19 17 Supper low fan speed 10
9 Breeze fan speed 0
-1 F fan speed
-5
-6 G fan speed
-10
-11 H fan speed
I fan speed
When low ambient cooling is in effect::
Outdoor fan speed control logic (low ambient cooling)
When T4 <15 (59 ) and T3 < 30 (86 ), the unit enters into low ambient cooling mode. The outdoor fan chooses a speed
according to T3. When T338 ℃ (100.4 ℉) or when T420 (68 ), the outdoor fan chooses a speed according to T4 again.
21
38
Exit low ambient cooling mode, run with high fan for 1 minute
Low
30
27
23
off
T3
Increase fan spe ed increase
Keep c urrent fan speed
Decrea se fan speed
Fan st op
LowCoolT3_ON
LowCoo lT3_Down
LowCoo lT3_OFF
6.4.3.2 Heating Mode
Under normal operating conditions, the system chooses a running fan speed according to ambient temperature:
Outdoor temperature℃
21
Breeze fan speed 19 18
Supper low fan speed 16 15
Low fan speed 13 12
Middle fan speed 10
0
High fan speed
-2
Supper high fan speed
6.4.4 Electronic Expansion Valve (EXV) Control
1. EXV remains fully closed while the device is powering up. EXV then remains on standby with 350P open. It opens to the target angle after the compressor starts.
2. EXV closes with -160P when the compressor stops. Then it remains on standby with 350P open. It opens to the target angle after the compressor starts.
3. The action priority for the EXVs is A-B-C­D-E.
4. The compressor and outdoor fan commence operation only after EXV initializes.
6.4.4.1 Cooling Mode
The initial open angle of the EXV depends on the size of the indoor model. The adjustment range is 100-400p.
When the unit has been running for 3 minutes, the outdoor receives indoor units' capacity demand and T2B information and then calculates their average. After comparing each indoor’s T2B with the
22
average, the outdoor gives the following modification commands:
---- If the T2Baverage, the relevant valve needs to open 16p more
---- If the T2B= average, the relevant valve’s open range remains as is
---- If the T2Baverage, the relevant valve needs to close 16p more
This modification is carried out every 2 minutes.
6.4.4.2 Heating Mode
The initial open angle of the EXV depends on the size of the indoor model. The adjustment range is 150-350p.
When the unit has been running for 3 minutes, the outdoor unit receives the indoor units' indoor units' capacity demand and T2 information and then calculates their average.
After comparing each indoor unit’s T2 with the average, the outdoor gives the following modification commands:
----If the T2average+2, the relevant valve needs to close 16p more
---- If average+2≥the T2≥ average-2, the relevant valve’s open range remains as is
----If the T2average-2, the relevant valve needs to open 16p more
This modification is carried out every 2 minutes.
6.4.5 Four-Way Valve Control
In heating mode, a four-way valve is opened.
In defrosting, a four-way valve operates according to the current defrosting action.
In other modes, a four-way valve is closed.
When the unit is switched from heating to other modes, the four-way valve turns off after the compressor has been off for 2 consecutive minutes.
Failure or protection (excluding discharge temperature protection and high/low pressure protection) causes the four-way valve to immediately shut down.
23
7. Wiring Diagrams
7.1 Wiring diagram of 1 drive 2 outdoor
MCH2U-18PHH2
24
7.2 Wiring diagram of 1 drive 3 outdoor
MCH3U-27PHH2
25
7.3 Wiring diagram of 1 drive 4 outdoor
MCH4U-36PHH2
26
7.4 Wiring diagram of
MCH5U-48PHH2
27
PCB board of MCH2U-18PHH2, MCH3U-27PHH2
S
N L
H
[1.4] 2015.08.27
1
P E Q
L-OUT
S N L
1
1
1
1
1
CE-KFR80W/BP2T4N1(AC MOTOR)-310.JD.FW.WXWKB.WP1-1
1
2
15
16
RUN
1
1
1
17122300001076
R121
CN36 C N35 CN34
CN33
CN32
P2
P1
C81
R119
C80
C50
C2
_1
D18
D16
D10
CN201
AS1
R116
R115
R114
R113
R112
R111
R98
R43
Q8
Q7
Q6
Q5
CN30
CN18
RY2
CN8
N
CN5
N
CN9
HEAT2
CN2
N
CN6
HEAT1
CN1
4-WAY
SW1
CN15
T2B
CN27
PFC-CONTROL
CN26
TestPort
L1
L2
R110
R109
R108
R107
R106 R105
R104
R103
R97
R57
R56
R55
IC9
D28
D27
C79
C78
R77
DSP1
CN11
AC MOTOR
R46
+
E7
+
E8
+
E11
R12
C11
+
-
~
~
RY8
C77
C76
C75
C74
C73
C72
D1
C71
IC1
R87
IC15
D2
ZR3
ZR2
ZR1
RY7
RY6
RY4
RY3
RY1
R102
R101
R100
R99
R96
R95
R94
R93
R92
R91
R90
R89
R88
R86
R85
R84
R83
R82
R81
R80
R79
R78R76
R75
R74
R73
R72
R71
R70
R69
R68
R67
R66
R65
R63
R62
R61
R60
R59
R58
R54
R53
R52
R51
R50
R48
R47
R45
R44
R42
R41
R39
R38
R37
R36
R35
R34
R33
R32
R31
R30
R28
R27
R26
R25
R24
R23
R22
R21
R20
R19
R18
R17
R16
R15
R14
R13
R11
R10
R9
R8
R7
R6
R5
R4
R3
R2
R1
Q4
Q3
Q2
Q1
PTC1
P-1
GND
IC16
IC14
IC11
IC3
FUSE2
T30A 250VAC
+
E13
+
E12
+
E10
+
E9
+E6+
E4
+
E2
+
E1
D19
D17
D13
D12
D11D9D8
D7
D6
D5
D4
D3
CT1
CONdebug1
CN25
S-A
CN24
D
CN23
S-B
CN22
C
CN21
TO-DRIVE
CN20
S-C
CN19
B
A
CN17
T3/T4
CN16
S-D
CN14
LOW/HIGH
CN13
FAN-C`
CN10
FAN-C
CN7
PAI QI
C59
C58
C57
C56
C55
C54
C53
C51
C49
C47
C46
C44
C43
C41
C40
C39
C38
C37
C35
C33
C32
C31
C30
C28
C26
C25
C24
C23
C22
C21
C20
C17
C16
C15
C14
C13
C12
C10
C9
C5
C4
C3
C1
D20
D15
C60
C61
C62
C63
C64
C65
C66
C67
C68
C69
C70
+
E14
+
E5
IC6
RY5
X1
IC17
C8
C7
C52
C48
C6
CN4
N-IN
CN29
N-OUT
CN28
CN12
CompTop
FUSE1
T5A 250VAC
R120
+
LED1
P-2
GND
CN3
L-IN
R117 R118
D33
D32
D31
R64
R49
R40
R29
IC13
IC12
IC10
IC8
IC7
IC5
IC4
IC2
C45 C36
C34
C29
C27
C19
C18
D34
C42
D14
CN4(N-IN) power supply
208-230V AC
CN3(L-IN)
connect to the terminal
FUSE2 T30AL/250VAC
T5A 250VAC
FUSE1
CN9-CN8 (controled by RY4 relayer) connect to the heater when heater is ON, output 208-230V AC
CN6-CN5 (controled by RY3 relayer)
CN1-CN2 (controled by RY1 relayer) connect to the 4-WAY when 4-way is ON, output 208-230VAC
