
1
Midea R410A 50Hz
Compressor Condensing Unit
Technical Manual
Applicable Model:
MCCU-03CN1 MCCU-05CN1
MCCU-07CN1 MCCU-10CN1
MCCU-12CN1 MCCU-16CN1
MCCU-22CN1 MCCU-28CN1
MCCU-35CN1 MCCU-45CN1
MCCU-53CN1 MCCU-61CN1
MCCU-70CN1 MCCU-105CN1
Midea reserves the right to discontinue, or change specification or designs at any time without notices and
without incurring obligations.
DM15-01.01.17en

Midea R410A 50Hz T1 Compressor Condensing Unit
2
Content
Part. 1 Performance ............................. 3
Part. 2 Installation .............................. 38
Appendix: VRF Solution .................... 67

Midea R410A 50Hz T1 Compressor Condensing Unit
3
Part. 1 Performance
1. Product lineup ................................................................ 4
2. External Appearance ..................................................... 4
3. Nomenclature ................................................................. 6
4. Specifications ................................................................ 7
5. Dimensions (Unit: mm) ............................................... 18
6. Refrigerant circuits ...................................................... 24
7. Wiring Diagrams .......................................................... 28
8. Electrical datas ............................................................ 34
9. Sound Levels ............................................................... 34
10. Connection accessory list (Optional) ...................... 35

Midea R410A 50Hz T1 Compressor Condensing Unit
4
1. Product lineup
Model names of units with cooling only:

Midea R410A 50Hz T1 Compressor Condensing Unit
5
MCCU-12CN1
MCCU-16CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
6
3. Nomenclature
M CCU – 53 C N1
Refrigerant type: R410A
Function code
C: Cooling only
H: Heat pump
Nominal cooling capacity (53×1,000W)
Compressor Condensing Unit
Midea

Midea R410A 50Hz T1 Compressor Condensing Unit
7
4. Specifications
Ambient temperature range
Type / Quantity \ Rotary / 1
Oil charge \ 480 (Ester oil VG74)
Motor model \ YDK24-6F(B)
Type \ Copper tube and aluminum fin
Copper tube and aluminum fin
2×2.5mm2+1×1.5mm2 (Ground)
2×4.0mm2+1×2.5mm2 (Ground)
Notes:
Nominal cooling capacities are based on the following conditions: Indoor temperature: 27°CDB/19°CWB; outdoor
temperature: 35°CDB/24°C WB. Equivalent refrigerant pipe: 7.5m.

Midea R410A 50Hz T1 Compressor Condensing Unit
8
Ambient temperature range
Type / Quantity \ Rotary / 1
Oil charge \ 850 (Ester oil VG74)
Type \ Copper tube and aluminum fin
Copper tube and aluminum fin
2×6.0mm2+1×4.0mm2 (Ground)
4×4.0mm2+1×2.5mm2 (Ground)
Notes:
Nominal cooling capacities are based on the following conditions:
Indoor temperature: 27°CDB, 19°CWB; Outdoor temperature: 35°CDB, 24°C WB; Equivalent refrigerant pipe: 7.5m.

Midea R410A 50Hz T1 Compressor Condensing Unit
9
Ambient temperature range
Type / Quantity \ Scroll / 1
Oil charge \ 1,700 (FV68S)
Motor model \ YDK65-6F(B)
Type \ Copper tube and aluminum fin
Copper tube and aluminum fin
4×4.0mm2+1×2.5mm2 (Ground)
4×10.0mm2+1×6.0mm2 (Ground)
Notes:
Nominal cooling capacities are based on the following conditions:
Indoor temperature: 27°CDB, 19°CWB; Outdoor temperature: 35°CDB, 24°C WB; Equivalent refrigerant pipe: 7.5m.

Midea R410A 50Hz T1 Compressor Condensing Unit
10
Ambient temperature range
Hi: 920/930; Lo: 650/710 (4 blades/3 blades)
Copper tube and aluminum fin
Notes:
Nominal cooling capacities are based on the following conditions:
Indoor temperature: 27°CDB, 19°CWB; Outdoor temperature: 35°CDB, 24°C WB; Equivalent refrigerant pipe: 7.5m.

Midea R410A 50Hz T1 Compressor Condensing Unit
11
Ambient temperature range
Motor input W Hi: 621/587; Lo: 388/388 (4 blades/3 blades)
Hi: 1,180/1,230; Lo: 790/870 (4 blades/3 blades)
Copper tube and aluminum fin
Notes:
Nominal cooling capacities are based on the following conditions:
Indoor temperature: 27°CDB, 19°CWB; Outdoor temperature: 35°CDB, 24°C WB; Equivalent refrigerant pipe: 7.5m.

