liquid pipe 6.35 1/4F
gas pipe 12.7 1/2F
external diameter after
heat insulation 35
drain hose
external diameter after
heat insulation
Unit
Page 6
Installation & Maintenance Manual
II.Dimensions
CSU-18HCAA CSU-18HHAA CSU-21HCAA CSU-21HHAA
CSU-24HCAA CSU-24HHAAindoor unit
Four holes
Wireless remote controller
Indoor unit
Mounting board
HUALING
Porthhole
Air inlet
Power cable
2m to the right side
1m to the left side
Air outlet
190
Mounting board
liquid pipe 6.35 1/4F
gas pipe 12.7 1/2F
5
external diameter after
heat insulation 35
Drainage pipe
16
external diameter after
heat insulation
28
unit
4
Page 7
II.Dimensions
Outdoor unit
air inlet
air inlet
air outlet
Installation & Maintenance Manual
Above
100mm Above
100mm Above
350mm Above
If there exists only
50-60 cm clearance
from the back to the wall,
the left side of the outdoor
unit must be entirely open.
100mm Above
500mm
piping for liquid pipe joint 6.35
mounting hole distance
OUTDOOR UNITS DIMENSION
Model
CU-05CA
CU-07CA
CU-09C(H)A
A
B
C
D
E
piping for gas pipe joint 12.7
F
G
H
I
CU-12C(H)A
CU-18C(H)A
CU-21C(H)A
CU-24C(H)A
5
Page 8
III. Specification
Installation & Maintenance Manual
Model
CSU-05HCAA
CSU-07HCAA
CSU-09HCAA
CSU-09HHAA
Performance data
Functions
Power supply
kW
l/h
3
m/h
A
F
kW
%
A
A
A
Capacities
Other
electrical
data
Capacity
Dehumidifying capacity
Air supply capacity
Power supply capacity
Running capacitor
Input power
Power factor
Stockstill current
Compressor motor current
Fan motor current
EER
Winding resistance(at )
Compressor
Indoor fan motor
Outdoor fan motor
Dimensions
Weight
Other data
Model
Winding resistance(at )
Winding resistance(at )
Length
Indoor unit
Width
Heigth
Length
Outdoor unit
Width
Height
Indoor unit
Outdoor unit
Noise
Fan speed
Fan speed
stage
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Refrigerant R22
Thermister(at )
mm
mm
mm
mm
mm
mm
kg
kg
( )
dB A
( )
dB A
r/min
r/min
g
k
1Test conditions
cooling indoor unit dry bulb 27 wet bulb19
outddor unit dry bulb 35 wet bulb 24
2The data should subject to the nameplate they are different from those on the nameplate.
1.42
0.6
410
10
20
0.5
97
12
2.4
In0.22/out0.25
3.1
SD091CV-H3BU
740
243
200
600
600
232
232
502
502
7
23
5 and swing
26-39
54
1100/980/900
870
3
1
400
1010
In0.23/out0.48
PH108X1C
220 VAC 50Hz
1.932
0.65
430
10
25
0.62
97
15
2.8
3.12
740
243
200
600
232
502
7
23
5 and swing
26-39
54
1100/980/900
870
3
1
470
10
2.2
0.91
430
15
25
0.775
97
19.8
3.4
in0.23/out0.48
PH135X1C-8DZD2
740
243
200
600
232
502
7
23
5 and swing
29-39
54
1100/980/900
870
3
1
645
10
0.82/0.72
in0.35/out0.86
KH145VHEA
5 and swing
1100/980/900 cooling)
950/870/800(heating)
2.2/2.4
0.91
430
15
20
97
18
3.9
2.7
740
243
200
600
232
502
7
23
29-39
54
870
3
1
680
6
Page 9
III. Specification
Installation & Maintenance Manual
Model
CSU-12HCAA
CSU-12HHAA
CSU-18HCAA
CSU-18HHAA
Performance data
Cooling-only
4.5
1.9
680
8.35
50
1.8
97
39
8.1
in0.28/out0.56
2.5
Capacities
Other
electrical
data
Functions
Power supply
Cooling capacity
Dehumidifying capacity
Air supply capacity
Power supply capacity
Running capacitor
Input power
Power factor
Stockstill current
Compressor motor current
Fan motor current
EER
m/h
kW
l/h
3
A
F
kW
%
A
A
A
Cooling-only
3.1
1.27
490
5.4
35
1.15
97
29.9
5.55
in0.28/out0.56
2.68
Cooling AND HEATING
220 VAC 50Hz
3.2/3.42
1.31
490
5.4/5.2
35
1.16/1.13
97
29.9
5.55
in0.23/out0.48
2.75/3.0
Winding resistance(at )
Compressor
Indoor fan motor
Outdoor fan motor
Dimensions
Weight
Other data
Model
Winding resistance(at )
Winding resistance(at )
Length
Indoor unit
Width
Heigth
Length
Outdoor unit
Width
Height
Indoor unit
Outdoor unit
Noise
Fan speed
Fan speed
stage
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Refrigerant R22
Thermister(at )
PH215X2C-8FTC
mm
mm
mm
mm
mm
mm
kg
kg
( )
dB A
( )
dB A
r/min
r/min
g
k
740
200
243
772
254
540
8
35
5 and swing
35-41
54
1100/980/900
780
3
1
780
10
PH215X2C-8FTC
740
200
243
772
254
540
8
35
5 and swing
35-41
54
1200/1120/1050 cooling)
1260/1160/1100(heating)
780
3
1
115 0
10
TH310VEEC
1015
320
200
772
254
540
14
35
5 and swing
35-46
55
1050/980/900
780
3
1
1020
10
1Test conditions
cooling indoor unit dry bulb 27 wet bulb19
outddor unit dry bulb 35 wet bulb 24
2The data should subject to the nameplate they are different from those on the nameplate.
Cooling AND HEATING
8.35/7.6
1.8/1.65
8.1
in0.23/out0.48
TH310VEEC
5 and swing
1050/980/900 cooling)
1050/1000/960(heating)
4.48/4.98
2.3
680
50
97
39
2.5/3.0
1015
320
200
772
254
540
14
35
35-46
55
780
3
1
1130
10
7
Page 10
III. Specification
Installation & Maintenance Manual
Model
CSU-21HCAA
CSU-21HHAA
CSU-24HCAA
CSU-24HHAA
Performance data
Functions
Power supply
kW
l/h
3
m/h
A
F
kW
%
A
A
A
Capacities
Other
electrical
data
Capacity
Dehumidifying capacity
Air supply capacity
Power supply capacity
Running capacitor
Input power
Power factor
Stockstill current
Compressor motor current
Fan motor current
EER
Winding resistance(at )
Compressor
Indoor fan motor
Outdoor fan motor
Dimensions
Weight
Other data
Model
Winding resistance(at )
Winding resistance(at )
Length
Indoor unit
Width
Heigth
Length
Outdoor unit
Width
Height
Indoor unit
Outdoor unit
Noise
Fan speed
Fan speed
stage
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Refrigerant R22
Thermister(at )
mm
mm
mm
mm
mm
mm
kg
kg
( )
dB A
( )
dB A
r/min
r/min
g
k
1Test conditions
cooling indoor unit dry bulb 27 wet bulb19
outddor unit dry bulb 35 wet bulb 24
2The data should subject to the nameplate they are different from those on the nameplate.
5.1
2.0
680
8.9
50
1.92
97
42
9.3
in0.22/out0.25
2.65
SHW33TC4-U
1015
320
200
850
290
610
14
47
5 and swing
46
59
1200/1120/1000
820
3
1
1300
1010
In0.23/out0.48
TH310VEEC
1260/1160/1100(heating)
220 VAC 50Hz
5.08/5.8
2.1
680
8.7/8.5
50
1.96/1.85
97
38/42
8.1
2.58/3.1
1015
320
200
850
290
610
14
47
5 and swing
46
59
1200/1120/1050
820
3
1
1300
10
5.98
2.45
730
11.5
35
2.4
97
52
11.5
In0.23/out0.48
SHV33YC6-G
1015
320
200
850
290
610
14
53
5 and swing
46
59
1280/1150/1050(cool)
910
3
1
1600
10
11.4/11.4
2.38/2.38
in0.35/out0.86
SHV33YC6-G
5 and swing
1280/1150/1050
5.94/6.63
2.43
730
50
97
52
11.5
2.48/2.8
1015
320
200
850
290
610
14
53
46
59
910
3
1
1600
8
Page 11
Installation & Maintenance Manual
IV. Wiring diagram
Wiring diagram for heat pump indoor unit 5K/7K/9K/12K
3502Q0027230
AC-L44
TERMINAL
AC-L33
3/ON
4/COM
CNO7
Cn22
AC-N
AC-L55
AC-N1
HEAT
CNO8/CNO9
PT
CNO2
RT
CNO1
CNO4
CLEAR
CNI2
Optional
Wiring diagram for heat pump outdoor unit 5K/7K/9K/12K
9
Page 12
Installation & Maintenance Manual
IV. Wiring diagram
Wiring diagram for heat pump indoor unit 18K/21K
VALVE
AC-L44
AC-L33
OUTFAN
CN-03
AC-N
CN08/CN09
3502Q0028679
Circuit principle diagram for outdoor unit 18K
3502Q0010653
Circuit principle diagram for outdoor unit 21K
3502Q0011916
BLK
S1
BLK
S2
10
Page 13
Installation & Maintenance Manual
IV. Wiring diagram
Wiring diagram for heat pump indoor unit 24K
VALVE
AC-L44
AC-L33
OUTFAN
CN-03
AC-L22
AC-L
AC-N
CN08/CN09
3502Q0028680
X1
X2
X3
RELAY
Wiring diagram for only cooling indoor unit 24K
AC-L22
AC-L
AC-N
CN08/CN09
RELAY
3502Q0028680
X1
X2
X3
11
Page 14
Installation & Maintenance Manual
IV. Wiring diagram
Wiring diagram for heat pump outdoor unit 24K
TO INDOOR UNIT
3502Q0027178
4-WAY VAVLE COIL
TO INDOOR UNIT
TEMP. THERMISTOR
Wiring diagram for only cooling outdoor unit 24K
3502Q0017666
12
Page 15
V. Refrigerating circuit
Indoor
unit
Installation & Maintenacne Manual
Maximum height difference 5m
(regardless either unit is higher)
Max. Lenth of extended fitting pipe
Outdoor unit
Refrigerant replenishment (R22:g):
No refrigerant replenishment is required if extended length of fitting pipe is less than 7m.
If extended length of fitting pipe is over 7m, replenishing volume of refrigerant should be
calculated as per the following formula: replenishing volume Xg=15g/mX(A-7)m
Refrigerating circuit for heat pump type
Indoor unitOutdoor unit
4-way valve
Indoor heat
exchanger
Room-temperature
thermistor RT11
Pipe-temperature
thermisto
Connecting pipe
(with heat-insulating
pipe casing)
Joint of flared pipe
Shutoff valve
(with access door)
exchanger
Outdoor heat
Joint of flared pipe
Connecting pipe
(with heat-insulating
pipe casing)
Shutoff valve
13
Check valve
Compressor
Flow direction of refrigerant
Flow direction of refrigerant
Capillary(cooling)
Capillary(heating)
for cooling
for heating
Page 16
V. Refrigerating circuit
Refrigerating circuit for only cooling type
Indoor unitOutdoor unit
Installation & Maintenance Manual
4-way valve
exchanger
Room-temperature
thermistor RT11
Indoor heat
Pipe-temperature
thermisto
Connecting pipe
(with heat-insulating
pipe casing)
Joint of flared pipe
Joint of flared pipe
Connecting pipe
(with heat-insulating
pipe casing)
Shutoff valve
(with access door)
Shutoff valve
Compressor
Flow direction of refrigerant
exchanger
Outdoor heat
Capillary (cooling)
Maxinmum length of fitting capillary pipe for heat pump unit
Outer diameter of fitting pipe:(mm)
Gas pipe
9.52
12.7
12.7
15.8
15.8
Liquid pipe
6.35
6.35
6.35
9.52
9.52
Capillary
(cooling)
3 1.4 850
3 1.6 650
4 2 900
4 2 800
42550
Model
9K
12K
18K
21K
24K
Max length
of extended
fitting pipe (m)
10
15
15
15
15
Max Height
difference
(m)
5
5
5
7
7
Max number
of bent pipes
10 spots
10 spots
10 spots
10 spots
10 spots
for cooling
Capillary
(heating)
3 1.6X450
3 1.6 350
4 2 650
4 2 600
4 2 250
Maxinmum length of fitting capillary pipe for only cooling unit
Max length
Model
5K
7K
9K
12K
18K
21K
24K
of extended
fitting pipe (m)
10
10
10
15
15
15
15
Max Height
difference
(m)
5
5
5
5
5
7
7
Max number
of bent pipes
10 spots
10 spots
10 spots
10 spots
10 spots
10 spots
10 spots
Outer diameter of fitting pipe:(mm)
Gas pipe
9.52
9.52
9.52
12.7
12.7
15.8
15.8
Liquid pipe
6.35
6.35
6.35
6.35
6.35
9.52
9.52
14
Capillary
(cooling)
3 1.4 1000
3 1.4X1000
3 1.4X1000
3 1.6 600
4 2 1000
42700
42500
Capillary
(heating)
Page 17
VI. Installation instructions
1. Installation diagram
1-1.5K/7K/9K/12K
Above 120mm
H
UA
LING
Above 70mm
B
Installation & Maintenance Manual
Above 195mm
Above 30mm
C
Be careful!
Do not let drain hose run up.
Fitting pipe of pipeline may be led out
from back side, right side, lower side,
left side or left rear side.
Back side
Right
Rear
Downwards
Left rear
Front side
Left
6
5
Above 100mm
Above 500mm
Enclosed attachments
1
Mounting plate
2
Tapping screw ST4*25
3
Expansion plug
4
Expansion bolt
5
Battery for remote controller
6
Remote controller
Connecting cable
7
Above 100mm
Above 350mm
D
Above 100mm
7
E
A
Qty
Unit
Piece
1
Pcs
5
Pieces
5
Pieces
2
Pcs
2
Piece
1
Piece
1
Connect the pipeline at two sides, and
insulation should be carried out respectively.
Aerated plastics with a thickness of
8mm for heat insulation
If the pipeline is to be installed upon a
wall equipped with steel sheet
(galvanized sheet) or metal net, plank
with a thickness of 20mm should be
positioned between the wall and the
pipeline, or the pipeline should be
wrapped with 7~8 layers of insulating
plastic tape.
Installation attachments
A
Connecting pipe
Bandage
B
C
Tensioning rope
D
Masonry nail
Drain hose
E
Putty
F
G
Sealing oil
Qty
2
1
3
5
1
1
1
Unit
Pieces
Piece
Pcs
Pcs
Piece
Box
Bottle
15
Page 18
VI. Installation instructions
1. Installation diagram
1-2.18K
Installation & Maintenance Manual
Above 105mm
1
234
Above 155mm
Be careful!
Do not let drain hose run up.
Above 24mm
HUALING
Fitting pipe of pipeline may be led out
from back side, right side, lower side,
left side or left rear side.
Back side
Right
C
Above 70mm
B
D
6
5
Rear
Downwards
Connect the pipeline at two sides, and
insulation should be carried out respectively.
Left rear
Front side
Left
Above 100mm
Above 500mm
Enclosed attachments
1
Mounting plate
2
Tapping screw ST4*25
3
Expansion plug
4
Expansion bolt
5
Battery for remote controller
6
Remote controller
Connecting cable
7
Above 100mm
Above
ove 100mm
Ab
7
A
350mm
Qty
1
5
5
2
2
1
1
E
Unit
Piece
Pcs
Pieces
Pieces
Pcs
Piece
Piece
Aerated plastics with a thickness of
8mm for heat insulation
If the pipeline is to be installed upon a
wall equipped with steel sheet
(galvanized sheet) or metal net, plank
with a thickness of 20mm should be
positioned between the wall and the
pipeline, or the pipeline should be
wrapped with 7~8 layers of insulating
plastic tape.
Installation attachments
A
Connecting pipe
Bandage
B
C
Tensioning rope
D
Masonry nail
Drain hose
E
Putty
F
G
Sealing oil
Qty
2
1
3
5
1
1
1
Unit
Pieces
Piece
Pcs
Pcs
Piece
Box
Bottle
16
Page 19
VI. Installation instructions
1. Installation diagram
1-3.21K/24K
Installation & Maintenance Manual
Above
234
175mm
1
Above
242mm
Be careful!
Do not let drain hose run up.
Above 60mm
HUA
LING
Fitting pipe of pipeline may be led out
from back side, right side, lower side,
left side or left rear side.
Back side
70mm
C
Above
HUALING
6
5
Above
100mm
Above
100mm
B
D
100mm
Above
Right
Rear
Downwards
Connect the pipeline at two sides, and
insulation should be carried out respectively.
Aerated plastics with a thickness of
8mm for heat insulation
Left rear
Front side
Left
500mm
Above
Enclosed attachments
1
Mounting plate
2
Tapping screw ST4*25
3
Expansion plug
4
Expansion bolt
5
Battery for remote controller
6
Remote controller
Connecting cable
7
Above
7
A
350mm
Qty
1
5
5
2
2
1
1
E
Unit
Piece
Pcs
Pieces
Pieces
Pcs
Piece
Piece
Installation attachments
A
Connecting pipe
Bandage
B
C
Tensioning rope
D
Masonry nail
Drain hose
E
Putty
F
G
Sealing oil
17
If the pipeline is to be installed upon a
wall equipped with steel sheet
(galvanized sheet) or metal net, plank
with a thickness of 20mm should be
positioned between the wall and the
pipeline, or the pipeline should be
wrapped with 7~8 layers of insulating
plastic tape.
Unit
Qty
Pieces
2
Piece
1
Pcs
3
Pcs
5
1
Piece
Box
1
Bottle
1
Page 20
Installation & Maintenance Manual
VI. Installation instructions
2.Safety Regulations
Please read safety instructions carefully before installation
All items listed here are extremely important safety instructions, which must be followed.
Legends and their meanings are listed as follows:
Warning
Users don't try to install by themselves
Improper installation may cause fire,
electric shock, loose of parts or water
leakage. Please contact a Hualing agent
for installation and maintenance.