P-1(GND) connect to the earth
connect to the Earth(Optional)
P-2(GND)
FOR EMC
P1 connect to P2
NO USE
CN20 CN23 CN25
CN16
CN30
connect to the terminal
24VDC Pulse wave betweene (+CN4)-(-CN30)
Signal wire
NO USE
CN36 CN35 CN34
CN10
CN13
FAN-C FAN-C`
NO USE
CN18
Connect to Electric Expansion Valve
1
2
345
6
+12V DC
+12V DC
+12V DC pulse wave between (+4)-GND
+12V DC pulse wave between (+3)-GND
+12V DC pulse wave between (+2)-GND
+12V DC pulse wave between (+1)-GND
NO USENO USE
CN24 CN22
CN19
status light, by which you can judge the unit Normal or Error
LED1
(standby) Flashing once per second(low speed flashing)
(error) Flashing once p er half second (high speed flashing)
(running) aways on
NO USE
CN21
connect to IPM BOARD CN1
543
2
1
+12V
+5V
Low VOL supply
GND
(+4)-(-3) +5VDC Pulse wave (+5)-(-3) +5VDC Pulse wave
CN27
room temp sensor RT
pipe temp sensor RT
CN17
Exaust temp sensor RT
CN7
N-OUT
CN15
NO USE
NO USE
CN28
CN14
NO USE
CN12
L-OUT connect to IPM BOARD CN4
connect to IPM BOARD CN5
(L-OUT)-(N-OUT) 208-230V AC
(L-OUT)-(N-OUT) 208-230V AC
connect to the comperssor top temp. sensor
0V DC
NO USE
CN33 connect to DR module RED wire
(L-OUT)-(N-OUT) 208-230V AC
CN32 connect to DR module BLUE wire
NO USE
test port
connect to detector
CN26
connect to DR module
or
28
IPM board of MCH2U-18PHH2, MCH3U-27PHH2
BK
RD
BL
1
K
G
S
CTI 600V
17122000018251
W
V
U
17122000018251
250VAC
Time
Constant
IPM OCP
RD
BK
BL
64
16
J2
EU-KFR8 0W/BP 3(IR311+PS21997+
FAN_DC
SIM682 2+LOCK ).D.13.WP2-1
Pin1
CN7
CN9
CN10
5V→3.3V
3.3V→1.8V
U
V
W
3 2
4
CAUTION HI GH VOLTAGE
1
1
2 4
+
+
CN3
NTC1
R3
D2
41
CN8
Program_Debug
6
1
Online writing
R168
+
DZ10
+
DZ9
+
DZ8
R2
PTC2
J7 J6
J9
J8
F_DC Fan
R167
R166
R165
C81
CN1
CN11
ZR3 ZR2
ZR1
C13
R46
+
E15
C85
IC21
7805
C82
R164
C103
R
1
6
3
R162
R
1
6
1
IC2
CN4
L
CN5
N
CN2
R1_1
R1_2
R1_3
R1_4
R17
IC19
7805
CN13
D7
+
DZ6
C99
IC6
7815
R87
D14
R125
IC10 24LC2 5624LC08
C63
C50
C49
CY1
DZ4
R124
C1
+
E6
+
E5
PTC1
FUSE1 T/3.15A
- +
BR2
IC3
T1
IPM1
R121
R67
R90
R84
C7 C12
R
1
1
5
R114
R113
R112
R111
R110
R109
R108
R107
R105
R102
R101
R100
R99
R
9
7
R96
R95
R94
R93
R92
R91
R89
R88
R86
R83
R82
R81
R80
R79
R77
R76
R75
R74
R73
R72
R71
R69
R68
R65
R64
R63
R62
R61
R58
R54
R53
R51
R49
R48
R47
R44
R43
R40
R38 R37
R36
R35
R34 R33 R 31
R30
R29
R28
R27
R26
R25
