Middle Atlantic CWR-18-22PD Users Guide

Page 1
Instruction Sheet
CWR SERIES
CABLESAFETM WALL CABINET
U
R
C US
LISTED
L
CABLESAFE WALL CABINET WITH
STANDARD DOOR
THANK YOU
Thank you for purchasing the CWR Series CableSafe Cabling Wall Cabinet. Please read these
instructions thoroughly before installing/assembling this product.
PRODUCT FEATURES
• 26” width provides abundant space for patching
• Ships with front rackrail at a 4” setback to accomodate cable managers
• Swing open center section allows for easy front and rear access to equipment and cabling
• Available with vented, plexiglass or solid doors
CABLESAFE WALL CABINET WITH
I-00347 Rev C
Page 2
IMPORTANT SAFETY INSTRUCTIONS / INSTRUCTIONS IMPORTAANTES SUR LA SÉCURITÉ
SAVE ALL INSTRUCTIONS / CONSERVER CES INSTRUCTIONS
DANGER HAZARDOUS VOLTAGE/DANGER HAUTE TENSION
The lightning flash with the arrowhead symbol, within an equilateral
triangle is intended to alert the user to the presence of uninsulated dangerous voltage within the product’s enclosure that may be of sufficient magnitude to constitute a risk of electric shock to persons.
L'éclair avec le symbole de flèche dans un triangle équilatéral est
destiné à alerter l'utilisateur de la présence d'une tension dangereuse non isolée dans l'enceinte du produit qui peut être d'une ampleur suffisante pour constituer un risque de choc électrique pour les personnes.
CAUTION/ATTENTION The exclamation point within an equilateral
triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
Le point d'exclamation dans un triangle équilatéral est destiné à
alerter l'utilisateur de la présence d'importants instructions d’opération et de maintenance (entretien) dans la documentation accompagnant l'appareil.
WARNING: Failure to read, understand and follow the following information can result in serious personal injury, damage to the equipment or voiding of the warranty.
AVERTISSEMENT: Ne pas lire, comprendre et suivre les informations suivantes peut entraîner des blessures graves, des dommages à l'équipement ou de la nullité de la garantie.
CAUTION: To avoid an unstable condition, place heavier components at the bottom of the enclosure. When more than one component is placed in the enclosure, begin at the bottom of the enclosure and place equipment at the lowest available point, evenly distribute weight (horizontally) within the enclosure.
Component weight should be distributed as follows:
• 1/2 of the total component weight (at a minimum) placed in the bottom third of the cabinet
• 1/4 of the total component weight (at a maximum) placed in the middle third of the cabinet
• 1/4 of the total component weight (at a maximum) placed in the top third of the cabinet
ATTENTION: Pour éviter un état instable, placez composants les plus lourds au fond de l'enceinte. Lorsque plus d'un composant est placé dans la enceinte, commencer par le bas de l'enceinte et placer l'équipement à la point le plus bas disponible, de distribuer uniformément le poids (horizontalement) dans le enceinte.
Le poids des composants devrait être réparti comme suit:
• 1/2 du poids total de la composante (au minimum) placé dans le tiers inférieur de l'armoire
• 1/4 du poids total de la composante (au maximum) placé dans le tiers médian de l'armoire
• 1/4 du poids total de la composante (au maximum) placé dans le tiers supérieur de l'armoire
CAUTION: All installation and assembly steps must be performed by qualified personnel.
ATTENTION: Toutes installation et de montage étapes doivent être effectuées par du
personnel qualifié.
Page 2
Page 3
IMPORTANT SAFETY INSTRUCTIONS / INSTRUCTIONS IMPORTAANTES SUR LA SÉCURITÉ
CAUTION: Ensure that the wall has a structural load capacity that will support the weight of the cabinet fully loaded with equipment.
ATTENTION: Veiller à ce que le mur a une capacité de charge structurelle qui supporter le poids de le cabinet entièrement chargé avec l'équipement.
CAUTION: The following parts are not effectively bonded to the protective earth terminal: Rack rails, lace bars, Lever Lock™, shelves, baffle, blanking panels, and cable management. If any part needs to be bonded to the protective earth terminal it shall be done in accordance with Article 250 of the National Electrical Code.