Midea R410A 50Hz T1 Compressor Condensing Unit
12
Ambient temperature range
Motor input W Hi: 621/587; Lo: 388/388 (4 blades/3 blades)
Hi: 1,180/1,230; Lo: 790/870 (4 blades/3 blades)
Copper tube and aluminum fin
Notes:
Nominal cooling capacities are based on the following conditions:
Indoor temperature: 27°CDB, 19°CWB; Outdoor temperature: 35°CDB, 24°C WB; Equivalent refrigerant pipe: 7.5m.

Midea R410A 50Hz T1 Compressor Condensing Unit
13
Ambient temperature range
Motor input W Hi: 615/580; Lo: 425/420 (4 blades/3 blades)
Hi: 1,000/1,090; Lo: 780/870 (4 blades/3 blades)
Copper tube and aluminum fin
Notes:
Nominal cooling capacities are based on the following conditions:
Indoor temperature: 27°CDB, 19°CWB; Outdoor temperature: 35°CDB, 24°C WB; Equivalent refrigerant pipe: 7.5m.

Midea R410A 50Hz T1 Compressor Condensing Unit
14
Ambient temperature range
Copper tube and aluminum fin
Power wire \ 4×16.0mm2+1×10.0mm2 (Ground)
Notes:
Nominal cooling capacities are based on the following conditions:
Indoor temperature: 27°CDB, 19°CWB; Outdoor temperature: 35°CDB, 24°C WB; Equivalent refrigerant pipe: 7.5m.

Midea R410A 50Hz T1 Compressor Condensing Unit
15
Copper tube and aluminum fin
4×25.0mm2+1×16.0mm2 (Ground)
Notes:
Nominal cooling capacities are based on the following conditions:
Indoor temperature: 27°CDB, 19°CWB; Outdoor temperature: 35°CDB, 24°C WB; Equivalent refrigerant pipe: 7.5m.

Midea R410A 50Hz T1 Compressor Condensing Unit
16
Ambient temperature range
Copper tube and aluminum fin
(1,355×1,100)+(1,325×1,100)
4×25.0mm2+1×16.0mm2 (Ground)
Notes:
Nominal cooling capacities are based on the following conditions:
Indoor temperature: 27°CDB, 19°CWB; Outdoor temperature: 35°CDB, 24°C WB; Equivalent refrigerant pipe: 7.5m.

Midea R410A 50Hz T1 Compressor Condensing Unit
17
Copper tube and aluminum fin
(1,325×756)×2+(1367×756)×2
4×35.0mm2+1×16.0mm2 (Ground)
Notes:
Nominal cooling capacities are based on the following conditions:
Indoor temperature: 27°CDB, 19°CWB; Outdoor temperature: 35°CDB, 24°C WB; Equivalent refrigerant pipe: 7.5m.

Midea R410A 50Hz T1 Compressor Condensing Unit
18
5. Dimensions (Unit: mm)
MCCU-03CN1
MCCU-05CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
19
MCCU-07CN1
MCCU-10CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
20
MCCU-12CN1, MCCU-16CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
21
MCCU-22CN1, MCCU-28CN1
MCCU-35CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
22
MCCU-45CN1
MCCU-53CN1, MCCU-61CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
23
MCCU-70CN1
MCCU-105CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
24
6. Refrigerant circuits
MCCU-03CN1, MCCU-05CN1, MCCU-07CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
25
MCCU-10CN1, MCCU-12CN1, MCCU-16CN1, MCCU-22CN1, MCCU-28CN1, MCCU-35CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
26
MCCU-45CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
27
MCCU-53CN1, MCCU-61CN1, MCCU-70CN1, MCCU-105CN1
Notes: Two 4-way valves connected in refrigerant pipe systems are invalid.

Midea R410A 50Hz T1 Compressor Condensing Unit
28
7. Wiring Diagrams
MCCU-03CN1, MCCU-05CN1
MCCU-07CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
29
MCCU-10CN1
MCCU-12CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
30
MCCU-22CN1, MCCU-28CN1, MCCU-35CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
31
MCCU-45CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
32
MCCU-53CN1, MCCU-61CN1, MCCU-70CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
33
MCCU-105CN1

Midea R410A 50Hz T1 Compressor Condensing Unit
34
8. Electrical datas
Notes:
MCA: Min. Current Amps. (A) TOCA : Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A) MSC: Max. Starting Amps. (A)
RLA: Rated Locked Amps. (A) OFM: Outdoor Fan Motor
kW: Fan Motor Rated Output (kW) FLA: Full Load Amps. (A)
9. Sound Levels

