Middle Atlantic IUQFP-2 Installation Guide

Page 1
Instruction Sheet
UQFP SERIES
Ultra Quiet Fan Panels
(220V Models)
THANK YOU Thank you for purchasing the UQFP Series Ultra Quiet Fan Panel. Please read these instructions thoroughly before installing this product.
PRODUCT FEATURES
- Local and remote status notification
- On-board processor controls fan speed proportional to enclosure temperature
I-00467 Rev -
Page 2
SPECIFICATIONS
UQFP-2 & UQFP-2D/IUQFP-2 & IUQFP-2D Current Draw: 270 mA @ 5V DC (UQFP-2/IUQFP-2) Airflow: 50 CFM @ Full Speed 310 mA @ 5V DC (UQFP-2D/IUQFP-2D) RPM: 1900 @ Full Speed Noise: 24 dB @ Full Speed
UQFP-4 & UQFP-4D/IUQFP-4 & IUQFP-4D Current Draw: 510 mA @ 5V DC (UQFP-4/IUQFP-4) Airflow: 100 CFM @ Full Speed 560 mA @ 5V DC (UQFP-4D/IUQFP-4D) RPM: 1900 @ Full Speed Noise: 27 dB @ Full Speed
UQFP-2/IUQFP-2
UQFP-2D/IUQFP-2D
UQFP-4/IUQFP-4
UQFP-4D/IUQFP-4D
Page 2
Page 3
FUNCTIONS
Models UQFP-2 & UQFP-4/IUQFP-2 & IUQFP-4 (UQFP-4 Model Shown)
FAN
POWER (GREEN)
FRONT VIEW
(YELLOW)
OVERTEMP
(RED)
OVERTEMP ALARM OUTPUT
DO NOT OPEN. NO USER SERVICEABLE PARTS INSIDE.
OVER
5VDC
TEMP
2A
ALARM
(N.O.)
5V DC INPUT JACK
TEMPERATURE PROBE
REAR VIEW
POWER
FAN
(GREEN): This LED indicates that the unit is receiving power.
(YELLOW): When rack temperature reaches 81OF (27OC) this LED will begin to flash indicating that the fans have turned on. It will continue flashing proportional to the fan speed, as long as the fans are on.
OVERTEMP
(RED): If rack temperature reaches 100OF (37OC) this LED will light indicating an
over temperature condition within the rack.
OVERTEMP ALARM OUTPUT: This normally open dry contact closure will provide an alarm to an external (remote) monitoring system if your enclosure reaches overtemp condition.
5V DC INPUT JACK: Power supply connector
TEMPERATURE PROBE:
Remote temperature sensor. (9' long)
Page 3
Page 4
Models UQFP-2D & UQFP-4D/IUQFP-2D & IUQFP-4D
(UQFP-4D Model Shown)
FAN (YELLOW)
POWER (GREEN)
DISPLAY
ALARM
(RED)
FRONT VIEW
POWER (GREEN): This indicates that the unit is receiving power.
FAN
(YELLOW): When rack temperature reaches 81OF (27OC), this LED will begin to flash indicating
that the fans have turned on. It will continue flashing proportional to the fan speed, as long as the fans are on.
ALARM temperature condition within the rack. See Alarm Set Point Button
(RED): At the factory preset overtemp of 100OF (37OC), this LED will light indicating an over
instructions below to change the
overtemp alarm setting.
DISPLAY: The display will indicate the rack temperature and provide a read-out of the following fault codes during one of these conditions:
OVERTEMP: The temperature of the enclosure has risen above the alarm set point. Inspect airflow intake and output for obstructions. Additional cooling capacity may be required.
FAN FAULT: One or more of the fans has stopped. Check all fans for obstruction. If problem persists, call Technical Support at (800) 266-7225.
Page 4
Page 5
OVERTEMP ALARM OUTPUT
FAN FAULT ALARM OUTPUT
DO NOT OPEN. NO USER SERVICEABLE PARTS INSIDE.
5VDC
FAN
OVER
2A
FAULT
TEMP
ALARM
ALARM
(N.O.)
(N.O.)
REAR VIEW
ALARM SET POINT BUTTON
CONTROL SETTINGS
PUSH
Press once to view the current
overtemp alarm setting.
Each additional push will raise
the overtemp alarm setting
by 1
To toggle between Fahrenheit
and Celsius, press and hold for
3 seconds.
5V DC INPUT JACK
TEMPERATURE PROBE
O
.
SIDE VIEW
ALARM SET POINT BUTTON:
- To change display from Fahrenheit to Celsius, press and hold Alarm Set Point Button for 3 seconds.
- To view alarm set point, simply press and release the Alarm Set Point Button once.
- To change the factory preset alarm set point, repeatedly press the Alarm Set Point Button until
O
desired temperature is displayed. Factory preset overtemp alarm set point is 100
O
Adjustment range is from 95
FAN FAULT
/ OVERTEMP ALARM OUTPUT:
to 115OF (35O to 46OC)
F (37OC).
