Midea DHMSHA, DHMSHAQ09XA3, DHMSHAQ12XA1, DHMSHAQ24XA3, DHMSHAQ30XA3 Installation Instructions Manual

...
DHMSHA High Wall Ductless System Sizes 09 to 36
Installation Instructions
SAFETY CONSIDERATIONS........................................................2
PARTS LIST ....................................................................................3
SYSTEM REQUIREMENTS...........................................................4
WIRING ...........................................................................................4
Fig. 1 — Sizes 09K-36K
Fig. 2 — Remote Controller
DIMENSIONS..................................................................................5
CLEARANCES ................................................................................9
INSTALLATION TIPS....................................................................10
INDOOR UNIT INSTALLATION ..................................................10
ELECTRICAL DATA......................................................................11
CONNECTION DIAGRAMS..........................................................11
WIRELESS REMOTE CONTROL INSTALLATION ...................13
WIRED REMOTE CONTROL INSTALLATION..........................13
START-UP .......................................................................................13
TROUBLESHOOTING ...................................................................14
NOTES:
Read the entire instruction manual before starting the installation. Images are for illustration purposes only. Actual models may differ slightly.
Specifications subject to change without notice.

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start-up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as coil cleaning. All other operations should be performed only by trained service personnel. When working on the equipment, observe precautions in the literature
and on tags, stickers, and labels attached to the equipment. Follow all safety codes. Wear safety glasses and work gloves. Keep a quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment. Read these instructions thoroughly and follow all warnings or cautions included in the literature and attached to the unit. Consult the local building codes and National Electrical Code (NEC) for special requirements. Recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words: DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start-up.
2 Specifications subject to change without notice. IM-DHMSHA-02

PARTS LIST

Air Outlet
Se l
fC l
e a n
Fol
l o w
Me
L ED
Tu rb
o
I o n
iz er
S m
a rt
E y e
S ile
n c e
M o
d e
O n /
O ff
F a n
S
le e p
S
wi n g
T
im e r
TEMP
A U T
O C O
O
L
D R Y
H E A
T
F A
N H I G
H
M E
D
LOW
F.
P .
1
5
6
8
7
2
3
4
Interconnecting Piping/wiring
Table 1 — Parts List
Part No. Part Name Qty
1 Indoor Unit 1
2 Mounting Plate 1
3 Mounting Screw A ST3.9x25-C-H 5
4 Anchor 5
5 Air Filter 1
6 Wireless Remote Control 1
7 Wireless Remote Control Holder 1
8 Wireless Remote Control Mounting Screw B ST2.0x10-C-H 2
- Flare nuts for liquid and gas pipes 1
- Stencil (Mounting Template) 1
- Installation Instructions 1
- Owner's manual 1
- Warranty Card 1
- Carbon Filter 1
Fig. 3 — Parts List
NOTES:
- If the outdoor unit is higher than the indoor unit, prevent rain from flowing into the indoor unit along the connection pipe by making a inverted trap in the connection pipe before it enters the wall to the indoor unit. This ensures that rain drips from the connection pipe before it enters the wall.
- Piping and the interconnecting wiring are field supplied.
- The illustration above (Fig. 3) is only a sketch. Different models may be differ slightly.
The units listed in Table 2 are covered in these installation instructions.
Table 2 — Indoor Units
Description kBTUh V-Ph-Hz ID Model No.
High Wall Heat Pump
IM-DHMSHA-02 Specifications subject to change without notice. 3
12 115-1-60 DHMSHAQ12XA1
9 208/230-1-60 DHMSHAQ09XA3 12 208/230-1-60 DHMSHAQ12XA3 18 208/230-1-60 DHMSHAQ18XA3 24 208/230-1-60 DHMSHAQ24XA3 30 208/230-1-60 DHMSHAQ30XA3 36 208/230-1-60 DHMSHAQ36XA3

SYSTEM REQUIREMENTS

Allow sufficient space for airflow and unit service. See Fig. 8 — on page 9 for the minimum required distances between the unit and walls or ceilings.

Piping

IMPORTANT: Both refrigerant lines must be insulated separately.
• Table 3 lists the pipe sizes for the indoor unit. Refer to the outdoor unit’s installation instructions for other allowed piping lengths and refrigerant information.
Table 3 — Indoor Unit Pipe Sizes
UNIT SIZES
GAS PIPE
LIQUID PIPE
12K
(115V)
in 1/2 3/8 1/2 1/2 5/8 5/8 5/8
(mm) 12.7 9.52 12.7 12.7 16 16 16
in 1/4 1/4 1/4 1/4 3/8 3/8 3/8
(mm) 6.35 6.35 6.35 6.35 9.52 9.52 9.52
9K
(208/230V)
12K
(208/230V)
18K
(208/230V)
24K
(208/230V)
30K
(208/230V)
36K
(208/230V)

WIRING

All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. See the rating plate and/ or the installation instructions of the compatible outdoor unit for MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively.
Recommended Connection Method for Power and Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied 14/ 3 power/communication wiring from the outdoor unit to the indoor unit consists of four (4) wires and provides the power for the indoor unit. Two wires are high voltage AC power, one is communication wiring and the other is a ground wire. Wiring between the indoor and outdoor unit is polarity sensitive. The use of BX wire is NOT recommended.
If installed in a high Electromagnetic field (EMF) area and communication issues exists, a 14/2 stranded shielded wire can be used to replace L2/N and (S) between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only.
WARNING
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Wires should be sized based on NEC and local codes.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation. Be sure to comply with local codes while running wire from the indoor unit to the outdoor unit. Every wire must be connected firmly. Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Ensure all wiring is tightly connected. No wire should touch the refrigerant tubing, compressor or any moving parts. Disconnecting means must be provided and shall be located within sight and readily accessible from the air conditioner. Connecting cable with conduit shall be routed through the hole in the conduit panel.
NOTE: The main power is supplied to the outdoor unit.
When disconnecting the power of the outdoor unit, the indoor unit would lose power. A disconnect switch is not required on the Indoor unit side on the wiring between the Outdoor and Indoor unit. A 3 pole disconnect may be used for extra protection between the Indoor and Outdoor Unit.
4 Specifications subject to change without notice. IM-DHMSHA-02

DIMENSIONS

Fig. 4 — Indoor Unit
Table 4 — Dimensions
High Wall Unit Size 12K 9K 12K 18K 24K 30K 36K
Voltage (115V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V)
Height In (mm) 11.07 (281) 11.07 (281) 11.07 (281) 12.40 (315) 13.39 (343) 13.39 (343) 13.39 (343)
Width In (mm) 33.17 (842) 33.17 (842) 33.17 (842) 38.98 (990) 46.69 (1186) 46.69 (1186) 46.69 (1186)
Depth In (mm) 8.75 (222) 8.75 (222) 8.75 (222) 8.58 (218) 10.16 (258) 10.16 (258) 10.16 (258)
Weight- Net Lbs (kg) 19.18 (8.7) 19.18 (8.7) 19.18 (8.7) 24.46 (12.0) 40.12 (18.2) 40.12 (18.2) 40.12 (18.2)
IM-DHMSHA-02 Specifications subject to change without notice. 5
Loading...
+ 9 hidden pages