Midea R410A 50Hz T1 Compressor Condensing Unit
35
Notes:
1. H=(h+1)/2m.
2. The sound pressure value is the weighted average of four sides which include front, rear, left and right
side of the unit.
10. Connection accessory list (Optional)
Electromagnetic valve
solenoid

Midea R410A 50Hz T1 Compressor Condensing Unit
36
Electromagnetic valve
solenoid
Electromagnetic valve
solenoid
Electromagnetic valve
solenoid

Midea R410A 50Hz T1 Compressor Condensing Unit
37
T-KF700W/RN1.11 T-KF1050W/RN1.8
Electromagnetic valve
solenoid

Midea R410A 50Hz T1 Compressor Condensing Unit
38
Part. 2 Installation
1. Notes ............................................................................ 39
2. Transport and Fixed units ......................................... 40
3. Connection of Refrigerant Pipe ................................ 43
4. Heat Insulation of Refrigerant Pipe .......................... 54
5. Electric Connection .................................................... 54
6. Trial Run ...................................................................... 56
7. Trouble shooting ........................................................ 57
8. Maintenance ................................................................ 65

Midea R410A 50Hz T1 Compressor Condensing Unit
39
1. Notes
CAUTION:
Install the unit where enough space of installation and maintenance is available.
Install the unit where the air inlet and outlet are not baffled and the least affected by external air.
Install the unit where it is easy to lead out the connective pipe and the drain pipe.
Install the unit where no heat is emitted from a heat source directly.
Installing the equipment in any of the following places may lead to faults of the equipment (if that
is inevitable, consult the supplier):
The site contains mineral oils such as cutting lubricant.
Seaside where the air contains much salt.
Hot ring area where corrosive gases exist, e.g., sulfide gas.
Factories where the supply voltage fluctuates seriously.
Inside a car or cabin.
Place like kitchen where oil permeates.
Place where strong electromagnetic waves exist.
Place where flammable gases or materials exist.
Place where acid or alkali gases evaporate, or other special environments.
Install the unit where enough space of installation and maintenance is available.
Install the unit where the air inlet and air outlet are free from obstacles and strong wind.
Install the unit in a dry and well ventilated place.
For side-discharge outdoor unit, the air outlet and inlet are not impeded, and cannot be reached
by strong wind.
Install the unit where the bearing surface is level and can bear weight of the unit, and is suitable

Midea R410A 50Hz T1 Compressor Condensing Unit
40
for installing the unit horizontally without increasing noise or vibration.
Install the unit where the operation noise and the expelling of air do not affect neighbors.
Install the unit where no flammable gas is leaked.
Install the unit where it is convenient for pipe connection and electric connection.
2. Transport and Fixed units
When installing the unit, leave a space for maintenance shown in the following figure. Install the
power supply at the side of the outdoor unit.
MCCU-03CN1, MCCU-05CN1, MCCU-07CN1, MCCU-10CN1, MCCU-12CN1, MCCU-16CN1:
In case any obstacles exist above the outdoor unit, such obstacles must be 600mm above the
outdoor unit.
MCCU-22CN1, MCCU-28CN1, MCCU-35CN1:
Top view of the outdoor unit (Multiple units installed)
In case any obstacles exist above the outdoor unit, such obstacles must be 2000mm above the
outdoor unit.

Midea R410A 50Hz T1 Compressor Condensing Unit
41
MCCU-45CN1, MCCU-53CN1, MCCU-61CN1, MCCU-70CN1, MCCU-105CN1:
In case any obstacles exist above the outdoor unit, such obstacles must be 2000mm above the
outdoor unit.
Use 4 steel ropes of a diameter 6mm or bigger size to hoist the outdoor unit and move it into the
site.
In order to prevent scratch and deformity the unit, apply a guard board to the surface between
the steel wire and the air conditioner.
Remove the cushion for use in the transport after finishing the transport.
The distance of the foundation bolt is shown in following picture.
MCCU-03CN1, MCCU-05CN1, MCCU-07CN1, MCCU-10CN1, MCCU-12CN1, MCCU-16CN1:

Midea R410A 50Hz T1 Compressor Condensing Unit
42
MCCU-22CN1, MCCU-28CN1, MCCU-35CN1:
MCCU-45CN1, MCCU-53CN1, MCCU-61CN1, MCCU-70CN1, MCCU-105CN1:
(Unit: mm)