ATTENTION: Les pièces suivantes ne sont pas correctement liés à la borne de terre de protection: rails de rack, des bars de dentelle, Lever Lock ™, des étagères, des chicanes, des panneaux d'obturation, et la gestion des câbles. Si une partie doit être lié à la borne de terre de protection, il doit être fait conformément à l'article 250 du Code national de l'électricité.
CAUTION: Power cord(s), for fans or other accessories, need to be secured to ensure that they are routed away from pinch points and moving parts.
ATTENTION: Le cordon d'alimentation (s), pour les fans ou autres accessoires, doivent être fixé à veiller à ce que ils sont acheminés loin des points de pincement et des pièces mobiles.
CAUTION: Do not attempt to unload or move the enclosures alone. Make sure to have sufficient amount of personnel and equipment to safely move this product.
ATTENTION: Ne essayez pas de décharger ou déplacer les enceintes seul. Assurez-vous d'avoir quantité suffisante de personnel et de matériel pour déplacer ce produit en toute sécurité.
CAUTION: To reduce the risk of personal injury, these mounting instructions must be followed and proper weight capacities must be observed.
ATTENTION: Pour réduire le risque de blessures, ces instructions de montage doivent être respectées et les capacités de poids appropriées doivent être respectées.
WEIGHT RATINGS
Model Weight Rating
All 200 lbs.
Page 3
Page 4
TOOLS REQUIRED
• 5/16” Wrench
• 5/16” Socket
• 5/32” Hex Key
12 SPACE
18 SPACE
26 SPACE
STANDARD D-RING 8-32 ACORN NUT 8-32 STUD
QTY QTY QTY QTY
4 4 4 50
6 6 6 50
8 8 8 50
SUPPLIED HARDWARE
CABINET INSTALLATION
NOTE: The cabinet must be installed plumb and level for proper operation.
1. Separate backpan from center section and determine hinge side.
12-24 RACKSCREW
NOTE:
• CWR center section can be opened from left-to-right or vice versa depending on how backpan is installed.
• Ensure the wall to which the backpan will be mounted, consists of two (2) 3/4" plywood screwed to the studs.
2. Locate the studs in the wall behind the two (2) ¾” plywood. Align the mounting holes in the cabinet with the studs. Using 3/8” diameter lag bolts with a minimum length of 2” and flat washers in each mounting hole, secure the cabinet to the wall.
Page 4
Page 5
CABINET INSTALLATION (CONTINUED)
NOTE: A minimum of 1” clearance on the top and bottom of the cabinet is required. (FIGURE A)
5 MOUNTING HOLES CIRCLED
STUD
16” 1 ½”
MIN. 1” CLEARANCE REQUIRED TOP AND BOTTOM
TWO 3/4” PLYWOOD
12 ½”
NOTE: Center section removed for clarity
FIGURE A
12 ½”
21 ” 32 ⅜” 46 ⅜”
CWR-12 CWR-18 CWR-26
GROUNDING AND BONDING
Protective Earth Terminals (PET) are located in backpan of the wall rack. These terminals are marked with the symbol Wall rack parts, center section and door, contain or are provided with bonding points for connection to the backpan / PET. Protective earth and bonding connections shall be in accordance with Article 250 of the National Electric Code.
OPTIONAL PROTECTIVE EARTH TERMINAL KIT: #PET-K-CWR
PARTS LIST
• Backpan bonding wire [12 Gauge Wire
QTY
(1)
(#10 ring terminal to 1/4” ring terminal] 9”]
• Door bonding wire [12 Gauge Wire
(1)
(#10 ring terminal to #10 ring terminal) 9”]
• Thread forming screw M4 x .7
• Locking Nut 10-32
• Flange Nut 1/4-20
(1) (3) (1)
Page 5
(1) (1)
(3)
(1) (1)
Page 6
GROUNDING AND BONDING (CONTINUED)
1. Attach backpan bonding wire from 1/4”-20 backpan protective earth terminal (PET) to nearest center section bonding stud (10-32) using hardware provided. (FIGURE G)
NOTE: The main protective earth ground needs to be the first terminal placed on the PET and this terminal needs to be secured on its own with a nut. The bonding wire for the center section can be added to the PET after securing the nut for the main ground. (FIGURE G)
2. Attach door bonding wire (with male or female disconnect end) to door bonding stud with nut (included). (FIGURE G)
3. Attach remaining door bonding wire to nearest center section bonding stud (10-32) using hardware provided. (FIGURE G)
4. Connect male and female ends of door bonding wire set.
Center Section
SIDE VIEW
Center Section Bonding Studs
10-32 (2 Per Side)
Backpan
FIGURE G
Backpan
PET Stud
Door
FRONT VIEW
Door
Bonding
Stud
Page 6
Page 7
D-RING INSTALLATION
1. Install the supplied D-Rings to the pre-installed rackrail on both sides of the rack as shown with the supplied hardware. (FIGURE B)
8-32 STUD
8-32 ACORN NUT
D-RING RACKRAIL
STANDARD DOOR SWING REVERSAL
FIGURE B
1. Remove the two (2) 10-32 screws from both top and bottom hinges to remove the door (remove 4 screws total). (FIGURE C)
2. Reverse the door to install to the opposite side of the rack. Install the two (2) 10-32 screws to the top and bottom hinges.
HINGE
10-32 SCREWS
FIGURE C
Page 7
Page 8
4” DEEP DOOR SWING REVERSAL
1. Remove the 1/4-20 panhead screws and flange nuts from the top and bottom hinges to remove the door. (FIGURE D)
FLANGE NUT
HINGE
1/4-20 PANHEAD
FIGURE D
SCREWS
2. Remove the extended latch by removing the (2) two 10-32 screws. Install the latch to the opposite side of the rack. (FIGURE E)
10-32 SCREWS
LATCH EXTENDER
FIGURE E
Page 8
Page 9
NYLON PUSH RIVET 20
4” DEEP DOOR SWING REVERSAL (CONTINUED)
3. Reverse the door to install it to the opposite side of the rack using (2) two 1/4-20 panhead screws and (2) two 1/4-20 flange nuts per hinge (top and bottom). (FIGURE F)
FLANGE NUT
1/4-20 PANHEAD SCREWS
HINGE
FIGURE F
OPTIONAL COOLING KIT
CWR FAN KIT
PART NO. DESCRIPTION QTY
CWR-FKIT FANS (95 CFM per fan) 2
CORDS 2 GUARDS 2 VENT BLOCKER 1
Page 9
Page 10
WARRANTY
Middle Atlantic Products (the "Company") warrants the product to be free from defects in material or workmanship under normal use and conditions for the lifetime of the product.
The Company's entire liability to the purchaser, and the purchaser's (or any other party's) sole and exclusive remedy, under this warranty shall be limited, at the Company's option, to either (a) return of and refund of the price paid for, or (b) repair or replacement at the Company's factory of the products purchased, or any part or parts thereof, which the Company has determined to be defective after inspection thereof at the Company's factory.
This warranty does not cover damage due to acts of God, accident, misuse, abuse or negligence by parties other than the Company, or any modification or alteration of the products. In addition, this warranty does not cover damage due to improper handling, assembly, installation or maintenance.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES OF ANY KIND, EITHER EXPRESSED OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
TO THE MAXIMUM EXTENT PERMITTED BY APPLICABLE LAW, IN NO EVENT SHALL THE COMPANY BE LIABLE FOR ANY SPECIAL, INCIDENTAL, INDIRECT, OR CONSEQUENTIAL DAMAGES WHATSOEVER (INCLUDING, WITHOUT LIMITATION, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION OR ANY OTHER PECUNIARY LOSS) ARISING OUT OF THE USE OF THE PRODUCTS PURCHASED, EVEN IF THE COMPANY HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. THE COMPANY'S LIABILITY TO THE PURCHASER (OR ANY OTHER PARTY) HEREUNDER, IF ANY, SHALL IN NO EVENT EXCEED THE PURCHASE PRICE OF THE PRODUCTS PAID TO THE COMPANY.
Corporate Headquarters
Corporate Voice 973-839-1011 - Fax 973-839-1976 International Voice +1 973-839-8821 - Fax +1 973-839-4982 middleatlantic.com - info@middleatlantic.com
Middle Atlantic Canada
Voice 613-836-2501 - Fax 613-836-2690 middleatlantic.ca - customerservicecanada@middleatlantic.ca
Factory Distribution
USA: NJ - CA - IL Canada: ON - BC
At Middle Atlantic Products we are always listening. Your comments are welcome.
Middle Atlantic Products is an ISO 9001 and ISO 14001 Registered Company.
Page 10
Loading...