Read the entire instruction manual before starting the
installation.
Images are for illustration purposes only. Actual models
may differ slightly.
Specifications subject to change without notice.
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equipment can
be hazardous due to system pressures, electrical components, and
equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install,
start-up, and service this equipment.
Untrained personnel can perform basic maintenance functions such
as coil cleaning. All other operations should be performed only by
trained service personnel.
When working on the equipment, observe precautions in the literature
and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep
a quenching cloth and fire extinguisher nearby when brazing. Use
care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or
cautions included in the literature and attached to the unit. Consult
the local building codes and National Electrical Code (NEC) for
special requirements. Recognize safety information. This is the
safety-alert symbol . When you see this symbol on the unit and
in instructions or manuals, be alert to the potential for personal
injury. Understand these signal words: DANGER, WARNING,
and CAUTION. These words are used with the safety-alert
symbol. DANGER identifies the most serious hazards which will
result in severe personal injury or death. WARNING signifies
hazards which could result in personal injury or death. CAUTION
is used to identify unsafe practices which may result in minor
personal injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical
disconnect switch must be in the OFF position. There may be more
than 1 disconnect switch. Lock out and tag switch with a suitable
warning label.
WARNING
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing oxygen
for leak testing or operating refrigerant
compressors. Pressurized mixtures of air
or gases containing oxygen can lead to
an explosion.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the
ground. If any section of pipe is buried, there must be a 6 in. (152 mm)
vertical rise to the valve connections on the outdoor units. If more
than the recommended length is buried, refrigerant may migrate to the
cooler buried section during extended periods of system shutdown.
This causes refrigerant slugging and could possibly damage the
compressor at start-up.
2 Specifications subject to change without notice. IM-DHMSHA-02
PARTS LIST
Air Outlet
Se
l
fC
l
e
a
n
Fol
l
o
w
Me
L
ED
Tu
rb
o
I
o
n
iz
er
S
m
a
rt
E
y
e
S
ile
n
c
e
M
o
d
e
O
n
/
O
ff
F
a
n
S
le
e
p
S
wi
n
g
T
im
e
r
TEMP
A
U
T
O
C
O
O
L
D
R
Y
H
E
A
T
F
A
N
H
I
G
H
M
E
D
LOW
F.
P
.
1
5
6
8
7
2
3
4
Interconnecting
Piping/wiring
Table 1 — Parts List
Part No.Part NameQty
1Indoor Unit1
2Mounting Plate1
3Mounting Screw A ST3.9x25-C-H5
4Anchor5
5Air Filter1
6Wireless Remote Control1
7Wireless Remote Control Holder1
8Wireless Remote Control Mounting Screw B ST2.0x10-C-H2
-Flare nuts for liquid and gas pipes1
-Stencil (Mounting Template)1
-Installation Instructions1
-Owner's manual1
-Warranty Card1
-Carbon Filter1
Fig. 3 — Parts List
NOTES:
- If the outdoor unit is higher than the indoor unit, prevent rain from flowing into the indoor unit along the connection
pipe by making a inverted trap in the connection pipe before it enters the wall to the indoor unit. This ensures that rain
drips from the connection pipe before it enters the wall.
- Piping and the interconnecting wiring are field supplied.
- The illustration above (Fig. 3) is only a sketch. Different models may be differ slightly.
The units listed in Table 2 are covered in these installation instructions.
Table 2 — Indoor Units
DescriptionkBTUhV-Ph-HzID Model No.
High Wall Heat Pump
IM-DHMSHA-02 Specifications subject to change without notice. 3
Allow sufficient space for airflow and unit service. See Fig. 8 — on page 9 for the minimum required distances between the unit and walls or
ceilings.
Piping
IMPORTANT: Both refrigerant lines must be insulated separately.
• Table 3 lists the pipe sizes for the indoor unit. Refer to the outdoor unit’s installation instructions for other allowed piping lengths and
refrigerant information.
Table 3 — Indoor Unit Pipe Sizes
UNIT SIZES
GAS PIPE
LIQUID PIPE
12K
(115V)
in1/23/81/21/25/85/85/8
(mm)12.79.5212.712.7161616
in1/41/41/41/43/83/83/8
(mm)6.356.356.356.359.529.529.52
9K
(208/230V)
12K
(208/230V)
18K
(208/230V)
24K
(208/230V)
30K
(208/230V)
36K
(208/230V)
WIRING
All wires must be sized per NEC (National Electrical Code) or CEC
(Canadian Electrical Code) and local codes. See the rating plate and/
or the installation instructions of the compatible outdoor unit for MCA
(minimum circuit amps) and MOCP (maximum over current
protection) to correctly size the wires and the disconnect fuse or
breakers respectively.
Recommended Connection Method for Power and
Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied 14/
3 power/communication wiring from the outdoor unit to the indoor
unit consists of four (4) wires and provides the power for the indoor
unit. Two wires are high voltage AC power, one is communication
wiring and the other is a ground wire. Wiring between the indoor and
outdoor unit is polarity sensitive. The use of BX wire is NOT
recommended.
If installed in a high Electromagnetic field (EMF) area and
communication issues exists, a 14/2 stranded shielded wire can be
used to replace L2/N and (S) between outdoor unit and indoor unit
landing the shield onto ground in the outdoor unit only.
WARNING
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Wires should be sized based on NEC and local codes.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Be sure to comply with local codes while running wire from
the indoor unit to the outdoor unit.
Every wire must be connected firmly. Loose wiring may
cause the terminal to overheat or result in unit malfunction. A
fire hazard may also exist. Ensure all wiring is tightly
connected.
No wire should touch the refrigerant tubing, compressor or
any moving parts.
Disconnecting means must be provided and shall be located
within sight and readily accessible from the air conditioner.
Connecting cable with conduit shall be routed through the
hole in the conduit panel.
NOTE: The main power is supplied to the outdoor unit.
When disconnecting the power of the outdoor unit,
the indoor unit would lose power. A disconnect
switch is not required on the Indoor unit side on
the wiring between the Outdoor and Indoor unit. A
3 pole disconnect may be used for extra protection
between the Indoor and Outdoor Unit.
4 Specifications subject to change without notice. IM-DHMSHA-02