Midea MSG-09HRIN2, MSG-12HRIN2, MSG-09HRI, MSG-12HRI, MSG-21HRI Service Manual

...
Content
1
MSC-18HRIN1; MSH-18HRIN1(AAC-18ISCH) MSE-09HRIN2; MSE-12HRIN2 MSG-07CRIN2; MSG-09HRIN2 MSG-12HRIN2; MSG-09HRI ;MSG-12HRI MSG-21HRI ; MSG-24HRI
Content
2
Content
1. Precaution .......................................................................................................................... 1
1.1 Safety Precaution .............................................................................................................................. 1
1.2 Warning ............................................................................................................................................. 1
2. Function.............................................................................................................................. 3
3. Dimension........................................................................................................................... 5
3.1 Indoor unitAlfa............................................................................................................................ 5
3.2 Outdoor unitAlfa.......................................................................................................................... 5
3.3 Indoor unitCorona....................................................................................................................... 6
3.4 Outdoor unitCorona.................................................................................................................... 6
3.5 Indoor unit(Inverter Eco) .................................................................................................................... 7
3.6 Outdoor unit(Inverter Eco) ................................................................................................................. 7
3.7 Indoor unit(Inverter Star).................................................................................................................... 8
3.8 Outdoor unit(Inverter Star) ................................................................................................................. 8
4. Specification....................................................................................................................... 9
5. Refrigerant cycle diagram............................................................................................... 12
6. Operation limits................................................................................................................13
6.1 Cooling operation............................................................................................................................. 13
6.2 Heating operation ............................................................................................................................ 13
7. Schematic diagram and Wiring diagram........................................................................ 14
7.1. Schematic diagram .......................................................................................................................... 14
7.2. Wiring diagram ................................................................................................................................ 18
8. Installation details............................................................................................................23
8.1 Wrench torque sheet for installation ................................................................................................ 23
8.2 Connecting the cables ..................................................................................................................... 23
8.3 Pipe length and the elevation .......................................................................................................... 23
8.4 Air purging of the piping and indoor unit .......................................................................................... 24
8.5 Pumping down (Re-installation) ....................................................................................................... 25
8.6 Re-air purging (Re-installation) ........................................................................................................ 26
8.7 Balance refrigerant of the 2-way, 3-way valves................................................................................ 27
8.8 Evacuation ....................................................................................................................................... 28
8.9 Gas charging ................................................................................................................................... 29
9. Pressure table ..................................................................................................................30
9.1 MSH-18HRIN1................................................................................................................................. 30
9.2 MSC-18HRIN1................................................................................................................................. 30
10. Capacity table................................................................................................................... 31
10.1 MSH-18HRIN1................................................................................................................................. 31
10.2 MSC-18HRIN1................................................................................................................................. 32
10.3 MSG-09HRI ..................................................................................................................................... 33
10.4 MSG-12HRI ..................................................................................................................................... 33
10.5 MSG-21HRI ..................................................................................................................................... 34
10.6 MSG-24HRI ..................................................................................................................................... 34
Content
3
11. Electronic function........................................................................................................... 35
11.1. Display board................................................................................................................................... 35
11.2. Protection ........................................................................................................................................ 35
11.3. Fan-only mode................................................................................................................................. 35
11.4. Cooling mode .................................................................................................................................. 35
11.5. Dehumidifying mode ........................................................................................................................ 36
11.6. Heating mode .................................................................................................................................. 36
11.7. Defrosting operation (Available for heating only). ............................................................................ 38
11.8. Outdoor low temperature protection (optional) ................................................................................ 38
11.9. Automatic operation mode............................................................................................................... 38
11.10. Manual switch.................................................................................................................................. 39
11.11. Timer Function................................................................................................................................. 39
11.12. Sleep mode ..................................................................................................................................... 39
11.13. Auto restart function......................................................................................................................... 39
11.14. Turbo function.................................................................................................................................. 39
11.15. Plasma............................................................................................................................................. 39
12. Model and Parameters..................................................................................................... 40
13. Troubleshooting............................................................................................................... 42
13.1 Indoor Unit Error Display ................................................................................................................. 42
13.2 Diagnostic chart............................................................................................................................... 47
13.3 Resetting phenomenon often occurs during operation .................................................................... 48
13.4 Operation lamp flashes and Timer lamp off ..................................................................................... 48
13.5 Operation lamp flashes and Timer lamp on ..................................................................................... 48
13.6 Operation lamp off and Timer lamp flashes ..................................................................................... 49
13.7 Operation lamp on and Timer lamp flashes ..................................................................................... 49
13.8 Operation lamp flashes, Timer lamp flashes.................................................................................... 49
14 Characteristic of temperature sensor ............................................................................ 50
Service manual
1
1. Precaution
1.1 Safety Precaution
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. Before service unit, be sure to read this service manual at first.
1.2 Warning
¾ Installation
Do not use a defective or underrated circuit breaker.
Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a
qualified electrician, or an Authorized service center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
Always ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of control box
securely.
There is risk of fire of electric shock.
Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fore or electric shock.
Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
Do not modify or extend the power cable.
There is risk of fire or electric shock.
Do not install, remove, or reinstall the unit by
yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
Be caution when unpacking and installing the
product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an
Authorized service center.
There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation
stand.
It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate
with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time
when the humidity is very high and a door or a windows is left open.
Moisture may condense and wet or damage furniture.
Take care to ensure that power cable could not be
pulled out or damaged during operation.
There is risk of fire or electric shock.
Do not place anything on the power cable.
There is risk of fire or electric shock.
Do not plug or unplug the power supply plug during
operation.
There is risk of fire or electric shock.
Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
Do not place a heater or other appliance near the
power cable.
There is risk of fire and electric shock.
Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric shock.
Do not store or use flammable gas or combustible
near the product.
There is risk of fire or failure of product.
Do not use the product in a tightly closed space for a
long time.
Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas and
open a window for ventilation before turn the product on.
Do not use the telephone or turn switches on or off. There is risk of explosion or fire.
If strange sounds, or small or smoke comes from
product. Turn the breaker off or disconnect the power supply cable.
There is risk of electric shock or fire.
Stop operation and close the window in storm or
hurricane. If possible, remove the product from the window before the hurricane arrives.
There is risk of property damage, failure of product, or electric shock.
Do not open the inlet grill of the product during
operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
There is risk of physical injury, electric shock, or product failure.
When the product is soaked (flooded or submerged),
contact an Authorized service center.
There is risk of fire or electric shock.
Be caution that water could not enter the product.
There is risk of fire, electric shock, or product damage.
Ventilate the product from time to time when
operating it together with a stove, etc.
There is risk of fire or electric shock.
Turn the main power off when cleaning or
maintaining the product.
Service manual
2
There is risk of electric shock.
When the product is not be used for a long time,
disconnect the power supply plug or turn off the breaker.
There is risk of product damage or failure, or unintended operation.
Take care to ensure that nobody could step on or fall
onto the outdoor unit.
This could result in personal injury and product damage.
¾ CAUTION
Always check for gas (refrigerant) leakage after
installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained
away properly.
A bad connection may cause water leakage.
Keep level even when installing the product.
To avoid vibration of water leakage.
Do not install the product where the noise or hot air
from the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the
product.
Avoid personal injury.
Do not install the product where it will be exposed to
sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
¾ Operational
Do not expose the skin directly to cool air for long
periods of time. (Do not sit in the draft).
This could harm to your health.
Do not use the product for special purposes, such
as preserving foods, works of art, etc. It is a
consumer air conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
It may cause product failure.
Use a soft cloth to clean. Do not use harsh
detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when
removing the air filter. They are very sharp.
There is risk of personal injury.
Do not step on pr put anything on the product.
(outdoor units)
There is risk of personal injury and failure of product.
Always insert the filter securely. Clean the filter
every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other object through air inlet
or outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
Use a firm stool or ladder when cleaning or
maintaining the product.
Be careful and avoid personal injury.
Replace the all batteries in the remote control with
new ones of the same type. Do not mix old and mew batteries or different types of batteries.
There is risk of fire or explosion.
Do not recharge or disassemble the batteries. Do not
dispose of batteries in a fire.
They may burn of explode.
If the liquid from the batteries gets onto your skin or
clothes, wash it well with clean water. Do not use the remote of the batteries have leaked.
The chemical in batteries could cause burns or other health hazards.
Service manual
3
2. Function
Indoor unit
Operation ON/OFF by remote controller
Room temperature sensor. Pipe temperature sensor.
Sensing by room temperature
Maintain the room temperature in accordance with the setting temperature.
Room temperature control
Prevent the water being freezed on evaporator by sensing the evaporator pipe temperature in cooling mode
Anti-freezing control in cooling
Restarting is for approx. 3 minutes..
Time Delay Safety control
Turbo wind, high, med, low, breeze.
Indoor fan speed control
The unit will decide the louver direction according to operation mode.
Two-direction air vane
The fan is turn to low speed (cooling/heating). The unit will be turn off at the seventh hour.
Sleep mode auto control
The function is usually used in rainy days in springtime or damp areas.
Independent dehumidification
The louver can be set at the desired position or swing up and down automatically
Air flow Direction control
The mode can be change by the room temperature.
Auto mode
DSP High-speed Chip
Flexible wiring connection
Auto defrost
Temp. Compensation
The function will be operated in any operation mode.
Plasma (Optional)
Prevent the cold wind at the beginning of unit start.
Anti-cold function
Self-diag. function
Auto-restart function
When the power supply is interrupted and then restore, the air conditioners automatically restore the previous function setting.
Tele Remote control (Optional)
Driving heating at -15
High efficiency (30%)
Work voltage (160v-253v)
Service manual
4
The unit has 3 mins delay between continuously ON/OFF operations.
Outdoor unit
Power relay control
The hydrophilic fin can improve the heating efficiency at operation mode.
Hydrophilic aluminum fin
It is only operated in the heating operation mode except defrosting operation.
Anti-rust cabinet
Valve protection cover
4 way valve control
Made from electrolytic zinc steel sheet and anti-rust coated components.
It protects the valves and prevents water from dripping.
Low noise air flow system
Bird tail propeller fan makes the outdoor unit run more quietly.
Discharge pipe temperature protect
Service manual
5
3. Dimension
3.1 Indoor unitAlfa
3.2 Outdoor unitAlfa
Dimension
Mode
W H D
12K 815 280 215
Dimension
Mode
W H D
12K 760 590 285
Service manual
6
3.3 Indoor unitCorona
3.4 Outdoor unitCorona
Dimension
Mode
W H D
18K 920 292 225
Dimension
Mode
W H D L1 L2 L3
18K 845 695 335 560 360 560
Service manual
7
3.5 Indoor unit(Inverter Eco)
3.6 Outdoor unit(Inverter Eco)
Dimension
Mode
W H D
7K 750 250 188
9K 750 250 188
12K 815 280 195
Dimension
Mode
W H D
7K 780 540 250
9K 780 540 250
12K 780 540 250
Service manual
8
3.7 Indoor unit(Inverter Star)
3.8 Outdoor unit(Inverter Star)
Dimension
Mode
W H D
7K 750 250 205
9K 750 250 205
12K 815 280 215
Dimension
Mode
W H D
7K 760 590 285
9K 760 590 285
12K 760 590 285
Service manual
9
4. Specification
Ac AlfaAc Corona
Model MSH-18HRIN1 MSC-18HRIN1 MSE-09HRIN2 MSE-12HRIN2
Power supply Ph-V-Hz 1, 220-240V~, 50Hz 1, 220-240V~,50Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz
Capacity Btu/h 18000 18000 9000 12000
Input W 1670 1720 1100 1400
Rated current
A
9.0 7.5 5.1 6.4
Cooling
EER Btu/w.h 10.8 10.5, 8.2 8.6
Capacity Btu/h 20000 19000 12000 15000
Input W 1830 1790 1400 1700
Rated current
A
9.9 7.7 6.3 7.5
Heating
COP W/W 3.2 3.11 8.6 8.8
Max. current
A
15.5 18 12 18
Starting current
A
9.0 9.0
Model BA160X2CS-20KU BA160X2CS-20KU BG130X1C-20FZ BG130X1C-20FZ
Type Rotary Rotary Rotary Inverter Rotary Inverter
Brand TOSHIBA TOSHIBA TOSHIBA TOSHIBA
Capacity Btu/h 16140 16140 9468 9468
Input W 1630 1630 890 890
Rated current(RLA)
A
10.95 10.95 5.7 5.7
Locked rotor Amp(LRA) A 55 55
Thermal protector CS-74 CS-74 CS-74 CS-74
Capacitor uF No No No No
Compressor
Refrigerant oil ml 750 750 370 370
Model RPG28C RPG28C RPG13H RPG13D
Brand Welling Welling Welling Welling
Input W 45 55 39.5 44
Capacitor uF 1.5 1.5 1.2 1.5
Indoor \fan motor
Speed(hi/mi/lo) r/min 1200/1150/1000 1140/1060/980 1250/1100/850 1180/1000/850
Indoor air flow (Hi/Mi/Lo) m3/h 800/700/600 800/700/600 520/460/410 580/500/420
Indoor noise level (Hi/Mi/Lo) dB(A) 44/40/37 44/40/37 40/38/35 40/38/35
Model YDK53-6K YDK53-6C YDK24-6F YDK25-6-3
Brand Welling Welling Welling Welling
Input W 130 125 56 75
Capacitor uF 3.0 3.0 2.5 2.0
Outdoor fan motor
Speed r/min 750 800 800 900
Outdoor air flow m3/h 2500 2500 1600 1700
Outdoor noise level dB(A) 58 58 58 58
Refrigerant type R410A g 1650 1770 840 1200
Liquid side/ Gas side mm Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф9.53 Ф6.35/Ф12.7
Max. pipe length m 10 15 10 10
Refrigerant piping
Max. in level m 5 8 5 5
Operation temp 17-30 17-30 17-30 17-30
Ambient temp -15-43 -15-43 -15-50 -15-50
Application area m2 28-45 28-45
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are normally
somewhat different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product improvement.
Service manual
10
Inverter Eco
Model MSG-07HRIN2 MSG-09HRIN2 MSG-12HRIN2
Power supply Ph-V-Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz
1, 220-240V~,
50Hz
Capacity Btu/h 7000 9000 12000
Input W 780 990 1340
Rated current
A
4.8 4.5 5.8
Cooling
EER Btu/w.h 9.0 9.0 9.0
Capacity Btu/h 9000 12000 15000
Input W 940 1240 1560
Heating
Rated current
A
4.4 5.5 6.8
Model BG130X1C-20FZ BG130X1C-20FZ BG130X1C-20FZ
Type Rotary Inverter Rotary Inverter Rotary Inverter
Brand TOSHIBA TOSHIBA TOSHIBA
Refrigeran Type POE POE POE
Capacitor uF No No No
Compressor
Refrigerant oil ml 370 370 370
Model RPG13H RPG13H RPG13C Brand Welling Welling Welling
Capacitor uF 1.2 1.2 1.5
Indoor fan
motor
Speed(hi/mi/lo) r/min 1050/950/750 1100/1000/800 1060/900/800
Indoor air flow (Hi/Mi/Lo) m3/h 500/410/320 520/430/330 560/460/380
Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/26 36/32/26 36/32/26
Model YDK23-6-3 YDK23-6-3 YDK23-6-3 Brand Welling Welling Welling
Outdoor fan
motor
Capacitor uF 2.5 2.5 2.5
Outdoor noise level dB(A) 51 51 53
Refrigerant type R407C g 800 800 1150
Liquid side/ Gas side mm Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф12.7
Max. pipe length m 10 10 10
Refrigerant
piping
Max. in level m 5 5 5
Operation temp 17-30 17-30 17-30
Ambient temp -15-45 -15-45 -15-43
Application area m2 14-18 18-24 20-30
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are normally
somewhat different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product improvement.
Service manual
11
Inverter star
Model MSG-09HRI MSG-12HRI MSG-21HRI MSG-24HRI
Power supply Ph-V-Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz
1, 220-240V~,
50Hz
1, 220-240V~, 50Hz
Capacity Btu/h 9000 12000 21000 24000
Input W 1080 1380 2450 2700
Rated current
A
6.0 7.4 12.0 13.2
Cooling
EER Btu/w.h 8.3 8.7 8.6 8.9
Capacity Btu/h 12000 15000 28000 30000
Input W 1350 17900 2800 3030
Rated current
A
7.2 10.5 14.0 15.1
Heating
COP W/W 2.6 2.5 2.9 2.9
Model 2PV132N7BC02 2PV132N7BC02 BH240X2CS-20KU BH240X2CS-20KU
Type Rotary Rotary Rotary Rotary
Brand GD Matsushita GD Matsushita MIDEA TOSHIBA MIDEA TOSHIBA
Capacity Btu/h 9500 9500
Input W 855 855
Rated current(RLA) A 5.1 5.1
Thermal protector CS-7LN120 CS-7LN120
Capacitor uF No No No No
Compressor
Refrigerant oil ml 450 450 750 750
Model RPG13H RPG20A YDK36-4G YDK36-4G
Brand Welling Welling Welling Welling
Input W 36.5 35 70 70
Capacitor uF 1.2 1.0 3.0 3.0
Indoor
fan motor
Speed(hi/mi/lo) r/min 1100/1020/950 1060/900/800 1150/1050/950 1150/1050/950
Indoor air flow (Hi/Mi/Lo) m3/h 500/430/330 540/460/380 1150/1050/950 1150/1050/950
Indoor noise level (Hi/Mi/Lo) dB(A) 36/32/26 38/34/28 45/42/39 45/42/39
Model YDK20-6G YDK25-6-3 YDK53-6K YDK53-6K
Brand Welling Welling Welling Welling
Input W 70 75
Capacitor uF 2.5 2 2.5 2.5
Outdoor fan
motor
Speed r/min 800 890
Outdoor noise level dB(A) 50 53 55 55
Refrigerant type R22A g 870 1120 1820 1820
Liquid side/ Gas side mm Ф6.35/Ф9.53 φ6.35/φ12.7 Ф6.35/Ф16 Ф6.35/Ф16
Max. pipe length m 10 10 20 20
Refrigerant
piping
Max. in level m 5 5 10 10
Operation temp 17-30 17-30 17-30 17-30
Ambient temp -15-45 -15-45 -15-43 -15-43
Application area m2 18-24 20-30 35-50 40-56
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are normally
somewhat different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product improvement.
Service manual
12
5. Refrigerant cycle diagram
Service manual
13
6. Operation limits
6.1 Cooling operation
Outdoor unit air temp. DB
Indoor air temp. DB Note: The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage.
6.2 Heating operation
Indoor air temp. ℃ DB
Outdoor unit air temp. DB Note: The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage.