Middleby Marshall Oven User Manual

Page 1
SECTION 2
INSTALLATION
Your Middleby Marshall Ovens are shipped partially assembled. Each oven section will arrive in its own crate of the following size and weight:
PS360U/PS360L PS360WB-U/PS360WB-L
Length: 72 (183cm) 66 (167cm) Width: 48 (122cm) 57 (144cm) Height: 60 (152cm) 50 (127cm) Weight: 1675 lbs. (760kg) 1750 lbs. (780kg)
If you ordered stands for your ovens, they are shipped in separate crates.
When your common carrier or truck line notifies you of delivery, you must have a forklift at the facility to unload the crate(s).
If you have a door that is wider than the ovens, simply move the ovens into your facility and set up an appointment with your Middleby Marshall Authorized Installer.
SECTION 2
INSTALLATION
NOTE: The width of each oven can be reduced by about 1" (25mm) by removing the window from the oven. Window disassembly instructions are in the Cleaning section of this Owners Manual.
If the ovens are wider than your door opening, the oven will have to be dismantled according to the directions in the Pre­Installation Procedures Manual.
NOTE
There must be adequate clearance
between the oven and combustible con-
struction. Clearance must also be pro-
vided for servicing and for
operation.
WARNING
Do not obstruct the flow of combustion
and ventilation air to and from your
oven. There must be no obstructions
around or underneath the oven.
WARNING
This oven must be installed in accordance
with the rules in force. Use only in a
well ventilated area. Read the
instructions before use.
2-1
Page 2
SECTION 2 INSTALLATION
II. INSTALLATION, PREPARATION, AND
SUPPLY
When preparing the oven for installation at a location, the latest International, National or Local Requirements should be adhered to.
The ovens must be installed on an even (level) non-flammable flooring and any adjacent walls must be non-flammable. The minimum allowed distance from the rear of the oven to the wall is 12 (30cm).
The ovens can be supported only by legs. No casters are allowed. It should be made certain that there are no obstructions located around or underneath the oven that interfere with air circulation.
The ovens must be installed under a ventilating hood with electrical exhaust air sensing control.
The gas supply connection should be according to applicable ISO-228-1 or ISO-7-1 recommendations.
Normally, the oven is preparted and adjusted to the specific gas type used by the customer. Before operating the oven, check the label on the oven and also on the packaging that the gas type indicated matches the local supply at the installation. If not, refer to Section VI, PREPARATION FOR VARIOUS GASES, in this chapter and convert as directed.
18"
458mm
All installations, conversions and service work must be performed by an Authorized Service Agent according to the instructions supplied by the manufacturer.
When converting from one gas type to a different type, the orifices supplied with the conversion kit must be checked for proper size as specified in this manual to assure that the oven is operating at the nominal rated input.
2"
51mm
Minimum
18"
458mm
12"
305mm
3”
76mm
Figure 2-1 - Ventilation Hood Dimensions (RECOMMENDATIONS ONLY)
2-2
Page 3
III. VENTILATION SYSTEM
IMPORTANT
Where international, national, or local codes require
the installation of fire suppression equipment or other
supplementary equipment, DO NOT mount the
equipment directly to the oven.
MOUNTING SUCH EQUIPMENT ON THE OVEN MAY:
VOID AGENCY CERTIFICATIONS  RESTRICT SERVICE ACCESS  LEAD TO INCREASED SERVICE EXPENSES FOR
THE OWNER
REQUIREMENTS
A mechanically driven ventilation system is required for the oven.
PROPER VENTILATION OF THE OVEN IS THE RESPONSIBILITY OF THE OWNER.
RECOMMENDATIONS
NOTE THAT THE HOOD DIMENSIONS SHOWN IN FIG­URE 2-1 (PREVIOUS PAGE) ARE ONLY. INTERNATIONAL, NATIONAL, AND LOCAL CODES WILL VARY, AND MUST BE FOLLOWED WHEN INSTALLING THE VENTILATION SYSTEM. ANY AP­PLICABLE INTERNATIONAL, NATIONAL, AND LOCAL CODES SUPERSEDE THE RECOMMENDATIONS SHOWN IN THIS MANUAL.
The rate of air flow exhausted through the ventilation system may vary depending on the oven configuration and hood design. Consult the hood manufacturer or ventilation engineer for these specifications.
To avoid a negative pressure condition in the kitchen area, return air must be brought back to replenish the air that was exhausted. A negative pressure in the kitchen can cause heat­related problems to the oven components as if there were no ventilation at all. The best method of supplying return air is through the heating, ventilation and air conditioning (HVAC) system. Through the HVAC system, the air can be temperature­controlled for summer and winter. Return air can also be brought in directly from outside the building, but detrimental affects can result from extreme seasonal hot and cold temperatures from the outdoors.
NOTE: Return air from the mechanically driven system not blow at opening of bake chamber. Poor oven baking performance will result.
RECOMMENDATIONS
must
SECTION 2
INSTALLATION
OTHER VENTILATION CONCERNS
Special locations, conditions, or problems may require the
services of a ventilation engineer or specialist.  Inadequate ventilation can inhibit oven performance.  It is recommended that the ventilation system and duct
work be checked at prevailing intervals as specified by the
hood manufacturer and/or HVAC engineer or specialist.
2-3
Page 4
SECTION 2 INSTALLATION
Figure 2-2 - INSTALLATION KIT
PS360L/WB-L Tandem
PS360/WB Double Tandem
PS360U/WB-U Tri Tandem
Item Part # Description PS360U/WB-U Quad Tandem
1 22361-0001 Flexible Gas Hose 2 4 3 4
2 22450-0028 Adjustable Legs 8 8 12 16
3 30773 Flue Vent, 14"Lg. 2 - - -
4 30759 Flue Vent, 29-1/2"Lg. - 2 3 4
5 30758 Flue Vent, 50" Lg. - 2 - -
6 21256-0008 Screw, 10-32 x 3/8 A/R A/R A/R A/R
8 42400-0089 Master Link Kit, PS360
8 42400-0598 Master Link Kit, PS360WB
9 35122-0049 Attachment Strip - 4 - -
10 35000-1103 Stop, End Conv., PS360
10 35000-1899 Stop, End Conv., PS360WB
11 21292-0001 Scr, #2PT 10-16 x 3/4 Hx Wsh A/R A/R A/R A/R
12 33984 Thermocouple 2 4 3 4
13 27276-0001 Cable Clamp 2 4 3 4
14 1002040 Warranty,Parts & Serv. Dist.List 1 1 1 1
15 38615 Owners Manual,English 1 1 1 1
16 27126-0238 11 Piece Hex Key Set 1 1 1 1
17 31389 Silicone Tubing, 36 (914mm) L x
5/16 (8mm) ID x 7/16 (11mm) OD 2 4 3 4
2434
12 --
- 35000-1454
- 35000-1456 Front Gasket Spacer 2 4 4 4
- 35000-1457 Rear Gasket Spacer 2 4 4 4
- 37200-0013
- 37000-0696 Transition Floor Panel - - - 1
- 48009-0024 Transition Top Panel - - - 1
- 48009-0025 Transition Side Wall - - - 2
- 35000-1748 Transition Rear Support - - - 1
- 35000-1749 Transition Front Support - - - 2
- 37000-0697 Transition Top Support Channel - - - 2
Machinery Compartment Trim Strip
Baking Chamber Gasket and Frame
1222
1222
2-4
Page 5
2”
51mm
SECTION 2
INSTALLATION
Figure 2-3
Dimensions and Data: PS360L Tandem
3
45"
1143mm
45-1/2"
1156mm
42"
1067mm
1016mm
31-1/2" 800mm
40"
17-3/4" 451mm
2”
51mm
32”
4
144-1/2" 3670mm
109"
2769mm
17-3/4" 451mm
6-1/2"
165mm
4
42-3/4"
1086mm
813mm
27-1/4" 692mm
54-1/2"
1384mm
27-1/4" 692mm
2
1
10-1/2” 267mm
2
1
6”
152mm
11-1/2" 292mm
16-1/2" 419mm
Figure 2-4
Dimensions and Data: PS360WB-L Tandem
3
53"
1346mm
45-1/2"
1156mm
50"
1270mm
1219mm
31-1/2" 800mm
48"
17-3/4" 451mm
40”
1016mm
4
144-1/2" 3670mm
109"
2769mm
17-3/4"
451mm
6-1/2"
165mm
4
50-3/4”
1289mm
27-1/4" 692mm
54-1/2"
1384mm
27-1/4" 692mm
2
1
10-1/2” 267mm
2
1
6”
152mm
11-1/2" 292mm
16-1/2" 419mm