R
2
4
R23
R21 R20
R19
R18 R16
R15
R14
R13
R12
R11
R10
R9
R8R7R6
R4
Q2
OSC1
LED2+LED1
1
17
49
33
IC14
IC13
IC12
IC11
IC9
IC8
IC7
IC4IC1
C100C101
C4
C95
C96
C97
C98
+
E14
+
E13
E12
+
E11
+
+
E9
+
+
E8
C102
+
E4
+
E1
+
DZ5
+ DZ1
D19
D13
D12
+
D11
D6
+
D3
D1
C78
C77
C76
C75
C74
C73
C72
C71
C70
C69
C68
C67
C
6
6
C65
C64
C
6
2
C
6
1
C60
C59
C58
C57
C56
C54
C53
C
5
2
C51
C47
C46
C45
C44
C43
C42
C41
C40
C39
C37
C36
C35
C34
C33
C32
C31
C30
C29
C28
C27
C26
C25
C24
C23
C22
C21
C20
C19
C18
C17
C16
C
1
5
C14
C11
C10
C8
C5
C3
C2
IGBT1
D20
C6
IC15
IPM2
SIM6822M
+
E2
R106
CN16
R118
R85
R119
R120
R57
+
E3
R117
R116
R122
R123
R70
R78
C38
R50
R66
D9
J4
C80
C55
R138
R137
R136
C84
R135
R143
R133
R132
IC17
Q6
IC16
C79
C83
IC5
R145
Q8
Q9
R144
R141
R148
R147
R146
C90
R98
J3
E27
7815
+
DZ7
E26
+
E25
R
1
3
9
R
1
6
0
C91
D21
R158
R157
R156
R159
C
9
2
IC18
R127
C48
R140
R39
R41
D22
R42
D23
R10_1
R10_2
R10_3
R11_1
R11_2
R11_3
J2
R
1
3
4
BR1
C9
C86
L1
R52
CN_COMP
CN_Reactor
R45
R1
J1
J5
R32 R59
R22
Q1
R103
J
1
0
J12
J11
R83_1
J13
R5
power supply
CN4(L)-CN5(N)
connect to the m ain board no use
fuse1 T/3.15A
Compressor drive EEPROM
online writing
Compressor driv e Program
Debug
DC Fan Driver IP M module
10-200VAC (run ning)
0VAC (standby)
connect to the DC FAN motor
TXD
+12V DC
+5V DC
GND For +12V
RXD
5 4 3 2 1
no use
DC Fan fuse for DC FAN
T/3.15A
10-200VAC (run ning)
0VAC (standby)
connect to the c ompressor
no use
connect to the Reactor
29
PCB board of MCH4U-36PHH2
N
L
SHOW/SW
EARTH
[1.4]2014.06.26
EU-KFR105W/BP3T5N1-350S.D.13.WP1-1
L-OUT
N-OUT
CONNECT TO INVERTER driver
HIGH
LOW
T2B-E
T2B-D
T2B-C
T2B-BT2B-A
TP
T4 T3
S-E
S-D
S-C
S-B
S-A
FAN_OUT
FAN_IN
Q
E
P
AB
C
D
E
202302141206
CN19
D4
R134
R133
R89
R37
+
E12
+
E15
CN10
N
C18
CN9
ZR3
ZR2
ZR1
X1
S
RY8
RY7
RY6
RY5
RY3
RY2
R213
R212
R211
R210
R180
R170
R140
R131
R130
R129
R128
R127
R126
R125
R124
R123
R121
R120
R118
R117
R116
R115
R114
R113
R112
R111
R110
R109
R108
R107
R106
R105
R104
R103
R102
R101
R100
R99
R98
R96
R95
R94
R93
R92
R91
R90
R88
R81
R80
R79
R78
R77
R76
R75
R74
R73
R72
R71
R70
R69
R68
R67
R66
R65
R64
R63
R62
R61
R60
R59
R58
R57
R56
R55
R54
R53
R52
R51
R50
R49
R48
R47
R46
R45
R44
R43
R42
R41
R40
R39R38
R36
R35
R34
R33
R32
R31
R30
R29
R28
R27
R26
R25
R24
R23
R22
R21
R20
R19
R18
R17
R16
R15
R14
R13
R12
R11
R10
R9
R8
R7
R6
R5R4R3
R2
R1
Q5
Q2
PTC1
LED1
L3
IC30
IC22
IC21
IC20
IC19
IC18
IC17
IC16
IC15
IC14
IC13
IC12
IC10
IC9
IC8
IC7 IC6
IC5
IC2
IC1
FUSE2
5A/250V
FUSE1
T30A/250V
E21
E20
+
E19
+
E16+E14
E13
E11
E9
E8
E5
E4
E3
E1
DSP1
DSA1
D28
D27
D26
D25
D24
D23
D22
D21
D20
D19
D18
D17
D16
D15
D14
D13
D12
D11
D10
D9
D8
D7
D6
D5
D3
D2
D1
CONdebug
CN44
HEAT2
CN43
FAN
CN42
C
CN41
C
CN40
HEAT1
CN34
CN33
CN30
CN29
CN28
CN27
CN26
CN22
4-WAY
CN20
CN18
CN17
CN16
CN14
CompTop
CN12
CN11
CN8
CN6
CN5
CN4
N
CN3
N
CN2
N-IN
CN1
L-IN
C103
C98
C97
C96
C95
C94
C93
C92
C91
C90
C72
C70
C69
C68
C67
C66
C65C64
C62
C61
C60
C59
C58
C57
C56
C55
C54
C53
C52
C51
C50
C49
C48
C47
C46
C45
C44
C43
C42
C41
C40
C39
C38
C37
C36
C35
C34
C33 C32
C31
C30
C29
C28
C27
C26
C25
C24
C23
C22
C21
C20
C19
C17
C16
C15
C14
C13
C12
C11
C10
C9C8C7
C6
C5
C4
C3
C2
C1
JP1
JP2
D29
D30
CN23
SSR1
CN7
CN13
P-1
L1
R82
R83
R84
R85
R86
R87
R97
R119
R122
R132
CN35
N
CN37
FAN-L
Q3
Q6
Q7
Q8
Q9
CN36
FAN-H
E2
IC3
Q1
Q4
IC4
ZR4
RY4
CN32
CN38
L2
R135
SW1
CN21
Electric Expansion Value B
Electric Expansion Value E
Electric Expansion Value D
Electric Expansion Value C
Electric Expansion Value A
485 communication
testPort connect to detector
external drive DC fan motor input terminal
external drive DC fan motor ouput terminal
current loop communication A
current loop communication B
current loop communication C
current loop communication D
current loop communication E
digital display
Fuse T30A/250V
connect to high and low pressure sensor
connect to trmp. sensor
Fuse 5A/250V
connect to earth
CN23 reserve
digital display button
test report connect to detector
CN43-5,CN43-1/CN41,CN42 AC fan motor capacitor
connector
CN43-4/CN37 CONNECT TO AC FAN MOTOR(LOW SPEED)
CN43-3/CN36 AC fan motor low speed connector CN43-2/CN35 AV fan motor N phase
current loop communication C
Signal wire
24VDC Pulse wave
connect to the terminal
connect to the terminal
208-230V AC
power supply
room temp sensor
pipe temp sensor
(3.3V)
(3.3V)
high pressure sensor
low pressure sensor
Connect to the Indoor evap.pipe out temp. sensor T2B-A、T2B-B、T2B-C、T2B-D、T2B-E
+12V DC pulse wave between (+1)-GND
+12V DC pulse wave between (+2)-GND
+12V DC pulse wave between (+3)-GND
+12V DC pulse wave between (+4)-GND
+12V DC
+12V DC
6 5 4 3 2 1
when 4-way is ON, output 208-230VAC