Cover of electrical components on
indoor unit and maintenance board on
outdoor unit must be installed properly.
Improper installation of cover or panel
may cause fire or electric shock due to
dust or water.
Cables between indoor and outdoor
units must be properly connected by
specified cables and make sure that
joints properly fixed
If installed at a place without enough
strength, the unit may fall and hurt people
Installation must be made according
to installation instructions, the special
cables should be used
Inefficient capacity of the cable or
Improper installation may cause fire,
electric shock, loose of parts fall and
hurt people or water leakage.
The grounding is necessary
in construction
The ground wire must not be connected to
gas pipe, water pipe, lightning rod, telephone
ground wire. Improper connection of ground
wire may cause electric shock
Must not be installed at a place where
inflammable gas is leaking
If inflammable gas accumulated around
the unit, explosion may happen
Electrical components must be installed
according to instructions, and must use
specific electrical power supply
Insufficient electrical power capacity
or improper installation may cause fire
or electric shock.
The units must be installed at a place
where it can hold certain weight
If installed at a place without enough
strength, the unit may fall and hurt people
The attached or specified installation
accessories should be used in
installation
Improper accessory may cause fire, electric shock
or Fall unit and hurt people as well as water leakage
Don't crass to power cables in the
installation of electrical components,
don't use extension wire or octopuses
like wiring
Improper grounding or insulation may
cause fire or electric shock
After installation, make sure there is
no leakage of refrigerant
If the until is installed in a humid
environment, a switch for prevention
of electricity leakage must be installed
Without leakage prevention switch,
electric shock may happen
Drain hose and pipe must be installed
according to installation instructions
Improper installation of drain hose or pipe
may damage the unit or home furniture
18
Page 21
VI. Installation instructions
3.Installation of Unit:
3-1.How to select installing location:
3-1-1. How to select installing location for indoor unit
Air inlet/ air outlet should be far away from obstacles, ensuring that air flow must not be kept back;
Do not install the unit at a spot with direct sunshine;
Select a spot convenient for removal of condensed water and easy connection to outdoor unit;
The distance between the spot and TV set or acoustic equipment should be 1m at least;
Keep away from fluorescent lamps or incandescent lamps; (otherwise, it is possible that the wireless remote
controller cannot not be normally utilized to controlled)
Select a solid wall which can bear weight of machine body, free of increase of operating noises or vibration;
Maximum height difference between indoor unit and outdoor unit should be 5m.
3-1-2. How to select installing location for outdoor unit
The installing location can bear weight of machine body, free of strong vibration.
Select a spot with good ventilation, less dust, free of rainwater and direct sunshine
Select a spot from which the operating noise and exhausted hot air can not affect the neighbors;
There should be no obstacles around the outdoor unit, which keep back inlet air/outlet air for the unit;
Select a spot free of leakage of inflammable gases or erosive gases;
L1
L4
L2
L3
Model
5K/7K
09K
12K
18K
21K
24K
Dimension
Installation & Maintenance Manual
Unit: mm
L1
L2
368
600
600368278235
780500280250
780500280250
850500
850500310290
278
310
L4
L3
235
290
3-2.How to fix the mounting plate
Find a structural member of a wall (e.g. column etc.), and fix the mounting plate onto it horizontally.
5K/7K/9K/12K series
bove 120mm
A
(Away from
the wall)
Note:
Tie the rope at central hole
Mounting plate
Plumb bob
1. To avoid microshock of mounting plate, the hole pointed at by solid arrow must be secured.
2. If expansion bolt is adopted, it is required to adopt slotted holes 11*20or 11*26 with interval of over 450mm
to fix the mounting plate
Above 30mm
Above 195
(Away from
the wall)
Align the rope to the symbol
Tie the rope at central hole
175mm
Above
(Away from
the wall)
18K ,21K ,24K series
Mounting plate
Plumb bob
Above 60mm
242mm
Above
(Away from
the wall)
Align the rope to the symbol
19
Page 22
VI. Installation instructions
3-3.Drill holes on the wall
9K series12K series
180mm
Installation & Maintenance Manual
180mm
Mounting plate
10
Align the measuring rule to str aight line
18
Center of a hole with
diameter of 65mm
Align the measuring rule to str aight line
18K,21K,24K series
82mm99mm
10
Center of a hole with
diameter of 65mm
Insert the measuring
Align the measuring rule to str aight line
Indoor unit
3-4.How to install indoor unit
Outlet the pipeline through the wall hole,
and hoist the unit onto the mounting plate.
Bottom surface of indoor unit
Hang the rib into the hole in mounting plate.
3-5.How to connect wires for indoor/ outdoor units
Indoor unit Section:
8
Center of a hole with
diameter of 65mm
Mounting plate
Mounting plate
10
Center of a hole with
diameter of 65mm
18
Wire connection
Open the return air grille;
1
Remove screw for fixing electrical box cover, open (or remove) the electrical box cover;
2
remove fixing screws of clamping plate, and remove the clamping plate;
3
Properly connect the connecting cables, and tightly clamp the connecting cable by the removed clamping plate.
See the Figure as below:
Fixing screw
Connecting cable
(three core)
5K/7K/9K/12K series
Reassemble the electrical box cover, and close the return air grille.
Electrical box cover
Connecting terminal board
Fixing screw
Clamping plate
Ensure to insert the core
wire completely.
Clamping plate
Connecting cable
(four core)
18K,21K,24K series
Connecting terminal board
Electrical cover
Ensure to insert the core
wire completely.
20
Page 23
VI. Installation instructions
Installation & Maintenance Manual
Press plate
Power cord
Connecting cable
5K/7K/9K/12K BTU
Warning
1. It is required to adopt specified cable for wiring between indoor/outdoor units, ensuring that the connecting
terminals must be securely fixed, free of the direct influence of external forces. if it is improperly connected or
fixed, it is possible to cause a fire.
2. Indoor unit's cover of electrical box must be properly fixed. Otherwise, dust or water might cause a fire or
electrical shock.
3. The power cable for indoor unit of the air conditioner should be PVC-cased cord (cord 53# in IEC227) at least.
4. The power cable for outdoor unit of the air conditioner should be butadiene rubber cased cord
(cord 57# in IEC245) at least.
Power cord
Connecting cable
18K/21K/24K BTU
Press plate
21
Page 24
VI. Installation instructions
outdoor unit:
Installation & Maintenance Manual
outdoor connection
terminal board
cable connecting
indoor and outdoor units
3-6. Arrangement of refrigerant pipe and drain hose of indoor unit
3-6-1.Precautions:
Drain hose must be located below the coolant pipeline;
Do not hunch up or bend the drain hoses;
Do not pull at the drain hose to carry out wrapping operation;
If drain hose must pass through indoors, it must be wrapped
with heat-insulating material available in the market;
Use felt tape to wrap up fitting pipe and drain hose, and place
heat-insulation cushion upon the wall that contacts the aforesaid
two.
3-6-2. Direction of fitting pipe :
As shown in the Figure, part 1 of the case should be cut off if
fitting pipe is led out from right side; part 2 of the case should be
cut off if fitting pipe is led out from right lower side, part 3 of the
case should be cut off if fitting pipe is led out from left side.
3-6-3. Recondition of drain hose:
Drain hose
Liquid pipe
Felt tape
Gas pipe
Heat-insulation
cushion
If fitting pipe is led out from right or right lower side, it is
required to condition the drain hose, for fear of water leakage.
Drain plug
Drain hose
22
Page 25
Installation & Maintenance Manual
VI. Installation instructions
4. Completed connection of indoor and outdoor units and test run
4-1 flared joint
The flared joint is located on the indoor and outdoor sides.
Remove the valve cap of outdoor unit, and then connect the pipelines.
As shown in Figure below, coolant pipeline is used to connect indoor unit and
outdoor unit.
Connector
Indoor unit
Refrigerant pipeline
Model
5K/7K/9k
12k
18k
21k
24k
Liquid pipe
Gas pipe
Max length
of extended
fitting pipe (m)
10
15
15
15
15
Outdoor unit
Access door
Max Height
difference (m)
5
5
5
5
5
Max number
of bent pipes
10 spots
10 spots
10 spots
10 spots
10 spots
Outer diameter of fitting pipe:(mm)
Gas pipe
9.52
12.7
12.7
15.8
15.8
Refrigerant adjustment... If pipeline length is over 7m, auxiliary refrigerant (R22) is required.
(7m pipeline for outdoor unit is filled with refrigerant)
Pipeline length
Pipeline preparation
Maximum length 7m
Longer than 7m
Requiring no refrigerant replenishment
Requiring refrigerant
replenishment
50g/m
Liquid pipe
6.35
6.35
6.35
9.52
9.52
Fitting pipes of 3m or 4m are available.
Pipeline specifications listed in table below:
Pipeline
For liquid
Outer diameter
Mm
6.351/4
9.523/8
9.523/8
For gas
12.71/2
15.885/8
It is required to properly insulate the 2 pcs of refrigerant pipeline so as to avoid condensation.
Bending radius of refrigerant pipeline must be greater than 100mm.
Cautiously select the specified insulation thickness. Excessive thickness may disturb the cumulation
at back side of indoor unit while insufficient thickness may lead to condensed water dripping.