Midea R410A 50Hz T1 Compressor Condensing Unit
43
Snow protection facilities must be installed in the snowfall areas. In order to prevent influence
caused by snow, set up raised pavilion, and install snow protection sheds at the air inlet and air
outlet. The snow protection facilities are provided in the site.
3. Connection of Refrigerant Pipe
Schematic diagram of connection between indoor unit and outdoor unit:
MCCU-03CN1, MCCU-05CN1, MCCU-07CN1, MCCU-10CN1:
MCCU-12CN1, MCCU-16CN1:

Midea R410A 50Hz T1 Compressor Condensing Unit
44
MCCU-22CN1, MCCU-28CN1, MCCU-35CN1, MCCU-45CN1:
MCCU-53CN1, MCCU-61CN1, MCCU-70CN1, MCCU-105CN1:
The refrigerant pipe adapter is located inside the outdoor unit. So remove the right front board
first.
When the pipe is connected from the front side, the pipe can be led out through the right front
board.
The units which capacities are 53kW, 61kW, 70kW and 105kw have two separate systems, so
please mark the system codes, and correctly connect the pipes of each system.
When welding the refrigerant pipe, in order to prevent internal oxidation of the pipe, nitrogen

Midea R410A 50Hz T1 Compressor Condensing Unit
45
must be filled in. Otherwise, the oxidized chips may block refrigerating circulatory system.
Trash and foreign matters may come into the pipe in the process of installing the refrigerant pipe.
Be sure to blow them off with nitrogen before connecting the pipe to the outdoor units.
Use high-pressure nitrogen to clean the pipelines. Do not use the refrigerant of the outdoor unit
for cleaning.
Pipes size of the units.
All connections between indoor unit and outdoor unit are copper-to copper and should be brazed
with a phosphorous-copper alloy material such as Silfos-5 or equivalent. Do not use soft solder.
The outdoor units have reusable valves on both the liquid and vapor connections. The total
system refrigerant charge is retained within the outdoor unit during shipping and installation. The
reusable valves are provided to evacuate and charge per the instruction.
Dry nitrogen should always be supplied through the tubing while it is being brazed, because the
temperature required is high enough to cause oxidation of the copper unless an inert
atmosphere is provided. The flow of dry nitrogen should continue until the joint has cooled.
Always use a pressure regulator and safety valve to insure that only low pressure dry nitrogen is
introduced into the tubing. Only a small flow is necessary to displace air and prevent oxidation.
Install the connective pipe only after fixing the indoor unit and outdoor unit. Keep dry when
installing the connective pipe. Do not let moist intrude into the pipeline system.
The bending angle of refrigerant should not exceed 90°. Bending position is preferably in the

Midea R410A 50Hz T1 Compressor Condensing Unit
46
middle of the bendable pipe. Do not bend the pipe more than three times.
Be sure to use the same insulation materials when you buy the brass pipe.
Bend the tubing in proper way. Do not twist the pipe.
Put some refrigerant oil on the surfaces of the flare pipe and the joint nuts when wrench it for 3~4
rounds with hands before fasten the flare nuts.
Drill a hole in the wall (suitable just for the size of the wall sleeve), then set on the fittings such as
the wall sleeve and its cover.
Bind the connecting pipe and cables together tightly with binding tapes. Pass the bound
connecting pipe through the wall sleeve from outside. Make sure of the pipe allocation not to
damage the copper tubes.
Allowed length of refrigerant pipe and height difference.
MCCU-03CN1, MCCU-05CN1, MCCU-07CN1,
MCCU-10CN1, MCCU-12CN1, MCCU-16CN1:
MCCU-03CN1, MCCU-05CN1, MCCU-07CN1:
Max. actual length of pipe (L)
Max. height difference between
indoor and outdoor unit
Outdoor unit lower (lower)

Midea R410A 50Hz T1 Compressor Condensing Unit
47
MCCU-10CN1, MCCU-12CN1, MCCU-16CN1:
Max. actual length of pipe (L)
Max. height difference between
indoor and outdoor unit
Outdoor unit lower (lower)
Notes: The number of bends is up to the length of the Max. height drop. Usually for each 10m need a
bend. (It is only available for the units below 16kW.)
MCCU-22CN1, MCCU-28CN1, MCCU-35CN1, MCCU-45CN1,
MCCU-53CN1, MCCU-61CN1, MCCU-70CN1, MCCU-105CN1:
Max. actual length of pipe (L)
Max. height difference between
indoor and outdoor unit
Outdoor unit lower (lower)
Do not increase or decrease piping sizes.
As shown in following picture, when brazing the indoor and outdoor connective lines, pad a
sheet metal under the valve avoids the flame burning the chassis.
Precaution should be taken to prevent heat damage to the valve by wrapping a wet rag around it.
Remove the cap and Schrader core from both the liquid and vapor service valve service ports at