connect to the 4-WAY
when heater is ON, output 208-230V AC
connect to compressor heater
CN44 L CN10 N
CN40 L CN4 N
CN22 L CN3 N
connect to exhaust temp. sensor
connect to the terminal
208-230V AC
external drive DC fan motor connector
T3
T4
electric heater1
electric heater 2
30
IPM board of MCH4U-36PHH2
202302141237
PFC-L2
[1.6]2014.10.16
EU-KFR105W/BP2T3N1-350(767).D.13.MP2-1
PFC-L1
CN58
EARTH
C57
C56
6
J146J15
R65
C55
C53
E31
C50
D7
C49
+
E30
C47
C9
ZR1
DZ3
R8
E3
E2
CN55
TO-MAIN
E23
C46
R13
IC3
C113
W
V
U
1
6 7
1011
12
1314
15
3
8
T1
R208
R207
R206
R205
R204
R203
R202
R198
R197
R196
R194
R192
R187
R186
R185
R184
R183
R182
R181
R180
R179
R175
R174
R173
R170
R163
R160
R150
R147
R146
R144
R143
R141
R140
R139
R137
R135
R133
R132
R131
R130
R129
R128
R127
R126
R125
R124
R119
R114
R111
R107
R104
R96
R92
R91
R90
R82
R80
R79
R78
R77
R76
R75
R66
R63
R62
R61
R60
R59
R58
R57
R56
R55
R54
R53
R52
R51
R50
R49
R48
R47
R46
R45
R44
R43
R42
R41
R40
R39
R38
R37
R36
R35
R33
R32
R31
R30
R29
R27
R26
R25
R24
R23
R22
R21
R20
R19
R18
R17
R15
R14
R12
R11
R10
R9
R7
R5
R2
R1
Q2
OSC1
+
LED4+LED3
JR1
J201
6
J1
IPM2
1
IPM1
1
17
49
33
IC20
IC17
IC16
IC15 24C256
IC1424C08
IC10
IC7
IC4
IC2
E34
E33
E27
E25
+
E24
+
E22
+
E21
+
E20
+
E17
E16
E15
E14
E13
E12
E10
E9
+
E8
+
E7
+
E6
+
E5
E4
E1
+
DZ9
+
DZ8
+
DZ7
+
DZ6
+
DZ1
D26
D14
D13
D12
D11
D10
D9
D8
D6
D5
D4
D3
D2
CN57
1
CN56
CN54
L-IN2
CN53
N-IN2
CN52
CN51
CN19
OUTFAN(DC)
C124
C123
C122
C121
C120
C119
C118
C117
C116
C114
C111
C109
C108
C107
C106 C105
C104
C103
C102
C101
C100
C99
C97
C94
C82
C79
C78
C77
C76
C72
C71
C70
C69
C67
C66
C65
C64
C61
C60
C59
C54
C51
C40
C39
C38
C36
C33
C32
C31
C30
C29
C26
C25
C24
C23
C22
C21
C20
C19
C18
C17
C16
C15
C14
C13
C12
C11
C8
C7
C6
C5
C4
C3
C2
C1
BR1
R3
R4
R6
R16
C27
C28
+
E18
C10
+
E19
C34
+
D1
+
D15
+
D16
22
44
23
IC1
C52
D17
R28
6J36
J4
6
J2
6
J5
6
J6
6
J7
6
J8
6J96
J10
6
J11
6
J12
6
J13
C35
C37
C41
C42
C43
C44
C45
E26
E28
E29
IC11
IC12
R34
R64
C48
E11
CN53
power supply
connect to the terminal
208-230V AC
CN54
CN51
CN52
PFC inductance terminal
CN58
EATTH
­+
210-300VDC (Running)
CAPACITOR Voltage 290-330VDC (standby)
CN55
TO MAIN
CN19
connect to DC fan motor
U
V
W
10-200VAC (running)
0VAC (standby)
connect to the compressor
U
V
W
10-200VAC (running)
0VAC (standby)
CN57 Debug
Loading...
+ 101 hidden pages