Inch
Insulation thickness
6mm
6mm
6mm
6mm
6mm
Precautions:
23
Insulating material
Specific gravity of insulating
plastic foam is 0.045
Page 26
Installation & Maintenance Manual
VI. Installation instructions
4-2 Flared pipe processing
Defect in flared pipe processing will be a major cause of gas leak. Please
carry out flared pipe processing properly according to the following method:
1
Cut off tube
Use pipe cutting machine to cut off copper tubes correctly.
2
Deburring
Completely remove the burr on cut-off section of the pipe.
To prevent burr from dropping into the pipe, the cut off
opening of pipe line should be positioned downwards
during deburring operation
3
Assemble the nut
Remove the conical nut attached to indoor and outdoor unit, and
then fix them inside the pipes free of burr.
(After flared processing of pipe, it is impossible to fix them inside it.)
4
Flared pipe processing
Copper pipe
Burr
Good
90
Declined cutoff opening
Reamer-type pipe cutter
Conical nut
Poor
Burr
Copper pipe
Carry flaring process by the tools listed below.
Outer diameter
6.35mm
9.52mm
12.7mm
15.88mm
5
Check
Compare the flared shape to the right Figure.
If visible defect exists in flaring process, just
cut off the processed section, and flare it
again.
A()mm
2.0--2.5
3.0--3.5
3.5--4.0
4.0--4.5
Tools for flaring process
Smooth periphery
Uniform peripheral length
24
Tongs
Smooth inner side free of scratch
Too much
Inclined
Conical nut
Flared surface
with scratch
Poor sample
Copper pipe
With cracks
York tongs
Uneven
Page 27
Installation & Maintenance Manual
VI. Installation instructions
4-3 Pipeline connection
Pipeline connection for indoor unit
Connect liquid/gas fitting pipes to indoor unit.
Apply a layer of sealing oil on surface of pipe saddle (put it inside
installation attachments) .
Firstly align it to the center and connect it, and then manually screw down
the conical nut for 3-4 turns.
Refer to the following moment table; use 2 pcs of spanners to fasten the
pipe joints at side of indoor unit.
Pipeline diameter
6.35mm(1/4")
9.52mm(3/8")
12.7mm(1/2")
15.88mm(5/8")
To rq u e (N M)
13.7--17.6
34.3--41.2
49.0--56.4
73.0--78.0
Pipe connection of outdoor unit
As per the same method for indoor unit, connect the fitting pipe to pipe joint.
of shutoff valve (2-way and 3-way valves) on outdoor unit.
Use torque -adjustable spanner or wrench to fasten it at same moment as that for indoor unit.
4-4 air purge Leak test
Air purge procedures
Connect the coolant pipeline (liquid and gas pipelines)
between indoor unit and outdoor unit.
Remove the access door cover of shutoff valve aside the gas pipeline of outdoor unit. (The shutoff valve
reserved in factory-leaving state cannot function, because it is still completely sealed by a cap).
Connect the gauge manifold valve and vacuum pump to the access
door of shutoff valve aside the gas pipeline of outdoor unit.
Rotate the vacuum pump (vacuumize it for 15 minutes at least).
Use gauge manifold valve to check the vacuum degree,
and close the gauge manifold valve, stop the vacuum pump.
Lay it aside for one two minutes, and then check if the pointer of gauge manifold valve still points
to the original position. Check if the pressure is -0.1mega pascal (-76cm mercury column).
Close
Open
Allen wrenchShutoff valve
Gauge manifold valve
Connecting pipeline
25
Shutoff valve
Liquid pipeline
Allen wrench
Gas pipeline
Cap
Shutoff valve
Access door
Vacuum pump
Page 28
VI. Installation instructions
Quickly remove gauge manifold valve from access door for shutoff valve.
Properly connect and evacuate the refrigerant pipeline, and fully open all shutoff
valves aside the gas and liquid pipeline. If it is not operated with fully opened shutoff
valves, performance of the unit may be degraded, resulting in troubles.
Installation & Maintenance Manual
Maximum pipeline
length of 7m,
requiring no aeration.
If pipeline length is
longer than 7m,
aerate it with amount of gas.
Screw down the access door cover to get the initial state.
And then screw down the cap.
Screwing-down torque
(N m)(Kgf cm)
Leak test
Access door cover
Valve rod cap of
shutoff valve
13.7 17.7
19.6 29.4
140 180
200 300
4-5 Insulation and bandage wrapping
Cover the fitting pipe sleeve by pipe cap;
All fitting pipes and valves of outdoor unit should be heat-insulated;
All fitting pipes from the fitting pipe entry of outdoor unit must be wrapped with pipeline bandage;
Fix the ends of pipeline bandage by tapes applied with adhesive;
if fitting pipe passes ceiling board, lavatory or other place with high temperature and humidity,
the thickness of heat-insulating material should be increased for fear of condensation.
4-6 Arrangement of drain pipeline
For easier drainage through drain pipeline, ensure that the drain pipeline should be
positioned in a declined mode (as shown in Figure 1).
Do not connect the drain pipeline in the same way as shown in Figure 2 - Figure 5.
Declined
(Figure 1)
Water leak
(Figure 2)
If the length of drain hose assembled on the indoor unit is too short for
operation, just connect the drain hose in the attachment box to it for
operation.
If the drain hose has to pass the indoor spaces, it must be wrapped with
heat-insulating material available in the market.
Upwards
Water leak
Drain retention
Air retention
inside pipeline
(Figure 3)
26
(Figure 4)
End of drain hose
dipping into water
Less than 50mm
above the floor
(Figure 5)
Drain hose
Hose (inner diameter
of 15cm) or hard PVC pipe
Air
Water leak
Page 29
Seal it with putty
VI. Installation instructions
4-7 Wall hole sealing and pipeline fixing
.Seal the wall hole with putty;
.Use straining rope to fix the pipeline at appointed position.
Installation & Maintenance Manual
Cut off the surplus section
Fix it by
straining rope
Indoor unit
Masonry nail
Straining rope
4-8 Test run
Note:
1. Before test run, it is required to check once again if there is any incorrect wire connection, and check if any leak
occurs in the pipe joint (by soap water).
2. It is possible to start up the unit by pressing emergency operation switch. Once the emergency operation switch
is pressed, the unit will begin continuous test run in cooling mode for 30 minutes. Within the 30 minutes, the
preset temperature does not work; after the 30 minutes, the unit will begin emergency operation in cooling
mode at a certain preset temperature (24 ).
Test run procedures:
1. Press the emergency operation switch for the first time, the air
conditioner begins emergency cooling operation; press the switch for
the second time, the air conditioner stops all operations.
2. Press the ON/OFF button on the remote controller, and check if the
indoor unit gives out a sound toot; if yes, it indicates that the
remote controller can function, and the emergency operation is
released. After that, press every button on the remote controller, and
check if operation modes of the unit vary respectively.
(Emergency operating mode of air conditioner can be displayed in the
operation indicator.)
Cooling
Shutdown
Mode
Power indicator
(On)
4-9 Explanations to the customers
In accordance with the operation instructions, show the customers relevant methods for temperature
adjustment, disassembling method for air filter, cleaning methods, installating and disassembling method
for remote controller, and precautions during operation.
Urge and demand the customers to read the operation instructions.
5. Displacing installation and maintenance after initial installation
5-1 How to fix the face plate
Before installation of front panel, please set vertical
vane at the position as shown on Figure 1.
Close the front panel and match the panel with the unit.
Gently press emergency switch on the front
panel and see if the emergency button is
properly matched with inside emergency switch
Fix screw and fix the front panel on the air-conditioner and
replace the screw cover.
Air guide
downward
slightly
Figure 1
27
Page 30
Installation & Maintenance Manual
VI. Installation instructions
5-2 Disassembly of indoor unit
Release the bottom edge of indoor unit from the mounting plate.
Use Allen wrench
As shown in Figure below, use Allen wrench to pull
downward the bottom edge of indoor unit, and then pull
out the unit slight so as to release the bottom buckles;.
Insert the Allen
wrench, and hook the end.
Allen wrench (4cm)
In case the method in left column cannot be taken
If the method cannot be taken, just remove the face plate.
As shown in Figure below, insert the allen wrench into
the left and right square openings; and then push the
allen wrench upward so as to descend the indoor unit,
Square opening
Push
5-3 Refrigerant replenishment
If connecting pipe length is over 7m, refrigerant replenishment is required.
Refrigerant replenishing volume for cooling/heating unit are listed as follow: A = 15g/m * (L-7) .
(A in the formula indicates the refrigerant replenishing volume in g; L indicates connecting pipe length in m)
Pipe length (m)
Refrigerant replenishing
volume for unit(g)
Downward
Note: maximum length of connecting pipe for models 25 Series must not be longer than 10m, and the maximum
length of connecting pipe for models 35/50/70 Series must not be longer than 15m.
Detailed operation steps are listed as follow:
Align and connect the gas bomb onto access door of gas valve;
Carry out the air purge for pipeline (or hose) from gas bomb of refrigerant;
Replenish refrigerant of specified volume for normal operation of the air conditioner.