Midea R410A 50Hz T1 Compressor Condensing Unit
48
the outdoor unit. Connect low pressure nitrogen to the liquid line service port.
Braze the liquid line to the high pressure valve (liquid valve) at the outdoor unit. Be sure to wrap
the valve body with a wet rag. Allow the nitrogen to continue flowing.
Carefully remove the rubber plugs from the evaporator liquid and vapor connections at the
indoor unit.
Braze the liquid line to the indoor liquid connection. Nitrogen should be flowing through the
evaporator coil.
Slide the plastic cap away from the vapor connection at the indoor coil. Braze the vapor line to
the evaporator vapor connection.
Too large torque will harm the bell mouthing and too small will cause leakage. Please determine
the torque according to the following table:
Protect the vapor valve with a wet rag and braze the vapor line connection to the outdoor unit.
The nitrogen flow should be exiting the system from the vapor service port connection. After this
connection has cooled, remove the nitrogen source from the liquid fitting service port.
Replace the Schrader core in the liquid and vapor valves.
Leak test all refrigerant piping connections including the service port flare caps to be sure they
are leak tight.

Midea R410A 50Hz T1 Compressor Condensing Unit
49
Do not over tighten. (between 40 and 60 inch-lbs. maximum)
Evacuate the vapor line, evaporator and the liquid line, to 500 microns or less.
Replace cap on service ports. Do not remove the flare caps from the service ports except when
necessary for servicing the system.
Do not connect manifold gauges unless trouble is suspected. Approximately 3/4 ounce of
refrigerant will be lost each time a standard manifold gauge is connected.
Release the refrigerant charge into the system. Open both the liquid and vapor valves by
removing the plunger cap and with a hex wrench back out counter-clockwise until valve stem
just touches the chamfered retaining wall.
Replace plunger cap finger tight, then tighten an additional 1/12 turn (1/ hex flat). Cap must be
replaced to prevent leaks.
Never attempt to repair any brazed connections while the system is under pressure. Personal
injury could result.
After the pipes between the indoor unit and the outdoor unit are connected, replenish
compressed nitrogen to perform airtight test.
The airtight test is performed by using the compressed nitrogen, 2.94MPa (30kg/cm2G).
Leak test with a bubble type leak detector. Do not use the system refrigerant in the outdoor
unit to purge or leak test.
Tighten the spool of the low pressure valve and high pressure valve before compressing the
nitrogen.
Compress the nitrogen at the air vent of the gas valve.
The low pressure valve and high pressure valve are closed in the process of compressing
the nitrogen.
Do not use oxygen, flammable gas or toxic gas in the airtight test.
Vacuum
Length of connective pipe
(Single pass)
Procedure of expelling air
Use refrigerant in the outdoor unit.
Use vacuum pump or refrigerant tank.

Midea R410A 50Hz T1 Compressor Condensing Unit
50
Note: If the air conditioner is relocated, be sure to use a vacuum pump or refrigerant tank to expel air.
Use the refrigerant in the outdoor unit to expel air.
Screw up the pipe nuts at A, B, C and D completely.
Loosen and remove the square-head cover of valves A and B, rotate the square-head
spool of valve B counter-clockwise for 45 degrees and stay for about 10 seconds, and
then close the spool of valve B tightly.
Detect leak for all adapters at A, B, C and D. After making sure that no leak exists, open
the maintenance orifice nut of valve A. After all air is expelled, tighten the maintenance
orifice nut of valve A.
Open the spools of valves A and B completely.
Tighten the square-head cover of valves A and B completely.
Use refrigerant tank to expel air.
Screw up the pipe nuts at A, B, C and D completely.
Loosen and remove the square-head cover and maintenance orifice nut of valves A
and B.
Connect the filler hose of refrigerant tank with the maintenance orifice of valve A.
Loosen the valve of the refrigerant tank, continue filling refrigerant for 6 seconds to
expel the air, and tighten the nut of valve B quickly.
Loosen the valve of the refrigerant tank again, and fill the refrigerant for 6 seconds.
Detect leak for all adapters at A, B, C and D. After making sure that no leak exists,
screw off the filler hose. After all the filled refrigerant is expelled, screw up the
maintenance orifice nut of valve A quickly.
Open the square-head pools of valves A and B completely.
Tighten the square-head cover of valves A and B.
Use a vacuum pump