2-5
Page 6
SECTION 2 INSTALLATION
2”
51mm
Figure 2-5
Dimensions and Data: PS360 Double Tandem
3
45"
1143mm
81-1/2"
2070mm
42"
1067mm
52"
1321mm
1016mm
31-1/2" 800mm
40"
17-3/4"
451mm
32”
4
144-1/2"
109"
2769mm
3670mm
17-3/4"
451mm
6-1/2"
165mm
4
813mm
34"
864mm
27-1/4" 692mm
54-1/2"
1384mm
27-1/4" 692mm
1
2
2
1
5-27/32"
148mm
10-1/8"
258mm
1
2
2
1
6-1/4"
158mm
13
11-1/2" 292mm
11-1/2"
292mm
16-1/2" 419mm
Figure 2-6
Dimensions and Data: PS360WB Double Tandem
2-6
Page 7
2-7
Figure 2-7
Dimensions and Data: PS360U Tri Tandem
INSTALLATION
SECTION 2
Page 8
2-8
Figure 2-8
Dimensions and Data: PS360WB-U Tri Tandem
SECTION 2
INSTALLATION
Page 9
2-9
Figure 2-9
Dimensions and Data: PS360U Quad Tandem
INSTALLATION
SECTION 2
Page 10
2-10
Figure 2-10
Dimensions and Data: PS360WB-U Quad Tandem
SECTION 2
INSTALLATION
Page 11
Figure 2-11
Thermocouple Installation Locations
SECTION 2
INSTALLATION
IV.
THERMOCOUPLE INSTALLATION
1. Install the thermocouple sensing bulb into the correct hole in rear of bake chamber as shown in Figure 2-11.
2. Thread thermocouple lead through grommet and into the machinery compartment.
3. Remove the right-side ac­cess panel of the machinery compartment.
Thread the thermocouple lead through the side of the machin­ery compartment as shown in Figure 2-12, and into the elec­trical box (at the right-front of the machinery compartment).
Figure 2-12
Placing the Thermocouple Leads
2-11
Page 12
SECTION 2 INSTALLATION
4. Connect the thermocouple leads to the temperature con­troller as shown in Figure 2-13.
5. Repeat Steps 1-4 for each of the other ovens in the in­stallation.
8 = White = Positive
7 = Red = Negative
R = No Connection
8 7 6 5
4 L2 L1
9 10 11 12 13
14 15 16
Figure 2-13
Thermocouple Lead Connections
2-12
Page 13
V. ASSEMBLY
If the installation includes upper ovens mounted atop lower ovens, the ovens must be stacked before joining the tandem ovens together.
If the installation includes ovens that are to be mounted on stands, assemble the ovens to the stands before joining the ovens together. An exploded view of the stand is shown in Figure 2-14.
SECTION 2
INSTALLATION
Figure 2-14
Exploded View - Upper Oven Stand
2-13
Page 14
SECTION 2 INSTALLATION
JOINING THE OVEN BODIES
For TANDEM and DOUBLE TANDEM installations, perform Steps 1-7 to join the ovens.
For TRI TANDEM installations, perform Steps 1-7 to join two of the ovens together, and ensure that they are level; then, repeat Steps 1-7 to join the third oven to the two that are assembled.
For QUAD TANDEM installations, perform Steps 1-7 for EACH PAIR of ovens, producing two sets of two joined ovens. Do not assemble the center bridge section at this time.
1. Determine the proper position of the ovens by referring to Figure 2-15. Then, move the ovens to their approximate final locations.
NOTE: The Sealing Gasket Assembly is shown attached to the left oven in Figure 2-15, but may be pre-mounted to EITHER of the two ovens.
LEFT OVEN RIGHT OVEN
Sealing gasket assembly (pre-
mounted)
Alignment
plate
Slot for
alignment
plate
Figure 2-15
Oven Positioning and Alignment
2. Remove the rear axial cooling fans that are adjacent to the mating sides of the ovens, as shown in the diagram. Leave the fan wiring connected to the oven.