Indoor unit
Operation valve of
gas bomb for coolant
Charging bottle
of coolant
Connecting pipe
Liquid pipe
Gas pipe
Charging hose
Shutoff valve
Outdoor unit
Access door
Note:
1. During charing operation, do not turn over the gas
bomb for refrigerant replenishing for fear of any
Spring balance
(R-22 liquid ) charging
problem;
2. To keep the high pressure in the gas bomb, please
heat it by warm water (40 ) in cold seasons. Do not
put it on fire, or heat it by hot steam.
28
Page 31
installation & Maintenance Manual
VII. Troubleshooting
1. Precautions for malfunction repair:
(1) Before repairing, check the power supply to see if it is normal, also check the
connection of indoor and outdoor units to see if there is any error in connection.
(2) Play attention to the following items during repair:
Before disassembling the front panel, unit box, top plate and control panel,
disconnect the power supply.
When moving the control panel, please hold its edges, don't press any components.
When disassembling and installing connecting cable, please hold the plug instead
of pulling the cable.
cable
Pay attention to the following items during fault handling
Check the operation pilot lamp on the indoor unit to see if it's flashing, and
confirm the fault indication by 2 or 3 times.
If the fault is in the control panel, check its components to see if components
burnout or turned colors, and check the connection terminal to see if the
connection is correct.
When a fault occurs, make check and repair according to "Troubleshooting
Flow Chart" and "Table for Fault Handling and Repairing".
Replace batteries for remote controller
Old batteries will affect normal operation, old batteries must be replaced.
After replacing, press the "reset" button on the back of the remote controller.
cable plug
reset button
Special attention:
Indoor unit may not receive signals from remote controller in room with
florescent light because periodically-connected high-voltage manostat
or blocking oscillator (electric rectifier) are used.
29
Page 32
VII. Troubleshooting
2.Troubleshooting Flow Chart
installation & Maintenance Manual
start
indoor unit operates
but outdoor unit
doesn`t operates
outdoor unit
is in test
running mode.
check room
temperature
thermistor
Outdoor unit
is not in test
running mode
see page 34 for
"inspection on
outdoor unit"
indoor unit cannot
receive signal from
remote control
see page 33 for
" inspection on
receiver circuit board"
Reasons: indoor unit
flash twice- faults of room temperature
thermistor and pipe temperature
thermistor Flash thrice- faults of
indoor fan motor
check room temperature
thermistor, see page
32 for "check point
and its voltage"
indoor unit operation
pilot lamp flashes
(see the fault problem
self-check table)
see page 32 for
"inspection of
indoor fan motor"
indoor unit cannot receive
signal from remote controller,
operation pilot lamp doesn`t
flash when pressing
emergency switch
See page 34 for "inspection
on electric control board
check pipe temperature
thermistor, see page 32
for "check point and its voltage"
30
Page 33
Installation & Maintenacne Manual
Maintenance
Check if thermistor is
out of work
--
the plug
Reconnect the plug
Check the indoor
circuit board
unplug the plug CN211,
verify if signal is over 1.5V
measure the section
between Cn121 , and
Check the indoor fan mot or
Check the indoor electrical
control board
Replug
ork
Check if the thermistor is
out of w
Reconnect the plug
Check the indoor circuit
board
Check to see whether
thermistor is ineffective.
Reconnect socket.
Check indoor circuit
board.
Verifying method
Symptom
Double 8 of LED display
Trouble display
During operation,
shortcircuit and open
circuit the indoor room
temperature thermistor
Outdoor unit
fails to run
E2
or 5
During operation,
for 2 seconds respectively.
When the indoor fan motor
runs for the 12 seconds, it is
impossible to emit feedback
signal of rotation speed.
Indoor fan motor
runs for 12
seconds and
stops for 3
minutes. Motor
is damaged,and
fan fails to run.
E6
thermistor for 2 seconds
the indoor pipe-temperature
shortcircuit and open circuit
Outdoor unitfails
to run
E1
After compressor is
started, defrost
Outdoor unit
doesn't
thermistor is connected
E5
or disconnected.
operate
Trouble source
9K/12K/18K
Before troubleshooting, ensure that the symptom reoccurs for precise judgement.
VII.Troubleshooting
3. Trouble selfchecking table
NO,
Flickers twice and ON f
seconds repeatedly
Room
temperature
thermistor
1
Flickers thrice and ON for
5 seconds repeatedly.
Indoor fan
motor
2
Flickers for four times and ON
for 5 seconds repeatedly.
Pipe-
temperature
thermistor
3
sting
Outdoor
defro
thermistor
4
Page 34
installation & Maintenance Manual
VII.Troubleshooting
4. Fault standards of main components
Name of
component
Room
temperature
thermistor
and pipe
temperature
thermistor
commpressor
indoor fan
motor
Test methods and standards
use instruments to measure the resistor (at 10-30 )
Normal
8K ~20K
short circuit or open circuit
Abnormal
use instruments to measure the resistor (winding temperature at 20
Normal
CSU-09HHAACSU-12HHAACSU-21HHAACSU-24HHAB
3.528
2.510
use instruments to measure the resistor between connecting terminals (winding
temperature at 10-30 )
2.0
4.61
1.04
2.860
0.885
1.773
Normal
12K 18K-21K
267 ~
295 ~
218 ~
~
24K
~138
87 ~107
whiteblack
black-
Power cable
red
5K-9K
267 ~
295 ~
Connect power, test voltage of cable
brown-yellow
yellow-gray
signal cable
Normal
~
fan turns once 0V 5V 0V
Abnormal
keep 0V
or 5V
Abnormal
short
circuit
or open
circuit
Abnormal
short
circuit
or open
circuit
Schematic
diagram
WHI
compressor
5K-21K:
WHI
RED
BLU
fan
motor
YLW
GRAY
BRN
24K:
WHT
BLK
BLU
F
a
n
m
o
YLW
t
r
o
RED
ORG
BLURED
Use instruments to measure the resistor between connecting terminals
(winding resistance at 10-40 )
outdoor
fan motor
5K-9K
315 ~385
(red-blue)
~308
(yellow-)blue
use instruments to measure the resistor (when at 10-30
stepper
motor
Normal
~
short circuit or open circuit
Normal
12K
~
18K-21K
76 ~93
24K
33 ~40
(red-blue)(red-blue)(red-blue)
~
81 ~
58 ~70
(yellow-)blue(yellow-)blue(yellow-)blue
Abnormal
Normal
350 ~400
Abnormal
short circuit or open circuit
32
Abnormal
short
circuit
or open
circuit
red
yellow
fan
motor
blue
Page 35
installation & Maintenance Manual
VII.Troubleshooting
A.Inspection of indoor fan motor (apply only to 9K/12K)
Trun off power, check socket CN211
no
connect wire
is the wire connected well
yes
Are the weld point all reght
yes
Re-weld
Pull out the wire from socket CN211 of indoor
circuit board, measure DCresistor value
between wire - and -
Resistance is 0V (short circuit)
or (open circuit)
yes 0 or
no
Replace indoor
electric board
Replace indoor fan motor
B. Inspection on the receiver circuit board
Indoor unit is able to operate when the emergency switch is pressed, but unable
to operate with remote controller.
check the model of
remote controller
is the LCD clear
yes
Take batteries out
and re-insert,
does the remote
controller work?
yes
no
no
Is there any counter-phase fast
-start fluorescent lamp within 1 meter ?
Replace batteries
Turn on a radio and switch to AM,
press remote controller button
Is there any noise in the radio
yes
no
no
Replace remote controller
yes
Keep indoor unit far away from
fluorescent lamp
Apply a filter on its receiving section
switch on the power, press on/off button on remote controller,
measure the voltage between NO.1 and NO.2 of the connector CN100(9K/12K) :on the control board;
(18K) : measure the voltage between NO.1 and NO.2 of the connector LD101T on the control board;
(24K): measure the voltage between NO.3 and NO.5 of the connector CN70 on the control board;
is the voltage close to 4V DC
no 5V or 0V
Replace receiver
33
yes
Replace indoor electric control board
Page 36
installation & Maintenance Manual
VII.Troubleshooting
C.inspection on indoor electric control board
indoor remoter controller doesn`t work, at the same time, the operation pilot lamp
is not lit when the emergency switch is pressed button
Replace fuse
Fault of electric
control board
Is the voltage
close to 220V
Carefully check the
components side
and the circuit of
electric control board
on indoor unit
YES
Is fuse F11 Fuse melt down
Is varistor NR11 burn out
NO
NO
1.switch on the power
2.measure voltage between
TAB2 and optional pole of
protector tube for 9K/12K
/ LN of the terminal board
for 18K/24K)
YES
NO
YES
Replace varistor
D. Inspection of outdoor unit
Compressor and outdoor fan don't operate (only indoor fan operates)
start
press emergency switch: (at
this moment,3 minute delay
mode starts, test running
time is 30 minutes)
measure voltage between 2
and N of outdoor unit
terminals bed to see if it is
220V
NO
measure voltage between 2
and N of indoor terminals to
see if it is 220V
YES
YES
check outdoor fan motor and compressor
check indoor and outdoor connection
wires to see if they are normal
Power fault
NO
replace indoor electric
control board
34
Page 37
installation & Maintenance Manual
HL25GVX002A
BUZ
R21
RT1
RT2
R20
CN112(PT)
R47
SW1
C33
C26
C27
J18
CN111(RT)
R31
R48
CN121
1
3
R23
IEC127fuseT5AL250V
UL-fuse 5A 250V
CN151
51
D6
C32A
J1
D7
D8
RB3
RA3
TR16
JPH
J17
RU3
RU4
JPM
1
R32
7
CN100
R14
R12
R44
R11
IC6
J16
R53
TR13
RU2
R54
R55
RU1
R52
JF1
JF2
C25
C24
J2
CST
IC2
C14
R49
D9
RB1
CLK
C31
J14
J15
A/B
J13
R13
RB2
RB4
R22
IC1
24
IC1
R51
R50
J10
8
TR10
DATE:2003-10-16
9012
TR15
TR14
+5V
J12
TR17
RA2
RA4
RA1
IC3
IEC127fuseT5AL250V
CAUTION: HIGH VOLTAGE !