Midea R410A 50Hz T1 Compressor Condensing Unit
51
Loosen and remove the maintenance orifice nut of valve A, and connect the filler hose
of the manifold valve to the maintenance orifice of valve A (Tighten both valve A and
valve B).
Connect the filler hose adapter to the vacuum pump.
Open the low (Lo) pressure handle of the manifold valve completely.
Start the vacuum pump to extract air. At the beginning of extracting air, slightly loosen
the maintenance orifice nut of valve B, check whether any air enters it (The vacuum
pump noise changes, and the multi-meter indicates from negative to 0.). Then tighten
this maintenance orifice nut.
Upon completion of vacuuming, tighten the low pressure handle of the manifold valve
completely and stop the vacuum pump. Keep extracting air for over 15 minutes. Check
whether the multi-meter points at -1.0×10Pa (-76cmHg).
Loosen the remove the square-head cover of valves A and B. After opening valves A
and B completely, tighten the square-head cover of valves A and B.
Remove the filler hose of the maintenance orifice of valve A, and then tighten the nut.
Procedure of using stop valve
Open the spool until it touches the stop block. Do not attempt to open further.
Use a spanner or a similar tool to tighten the bonnet.
Upon completion of installation, open all valves before trial run. Each unit has two valves of
different sizes located at the outdoor unit side. Of the two valves, one is gas valve and the
other is liquid valve. The procedure of opening / closing the valve is shown in following
picture.

Midea R410A 50Hz T1 Compressor Condensing Unit
52
Procedure of opening the valve: Open the square-head cover, use a spanner to capture the
square head and open it thoroughly. Then tighten the square-head cover.
Procedure of closing the valve: Same as the procedure of opening the valve, but rotate the
spanner clockwise thoroughly.
After vacuum, according to the diameter and length of the connective pipe of liquid side between
the indoor unit and outdoor unit, calculate the refrigerant replenishment quantity. The refrigerant
for replenishment is R410A.
Diameter of liquid-side pipe
Quantity of refrigerant replenished
for 1m pipe length
Notes:
Please check and record the replenished quantity of the air conditioner.
Refrigerant leak precautions. This air conditioner uses refrigerant R410A. R410A is safe
refrigerant which is harmless and non-flammable. The room for placing the air conditioner should
have a proper space. Even if refrigerant leakage occurs, the density threshold will not be
crossed. Additional measures may also be taken.
Density threshold: Density of the Freon gas that does not harm the human body. Density
threshold of R410A: 0.3kg/m3.
Calculate the total quantity of refrigerant to be replenished [A (kg)].
Total refrigerant quantity = refrigerant replenishment quantity upon shipment + additional
refrigerant replenishment corresponding to the pipe length.

Midea R410A 50Hz T1 Compressor Condensing Unit
53
Calculate out the indoor volume [B (m3)] (according to the minimum volume)
Calculate out the refrigerant density:
[A (kg)] / [B (m3)] ≤ Density threshold: 0.3kg/m
3
Measures against crossing of the refrigerant density threshold.
In order to keep the refrigerant density below the threshold value, please install a mechanic
ventilation device. (Perform ventilation often.)
In case frequent ventilation is impossible, please install the leakage detection alarm device
linked with the mechanical ventilation device.

Midea R410A 50Hz T1 Compressor Condensing Unit
54
4. Heat Insulation of Refrigerant Pipe
In order to prevent faults caused by condensate of the refrigerant pipe and drain pipe, perform
condensate prevention and heat insulation properly. If it is forecast that high humidity and
temperature environment (Condensate temperature is over 23°C ) may exist in the ceiling, e.g., inside
the ceiling with slab, ceiling which is in the same environment as the outdoor air. It is necessary to
apply 10mm or thicker adiabatic wool (16~20kg/m2) to the refrigerant pipe and the drain pipe in
addition to applying the general heat insulation materials. Enough heat insulation materials should
also be applied to the refrigerant joint and the pipe joint.
Note: the heat insulation of drain pipe refer to the installation of indoor unit.
Please use heat-resistant materials as heat insulation material of the air-side pipe. (e.g., EPT)
Cover heat insulation materials separately at the liquid side and the air side. Moreover, perform
heat insulation thoroughly for the air-side pipes of the indoor unit, and prevent water from
dripping outside the unit.
After applying the auxiliary heat insulation materials, use vinyl resin tape to seal refrigerant pipe
and drainage pipe to prevent water leak.
5. Electric Connection
5.1 Caution
Use special power supply for the air conditioner. Design power supplies specific to the indoor
unit and outdoor unit. The supply voltage must comply with the nominal voltage.
The external supply circuit of the air conditioner must have a ground wire, and the power supply
ground wire of the indoor unit must be connected with the external ground wire firmly.
The wiring must be performed by professional technicians according to the circuit diagram
labels.
Distribute the wires according to the relevant electric technical standards promulgated by the
State, and set the Residual Current-operated Circuit Breaker (RCCB) properly.