Mating surface of
ovens (shown
from lower rear)
Wiring is still
Figure 2-16
Cooling Fan Removal
2-14
connected
Page 15
3. Insert three of the supplied 1/2 x 5 bolts through the holes in the frame of the right oven, pointing outward as shown in Figure 2-17. Then, slide the spacers into place on the bolts.
SECTION 2
INSTALLATION
2-1/2 x 2-1/2
( 64 x 64mm)
spacers
Bolts
2-1/2 x 8
(64 x 203mm)
spacers
4. Push the ovens together. Check that the mounting bolts, alignment plate, and sealing gasket are properly aligned.
Figure 2-17
Bolts and Spacers
Figure 2-18
Aligning the Ovens for Assembly
2-15
Page 16
SECTION 2 INSTALLATION
5. Check the alignment of the track rails using a straightedge. The rails MUST BE LEVEL across the gap between the ovens. If necessary, adjust the oven legs to align the track rails.
Figure 2-19
Checking Track Rail Alignment
6. Tighten all of the attaching bolts. Check that the mating edges of the ovens align properly. If gaps appear between the tops of the ovens, it will be necessary to loosen the connecting bolts and realign the ovens.
IMPORTANT: If it is necessary to realign the ovens, remember to re-check the alignment of the track rails.
7. Attach the front trim strip between the two ovens, as shown in Figure 2-20.
Trim strip
Figure 2-20
Trim Strip Positioning
8. Perform one of the following, as appropriate:
 For PS360/360WB Tandem and Double Tandem
installations, skip ahead to the INSTALLING THE CONVEYOR FRAME AND BELT section (Page 2-19).
 For PS360/360WB Tri Tandem installations, perform
Steps 1-7 again to attach the third oven to the two that have just been assembled. Then, skip ahead to the
INSTALLING THE CONVEYOR FRAME AND BELT
section (Page 2-19).
 For PS360/360WB Quad Tandem installations, perform
Steps 1-7 again to attach the two remaining ovens to each other. Then, continue on to Step 9 to attach the center (transition) section.
2-16
Page 17
9. Test-fit the transition section of the conveyor frame, as shown in Figure 2-21. The alignment pins on the bottom of the frame ensure correct spacing of the center ovens.
SECTION 2
INSTALLATION
Figure 2-21
Transition
Frame Placement
10. Attach the two angled support brackets between the two center ovens, as shown in Figures 2-22a and 2-22b.
Note that a LOWER OVEN (PS360L, PS360WB-L) uses different support brackets for the front and rear, while an UPPER OVEN (PS360U, PS360WB-U) uses identical brackets on the front and rear.
Figure 2-22a
Support Brackets -
Lower Oven
Conveyor frame shown removed
for clarity
Figure 2-22b
Support Brackets -
Upper Oven
2-17
Page 18
SECTION 2 INSTALLATION
10. Remove the transition section of the conveyor frame. Place the transition floor panel into place atop the support brackets. See Figure 2-23.
Figure 2-23
Installing the Transition
Floor Panel
11. Replace the transition (center) conveyor section, as shown in Figure 2-24.
Figure 2-24
Replacing the
Transition Frame
2-18
Page 19
For a TANDEM or DOUBLE TANDEM oven, slide the conveyor frame assembly into either end of the oven.
INSTALLING THE CONVEYOR FRAME AND BELT
ALL TYPES OF OVENS, ENSURE THAT THE DRIVE
FOR SECTION/END OF THE CONVEYOR FRAME IS PLACED ON THE SAME END OF THE OVEN AS THE CONVEYOR DRIVE MOTOR.
1. Insert the conveyor frame into the oven as follows:
Figure 2-25a
Installing the Conveyor Frame-
Tandem and Double Tandem Ovens
SECTION 2
INSTALLATION
For TRI TANDEM ovens, slide one center section and one end section of the frame into EACH END of the oven. The four sections should butt against each other.
For QUAD TANDEM ovens, slide two intermediate sections and one end section of the frame into EACH END of the oven. Butt the two inner intermediate sections against the transition (center) frame section. The other frame sections should butt against each other.
Figure 2-25b
Installing the Conveyor Frame-
Tri Tandem Ovens
Figure 2-25c
Installing the Conveyor Frame-
Quad Tandem Ovens
2-19
Page 20
SECTION 2 INSTALLATION
2. Slide the conveyor belt through the support rods underneath the frame, and thread it through the oven. Then, reach through the oven window and pull the free end of the belt through the oven so that it lies atop the conveyor frame.
Check that the links on the conveyor are oriented as shown in Figure 2-26.
Direction
of travel
Figure 2-26
Conveyor Link Orientation
3. Connect the inside master links. Check that the links are oriented as shown in Figure 2-27.
4. Connect the outside master links. Note that the outside master links have right and left sides. The right-side master link has an open hook facing you, as shown in Figure 2-28.
Incorrect
position
Direction
of travel
Correct
position
Figure 2-27
Inside Master Links
Figure 2-28
Outside Master Links
2-20
Page 21
5. For a TANDEM, DOUBLE TANDEM, or TRI TANDEM oven installation, skip ahead to the next section. For a QUAD TANDEM oven installation, continue on to Step 6.
SECTION 2
INSTALLATION
6. Slide the top transition panel into place. Then, slide the two transition side panels into place. See Figure 2-29.
7. If the four latches are not already attached to the side and top transition panels, attach them in place as shown in Figure 2-29.
Fasten the latches on the side and top panels to hold the panels in place.
8. LOOSELY attach the conveyor drive motor to the end wall of the oven, as shown in Figure 2-30.
Latches
Figure 2-29
Transition Assembly
Latches
9. Assemble the conveyor drive chain in place on the motor and conveyor drive sprockets.
10. Position the motor to adjust the tension of the drive chain. The deflection of the chain should not exceed 1/4 (6mm). Then, tighten the motor in place.
Figure 2-30
Conveyor Motor and Drive Chain Assembly
11. Assemble the end plugs and motor housing onto the oven.
TANDEM AND DOUBLE TANDEM OVENS ONLY: Assemble the conveyor crumb trays and conveyor extension covers onto the oven.
2-21
Page 22
SECTION 2
6
6
4
5
2
2
3
3
1
5
INSTALLATION
UTILITY ROUGH-IN DIMENSIONS AND POSITIONING
CAUTION
IT IS REQUIRED THAT THE OVEN BE
PLACED UNDER A VENTILATION
HOOD FOR ADEQUATE AIR SUPPLY
AND VENTILATION.
GAS SUPPLY
&
ELECTRICAL SUPPLY
PROVIDED BY CUSTOMER
DO NOT USE CONDUIT
FOR GROUND
CIRCUIT BREAKER
1 circuit breaker/fused disconnect switch with lockout/tagout is required for each oven
cavity. Wire each oven cavity separately.
ELECTRICAL SPECIFICATIONS
220-230V, 1 Ph, 8 Amp draw, 50 Hz, 2 pole, 3 wire system per oven cavity (2 hot, 1 grd).
GAS RATING
Models PS360U/L: 135,000 BTU/HR, 34,020kcal/HR, 40kW/HR Models PS360WB-U/-L: 170,000 BTU/HR, 42,840kcal/HR, 50kW/HR
MINIMUM GAS METER RATING
600 Ft.3/Hour (17m3h) for 1 or 2 oven cavities. 1200 Ft.3/Hour (34m3h) for 3 or 4 oven cavities.
Minimum rating does not take other gas appliances into consideration. Gas consumption varies at each site. Total BTU/HR (kcal/hr) must be calculated on high flame off of each appliance to determine if meter needs to be larger.
MINIMUM GAS PIPE SIZE
Natural: 2" (51mm) ID for 1 or 2 oven cavities
with runs up to 200 ft.(61m).
2-1/2" (64mm) ID for 3 or 4 oven cavities with runs up to 200 ft.(61m)
Runs over 200 ft. consult factory
Propane: 1-1/2" (38mm) ID for 1 or 2 oven
cavities with runs up to 200 ft.(61m).
2" (51mm) ID for 3 or 4 oven cavities with runs up to 200 ft.(61m).
Runs over 200 ft. consult factory
OR
Must be a dedicated line.
OR
Must be a dedicated line.
GAS OVEN ROUGH-IN
To
Oven
To
Oven
To
Oven
GAS VALVES
3/4" (19mm) ID full flow gas shut-off valve. A separate connection and valve must be provided for each oven.
REQUIRED SUPPLY GAS PRESSURE
Natural: 20-30mbar Propane: 50mbar
SUGGESTED
If space permits, service should be located to the left of the ovens to allow access to switches and valves.