X64
LD62(YLW)
X63
LD63(RED)
X62
UL-fuse 5A 250V
R62
C5
R63
C6
TAB2(BLU)
FUSE
NR11
CN211
LD65(BLU)
C7
R61
+
R40
52C/X10
TR11
J4
J3
R25
J6
J5
LD64(BRN)
TR12
R46
C32
R24
J8
C13
C28
D1
C30
R43
D4
D3
D2
R30
J7
R45
J9
C1
L102
C4
J19
IC8
TRAN
D10
C22
J11
R42
C23
R41
GND
D5
C12
+
C21
IC5
C11
+
C10
C20
IC4
R60
IC7
C3
R145
VII.Troubleshooting
E. Location of detecting points and their voltage
1.5K/7K/9K/12K series
DATE:2003-10-16
CN100
C27
C26
Pipe-temperature
thermistor
TR17
RA3
JPM
JPH
RU4
JF2
RU2
BUZ
RT2
RT1
J17
Emergency switch
HL25GVX002A
TR14
RU1
RB2
CST
IEC127fuseT5AL250V
C32A
Room temperature
thermistor
Indoor electrical control board
J7
LD64(BRN)
LD62(YLW)
LD63(RED)
52C/X10
CAUTION: HIGH VOLTAGE !
NR11
LD65(BLU)
FUSE
IEC127fuseT5AL250V
UL-fuse 5A 250V
C1
TAB2(BLU)
Characteristics of resistors RT11 and RT12
CN211
R60
Resistance value
K
Temperature
35
Page 38
installation & Maintenance Manual
-
+
DC12V
DC5V
+
-
VII.Troubleshooting
E. Location of detecting points and their voltage
3.18K/21K/24K series
DC12V
Stepping motor
Emergency switch
Indoor electrical control board
Room temperature thermistor
Pipe-temperature
thermistor
Remove frost
thermistor
36
Fuse AC250V/5A
Resistance value
Input power supply
AC220V/240V
Characteristics of resistors RT11 and RT12
Temperature
Page 39
VIII.Parts list
indoor unit
Installation & Maintenance Manual
13
12
11
10
9
8
3
No.
7
14
6
15
5
4
19
20
17
18
16
22
21
24
23
25
27
28
2
indoor unit
NameQuantityCodeRemark
Display board
Box for display board
Front panel
Air filter
Air filtert
Panel frame
Optional
1
37
Page 40
VIII.Parts list
Installation & Maintenance Manual
Number
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Designation
Evaporator
Bearing holderl
Cross flow fan ,assy
Air out frame
Drain hose
Chassis
Installation plate
Louver motor
Horizontal louverr
Fan motor
Fixing part for motor
Indoor temp. Sensor
Evaporator temp. Sensor
Wired controller
E- part box cover
Main control board
Tranformer
E-parts box
QtyCode
1
Remark
26
27
Wire clamp for power cord
Wire joint
38
Page 41
VIII.Parts list
18K/21K/24K indoor unit
Installation & Maintenance Manual
No.
7
8
9
10
11
12
13
14
15
NameQuantityCodeRemark
Display board
Box for display board
Front panel
Air filter
Air filtert
Panel frame
Evaporator
Bearing holderl
Cross flow fan ,assy
Air out frame
Drain hose
Chassis
Installation plate
Louver motor
Horizontal louverr
Optional
1
1
16
17
18
19
20
21
22
23
24
25
26
27
Fan motor
Fixing part for motor
Indoor temp. Sensor
Evaporator temp. Sensor
Wired controller
E- part box cover
Main control board
Tranformer
E-parts box
Wire clamp for power cord
Wire joint
39
Page 42
VIII.Parts list
5K,7K,9K, series outdoor unit
19
Installation & Maintenance Manual
3
4
5
6
7
8
9
2
40
Page 43
VIII.Parts list
5K/7K/9K series outdoor unit
Installation & Maintenance Manual
Number
1
2
3
4
5
6
7
8
9
10
11
12
Designation
Top plate
Right side plate
Heat exchanger
Motor mounting
Fan motor
Capacity of fan
Capacity of compressor
Terminal block
Return air pipe
Shutoff valve (liquid)
Shutoff valve (gas)
Rubber shock absorber
of compressor
Qty
CodeNote
MF
C1
TB
YDK-20AF-6
1.5 F/450V
30 F/450V
3
1/4F
3/8F
13
14
15
16
17
18
19
Compressor
Base
Maintenance panel
Foreplate
Outdoor grille
Axial flow fan
Capillary
MC
1
44R212AE-FJS
41
Page 44
VIII.Parts list
12K,18K series outdoor unit
20
Installation & Maintenance Manual
15
16
14
13
11
3
4
5
6
7
8
9
10
19
17
18
42
Page 45
VIII.Parts list
12K;18K series outdoor unit
Installation & Maintenance Manual
No.
NameQuantityCodeRemark
Toppanel
Roar plate
Fan capacitor
Compressor capacitor
Terminal board
Process pipe
Stop valve (liquid)
Stop valve (gas)
Upper cover of sound-proof pad
Compressor anti-vibration pad
Compressor
Base support
TB
1/2F
44R332AK-5ES
Heat exchanger
Motor support
Fan motor
Axial flow fan
Front panel
Outdoor grid
Handle
Capillary
YDK-45M-6
See (page 9) cooling loop
for detailed specification
indoor unit 746*245*196 746*245*196 746*245*196 940*270*180
Net
Dimension
outdoor
unit
700*225*500 700*225*500 795*255*540 795*255*540
model
CS-66H3-N**ASCS-88H3-Q**AT
indoor unit 1000*320*200 1225*330*245
Net
Dimension
outdoor
unit
870*310*700 900*330*835
2、Model explaining
c
Improve an ordinal number
Divide the body outdoors box a body code
External appearance characteristic code
Separately the body indoor machine(or whole type) style code
Code of refrigerant type:no code - R22;C-R407c、A-R410a
Power type:1:115v/60Hz 2:220V/60Hz;3:220-240V/
50Hz;4:240V/50Hz;
Main function code: c-Cold breeze type;H-Hot pump type;A-Hot
pump the type take assistance electricity to heat;E-The electricity
heat
Capacity code: x1000W
Separately the body pit code inside the indoor machine(or whole
type)
Structure form code
Special craft code:Q-Deal with contact quickly;S-Soft start;dOutside tube in addition to frost
The weather type code(T1 type code abridge)
"C" CHIGO brand
Model :CS-25C3A-V85AY1
T1 climate type,wall split type air conditioner, cooling capacity is 2500W,power is 220V~
/50Hz/1PH,refrigeration is R410A,the kernel of indoor unit is fresh 98,the pattern no . is 85,first
time design, outdoor unit is 1HP of 2003 year。
Indoor unit modle is:
CS-25C3A-V85A,outdoor unit model is:CS-25C3A-Y1。
Page 53
第 5 页 共 59 页
3. Attention of installation
3.1 Safety Precaution
■To prevent injury to the user or other people and property damage, the following instructions must be followed.
■
Incorrect operation due to ignoring instruction will cause harm or damage.
■Before service unit, be sure to read this service manual at first.
3.2 Warning
﹥Installation<
■Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
■For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized service center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
■Always ground the product.
There is risk of fire or electric shock.
■Install the panel and the cover of control box securely.
There is risk of fire of electric shock.
■Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fore or electric shock.
■Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
■Do not modify or extend the power cable.
There is risk of fire or electric shock.
■Do not install, remove, or reinstall the unit by yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
■Be caution when unpacking and installing the product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and
evaporator.
■For installation, always contact the dealer or an Authorized service center.
There is risk of fire, electric shock, explosion, or injury.
■Do not install the product on a defective installation stand.
It may cause injury, accident, or damage to the product.
■Be sure the installation area does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal
injury.
■Do not let the air cond itioner run for a long time when th e humidit y is very h igh and a door or a windows is
left open.
Moisture may condense and wet or damage furniture.
■Take care to ensure that power cable could not be pulled out or damaged during operation.
There is risk of fire or electric shock.
■ Do not place anything on the power cable.
There is risk of fire or electric shock.
■Do not plug or unplug the power supply plug during operation.
There is risk of fire or electric shock.
■Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
■Do not place a heater or other appliance near the power cable.
Page 54
第 6 页 共 59 页
There is risk of fire and electric shock.
■Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric shock.
■Do not store or use flammable gas or combustible near the product.
There is risk of fire or failure of product.
■ Do not use the product in a tightly closed space for a long time.
Oxygen deficiency could occur.
■When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on.
Do not use the telephone or turn switches on or off. There is risk of explosion or fire.
■If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the power
supply cable.
There is risk of electric shock or fire.
■Stop operation and close the window in storm or hurricane. If possible, remove the product from the window
before the hurricane arrives.
There is risk of property damage, failure of product, or electric shock.
■Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so
equipped.)
There is risk of physical injury, electric shock, or product failure.
■When the product is soaked (flooded or submerged), contact an Authorized service center.
There is risk of fire or electric shock.
■Be caution that water could not enter the product.
There is risk of fire, electric shock, or product damage.
■Ventilate the product from time to time when operating it together with a stove, etc.
There is risk of fire or electric shock.
■Turn the main power off when cleaning or maintaining the product.
There is risk of electric shock.
■When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
There is risk of product damage or failure, or unintended operation.
■Take care to ensure that nobody could step on or fall onto the outdoor unit.
This could result in personal injury and product damage.
﹥CAUTION<
■Always check for gas (refrigerant) leakage after installation or repair of
product.
Low refrigerant levels may cause failure of product.
■Install the drain hose to ensure that water is drained away properly.
A bad connection may cause water leakage.
■Keep level even when installing the product.
To avoid water leakage from vibration。
■Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
■Use two or more people to lift and transport the product.
Avoid personal injury.
■Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause
product malfunction or inefficient operation.
Page 55
第 7 页 共 59 页
>
Operation <
■Do not expose the skin directly to cool air for long periods of time. (Do not sit in
the draft).
This could harm to your health.
■ Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air
conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
■ Do not block the inlet or outlet of air flow.
It may cause product failure.
■Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
■ Do not touch the metal parts of the product when removing the air filter. They are very sharp.
There is risk of personal injury.
■ Do not step on pr put anything on the product. (outdoor units)
There is risk of personal injury and failure of product.
■Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
■Do not insert hands or other object through air inlet or outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
■ Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
■Use a firm stool or ladder when cleaning or maintaining the product.
Be careful and avoid personal injury.
■Replace the all batteries in the remote control with new ones of the same type. Do not mix old and mew batteries
or different types of batteries.
There is risk of fire or explosion.
■ Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
They may burn of explode.
■ If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the
remote of the batteries have leaked.
The chemical in batteries could cause burns or other health hazards.
3.3 Installation details
■ Wrench torque sheet for installation
Outside diameter Torque
mm inch Kg.m
φ6.35 1/4 1.8
φ9.52 3/8 4.2
φ12.7 1/2 5.5
φ15.88 5/8 6.6
φ19.05 3/4 6.6
Page 56
第 8 页 共 59 页
■Connecting the cables
The power cord of connect should be selected according to the following specifications
sheet.
Grade
Unit 7K 9K 12K 18K 24K 28K
mm2 1.0 1.0 1.5 2.5 2.5
2.5
■ Pipe length and the elevation
Standard
length
Max. Max.
Addition
al Capaci
ty
Pipe size
(m) Elevation Elevation
refrigera
nt
Btu/h GAS LIQUID B (m) A (m) (g/m)
9K-12K 3/8’’
(φ9.52)
1/4’’
(φ6.35)
3.5 5 10 30
18K-2
2K
1/2’’
(φ12.7)
1/4’’
(φ6.35)
4 10 15 30
24K-2
8K
5/8’’
(φ15.88)
3/8’’
(φ9.52)
5 15 20 65
Caution: Capacity is base on standard length and maximum allowance length is base
of reliability .Oil trap should be installed per 5-7 meters.
Page 57
第 9 页 共 59 页
Page 58
第 10 页 共 59 页
Selection of installation positions for outdoor unit
z To install the outdoor unit at the places which can stand the load of the machine weight and will
not cause big vibrations and noises;
z To install the unit at the places not to be exposed to rain or direct sunshine, and the places with
good ventilation;
z The noises generated from the unit will not affect the neighboring places;
z Do not install the unit on non-metal frame;
z Not to install the unit at the places where there might occur the generation, inflow, stay or
leakage of inflammable gases;
z Pay attention to the drainage of the condensed water from the base plate during operations;
z To avoid the air outlet being directly against the wind.
Detailed space requirements around the outdoor unit
Page 59
第 11 页 共 59 页
Page 60
第 12 页 共 59 页
Page 61
第 13 页 共 59 页
Page 62
第 14 页 共 59 页
Page 63
第 15 页 共 59 页
Page 64
第 16 页 共 59 页
Page 65
第 17 页 共 59 页
Page 66
第 18 页 共 59 页
Page 67
第 19 页 共 59 页
*Installation Guide*
4、
Indoor unit and outdoor unit explosion diagram and spare parts list
Page 68
第 20 页 共 59 页
CS-23H3-V77AY1A CS-25H3-V**AY1A CS-32H3-V**AH4 INDOOR UNIT
1 挂墙板 Wall-mounting frame 311010010
2 底 座 Base 391060109
3 贯流风轮 Cross flow fan 100010018
4 贯流风轮轴承 Fan Bearing ——
5 贯流风轮轴承胶圈 Ring of Bearing ——
6 室温探头架 Room temp. Sensor Holder 100280105
7 蒸发器组件 Evaporator Assy 080020092
8 蒸发器左端板 Evaporator left plate 391990164R
9 电加热器 Electric heater ——
10 出风主体 Outlet part 391800030
11 上导风条 Up Louver 391190050
12 下导风条 Down louver 391190051
13 左大连杆 A Left Connecting rod A 391200088
14 轴套 D Guide Louver Bearing D 391200096
15 步进电进左支架 Step motor left support 391200081
16 导风叶片(小)Swing louver 391200095
17
导风叶片右支架 Swing louver right
support
391200094
18
导风叶片中支架 Swing louver middle
support
391200093
19 导风叶片左支架 Swing louver left support 391200092
20 风口护网 Air outlet protect net ——
21 中框 Middle frame 391220062
22 螺钉盖 Screw cover 391990157
23 冷触媒 Cold Catalyst 119990011
24 左过滤网 Left Air filter 391120045
25 右过滤网 Right Air filter 391120046
26 面板 Front Panel 391220140
27 底座右镶块 Right angle plate 391990159
28 电机固定座 Motor holder 391990160
29 电机 Motor 320202014
30 电机护盖 Motor cover 391990161
31 电器盒 Electrical box 020150086
32 过线扣 Hook for the wire 391110013
33 压线板 Wire Clamp 391110013
34 电器盒内件 1 Electric box Panel 1 100430080
35 电器盒内件 2 Electric box Panel 2 100430081
36 指示灯架 display lamp frame 391110014
37 室温探头 Room Temp. Sensor
38 管温探头 Tube Temp. Sensor
331300306
Page 83
第 35 页共 59 页
39 电控板 Electric control plate
40 电源线 Power cord 050010076
41 端子台 Terminal Board 030090035
42 室外连接电缆线 Connecting cable
050020082
342300078
43 保温水管 Thermal insulation pipe 099990080
44 导风条轴套 391200085
45 左中连杆 Left middle Connecting rod 391200086
46 左大连杆 B Left Connecting rod B 391200090
47 右中连杆 Right middle Connecting rod 391200087
48 右大连杆 B Right Connecting rod B 391200091
49 右大连杆 A Right Connecting rod A 391200089
50 轴套连杆 391200084
51 步进电机右支架 Step motor right support 391200098
52 外风门步进电机 Step motor 320273013
53 轴套 A Guide Louver Bearing A 391200082
54 轴套 B Bearing B 391200083
55 压线扣 Wire Clip 391110015
56 挡水板 Water-resistant board 391990162
57 电器盒盖 Electric box cover 311020006
58 轴套 C bearing C 391200097
59 立体风左步进电机 320273015
60 立体风右步进电机 320273014
61 显示盒 Display box 391130019
62 显示灯板 Display lamp panel ——
63 遥控器 Remote controller 336815011
PART LIST (OUTDOOR UNIT)
序号
(Serial Number)
名称
(Part Name)
CS-23H3-V77AY1A CS-25H3-V77AY1A
1 前网罩 Front Grill 020120002 020120002R
2 前网扣 Grill Clip 109990256 109990256R
3 面 板 Front Panel 020070001 020070001R
4 小抽手 Small handle 100050001 100050001R
5 螺 母 Nut 150020019 150020019
6 垫 片 Gasket 150030016 150030016
7 轴流风轮 Axial flow fan 100030013 100030013
8 电 机 Motor 030020201 030020201
9 电机支架 Motor support 313040004 020040029
NOTE: Ts is the set temperature, Tr is indoor room temperature, TP1 is indoor coil pipe temperature, TP2 is
outdoor coil pipe temperature.
Display panel
Cooling
● Start up the compressor: when the room temperature is more than Ts+1℃, compressor → start-up
● Shut down the compressor: when the room temperature is less than or equal to the set temperature Ts-1℃,
compressor → shutdown
●When the temperature of coil pipe of the indoor units is less than or equal to 1℃ for one minute and the
compressor has continuous run for more than ten minutes, the compressor and outdoor blower fan shut
down through the electric control board and the indoor blower fan is running at low speed.
Page 93
第 45 页 共 59 页
●When the temperature of coil pipe of the indoor units is more than or equal to 7℃ and the compressor has
shutdown for more than three minutes, the compressor and outdoor blower fan start to run and the indoor
blower fan is running at set speed.
●When the temperature of coil pipe of the indoor units is equal to or less than -10℃ for three minutes in
the compressor has continuous run for three minutes, the compressor, indoor and outdoor blower fans and
swinging wind shut down. Restart up six minutes later; if the above situations appear again within six
minutes, all the outputs are shut down through the electric control board and display failure.
●When you press turbo button of remote, the air conditioner enter turbo running, compressor and outdoor
blower fan turn on all along, indoor blower fan run at high speed, turbo indication is light.
●After the compressor runs five minutes, the lamp flashes 4 times per six seconds or display E4 if the
temperature of indoor coil pips is more than 25℃ in the continuous 20 minutes. The controller will
automatically shut down if the temperature of indoor coil pips is more than 25℃ in another continuous 20
minutes, that is the abnormality protection of outdoor units and the indicator lamp keeps its former state of
flashing. If the temperature of indoor coil pips is less than 25℃ in the second 20 minutes or the compressor
shuts down, the electric control board will store to the normal display and the time is restarted when starting
up the compressor next time.
1° C
7° C
Tr
-10° C
compresso
r
outdoorblowerfan
door
blowerfan
Page 94
第 46 页 共 59 页
compresso
r
door
blowerfan
Tr
Heating (only applicable to heat pump units)
● Start up the compressor: when the room temperature is less than Ts-1℃, compressor → start-up
● Shut down the compressor: when the room temperature is more than or equal to the set temperature Ts+3℃,
compressor → shutdown
●The electric heating start-up in the heating mode shall meet the following conditions: ① start up the
compressor and indoor blower fan ② none defrost ③ TP1< 49℃ ④Tr ≤20℃.
●The electric heating shutdown in the heating mode shall meet one of the following conditions: ①
shutdown indoor blower fan ② Tr ≥ 23℃ ③ TP1≥50℃.
●In the heating mode, the indoor flower fan can be set as high/ medium/ low /automatic running mode by
remote control however the anti cool air function is prior. In the heating mode, the anti cool air control
function is to control shutdown of the indoor blower fan by detecting the temperature of coil pipe of
evaporator so as to attain the purpose of preventing cold air from blowing.
●For the waste heat emission function in the heating mode, in principle, the indoor blower fan shall be on for
fifteen seconds after the electric heating is closed.
●When the temperature of coil pipe of indoor units is more than or equal to 56℃, the outdoor blower fan
shuts down and it enters the overload protection; when the temperature of coil pipe of indoor units is less
than or equal to 52℃, the outdoor blower fan starts up and it exit the overload protection.
●When the temperature of coil pipe of indoor units rises to 63℃, the compressor and outdoor blower fan are
Page 95
第 47 页共 59 页
closed and two minutes later, the change valve is closed. The indoor blower fan is running at the set speed.
Restart up six minutes later; if the above situations appear again within ten minutes, all the outputs are shut
down through the electric control board and display failure.
●When you press turbo button of remote, the air conditioner enter turbo running, compressor ,outdoor blower
fan and four-way valve turn on all along, indoor blower fan run at high speed and it must meet start
condition, turbo indication is light.
●After the compressor runs five minutes, the lamp flashes 4 times per six seconds or display E4 if the
temperature of indoor coil pips is less than 30℃ (heating) in the continuous 20 minutes. The controller will
automatically shut down if the temperature of indoor coil pips is less than 30℃ in another continuous 20
minutes, that is the abnormality protection of outdoor units and the indicator lamp keeps its former state of
flashing.
+
3
-
1
COMPRESSOR
start-up
start-up
outdoor
blower fan
start-upstart-up
start-up
start-up
blowerfa
n
lower
speed
low
speed
low
speed
lower
speed
low
speed
start-up
2 MIN
2 MIN
start-up
start-up
over 6 MIN
four-way
valve
compresso
r
door
blowerfan
Tr
36
Page 96
第 48 页 共 59 页
Defrost (only applicable to the heating mode)
1. the intelligent defrost
In the heating mode, the electric control board checks and compares the temperature of indoor room and indoor
coil pipe after the compressor works for a while; judge whether the outdoor heat exchanger part is frosted or not
according to conditions such as the change of indoor coil pipe temperature; if it is judged as frosted, it automatically
enters defrosting process. When defrosting, close the indoor and outdoor blower fan and four-way valve.
2. Outdoor PCB for defrost.
In the heating mode, the unit defrost by outdoor control board:
unit start defrost shall① all meet the following conditions:
a、compressor continuous running over 7 minutes;
b、defrost relay shut off;(-5℃)
c、compressor cumulate running time over 50 minutes.; first defrost interval time is 50 minutes, later defrost interval time decided by last defrost time.②
(2)end defrost condition(meet one of follows)
a、defrost time have fifteen minutes.
b、defrost relay turn on;(>8℃)
c、press ON/OFF key in defrost process.
3. Outdoor sensor for defrost
unit start defrost shall meet one of the following conditions:
compressor cumulate running time over 30 minutes and it continuous running over 3 minutes, the temperature of
coil pipe of the outdoor units is equal to or less than -15 for one minutes (Tp2≤℃-15 ).℃
compressor cumulate running time over 40 minutes and it continuous running over 3 minutes, the temperature of
coil pipe of the outdoor units is equal to or less than -5 for one minutes (Tp2≤℃-15 ).℃
Air conditioner first power on or it wait over 30 minutes ,the temperature of coil pipe of the outdoor units is
equal to or less than -2 (Tp2≤℃-15 )℃
end defrost condition② (meet one of follows)
The temperature of coil pipe of the outdoor units is more than 15 (Tp2≥℃-15 ).℃
Defrost time has fifteen minutes.
Page 97
第 49 页 共 59 页
compresso
r
outdoorblowerfan
door
blowerfan
TP2
Tr
compresso
r
outdoor
blowerfan
door
blowerfan
TP2
Tr
Page 98
第 50 页 共 59 页
Tr
compresso
r
outdoorblowerfan
door
blowerfan
TP2
outdoorblowerfan
door
blowerfan
TP2
defrost time over 15 MIN or TP2 >15° C
Tr
compresso
r
■ Sequence chart in defrosting mode
Page 99
第 51 页 共 59 页
end defrost
start-up
shutdown
start-up
shutdown
start-up
start-up
start-up
shutdown
defrost
our-way
valve
door
blowerfa
n
start-up
start-up
start-up
start-up
shutdown
shutdown
outdoor
blower fan
compressor
start defrost
Dehumidification
Dehumidification running is to eliminate the water vapor in the air by using the cool circulating capacity, but the
dehumidification will not decrease the indoor temperature in great deal. The air conditioner automatically repeats
on and off circulation according the room temperature, which is shown in the following figure.
indoor
blower fan
°C
°C
door
blowerfa
n
Tr
shutdown
shutdown shutdownshutdownshutdown
shutdown
shutdownshutdownshutdownshutdown
low speed
Tr≤10℃
shutdown
start-up
start-up
start-up
start-upstart-up
start-up
start-up
start-up
forbid
dehumidify
●In the dehumidification mode, the indoor fan is running at the low speed for twenty seconds at first, then it
selects working mode.
Ventilation working mode
Page 100
第 52 页共 59 页
In the ventilation mode .When ventilating, the compressor, outdoor blower fan, four-way valve and electric
heating are all closed and the indoor blower fan is running at the set speed.
Automatic mode
●Conditions for entering the automatic running mode are: After power-up for the first time, start up and select
the automatic operating mode of remote or press emergency key, the working mode depends on Tr and if the
working mode had set , it doesn’t change by Tr and the default set temperature is 25 ℃.
Time on and time off
When the time on or time off is used, the clock of remote controller shall be corresponding to the current clock
and the timing times is less than or equal to 24 hours, when the timing time is reached, unit will start-up or
shutdown.
Sleep function
When the sleep key is press, air conditioner enter sleep state, indoor blower fan running at low speed, only sleep
indication display.
Emergency key function
There is a forcible execution key on the panel of indoor units and the air conditioner can run by pressing the key
when the remote control is out of work or missing.
When pressing down the forcible execution key, then power up and enter the self-check program.
Failure display
LED lamp display
code explain code explain
failure The reason of fault and solution
DF
display at
on state
flicker 1/1
SEC
defrost
indication
Normal, the defrost state is removed, it will
return to normal condition automatically
display at
off state
flicker 1/3
SEC
anti cold wind
1、 Normal (during heating mode )
2、It will be removed when the coil pipe
temperature sensor reaches certain
temperature.
E2
display at
off state
flicker 1/1
SEC
display
at on/off
state
room temp.
sensor fault
1、Check whether the resistance of the
sensor is normal (the resistance is 5КΩ in
the normal temperature 25℃), when it is
abnormal the sensor should be replaced.
2、Check whether there is short circuit or
open circuit in the wire of the sensor, and
whether the plug is connected well,
whether there is welding off or rosin joint
on the electric control board, if there is
any, it should be repaired.
3、When the 1 and 2 are both normal, then
the components or integrated circuit is
damaged, the electric control board
should be replaced.
E3
display at
off state
flicker 3/5
SEC
display
at on/off
coil temp.
sensor fault
1 、 Check whether the resistance of the
sensor is normal (the resistance is 5КΩ in
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.