Midea R410A 50Hz T1 Compressor Condensing Unit
55
The power wire and the signal wire shall be laid out neatly and properly, without mutual
interference or contacting the connection pipe or valve.
No power cable is attached to this equipment. The user can select the power cable by reference
to the stipulated power supply specifications. No joint of wires is allowed.
Upon completion of wire connection, double check it and then connect the power supply.
An all-pole disconnection device which has at least 3mm separation distance in all pole and a
residual current device (RCD) with the rating of above 10mA shall be incorporated in the fixed
wiring according to the national rule.
The appliance shall be installed in accordance with national wiring regulations.
In order to prevent disoperation of the air conditioner, do not interleave or entwine the power
cable with the connection wires (Low-voltage wires) of the indoor and outdoor unit.
5.2 Specifications of power supply
Switch capacity of
the main power
supply / Fuse
Connective wire
of indoor
&outdoor unit

Midea R410A 50Hz T1 Compressor Condensing Unit
56
5.3 Schematic diagram
5.4 Electric wire diagram
When connect the wire, pay attention to the phase sequence of the power supply. If the phase
sequence is reversed, the compressor will not start. Meanwhile, the fault indicator of the outdoor
electric control board will light up. After shifting the phase sequence, power on the unit until the
fault indicator goes out and the compressor starts up normally.
6. Trial Run
Please conduct in accordance with the nameplate of Trial Run Tenor on the electric control box.
Perform the trial run only after the outdoor unit has been powered on for over 12 hours.
Check whether all valves are opened before trial run.
Check the electric safety before trial run.
Do not perform compulsory operation in any way, because it is very dangerous if the protection
device is not active.
Perform trial run only after all installations are finished.
Confirm the following issues before trial operation:
Whether the indoor and outdoor units are installed properly.
Whether the refrigerant pipeline system is inspected for leakage.
Whether the drain is smooth of CCU.
Whether the heat insulation of pipeline system is perfect.
Whether the ground cable is connected correctly.
Whether the pipe length and the refrigerant amount are recorded.
Whether the supply voltage is equal to the voltage of unit.
Whether the liquid and gas valves are opened.

Midea R410A 50Hz T1 Compressor Condensing Unit
57
7. Trouble shooting
7.1 Phenomena not attributable to faults of air conditioner
The system does not run.
It does not run immediately because the safety device in the system is active to prevent
overload.
Three minutes later, the air conditioner compressor will run automatically.
7.2 Faults of air conditioner and cause
If any of the following exceptions occur, operation of the air conditioner will be immediately
stopped. Turn off the power switch, and check it.
The fuse blows out frequently, or the circuit breaker protection occurs frequently.
Foreign substance or moist enters the air conditioner or other exceptions occur.
If the air conditioner fails but does not meet the foregoing phenomena obviously, check the
system in the following procedure:
The cooling effect is
poor.
The condenser or evaporator is
too dirty, or block.
Clean the heat-exchanger. Remove
foreign matters to keep well ventilated.
The door or window is opened.
Close all the windows and doors.
Directly exposed to sunlight.
Obstruct sunlight by curtains or
jalousie.
Too high outdoor environment
temperature.
It is normal, and the cooling effect of the
air conditioner is deteriorated.
The refrigerant is leaked or the
replenishment is deficient.
Detect leak, and fill the refrigerant of a
correct quantity.
The system does
not run.
Power supply fails.
Operate it after power supply resumes
and connect the power supply properly.
Power switch is disconnected.
The fuse blows out or the circuit
breaker acts.
Replace the fuse or check whether
electric leakage occurs.
The Indoor unit
sends air out without
cool air.
3-minutes protection of the
compressor.

Midea R410A 50Hz T1 Compressor Condensing Unit
58
7.3 Outdoor unit malfunction and protection codes
MCCU-10CN1, MCCU-12CN1, MCCU-16CN1:
Phase sequence protection
Lack of phase (Phase A or B)
Protection of low pressure
Protection of over-current
Outdoor condenser Temp. sensor error
Outdoor ambient Temp. sensor error
Protection of condenser hi-temp.
Notes:
★: Flash
◇: Extinguish;
MCCU-22CN1, MCCU-28CN1, MCCU-35CN1:
Phase sequence protection
Outdoor condenser Temp. sensor error
Outdoor ambient Temp. sensor error
Protection of low pressure
Protection of high pressure
Protection of over-current
Protection of condenser hi-temp.
Notes:
☆: Light for 1 second, extinguish for 1 second;
◆: Light;
◇: Extinguish;
●: Light for 0.4 second, extinguish for 0.4 second;
★: Light for 2 second, extinguish for 2 second.