User Supplied Items:
ITEM DESCRIPTION
1 2"(51mm) X 2"(51mm) X 3/4"(19mm) TEE 2 3/4"(19mm) X 3"(76mm) NIPPLE 3 3/4" (19mm)FULLFLOW GAS SHUT-OFF VALVE 4 2"(51mm) X 3/4"(19mm) 90° REDUCER ELBOW 5 2"(51mm) ID GAS SUPPLY PIPE LINE-NATURAL GAS 6 15 AMP TOGGLE SWITCH - 2 POLE for GAS
To
Oven
Figure 2-31
Oven Rough-In
2-22
Page 23
VI. ELECTRICAL CONNECTION
Check the oven data plate before making any electric supply connections. Electric supply connections must agree with data on the oven data plate. A typical oven data plate is shown in Figure 2-34 (on Page 2-24).
NOTE: When the oven is installed, it must be electrically grounded in accordance with current IEC/CEE requirements and also with local codes.
The electrical installation, including the service connection, must comply with current IEC/CEE requirements and to local codes. The installation must undergo a complete electrical check before operating the oven.
Special attention must be given to the polarity of the supply when connecting to oven input terminals.
All connections are made at one common connection at the back of each oven. Refer to Figures 2-32 and 2-33.
NOTE: At the installation location, it is required that the electrical supply for each oven incorporates a main circuit breaker (not furnished). The circuit breaker must have 3mm contact gaps breaking all poles of the supply.
SECTION 2
INSTALLATION
WARNING: If your electrical supply has fast-acting circuit breakers, then the initial starting current of the blower motors in Model PS360WB-U and PS360WB-L may trip the breakers. It is suggested to use slow-acting circuit breakers with these models.
For further electrical information, refer to the wiring diagram.
WARNING: The connections to the exhaust system, electrical supply, and gas supply must follow the installation instructions. Initial start-up of the oven can be performed only by an authorized agent.
Figure 2-32
Junction Connection Box (Lower Oven)
Figure 2-33
Junction Connection Box (Upper Oven)
3/4 (19mm) pipe for gas
oven connection
3/4 (19mm) pipe for gas oven connection
2-23
Page 24
SECTION 2 INSTALLATION
Figure 2-34
Typical Oven Data Plate - Models PS360/PS360WB
2-24
Page 25
VII.
GAS SUPPLY FOR GAS HEATED OVENS
Pipe sizing -- Always install a shut off valve in the gas supply line to the oven. This valve should be the same size as the supply line.
Please remember that the longer the pipe runs, the more the pressure drops. One 90° elbow equals a 1,2 m length of pipe.
Each oven section requires a nominal gas input as follows:
PS360U,L (per oven) 40 kW PS360WB-U, -L (per oven) 50 kW
Follow the recommended pipe sizing and meter sizing as indicated in the Rough-in Drawing (Figure 2-31,Page 2-22).
The flexible hose furnished with the oven must be positioned as shown in Figure 2-35.
NOTE: The recommended pipe sizes are larger than usually required to eliminate any operation problems. It is much less expensive to make the initial installation large enough to do the job rather than redoing the job later.
For lighting instructions, refer to Step-by-Step Operation in the OPERATION Section of this manual.
SECTION 2
INSTALLATION
WARNING:
To prevent damage to control valve regulator during initial turn on of gas, it is important to open manual shutoff valve very slowly.
After the initial gas turn on, the manual shutoff valve must remain open except during pressure testing as outlined in the above steps or when necessary during service maintenance.
very
CAUTION
DURING PRESSURE TESTING NOTE ONE OF THE FOLLOWING:
1. The oven and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressure in excess of 1/2 psig (3.45 kPA).
2. The oven must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 psig (3.45 kPA).
3. If the incoming pressure is over 50 mbars, a separate regulator must be installed before the 3/4 manual gas shutoff valve located at the rear outside of the oven.
To Gas
Supply Pipe
Appliance Connection/ Male Nipple
90° ST
Elbow
Union
Full-Flow Gas
Shutoff Valve
Flexible Hose
Correct Position
Figure 2-35
Flexible Hose Connector Installation
2-25
Page 26
SECTION 2 INSTALLATION
VIII. PREPARATION FOR VARIOUS GASES
Before proceeding to set up the oven for a specific gas, the main gas supply valve and the electrical supply circuit breaker should be turned off.
When preparing the oven for use of Group H or L Natural gases, the orifice (Manifold) pressure should be adjusted to the values shown in the chart on Page 1-1.
The main orifice and also the by-pass (low flame) orifice should be changed for the specific gas type used as shown in the following Table, also refer to Section IX, CHANGING ORIFICES.
FOR USE WITH NATURAL GAS
The input to the burner can be determined using the orifice (manifold) pressure data or by the volume supplied using the gas meter.
Using the orifice pressure data you must know the specific gas quality used and when using the volume method you must know the heat value (HuB) of the gas used (Obtainable from your local gas supplier).
If you used the orifice pressure method, you should double check the rated input using the volume method.
If the measured input does not correspond with the rated input, check first that correct orifices are installed. If the orifice sizes are as specified, check and correct the supply and orifice pressures to obtain the correct input based on the gas meter reading.
FOR USE WITH LIQUID (LP) GAS
When using liquid gas the converter in the multifunction gas valve has to be turned end over end - 180° (Refer to Figure 2-
36). This takes the governor out of operation.
2-26
Page 27
IT ...... II
GB .... II
FR .... II
DE .... II
DE .... II
ES .... II
NL ..... II
BE .... I
IT ...... II
GB .... II
FR .... II
DE .... II
ES .... II
NL ..... II
BE .... I
...................
2H3+
...................
2H3+
.................
2E+3+
2ELL3B/P
2ELL3B/P
...................
2H3+
................
2L3B/P
.......................
2E+
...................
2H3+
...................
2H3+
.................
2E+3+
2ELL3B/P
...................
2H3+
................
2L3B/P
.........................
3+
GAS TYPE AND PRESSURE LABEL
Predisposto per gas metano .................................................... 20 mbar
Adjusted for natural gas ........................................................... 20 mbar
Essaye au gaz naturel (E/L) ................................................ 20-25 mbar
Eingestellt auf Erdgas (E) ........................................................ 20 mbar
...........
Eingestellt auf Erdgas (LL) ....................................................... 20 mbar
...........
Preparado para gas natural...................................................... 20 mbar
Aangelegd op aardgas ............................................................. 25 mbar
Essaye au gaz naturel/aangelo op aardgas ........................ 20-25 mbar
GAS TYPE AND PRESSURE LABEL
Predisposto per G.P.L. ................................................... 28-30/37 mbar
Adjusted for L.P.G. ......................................................... 28-30/37 mbar
Essaye au gaz naturel liquide ........................................ 28-30/37 mbar
Eingestellt auf Flüssiggas ........................................................ 50 mbar
...........
Preparado para gas liquido ............................................ 28-30/37 mbar
Aangelegd op vloeibaar gas ..................................................... 30 mbar
Aangelegd op vloeibaar gas/essaye au gaz liquide ....... 28-30/37 mbar
SECTION 2
INSTALLATION
Insert Converter In this
Position for Pressure
Regulation
Outlet Pressure Tap
Governor Adjustment
Gas Converter
Insert Converter In this
Position for use with LP
Gas
Burner Blower
Air Adjustment
PlateBurner
High Flame
Solenoid Valve
Main Orifice
1/2 Nuts
Inlet Pressure Tap
1/2 Compression Nut
3/4 Union
Pilot Line
Combination
Gas Control
Valve
Figure 2-36
Burner/Piping Assembly
2-27
Low Flame
Bypass Orifice
Low Flame
Bypass Line
Page 28
SECTION 2 INSTALLATION
IX. CHANGING ORIFICES
TO CHANGE MAIN ORIFICE (Refer to Figure 2-36)
1. Turn off main gas supply valve.
2. Open 3/4" union in gas supply line.
3. Remove 1/2" nuts securing gas train to the burner housing.
4. Using a 11/16" wrench remove orifice from the mounting flange.
5. Install new orifice in reverse order.
WARNING
Before operating oven check for gas leaks!
TO CHANGE BYPASS (LOW FLAME) ORIFICE (Refer to Figure 2-36)
1. Turn off main gas supply valve.
2. Open 3/4" union in gas supply line.
3. With 1/2" wrench loosen compression nuts securing bypass tube to solenoid valve.
4. Remove orifice from bypass tube.
5. Install new orifice in reverse order.
X. VOLUMETRIC METHOD
WARNING
Before operating oven check for gas leaks!
IMPORTANT
During these measurements, no other gas appliance should be in operation being supplied from the same gas meter.
To determine gas flow setting value E: E = Liters/min.
NB = Rated input in kW HuB = Heat (Calorific) value of gas in kW/m
E = NB
HuB
3
To determine the time of 0.1m
Time in minutes =100
E
The time of the gas flow through the meter should be taken with a stopwatch.
1. Remove cover screw from the gas valve pressure (governor)
adjustment valve.
2. Open main gas supply valve and start oven according to
supplied instructions with the temperature control at maximum setting.
3. Once oven is in operation, adjust pressure valve (governor)
to the calculated volume using the time for 100 liters of flow through. Turning the adjustment screw clockwise will increase the flow and counter-clockwise will reduce it.
(100 liters) gas usage:
3
2-28
Page 29
4. Replace cover screw on adjustment valve and turn off main gas supply valve.
5. Record the reading obtained from the gas meter and calculate obtained gas flow. Compare this to the indicated flow in the CHART OF ORIFICE SIZES, GAS PRESSURES, NOMINAL INPUT RATINGS AND GAS FLOW on Page 1.
6. Note the following comments and procedures to assure correct gas supply pressure and adjusting the gas valve to obtain proper orifice (manifold) pressure.
XI. VARIATIONS OF RATED SUPPLY
PRESSURES
Special attention should be given to the supply pressure and gas flow pressure at the supply connection to the oven. The nominal supply pressure for gas family Group 2 (natural gas) should be 20 mbar.
If the supply pressure is lower or higher than the rated (nominal) pressure then the reason should be investigated and the gas supplier contacted.
If the supply pressure is lower than 17 mbars or higher than 25 mbars then the oven should be shut down and the gas supplier notified. No adjustment of the oven controls should be made and the oven should not be operated.
SECTION 2
INSTALLATION
TO CHECK GAS SUPPLY PRESSURE:
1. Close main gas supply valve.
2. Remove supply (inlet) pressure measuring stud screw from
gas valve and attach the manometer to the stud.
3. Open main gas supply valve and restart oven with
temperature control at maximum setting.
4. Measure inlet (supply) pressure. For all natural gases this
should be between 17 and 25 mbars.
5. Turn oven off, close main gas supply valve, remove
manometer from stud and tighten cover screw in to pressure measuring stud.
ORIFICE (MANIFOLD) PRESSURE METHOD:
1. Turn off main gas supply valve.
2. Remove pressure measuring stud screw located at the
out-flow (closest to gas burner) of the gas valve and attach a manometer.
3. Remove cover screw from the gas valve pressure (governor)
adjustment valve.
4. Open main gas supply valve and start oven according to
supplied instructions with the temperature control at maximum setting.
5. Once oven is in operation, adjust pressure valve (governor)
to the orifice pressure value as shown for the specific gas in the Gas Specifications Table.
6. Turn oven off, close main gas supply valve, remove U tube
manometer and tighten cover screw into pressure measuring stud.
2-29
Page 30
SECTION 2 INSTALLATION
SPECIAL NOTICES:
The ovens should be operated only in an area that has good air circulation.
The oven must be installed under an electrically powered ventilating hood.
Installation of replacement parts requiring access to the interior of the oven is permitted only by authorized service personnel.
The operator should be properly trained to the functioning of the oven.
This instructions manual should be supplied to the operator.
Constructional changes to the area where the oven is installed shall not affect the air supply to the oven.
The installation, start-up and changes required when changing from one gas type to another can be performed only by a certified professional.
These ovens are intended only for commercial use and are to be operated only by professionals.
It is required that the oven is regularly inspected for proper functioning. The frequency of inspections are dependent on the oven usage, however it should be performed at least once a year.
After adjustments or service work the oven has to be checked for gas leaks.
NOTE: After conversions, readjustments or service work the oven has to be tested for proper functioning. Basically the following applies:
Testing for gas leaks,  Testing for correct air supply, specifically to the burner
blower,  Testing of proper combustion and gas supply,  Testing of correct gas supply controls,  Testing the flue gas escape from the oven,  Testing the vent system of the installation location.
2-30
Loading...