These normally open dry contact closures will provide an alarm to an external (remote) monitoring system if your enclosure experiences a fan fault or overtemp condition.
5V DC INPUT JACK: Power supply connector
TEMPERATURE PROBE:
Remote temperature sensor (9' long).
Page 5
Page 6
INSTALLATION
UQFP-2D (left) & UQFP-4D (right) Shown.
CONTROL SETTINGS
PUSH
Press once to view the current
overtemp alarm setting.
Each additional push will raise
the overtemp alarm setting
To toggle between Fahrenheit
by 1
O
and Celsius, press and hold for
.
3 seconds.
FAULT ALARM (N.O.)
5VDC
2A
OVER TEMP
FAN
ALARM (N.O.)
WIRE TIE HERE
TIE SADDLE
TEMPERATURE PROBE
CONTROL SETTINGS
PUSH
Press once to view the current
overtemp alarm setting.
Each additional push will raise
the overtemp alarm setting
To toggle between Fahrenheit
by 1
O
and Celsius, press and hold for
.
3 seconds.
FAN FAULT ALARM
(N.O.)
OVER
TEMP ALARM (N.O.)
5VDC
2A
WIRE TIE HERE
TECH TIP: Ensure that you have access to the rear of the panel to make connections and configure settings once mounted. If access to rear of unit is limited, cable management and setting configurations must be done prior to mounting the panel.
1) Route Temperature Probe, Alarm Output, and Power Supply wires along the rear of the panel as shown above. Tie points are provided to route wires left or right. Do not allow wires to interfere with fan operation.
2) Using tie saddle included, mount the temperature probe wire into highest available area inside of rack. In order to achieve proper temperature sensing, the probe should be installed near the top of the rack. The probe is provided with a generous 9' lead.
3) (220V models only) Select appropriate wall plug for your region and attach to provided power supply. Connect power supply to power source.
Page 6
Page 7
THERMAL MANAGEMENT GUIDELINES
- Mount fan panel in highest available location of enclosure.
- Use vent blockers to cover any vent at the top of side panels.
- Do not place vent panels within six rackspaces below fan panel. Cover any of these spaces.
- If heat producing equipment is in the middle of the rack, use a 3 space vent panel at the bottom
- Use a 2 space vent panel if heat producing equipment is at the bottom of the enclosure.
UQFP-4D (SHOWN)
Page 7
VENT PANEL
Page 8
WARRANTY Middle Atlantic Products, Inc. (the "Company") warrants the UQFP Series Ultra Quiet Fan Panels to be free from defects in material or workmanship under normal use and conditions for a period of three (3) years from date of shipment by the Company.
The Company's entire liability to the purchaser, and the purchaser's (or any other parties) sole and exclusive remedy, under this warranty shall be limited, at the Company's option, to either (a) return of and refund of the price paid for, or (b) repair or replacement at the Company's factory of the products purchased, or any part or parts thereof, which the Company has determined to be defective after inspection thereof at the Company's factory.
This warranty does not cover damage due to acts of God, accident, misuse, abuse or negligence by parties other than the Company, or any modification or alteration of the products. In addition, this warranty does not cover damage due to improper handling, assembly, installation or maintenance.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES OF ANY KIND, EITHER EXPRESSED OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
TO THE MAXIMUM EXTENT PERMITTED BY APPLICABLE LAW, IN NO EVENT SHALL THE COMPANY BE LIABLE FOR ANY SPECIAL, INCIDENTAL, INDIRECT, OR CONSEQUENTIAL DAMAGES WHATSOEVER (INCLUDING, WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION OR ANY OTHER PECUNIARY LOSS) ARISING OUT OF THE USE OF THE PRODUCTS PURCHASED, EVEN IF THE COMPANY HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. THE COMPANY'S LIABILITY TO THE PURCHASER (OR ANY OTHER PARTY) HEREUNDER, IF ANY, SHALL IN NO EVENT EXCEED THE PURCHASE PRICE OF THE PRODUCTS PAID TO THE COMPANY.
Corporate Headquarters Corporate Voice 973-839-1011 - Fax 973-839-1976 International Voice +1 973-839-1011 - Fax +1 973-831-4982 middleatlantic.com - info@middleatlantic.com
Middle Atlantic Canada 113 Iber Road - Ottawa, ON - K2S 1E7 Voice 613-836-2501 - Fax 613-836-2690 middleatlantic.ca - customerservicecanada@middleatlantic.ca
Factory Distribution USA: NJ - CA - IL Canada: ON - BC
At Middle Atlantic Products we are always listening. Your comments are welcome.
Middle Atlantic Products is an ISO 9001 and ISO 14001 Registered Company.
Page 8
30% Recycled Paper
Loading...