Midea R410A 50Hz T1 Compressor Condensing Unit
59
MCCU-45CN1:
Phase sequence or lack of phase.
Condenser temperature sensor error.
Ambient temperature sensor error
System low pressure protection.
Three times low pressure protections within 1 hour.
System hi-pressure protection, hi-temperature protection
of compressor discharger.
Current overload protection.
High temperature protection of condenser.
Notes:
●: Light ○: Extinguishing ☆: Rapidly flash ★:Slowly flash
When the outdoor unit protections of temperature or system pressure are triggered three times within 1
hour, the unit will resume after power on again.
MCCU-53CN1, MCCU-61CN1, MCCU-70CN1, MCCU-105CN1:
Phase sequence or lack of phase.
Condenser temperature sensor error.
Low temperature protection of suction, system A.
Fault of suction temperature sensor, system A.
Discharge temperature or hi-pressure protection, system A.
Low pressure protection, system A.
Current over-load protection, system A.
Low temperature protection of suction, system B.
Fault of suction temperature sensor, system B.
Discharge temperature or hi-pressure protection, system B.
Low pressure protection, system B.
Current over-load protection, system B.
Notes:
○: Extinguishing ☆: Rapidly flash
☆1/3S: Rapidly flash1 times, and then stop for 3 seconds.
☆2/3S: Rapidly flash2 times, and then stop for 3 seconds.

Midea R410A 50Hz T1 Compressor Condensing Unit
60
☆3/3S: Rapidly flash3 times, and then stop for 3 seconds.
☆4/3S: Rapidly flash4 times, and then stop for 3 seconds.
☆5/3S: Rapidly flash5 times, and then stop for 3 seconds.
☆6/3S: Rapidly flash 6 times, and then stop for 3 seconds.
If a system has error or protection, another one will be stopped operation after 1 hour. If two systems
have error or protection at the same time, then only system A will be display the codes.
Phase sequence or lack of phase
Condenser temperature sensor error

Midea R410A 50Hz T1 Compressor Condensing Unit
61
Low temperature protection of suction
Fault of suction temperature sensor

Midea R410A 50Hz T1 Compressor Condensing Unit
62
Discharge temperature protection

Midea R410A 50Hz T1 Compressor Condensing Unit
63
Hi-pressure protection

Midea R410A 50Hz T1 Compressor Condensing Unit
64
Low pressure protection

Midea R410A 50Hz T1 Compressor Condensing Unit
65
Current overload protection
Notes:
8. Maintenance
Operation required before leaving the unit idle for a long period.
When the main power switch is turned on, a certain extent of electric power is
consumed even if the air conditioner does not run. Turning off the main power switch
can save energy.
After the air conditioner has been in service for several seasons, foreign substance
accumulates inside the unit to an extent dependent on the working conditions.
Therefore, shut down the air conditioner and cut off the power supply.
Startup after a long period out of service.
Check the following issues:
Check whether the air inlet or outlet of the unit is blocked. Remove foreign substance if

Midea R410A 50Hz T1 Compressor Condensing Unit
66
any.
Check whether the ground wire is connected properly.
Check whether the insulation work of refrigerant circuit and ventilating duct is on sound
status.
Check whether the installing seat is corroded or rusted.
Startup
Connect the indoor unit 12 hours after connect the outdoor unit to power supply.
Maintenance and upkeep of outdoor unit
The edge of some sheet metal assemblies and the fin of the condenser are very sharp.
Incorrect operation may cause harm. Be cautious when cleaning them up.
Check the air inlet and outlet of the outdoor unit periodically to see whether they are
blocked by stain or lampblack.

Midea R410A 50Hz T1 Compressor Condensing Unit
67
Appendix: VRF Solution
Midea VRF units also have another solution of DX AHU applications, through the AHU connection kit.
The AHU connection kit is consisted of controller, EXV (electronic expansion valve), distributor and
sensor, the external appearance as the following picture:
Midea VRF units totally have6 standard models: 25.2kW, 28kW, 33.5kW, 40kW, 45kW and 50kW.
They can be freely combined to achieve larger capacities, and the largest capacity could reach
180kW. VRF units adopt DC inverter compressor or digital scroll compressor, adjustable output to fit
the change of cooling and heating load. The VRF solution is shown as following picture: